Updated 05/24/2018 Printed 08/02/2019 Page 1 of 1 Project No. 46012-E DESIGN & CONSTRUCTION GROUP THE GOVERNOR NELSON A. ROCKEFELLER EMPIRE STATE PLAZA ALBANY, NY 12242 ADDENDUM NO. 1 TO PROJECT NO. 46012 ELECTRICAL WORK PROVIDE LIGHTING UPGRADES DMNA HEADQUARTERS 330 OLD NISKAYUNA ROAD LATHAM, NY AUGUST 2, 2019 NOTE: This Addendum forms a part of the Contract Documents. Insert it in the Project Manual. Acknowledge receipt of this Addendum in the space provided on the Bid Form. DRAWINGS 1. Revised Drawings: a. Drawing Nos. E-001, E-102, E-135 and E-501, noted “REVISED DRAWING 7/26/2019” accompany this Addendum and supersede the same numbered originally issued drawings. END OF ADDENDUM Erik T. Deyoe, P.E. Director, Division of Design Design & Construction

Upload: others

Post on 08-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DESIGN CONSTRUCTION GROUP THE GOVERNOR NELSON A ... 01 E.pdf · updated 05/24/2018 printed 08/02/2019 page 1 of 1 project no. 46012-e design & construction group the governor nelson

Updated 05/24/2018

Printed 08/02/2019 Page 1 of 1 Project No. 46012-E

DESIGN & CONSTRUCTION GROUP

THE GOVERNOR NELSON A. ROCKEFELLER

EMPIRE STATE PLAZA

ALBANY, NY 12242

ADDENDUM NO. 1 TO PROJECT NO. 46012

ELECTRICAL WORK

PROVIDE LIGHTING UPGRADES

DMNA HEADQUARTERS

330 OLD NISKAYUNA ROAD

LATHAM, NY

AUGUST 2, 2019

NOTE:This Addendum forms a part of the Contract Documents. Insert it in the Project Manual.

Acknowledge receipt of this Addendum in the space provided on the Bid Form.

DRAWINGS

1. Revised Drawings:

a. Drawing Nos. E-001, E-102, E-135 and E-501, noted “REVISED DRAWING

7/26/2019” accompany this Addendum and supersede the same numbered originally

issued drawings.

END OF ADDENDUM

Erik T. Deyoe, P.E.

Director, Division of Design

Design & Construction

Page 2: DESIGN CONSTRUCTION GROUP THE GOVERNOR NELSON A ... 01 E.pdf · updated 05/24/2018 printed 08/02/2019 page 1 of 1 project no. 46012-e design & construction group the governor nelson

DESIGN & CONSTRUCTION

SAGE ENGINEERINGASSOCIATES, LLP

RECESSED PANELBOARD

SURFACE MOUNTED PANELBOARD

JUNCTION BOX

HOME RUN TO PANEL. 2#12, #12G, 3/4"C UNLESSOTHERWISE NOTED. PROVIDE SEPARATE GROUND ANDNEUTRAL FOR EACH BRANCH CIRCUIT.

'X'-INDICATES PANEL'Z, Y'-INDICATES CIRCUIT NUMBERS

CIRCUIT CONTINUATION WITH 'Y' INDICATING DEVICE ORAREA DESCRIPTION

'X'-INDICATES PANEL'Z, Y'-INDICATES CIRCUIT NUMBERS

CIRCUIT CONSISTING OF GROUND, NEUTRAL AND PHASECONDUCTORS. . A SEPARATE GREEN GROUNDCONDUCTOR SHALL BE PLACED IN ALL CIRCUITS

