Design Fires for Smoke Control
Dr. John H. Klote PEFire and Smoke Consulting
www.SmokeControlExpert.com
![Page 2: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/2.jpg)
Learning Objectives• Provide an understanding of fire
growth, flashover, fully developed fire and fire decay.
• Provide an overview of the basic concepts of developing design fires for smoke control systems.
![Page 3: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/3.jpg)
• Extensive Treatment of All Aspects of Smoke Control
• For more information about design fires, see Chapter 5 “Fire Physics & Design Fires”
![Page 4: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/4.jpg)
Design Fires
• Used for Atrium Smoke Control and Tenability Systems
• IBC– No Prescribed Design Fires– Requires Analysis of Design Fires
• Many Engineers – New to Design Fires
• This Talk: – Overview of Analysis of Design Fires– Focus on Highlights
![Page 5: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/5.jpg)
UK Information on Design Fires
• Industrial & Warehouse (not high racked) -1990 Smoke Ventilation Association Guide:– Sprinklered Steady Fires - 3m x 3m to 9m x 9m.– Unsprinkleres Steady Fires – 2 Times as Big
• Steady Fires in Car Parks – BS 7346-7• Guidance for Offices & Hotels – BS 7346-4 and
5 and in BR368• General Information on Specific Objects:
– BS 7974 (UK fire engineering standard) – BRE design fires database CD
![Page 6: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/6.jpg)
![Page 7: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/7.jpg)
Design Fires
• Normally Most Important Property - Heat Release Rate (HRR)
• Other Properties (toxic gases, reduced visibility, etc.) - Tenability Systems
• For simplicity - Only Discuss HRR
• HRR of a Design Fire:– Steady – Unsteady
• Steady HRR – Peak of Unsteady HRR
![Page 8: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/8.jpg)
![Page 9: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/9.jpg)
![Page 10: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/10.jpg)
![Page 11: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/11.jpg)
![Page 12: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/12.jpg)
![Page 13: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/13.jpg)
![Page 14: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/14.jpg)
![Page 15: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/15.jpg)
![Page 16: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/16.jpg)
Fully Developed Fire
• Called “Ventilation Controlled Fire”• Room with One Opening
– HRR Controlled by Opening Size – HRR Equation
1/ 21260 w wQ A H
where Q = HRR (kW) Aw = area of opening (m2), Hw = height of opening (m).
![Page 17: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/17.jpg)
HRR Measurement
• Oxygen Consumption Calorimeters– HRR per unit O2 Consumed – Almost
Constant (13.1 MJ per kg of oxygen + 6%)– Open Air Calorimeter – Room Calorimeter
![Page 18: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/18.jpg)
![Page 19: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/19.jpg)
![Page 20: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/20.jpg)
![Page 21: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/21.jpg)
![Page 22: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/22.jpg)
![Page 23: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/23.jpg)
![Page 24: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/24.jpg)
Design Fires
• Normal Fuels - Objects Planned for Space• Transient Fuels - In a Space Temporarily
– Examples: Trash, Stacked Wood Pallets, Furniture After Delivery, etc.
• Atrium Fires– Normal & Transient Fuels– No Benefit of Sprinklers (Ceilings > 35 – 45 ft)– Transient Fuels: Suggest Min. 2000 Btu/s
• Non-Atrium Fires– Normal & Transient Fuels– Fires w/ Axisymmetric Plume – CFAST– Shielded Fires (NIST & NRCC Models)
![Page 25: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/25.jpg)
![Page 26: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/26.jpg)
![Page 27: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/27.jpg)
![Page 28: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/28.jpg)
![Page 29: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/29.jpg)
![Page 30: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/30.jpg)
![Page 31: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/31.jpg)
![Page 32: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/32.jpg)
![Page 33: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/33.jpg)
![Page 34: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/34.jpg)
![Page 35: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/35.jpg)
![Page 36: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/36.jpg)
![Page 37: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/37.jpg)
![Page 38: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/38.jpg)
![Page 39: Design Fires for Smoke Control Dr. John H. Klote PE Fire and Smoke Consulting john@SmokeControlExpert.com](https://reader030.vdocuments.mx/reader030/viewer/2022033022/56649d355503460f94a0c5da/html5/thumbnails/39.jpg)