designing either chilled beam or vav systems for high performance

22
1 © 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional. Designing Either Chilled Beam or VAV Systems for High Performance John Murphy, LEED ® AP BD+C Applications Engineer Trane Ingersoll Rand La Crosse, Wisconsin “High-Performance” Systems Brief review of today’s technical session Overview of chilled beam systems Assess marketed advantages of chilled beams vs. VAV Discuss challenges of applying chilled beam systems “High-performance” chilled beam systems “High-performance” VAV systems 2

Upload: edward-siu

Post on 11-Nov-2014

42 views

Category:

Documents


19 download

TRANSCRIPT

Page 1: Designing Either Chilled Beam or VAV Systems for High Performance

1

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Designing Either Chilled Beamor VAV Systems for High Performance

John Murphy, LEED® AP BD+C Applications EngineerTraneIngersoll RandLa Crosse, Wisconsin

“High-Performance” Systems

• Brief review of today’s technical session– Overview of chilled beam systems– Assess marketed advantages of chilled beams vs. VAV– Discuss challenges of applying chilled beam systems

• “High-performance” chilled beam systems• “High-performance” VAV systems

2

Page 2: Designing Either Chilled Beam or VAV Systems for High Performance

2

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Passive or Active Chilled Beamsprimary air

nozzles

ceiling

coils

induced airinduced air

+primary air

active chilled beam

3

perforatedmetal casing

coilwaterpipes

passive chilled beam

active chilled beam

active chilled beamsPrimary Air System

primaryair handlerOA

activechilled beamPA

RA RA RA

PA

EARA

4

Primary air must be sufficiently drier than space: • to offset space latent load, and • to keep space DP below chilled beam surface temp

Page 3: Designing Either Chilled Beam or VAV Systems for High Performance

3

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

active chilled beam systems compared to VAV systemsSummary of Today’s Technical SessionPotential advantages of ACB• Smaller ductwork and

smaller air handlers

Challenges of ACB• High installed cost• Need to prevent

– Primary airflow < supply airflow, but likely > outdoor airflow

• Low sound levels• Impact on overall system energy?

– Primary airflow < supply airflow, but constant airflow

– Warm water for beams,

Need to prevent condensation

• Risk of water leaks• No filtration of local

recirculated air• Limited heating capability

5

but cold water primary AHU– Increased pumping energy– No DCV, limited airside

economizing

10,000,000

12,000,000

Use

, kB

tu/

yr

Pumps

Fans

Heating

Houston Los Angeles Philadelphia St. Louis

Example Energy Analysis

2,000,000

4,000,000

6,000,000

8,000,000

An

nu

al B

uild

ing

En

erg

y U Heating

Cooling

Plug Loads

Lighting

6

Page 4: Designing Either Chilled Beam or VAV Systems for High Performance

4

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

office buildingExample Energy Analysis• “Baseline” chilled-water VAV system

– ASHRAE 90.1-2007, Appendix G (55°F supply air)

• Active chilled beam systemActive chilled beam system– Four-pipe active chilled beams– Separate primary AHUs for perimeter and

interior areas (with SAT reset and economizers)– Separate water-cooled chiller plants

(low-flow plant supplying primary AHUs)

• “High-performance” chilled-water VAV system48°F l i (d t k t d i d)

7

– 48°F supply air (ductwork not downsized)– Optimized VAV system controls

(ventilation optimization, SAT reset)– Parallel fan-powered VAV terminals– Low-flow, water-cooled chiller plant

“High-Performance” Systems

• Brief review of today’s technical session– Overview of chilled beam systems– Assess marketed advantages of chilled beams vs. VAV– Discuss challenges of applying chilled beam systems

• “High-performance” chilled beam systems• “High-performance” VAV systems

8

Page 5: Designing Either Chilled Beam or VAV Systems for High Performance

5

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

“High Performance” Chilled Beam Systems

• How can active chilled beam systems be designeddifferently for “high performance”?