LINE TYPE SHOWING WIRING BETWEEN LIGHTING POWERPACKS AND OCCUPANCY SENSORS

CONNECTION POINT

CONDUIT TURNED UP

CONDUIT TURNED DOWN

CAPPED CONDUIT

LINE THICKNESSES FOR EQUIPMENT, DEVICES ANDCONDUIT EXISTING TO REMAIN

LINE THICKNESSES FOR EQUIPMENT, DEVICES ANDCONDUIT REMOVED, PROVIDED, OR RELOCATED UNDERTHIS CONTRACT

X-Z, Y

OR

X-Z, Y

J J

D

PP

OS

PC

SINGLE POLE SWITCH, 20 AMP 120/277 UNLESS NOTEDOTHERWISE

'F'-INDICATES FAN CONTROL SWITCH'P'-INDICATES PILOT LIGHT'WP'-INDICATES WEATHER PROOF'3' INDICATES THREE WAY SWITCH'4' INDICATES FOUR WAY SWITCH'D' INDICATES LINE VOLTAGE DIMMER'K' INDICATES KEYED SWITCH'OS' INDICATES OCCUPANCY SENSOR SWITCH'VS' INDICATES VACANCY SENSOR SWITCH

'LV6' INDICATES MULTIPLE LOW VOLTAGE SWITCHES AND 5BUTTON SCENE SWITCH

'LVD' INDICATES MULTIPLE LOW VOLTAGE DIMMING SWITCH

CEILING MOUNTED OCCUPANCY SENSOR. DUAL TECHNOLOGYULTRASONIC/PIR UNLESS NOTED OTHERWISE. VACANCY OROCCUPANCY SENSING FIELD ADJUSTABILITY.

'MP'-INDICATES MICROPHONICS'XR'-INDICATES EXTENDED RANGE

LIGHTING CONTROL POWER PACK OR CONTROLLER 'D'-IF SHOWN, INDICATES DIMMING FUNCTION

TIME CLOCK

EXTERIOR PHOTOCELL USED FOR ON/OFF CONTROL OFEXTERIOR LIGHTING.

INTERIOR CEILING MOUNTED PHOTOCELL USED FOR ON/OFFCONTROL OF INTERIOR LIGHTING.

DIMMING ROOM CONTROLLER

SYMBOLS: (SOME SYMBOLS MAY NOT BE USED)

ABBREVIATIONS: (SOME ABBREVIATIONS MAY NOT BE USED)

A AMPAC ABOVE COUNTERAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAWG AMERICAN WIRE GAGEC CONDUITCAT CATEGORYCB CIRCUIT BREAKERCKT CIRCUITCOMM COMMUNICATIONCU COPPERCVT CONTROL VOLTAGE TRANSFORMERDLC DESIGN LIGHTS CONSORTIUMDMNA DIVISION OF MILITARY AND NAVAL AFFAIRSDSP GARBAGE DISPOSALDW DISHWASHER

EM EMERGENCY, EMERGENCY BATTERY OPTIONEMT ELECTRICAL METALLIC TUBINGELU EMERGENCY LIGHTING UNITEXR EXISTING TO REMAINFC FOOT CANDLESFLA FULL LOAD AMPSG GROUNDHC HANDICAP ACCESSIBLEJB JUNCTION BOXK KILOKVA KILO-VOLT AMPERELV LOW VOLTAGEMC METAL CLAD CABLEMCB MAIN CIRCUIT BREAKERMTG MOUNTING

NEC NATIONAL ELECTRIC CODENL NIGHT LIGHTNO/NC NORMALLY OPEN/NORMALLY CLOSEDP POLEPC PHOTOCELLPE PHOTO EYEPH PHASEPR PAIRREL RELOCATEREM REMOVEREP REPLACERGS RIGID GALVANIZED STEELSCH SCHEDULESH SHIELDED

TSP TWISTED SHIELDED PAIRTW TWISTEDTYP TYPICALUG UNDERGROUNDUON UNLESS OTHERWISE NOTEDUPS UNINTERRUPTIBLE POWER SUPPLYUTP UNSHIELDED TWISTED PAIRV VOLTW WATTW/ WITHWP WEATHERPROOF, WALL PACK

TC

GENERAL NOTES APPLICABLE TO ALL DRAWINGS: 1. CEILING CONDITION IS 2 X 2 OR 2 X 4 T-BAR SUSPENDED TILE GRID CEILING AT A HEIGHT OF 12 FEET MAXIMUM AFF UON.

2. REMOVE ALL LIGHTING FIXTURES, WIRING, AND ASSOCIATED DEVICES SHOWN ON REMOVAL DRAWINGS UON.

3. REMOVE ALL LINE VOLTAGE SWITCHES CONTROLLING LIGHT FIXTURES, UON. EXISTING BACK BOX AND RACEWAY TO BOX REMAINS.

4. WHERE DRAWINGS INDICATE REMOVAL OF LINE VOLTAGE SWITCH AND PROVIDING LOW VOLTAGE SWITCH:-REMOVE LINE VOLTAGE CONDUCTORS FROM BOX AND RACEWAY BACK TO NEAREST ACCESSIBLE JUNCTION BOX-DISCONNECT RACEWAY FROM JUNCTION BOX-PROVIDE BLANK FILLER TO CLOSE OPENING CREATED IN JUNCTION BOX BY DISCONNECTING CONDUIT-PROVIDE CONNECTOR AND INSULATING BUSHING ON END OF CONDUIT-PROVIDE SUPPORT, INDEPENDENT OF BOX, FOR END OF CONDUIT-REUSE CONDUIT FOR CAT5e CABLE FROM LOW VOLTAGE SWITCH.

5. COORDINATE THE TURNING OVER OF LIGHT FIXTURES TO THE FACILITY SUPERINTENDENT. PROPERLY DISPOSE OF REMOVED AND UNWANTED MATERIALS,INCLUDING BUT NOT LIMITED TO FIXTURES, LAMPS, AND WIRING DEVICES OFF SITE. DO NOT USE DMNA TRASH RECEPTACLES OR DUMPSTERS.

6. MAINTAIN EXISTING MOUNTING HEIGHTS OF FIXTURES INCLUDING BUT NOT LIMITED TO GRID-INSTALLED, PENDANT, OR WALL-MOUNTED FIXTURES.

7. CIRCUIT ALL EXIT SIGNS AND EMERGENCY LIGHTING UNITS, INDICATED TO BE PROVIDED, TO LOCAL LIGHTING CIRCUIT AND AHEAD OF LOCAL SWITCHING.EXTEND EXISTING CIRCUITS WITH MATERIALS EQUAL TO EXISTING.

8. DRAWINGS INDICATE REMOVALS OF 2'X4' FIXTURE AND REPLACEMENT WITH 2'X2' FIXTURE. PROVIDE GRID T-BAR (USG #X-TEES 2' SDX 216-WHITE) TO MATCHEXISTING AND 2'X2' SUSPENDED GRID TILE (USG #808 SAND DRIFT WHITE) TO MATCH EXISTING FOR EACH LOCATION WHERE A 2'X2' FIXTURE REPLACES A 2'X4'FIXTURE. ALSO PROVIDE SAME 2' GRID SECTION AND UP TO (2) CEILING TILES FOR REMOVAL OF EACH FIXTURE WHERE REPLACEMENT FIXTURE IS NOT TO BEPROVIDED.

9. VERIFY EXISTING PANEL DIRECTORIES ACCURATELY DESCRIBED LOADS OR AREAS SERVED BY EACH BREAKER. PROVIDE UPDATED TYPEWRITTENDIRECTORIES FOR ALL PANELS THAT SERVE LIGHTING CIRCUITS INDICATED UPDATED INFORMATION FOR LIGHTING CIRCUITS. VERIFICATION OF NON-LIGHTINGLOADS (RECEPTACLES, MOTORS, ETC.) NOT IN CONTRACT; TRANSFER INFORMATION TO DIRECTORY.

10. COORDINATE WORK WITH OTHER CONTRACTS IN PROGRESS ON THE SITE AND WITH THE DIRECTOR'S REPRESENTATIVE AND DMNA HEADQUARTERS FACILITY.

11. PROVIDE PROVISIONS TO ENSURE OCCUPANT SAFETY IN AREAS OF WORK THROUGHOUT THE DURATION OF CONSTRUCTION. WORK AREAS WILL BE OCCUPIED.