9

ACB challengesHigh Installed Cost

• Limited cooling capacity = lots of ceiling space– Warmer water temperature requires

more coil surface area– Induction with low static pressures requires more

coil surface area to keep airside pressure drop low

i h (8) i hill d b

10

Example: 1000-ft2 office space Example: 1000-ft2 classroom

four (4) active chilled beams,each 6-ft long x 2-ft wide

eight (8) active chilled beams,each 4-ft long x 2-ft wide

Page 6: Designing Either Chilled Beam or VAV Systems for High Performance

6

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

System design variable

Impact on installed cost of the chilled beams

Impact on performance of the overall system

2-pipe versus 4-pipe chilled beams

A 2-pipe beam provides more cooling capacity than a 4-pipe beam because more coil surface is available

Using 2-pipe beams requires a separate heating system, otherwise it can result in poorer comfort control because either cold water or warm water is delivered to all zones

Primary airflow rate (cfm)

Increasing the primary airflow rate through the nozzles results in more air being induced from the space which increased

Increasing the primary airflow rate increases primary AHU fan energy use, increases noise in the space and requires a larger primaryinduced from the space, which increased

the capacity of the chilled beam coilsin the space, and requires a larger primary AHU and larger ductwork

Inlet static pressure of the primary air

Increasing the static pressure at the inlet to the nozzles results in more air being induced from the space, which increased the capacity of the chilled beam coils

Increasing the inlet pressure increases primary AHU fan energy use, and increases noise in the space

Dry-bulb temperature of the primary air

Delivering the primary air at a colder temperature means that less of the space sensible cooling load needs to be offset by the chilled beams

Using a colder primary-air temperature may cause the space to overcool and low sensible cooling loads, thus requiring the chilled beam (or separate heating system) to add heat to

11

the chilled beams (or separate heating system) to add heat to prevent overcooling space

Entering water temperature

Supplying colder water to the chilled beam increases the cooling capacity of the beam

Using a colder water temperature requires the space dew point to be lower to avoid condensation, which means the primary air needs to be dehumidified to a lower dew point

Water flow rate (gpm)

Increasing the water flow rate increases the cooling capacity of the beam

Increasing the water flow rate increases pump energy use and requires larger pipes and pumps

“High Performance” Chilled Beam Systems

• How can active chilled beam systems be designeddifferently for “high performance”?

U t i b h ibl– Use two-pipe beams as much as possibleUse primary air system for morning warm-upConsider using a separate heating system

12

Page 7: Designing Either Chilled Beam or VAV Systems for High Performance

7

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

System design variable

Impact on installed cost of the chilled beams

Impact on performance of the overall system

2-pipe versus 4-pipe chilled beams

A 2-pipe beam provides more cooling capacity than a 4-pipe beam because more coil surface is available

Using 2-pipe beams requires a separate heating system, otherwise it can result in poorer comfort control because either cold water or warm water is delivered to all zones

Primary airflow rate (cfm)

Increasing the primary airflow rate through the nozzles results in more air being induced from the space which increased

Increasing the primary airflow rate increases primary AHU fan energy use, increases noise in the space and requires a larger primaryinduced from the space, which increased

the capacity of the chilled beam coilsin the space, and requires a larger primary AHU and larger ductwork

Inlet static pressure of the primary air

Increasing the static pressure at the inlet to the nozzles results in more air being induced from the space, which increased the capacity of the chilled beam coils

Increasing the inlet pressure increases primary AHU fan energy use, and increases noise in the space

Dry-bulb temperature of the primary air

Delivering the primary air at a colder temperature means that less of the space sensible cooling load needs to be offset by the chilled beams

Using a colder primary-air temperature may cause the space to overcool and low sensible cooling loads, thus requiring the chilled beam (or separate heating system) to add heat to

13

the chilled beams (or separate heating system) to add heat to prevent overcooling space

Entering water temperature

Supplying colder water to the chilled beam increases the cooling capacity of the beam

Using a colder water temperature requires the space dew point to be lower to avoid condensation, which means the primary air needs to be dehumidified to a lower dew point

Water flow rate (gpm)

Increasing the water flow rate increases the cooling capacity of the beam

Increasing the water flow rate increases pump energy use and requires larger pipes and pumps

active chilled beamsDetermining Primary Airflow Rate

• Primary airflow (PA) is b d l t f

PAbased on largest of:– Minimum outdoor airflow

required (ASHRAE 62.1)– Airflow required to offset

space latent load (depends on dew point of PA)Airflow needed to induce

RA

SA SA

14

– Airflow needed to induce sufficient room air (RA) to offset the space sensible cooling load

Page 8: Designing Either Chilled Beam or VAV Systems for High Performance

8

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

active chilled beamsDetermining Primary Airflow Rate

Minimum OA per ASHRAE 62.1(to achieve LEED IEQc2)

C

Example: office space0.085 cfm/ft2(0.085 × 1.3 = 0.11 cfm/ft2)

ACB systemAirflow required to offset space latent load

Airflow needed to induce sufficient room air to offset

ibl li l d

0.085 cfm/ft2 (DPTPA = 47°F)0.11 cfm/ft2 (DPTPA = 49°F)0.36 cfm/ft2 (DPTPA = 53°F)

0.36 cfm/ft2 (55°F primary air)(four, 6-ft long beams)

15

space sensible cooling loadVAV systemAirflow needed to offset space sensible cooling load

0.90 cfm/ft2(55°F supply air)

example office spaceCold vs. Neutral Primary Air

“Cold” (55°F) primary-air temperature

• four (4) ACBs, each 6-ft long x 2-ft widePA

( ) , g• primary airflow at design conditions = 0.36 cfm/ft2

• total water flow = 6.0 gpmRA

0.36 cfm/ft2

55°F

PA

0 50 f /ft2

“Neutral” (70°F) primary-air temperature

• six (6) ACBs, each 6-ft long x 2-ft widei i fl t d i diti 0 50 f /ft2

16

RA

0.50 cfm/ft2

70°F• primary airflow at design conditions = 0.50 cfm/ft2

• total water flow = 9.0 gpm

Page 9: Designing Either Chilled Beam or VAV Systems for High Performance

9

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

“High Performance” Chilled Beam Systems

• How can active chilled beam systems be designeddifferently for “high performance”?

U t i b h ibl– Use two-pipe beams as much as possibleUse primary air system for morning warm-upConsider using a separate heating system

– Minimize primary airflow requiredDeliver primary air at a cold (rather than neutral) temperatureUse multiple, smaller primary AHUs to allow SAT reset (maximize cooling benefit minimize need for reheat)

17

(maximize cooling benefit, minimize need for reheat)

active chilled beamsDetermining Primary Airflow Rate

Minimum OA per ASHRAE 62.1(to achieve LEED IEQc2)

C

Example: K-12 classroom0.47 cfm/ft2(0.47 × 1.3 = 0.61 cfm/ft2)

ACB systemAirflow required to offset space latent load

Airflow needed to induce sufficient room air to offset

ibl li l d

0.47 cfm/ft2 (DPTPA = 44°F)0.61 cfm/ft2 (DPTPA = 47°F)1.20 cfm/ft2 (DPTPA = 51°F)

0.47 cfm/ft2 (55°F primary air)(eight, 4-ft long beams)

18

space sensible cooling loadVAV systemAirflow needed to offset space sensible cooling load

1.20 cfm/ft2(55°F supply air)

Page 10: Designing Either Chilled Beam or VAV Systems for High Performance

10

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

ACB challengesNeed to Prevent Condensation

• Primary air system used to limit indoor dew point (t i ll b l 55°F)(typically below 55°F)

• Warm chilled-water temperatures delivered to beams (typically between 58°F and 60°F)

19

primary80

180

160

140

hum

idity

space 75°F DB50% RH55°F DP65 gr/lb

45-53°F DPair (PA)

70

50

4030

60

120

100

80

60

40

20

ratio, g

rains/lb

of d

ry air

spacespace

PAPA

44-60 gr/lb

Qlatent,space = 0.69 × CFMPA × (Wspace – WPA)

20

11030 40 50 60 70 80 10090dry-bulb temperature, °F

Primary air must besufficiently drier than the space

latent,space PA ( space PA)

Page 11: Designing Either Chilled Beam or VAV Systems for High Performance

11

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

active chilled beamsPrimary Air System

primary air handlerwith series desiccant wheel

OA

EA

activechilled beamPA

RA RA RA

PA

EA

RA

21

Primary AHU for ACB Systems

series desiccantdehumidification wheel

total-energywheel

preheatcoil

OA'

CA

OA

EA

MA'MA

22

coolingcoil

RA PA

Page 12: Designing Either Chilled Beam or VAV Systems for High Performance

12

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

180

160

hum

OA 95°F DB118 gr/lb

RA 75°F DB50% RH55°F DP

series desiccant requires:• less cooling tons• no reheat• warmer coil temperature