12. CONFIRM ALL LOCATIONS WITH FIELD OBSERVATIONS, MEASUREMENTS AND INVESTIGATION. THE UNDERGROUND STRUCTURES AND UTILITIES SHOWN ON THISDRAWING HAVE BEEN PLOTTED FROM AVAILABLE SURVEYS, DOCUMENTATION, AND RECORD DRAWINGS, THEY ARE NOT CERTIFIED TO THE ACCURACY OFTHEIR LOCATION AND/OR COMPLETENESS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE LOCATION AND EXTENT OF ALL UNDERGROUNDSTRUCTURES AND UTILITIES PRIOR TO ANY DIGGING OR CONSTRUCTION ACTIVITIES IN THEIR VICINITY. THE CONTRACTOR SHALL HAVE ALL EXISTING UTILITIESFIELD STAKED BEFORE STARTING WORK. ADDITIONAL UTILITIES MAY EXIST.

13. PROVIDE MOUNTING HARDWARE AND MANUFACTURER'S ACCESSORIES FOR LIGHTING FIXTURES AS REQUIRED FOR A COMPLETE INSTALLATION.

14. PROVIDE LIFTS, LADDERS AND OTHER EQUIPMENT REQUIRED TO GAIN ACCESS FOR ALL ELEVATED WORK. OWNER'S LIFTS AND LADDERS SHALL NOT BE USED.

15. OBTAIN SCHEDULE OF ROUTINE DAILY ACTIVITIES AND OF INDIVIDUAL EVENTS FROM THE DIRECTOR'S REPRESENTATIVE. SEQUENCE WORK AROUND THEFACILITY'S ACTIVITIES SCHEDULE. BUILDINGS AND AREAS WILL BE OCCUPIED DURING WORK.

16. KEEP ALL AREAS TO BE KEPT CLEAN WHILE PERFORMING WORK.

17. WITH MATERIALS OF CONSTRUCTION TO MATCH EXISTING SURFACES, REPAIR ALL OPEN PENETRATIONS CREATED BY REMOVAL OF ELECTRICAL RACEWAYS.

18. PROTECT SMOKE DETECTORS DURING CONSTRUCTION. TAKE MEASURES TO PREVENT FIRE ALARM SYSTEM TRIP DUE TO CONSTRUCTION. RESTORE FIREALARM TO FULL FUNCTION WHEN CONSTRUCTION WORK CEASES EACH DAY OR PORTION OF WORK DAY.

19. MAINTAIN ONE LANE OPEN ON ROADWAYS AT ALL TIMES. COORDINATE WITH DIRECTOR'S REPRESENTATIVE PRIOR TO BLOCKING PARKING SPACES FOREXTERIOR LIGHTING WORK.

20. REPAIR ANY AREA DISTURBED BY THE WORK TO MATCH THE EXISTING SURROUNDING UNDISTURBED AREA.

21. REFER TO CONTROL DIAGRAMS AND DETAILS FOR CONDUCTOR SIZES.

22. OVERHEAD UTILITIES WILL REMAIN IN PLACE AND WILL REMAIN ENERGIZED. MEASURE CLEARANCES TO ROAD SURFACES. PROVIDE CONSTRUCTIONEQUIPMENT AND DELIVERY VEHICLES COMPATIBLE WITH EXISTING CLEARANCES.

23. PROVIDE PROFESSIONAL LIFTING, CRANE, AND MATERIAL HANDLING SERVICES TO TRANSFER MATERIALS FROM DELIVERY VEHICLES TO WORK LOCATIONS.PROVIDE EQUIPMENT SPECIFICALLY DESIGNED FOR LIFTING, CRANE, AND MATERIAL HANDLING.

24. WHERE A SPECIFIC MANUFACTURER AND/OR MODEL NUMBER IS DESCRIBED IN THE DRAWINGS, THE WORDS 'OR APPROVED EQUAL' SHALL BE INCORPORATEDBY REFERENCE.

25. INTERCEPT AND EXTEND EXISTING UNSWITCHED BRANCH CIRCUIT TO LIGHTING CONTROLLERS. PROVIDE MATERIALS EQUAL TO EXISTING.

26. PROVIDE WIREMOLD 5751 FLUSH-TYPE EXTENSION ADAPTER FOR WALL MOUNTED OCCUPANCY/VACANCY CONTROL SENSORS WHERE INSTALLATION OFSENSOR EXCEEDS EXISTING BOX FILL ALLOWANCES.

27. MAINTAIN CIRCUIT CONTINUITY TO SYSTEMS AND ROOMS ADJACENT TO RENOVATION AND CONSTRUCTION AREAS. PERMANENTLY REPAIR CIRCUITS OR WIRINGDISTURBED, MODIFIED, OR DISPLACED BY THE WORK.

28. PROVIDE SUPPORT WIRES FOR EACH FIXTURE WITH AN EMERGENCY BACKUP BALLAST. PROVICE A MINIMUM OF TWO INDEPENDENT GALVANIZED CARBONSTEEL, SOFT TEMPER, PRE STRETCHED SUPPORT WIRES NOT LESS THAN 12 GAGE, .106 DIAMETER ON OPPOSITE CORNERS OF EACH FIXTURE. ATTACHSUPPORT WIRES TO STRUCTURE, INDEPENDENT OF SUPPORTS AND SUPPORT WIRES FOR SUSPENDED CEILING.

29. LIGHTING CONTROL DETAILS ARE DIAGRAMMATIC. PROVIDE QUANTITIES OF MATERIALS INCLUDING BUT NOT LIMITED TO POWER PACKS, SWITCHES, DIMMERS,PHOTOSENSORS, CABLES, AND SUPPORTS AS REQUIRED FOR A COMPLETE INSTALLATION AS INDICATED ON THE DRAWINGS.

30. LIGHTING CONTROLS FOR SITE LIGHTING AND BUILDING-MOUNTED LIGHTING EXISTING TO REMAIN. PROVIDE LABOR TO VERIFY OPERATION OF EXISTINGCONTROLS FOR SITE LIGHTING AND BUILDING-MOUNTED LIGHTING.

31. PROVIDE EXIT SIGN OR EMERGENCY LIGHTING UNIT IMMEDIATELY UPON REMOVAL OF THOSE EXISTING.

32. CORRIDORS: PROVIDE UNSWITCHED EXTENSION OF BRANCH CIRCUIT TO EACH FIXTURE DESIGNATED AS NIGHT LIGHT OR EMERGENCY FIXTURE.

33. AREAS WITH LOW VOLTAGE CONTROLS, AND WITH NIGHT LIGHTS AND/OR EMERGENCY FIXTURES: PROVIDE EMERGENCY LIGHTING CONTROL UNIT (ELCU).PROVIDE UNSWITCHED EXTENSION OF BRANCH CIRCUIT TO EMERGENCY LIGHTING CONTROL UNIT AND TO NIGHTLIGHT AND EMERGENCY FIXTURE.

34. AREAS WITH LINE VOLTAGE CONTROLS, AND WITH NIGHT LIGHTS AND/OR EMERGENCY FIXTURES: PROVIDE UNSWITCHED EXTENSION OF BRANCH CIRCUIT TOEACH FIXTURE DESIGNATED AS NIGHT LIGHT OR EMERGENCY FIXTURE.

35. PROVIDE REPLACEMENT CEILING GRID TILES FOR ALL TILES DAMAGED OR BROKEN INCLUDING BUT NOT LIMITED TO DURING FIXTURE REMOVALS ANDINSTALLATIONS, INSTALLATION OF CONTROLS, AND INSTALLATION OR MODIFICATION OF BRANCH CIRCUIT WIRING.

36. ALL LIGHTING AND BRANCH CIRCUIT PANELBOARDS SHOWN ON PLANS ARE EXISTING TO REMAIN.

37. PROVIDE TYPE WRITTEN LABELING FOR CONDUCTORS AT TERMINATION LOCATIONS, INDICATING POWER SOURCE AND CIRCUIT.

ALTERNATE #1: 1. INTERIOR LIGHTING WORK FOR THE AASF-3 BUILDING.