… than cool + reheat

OA' 81°F DB81 gr/lb

80

70

50

40

60

MA

MA 160

140

120

100

80

60

40

mid

ity ratio, g

rains/lb

of d

ry aRA

OA

OA'

CA

76°F DB68 gr/lb

MA' 72°F DB79 gr/lb

CA 51°F DB52 gr/lb

PA 55°F DB41 gr/lb43°F DP

MA'

23

11030 40 50 60 70 80 10090dry-bulb temperature, °F

4030 CAreheat 20

ir

PA

primary AHU with series desiccant wheel

“High Performance” Chilled Beam Systems

• How can active chilled beam systems be designeddifferently for “high performance”?

U t i b h ibl– Use two-pipe beams as much as possibleUse primary air system for morning warm-upConsider using a separate heating system

– Minimize primary airflow requiredDeliver primary air at a cold (rather than neutral) temperatureUse multiple, smaller primary AHUs to allow SAT reset (maximize cooling benefit minimize need for reheat)

24

(maximize cooling benefit, minimize need for reheat)Deliver primary air at a lower dew point(may even allow for the delivery of colder water to beams)

Page 13: Designing Either Chilled Beam or VAV Systems for High Performance

13

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

System design variable

Impact on installed cost of the chilled beams

Impact on performance of the overall system

2-pipe versus 4-pipe chilled beams

A 2-pipe beam provides more cooling capacity than a 4-pipe beam because more coil surface is available

Using 2-pipe beams requires a separate heating system, otherwise it can result in poorer comfort control because either cold water or warm water is delivered to all zones

Primary airflow rate (cfm)

Increasing the primary airflow rate through the nozzles results in more air being induced from the space which increased

Increasing the primary airflow rate increases primary AHU fan energy use, increases noise in the space and requires a larger primaryinduced from the space, which increased

the capacity of the chilled beam coilsin the space, and requires a larger primary AHU and larger ductwork

Inlet static pressure of the primary air

Increasing the static pressure at the inlet to the nozzles results in more air being induced from the space, which increased the capacity of the chilled beam coils

Increasing the inlet pressure increases primary AHU fan energy use, and increases noise in the space

Dry-bulb temperature of the primary air

Delivering the primary air at a colder temperature means that less of the space sensible cooling load needs to be offset by the chilled beams

Using a colder primary-air temperature may cause the space to overcool and low sensible cooling loads, thus requiring the chilled beam (or separate heating system) to add heat to

25

the chilled beams (or separate heating system) to add heat to prevent overcooling space

Entering water temperature

Supplying colder water to the chilled beam increases the cooling capacity of the beam

Using a colder water temperature requires the space dew point to be lower to avoid condensation, which means the primary air needs to be dehumidified to a lower dew point

Water flow rate (gpm)

Increasing the water flow rate increases the cooling capacity of the beam

Increasing the water flow rate increases pump energy use and requires larger pipes and pumps

Waterside Economizer

chillers

variable-flowpumps

bypass forminimum flow mixing

valveTT

variable-flowpump

42°F57°F

26

primaryair handlers

chilled beamsfrom

cooling tower waterside economizerheat exchanger

42°F 58°F

63°F

54°F

Page 14: Designing Either Chilled Beam or VAV Systems for High Performance

14

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

42°F

i bl fl

water chillers

58°F

42°F

54°F

variable-flowpumps

bypass forminimum flow

mixingvalve

primaryAHU coils

27

variable-flowpump

TT

58°F63°F

fromcooling tower

waterside economizerheat exchanger

activechilled beams

“High Performance” Chilled Beam Systems

• How can active chilled beam systems be designeddifferently for “high performance”?

U t i b h ibl– Use two-pipe beams as much as possibleUse primary air system for morning warm-upConsider using a separate heating system

– Minimize primary airflow requiredDeliver primary air at a cold (rather than neutral) temperatureUse multiple, smaller primary AHUs to allow SAT reset (maximize cooling benefit minimize need for reheat)

28

(maximize cooling benefit, minimize need for reheat)Deliver primary air at a lower dew point

– Incorporate a waterside economizer, if possible

Page 15: Designing Either Chilled Beam or VAV Systems for High Performance

15

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

“High-Performance” Systems

• Brief review of today’s technical session– Overview of chilled beam systems– Assess marketed advantages of chilled beams vs. VAV– Discuss challenges of applying chilled beam systems

• “High-performance” chilled beam systems• “High-performance” VAV systems

29

“High Performance” VAV Systems

• How are VAV systems being designeddifferently today for “high performance”?

O ti i d VAV t t l– Optimized VAV system controls

30

Page 16: Designing Either Chilled Beam or VAV Systems for High Performance

16

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

staticpressure

Fan-Pressure Optimization

VAV terminalswith DDC controllers

pressuresensor

supplyfan P

VFDVFD

31

system-level controller

Supply-Air Temperature Reset

system-level controller

TTT

T

T

T

32

Page 17: Designing Either Chilled Beam or VAV Systems for High Performance

17

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Ventilation Optimizationair-handling (or rooftop) unit with Traq™ dampers• Reset outdoor airflow

SA RA

33

CO2 OCC

• Required ventilation (TOD, OCC, CO2)• Actual primary airflow (flow ring)• Calculate OA fraction

VAV controllers

CO2TOD TODOCC

system-level controller• New OA setpoint

…per ASHRAE 62

“High Performance” VAV Systems

• How are VAV systems being designeddifferently today for “high performance”?

O ti i d VAV t t l– Optimized VAV system controls– Cold air distribution

34

Page 18: Designing Either Chilled Beam or VAV Systems for High Performance

18

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Lower Supply-Air Temperature

• Reduces supply airflowLess supply fan energy– Less supply fan energyand less fan heat gain

– Smaller fans, air handlers,VAV terminals, and ductwork

• Can reduce HVAC installed cost• Can reduce building construction cost• Improves occupant comfort

35

– Lowers indoor humidity levels– Lowers indoor sound levels

“High Performance” VAV Systems

• How are VAV systems being designeddifferently today for “high performance”?

O ti i d VAV t t l– Optimized VAV system controls– Cold air distribution– Parallel fan-powered VAV terminals

36

Page 19: Designing Either Chilled Beam or VAV Systems for High Performance

19

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Parallel Fan-Powered VAV

heating coil(second stage of heat)

cool primary air fromVAV air-handling unit

warm air recirculatedfrom ceiling plenum(first stage of heat)

(second stage of heat)

37

(first stage of heat)

“High Performance” VAV Systems

• How are VAV systems being designeddifferently today for “high performance”?

O ti i d VAV t t l– Optimized VAV system controls– Cold air distribution– Parallel fan-powered VAV terminals– “High-performance” chilled-water system

38

Page 20: Designing Either Chilled Beam or VAV Systems for High Performance

20

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

“High-Performance” Chilled-Water System

• Low flow, low temperature• Ice storage• Variable primary flow• High-efficiency chillers• Optimized plant controls• Waterside heat recovery• Central geothermal

39

• Central geothermal

Summary

• Chilled beam and VAV systems h h d t d d b keach have advantages and drawbacks

• We need to move toward designing “high-performance” systems… not just the way it’s always been done!

40

Page 21: Designing Either Chilled Beam or VAV Systems for High Performance

21

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Advanced Energy Design Guides

• Funded by U.S. Dept of Energy• Climate-specific recommendations

www.ashrae.org/freeaedg

pfor achieving 30% or 50% energy savings(envelope, lighting, HVAC, water heating)

• Based on building energy simulations

41

Advanced Energy Design Guides

AEDG for Small or Medium Office Buildings• “High-performance rooftop VAV systems are included

as an option to achieve 50% energy savings

AEDG for K-12 Schools• Both rooftop VAV and chilled-water VAV systems are

included as options to achieve 30% energy savings

AEDG for Small Hospitals and Healthcare Facilities

42

p• Both rooftop VAV and chilled-water VAV systems are

included as options to achieve 30% energy savings

Page 22: Designing Either Chilled Beam or VAV Systems for High Performance

22

© 2010 Trane, a business of Ingersoll-Rand

Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Additional Resources

• “Understanding Chilled Beam Systems,” TraneEngineers Newsletter ADM-APN034-EN (2009),www.trane.com/engineersnewsletter

• Chilled-Water VAV Systems, Traneapplication manual SYS-APM008-EN (2009)

• Cold Air Distribution System Design Guide, ASHRAE (1996)

• Advanced Energy Design Guide series, ASHRAE, www.ashrae.org/freeaedg

43