2. INTERIOR LIGHTING WORK FOR THE READINESS CENTER.

PC

CODE SUMMARY CLASSIFICATION OF WORK (IEBC CHAPTER 5, SECTION 503): ALTERATION LEVEL 2

OCCUPANCY CLASSIFICATION (IBC, SECTION 302): B (HEADQUARTERS), U (ARMORY), S-1 (AASF)

CONSTRUCTION CLASSIFICATION (IBC, SECTION 602): TYPE II (B)

SEISMIC REQUIREMENTS (BC1613 AND ASCE 7-10):

SEISMIC RISK CATEGORY IISITE CLASS - DSEISMIC DESIGN CATEGORY - B

ELECTRICAL INSTALLATIONS (NFPA 70 - IBC, CHAPTER 1):

ALL ELECTRICAL (BRANCH CIRCUITING, CONDUIT, CONDUCTORS, BOXES, AND SUPPORTING HARDWARE) REQUIRED TO POWER LIGHTING FIXTURES AND CONTROLS.

LEGEND:

ELECTRICAL COMPONENTS ARE EXEMPT FROM SEISMIC RESTRAINT REQUIREMENTS.

EBC 2015 - INTERNATIONAL EXISTING BUILDING CODE WITH NYS 2017 UNIFORM CODE SUPPLEMENT IBC 2015 - INTERNATIONAL BUILDING CODE WITH NYS 2017 UNIFORM CODE SUPPLEMENT NFPA 70 (NEC) - NATIONAL ELECTRICAL CODEIECC 2015 - INTERNATIONAL ENERGY CONSERVATION CODE WITH NYS 2016 SUPPLEMENT TO THE NYS ENERGY CONSERVATION CONSTRUCTION CODE

BUILDING CODE NOTE ENERGY CODE NOTE

DRC

WALL MOUNTED LED EXIT SIGN. PROVIDE DIRECTIONALARROWS AS SHOWN ON DRAWINGS.

CEILING MOUNTED LED EXIT SIGN. PROVIDE DIRECTIONALARROWS AS SHOWN ON DRAWINGS

WALL MOUNTED COMBINATION EXIT SIGN / EMERGENCYLIGHTING UNIT

CEILING MOUNTED COMBINATION EXIT SIGN / EMERGENCYLIGHTING UNIT

WALL MOUNTED EMERGENCY LIGHTING UNIT

CEILING MOUNTED EMERGENCY LIGHTING UNIT

LINEAR WALL MOUNTED FIXTURE.

1 X 4 FIXTURE.

1 X 4 PENDANT MOUNTED FIXTURE.

2 X 2 FIXTURE. SEE LIGHT FIXTURE SCHEDULE FOR TYPE

RECESSED DOWNLIGHT. SEE LIGHT FIXTURE SCHEDULE FORTYPE

SURFACE MOUNTED DOWNLIGHT.

TRACK LIGHTING

PENDANT MOUNT INCANDESCENT FIXTURE

WALL MOUNT, WALL SCONCE FIXTURE

SINGLE POLE-MOUNTED FIXTURE ON EXISTING POLE. SEEFIXTURE SCHEDULE FOR TYPE.

DUAL POLE-MOUNTED FIXTURES. PROVIDE LIGHTING STANDARD(POLE). SEE FIXTURE SCHEDULE FOR TYPE.

GROUND MOUNTED ACCENT FLOOD LIGHT. SEE FIXTURESCHEDULE FOR TYPE.

OR

DEV (EXR)C (EXR)

DEVC

1

1

1

REVISED DRAWING DATED 7/26/2019

Page 3: DESIGN CONSTRUCTION GROUP THE GOVERNOR NELSON A ... 01 E.pdf · updated 05/24/2018 printed 08/02/2019 page 1 of 1 project no. 46012-e design & construction group the governor nelson

3

33

b

a

a

a

a

(EXR)

(EXR)

(EXR)

(EXR) 3

(EXR)

(EXR)

b

a

1 2

2

3

3

3

3

3

3 3

3

3

3

3

3

3

3

3

3

1

1

3

1

DESIGN & CONSTRUCTION

SAGE ENGINEERINGASSOCIATES, LLP

GENERAL REMOVAL NOTES:

PENDANT LED LIGHTS ABOVE IN ATTRIUM ARE NOT SHOWN. THIS LIGHTING IS NOT INCONTRACT AND EXISTING TO REMAIN. MAINTAIN EXISTING CIRCUITING AND CONTROLS.

KEYED NOTES:1

PLANNORTH

1. REFER TO SHEET E-001 FOR ADDITIONAL NOTES.

2. PROVIDE TEMPORARY LIGHTING TO 20FC PRIOR TO REMOVAL OF ANY LIGHT FIXTURESOR POWER SOURCE SERVING ANY LIGHT CIRCUITS.

3. COORDINATE ALL REMOVALS WITH SEQUENCE OF CONSTRUCTION DRAWING NOTESAND REQUIREMENTS OF SPECIFICATION SECTION 011000 BEFORE PROCEEDING WITHACTUAL REMOVALS.

1 CEILING IN THIS SPACE IS EXPOSED TO DECK AND/OR STRUCTURE.

CEILING IN THIS SPACE IS GYPSUM BOARD WITH LIGHTING FIXTURES RECESSED ORSURFACE MOUNTED BASED ON FIXTURE TYPE.

ACCESS TO THIS SPACE IS LIMITED. VERIFY WORK REQUIREMENTS AND OBTAINAPPROVAL FOR ACCESS WITH OWNER'S RESPRESENTATIVE PRIOR TO ENTRY ANDCOMPLETING ANY WORK.

CONSTRUCTION KEYED NOTES:

2

3

1

REVISED DRAWING DATED 7/26/2019

Page 4: DESIGN CONSTRUCTION GROUP THE GOVERNOR NELSON A ... 01 E.pdf · updated 05/24/2018 printed 08/02/2019 page 1 of 1 project no. 46012-e design & construction group the governor nelson

PANELBDR(EXR)

BCP

PANELPP-BR(EXR)

MDP (EXR)

PANEL PB(EXR)

TOOLS 22

SUPPLYROOM 21

ENGINEREPAIR 20

17

AVIONICS13

TECHNICALINSPECTIONS &PUBLICATIONS 12

STORAGE 11

BOILER 19

13A

BATTERYSHOP 14

SHEETMETALSHOP 15

STORAGE 16

18

25

WP1 WP1 WP1 WP1 WP1WP1WP1 WP1

WP1

WP1 WP1

LV

LV

VS

LV VS

LV

LV LV LV LV LV

LV

LV LV6 LV6

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1-EM

F1

F1

F1 F1

F1-EM

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

F1

(EXR)

(EXR)

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

F4

(EXR) (EXR)

(EXR) (EXR)

(EXR) (EXR)

(EXR) (EXR)

(EXR) (EXR)

(EXR) (EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

F3F3

F3F3

PP

OS

PP

OS

OS

PP

OS

OS

PP

OS

OS

OS

PP

PP

OS

LV

PP

OS

OS

OS

OS OS

PP

OS

D1

D1

D1

D1

D1

PP PP

(EXR) (EXR)

PP PP PP

FLOOD LIGHT FL-1ON HANGAR ROOF

WP1

F3F3

F3F3

F3F3 PP

PANELPP-6(EXR)

LV

F1 F1

F4

PP

F4

F4

F4

F4

F4

F4

F4

F4 1

1

1

1

1

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LALA

LA

LA

(EXR)

(EXR)

(EXR)

(EXR)

(EXR)

LA

F1

F1

LA1

WP1

WP1

WP1

WP1 WP1 WP1

DESIGN & CONSTRUCTION

SAGE ENGINEERINGASSOCIATES, LLP

GENERAL NOTES:1. REFER TO SHEET E-001 FOR ADDITIONAL NOTES APPLICABLE TO THIS DRAWING.

SHORTEN AND RETHREAD EXISTING PENDANT CONDUITS SUPPORTING EXISTINGFIXTURES TO BE REMOVED. PROVIDE JUNCTION BOX AT END OF EACH CONDUIT STEMAND FLEXIBLE METAL CONDUIT TO REFEED REPLACEMENT FIXTURES SHOWN FOR BOTHPOWER AND CONTROL.

KEYED NOTES:1

1 CEILING IN THIS SPACE IS EXPOSED TO DECK AND/OR STRUCTURE.

CEILING IN THIS SPACE IS GYPSUM BOARD WITH LIGHTING FIXTURES RECESSED ORSURFACE MOUNTED BASED ON FIXTURE TYPE.

ACCESS TO THIS SPACE IS LIMITED. VERIFY WORK REQUIREMENTS AND OBTAINAPPROVAL FOR ACCESS WITH OWNER'S RESPRESENTATIVE PRIOR TO ENTRY ANDCOMPLETING ANY WORK.

CONSTRUCTION KEYED NOTES:

2

3

1 LIGHTING FIXTURE LOCATED IN A DAYLIGHTING ZONE. PROVIDE LIGHTING CONTROLSINDICATED TO DIM OR TURN OFF LIGHTING FIXTURE APPROPRIATELY WHEN THEPHOTOSENSOR INDICATES THE PRESENCE OF DAYLIGHT. REFER TO LIGHTING CONTROLDETAILS ON OTHER SHEETS.

PROVIDE LIGHTING CONTROLS IN THIS ROOM TO OPERATE HALF OF FIXTURES INVACANCY MODE AND HALF OF FIXTURES IN OCCUPANCY MODE. DISTRIBUTE FIXTURESOPERATING IN EACH MODE EVENLY AND EQUALLY ACROSS ROOM.

LIGHTING CONTROLS KEYED NOTES:

PLANNORTH

PLANNORTH

2

REVISED DRAWING DATED 7/26/2019

Page 5: DESIGN CONSTRUCTION GROUP THE GOVERNOR NELSON A ... 01 E.pdf · updated 05/24/2018 printed 08/02/2019 page 1 of 1 project no. 46012-e design & construction group the governor nelson

DESIGN & CONSTRUCTION

SAGE ENGINEERINGASSOCIATES, LLP

EQUIPMENT NAMEXXX VOLTS, X PH, X WIRE

FED FROM PANEL XXXCIRCUIT XX, XX, XX

NOTES:

1. EXAMPLE PLATE SHOWN.

2. PROVIDE MINIMUM 1/4" HEIGHT WHITE LETTERINGON BLACK BACKGROUND.

3. ATTACH WITH WATERPROOF ADHESIVE.

1. THE ABOVE MOUNTING HEIGHTS SHALL APPLY TO ALL DEVICES UNLESS NOTED OTHERWISE ON THE PLANS. ALL NOTEDDIMENSIONS ARE TO THE CENTERLINE OF THE DEVICE FROM THE FINISHED FLOOR UNLESS NOTED OTHERWISE.

2. WHERE SPECIAL CONDITIONS PREVENT THE INSTALLATION OF DEVICES AT THE ABOVE HEIGHTS, THE EC SHALL VERIFYHEIGHTS ON SITE WITH THE DIRECTOR'S REPRESENTATIVE.

3. WHERE DEVICES ARE PROVIDED ABOVE OR BELOW EACH OTHER ALL DEVICE BOXES SHALL ALIGN VERTICALLY.

4. WHERE DEVICES ARE PROVIDED ON EACH SIDE OF A RATED WALL THE DEVICES SHALL BE OFFSET.

NOTES:

48" LIGHT SWITCHOR DIMMER

WALL MOUNTED EXIT SIGN

96"

54"

LIGHTING CONTROLINTERFACE

SCALE: NONEE-501

1

SCALE: NONEE-501

2

REVISED DRAWING DATED 7/26/2019