demonstration thermography report of trace & access of heating pipework & leaks

17
Demonstration Thermography Report Company Device Customer E-Mail: [email protected] Phone: 01420 544433 Andy McGrath - Testo Tester: 01790945 Serial No.: Testo 875-2 Alton Newman Lane Testo Ltd Various Dates Measuring Date: Trace & Access Heating System Pipework Demonstration Thermography Report Measuring Site: Demonstration Thermography Report to highlight the capabilities of the Testo 875 series Thermal Imaging cameras and IR software for the application of Tracing Heating System pipework and leaks. Task Alton, Hampshire, GU34 2QJ Cheriton House, Newman Lane, Testo Ltd 1/17 Page

Upload: testo-limited

Post on 02-Jul-2015

344 views

Category:

Business


0 download

TRANSCRIPT

Page 1: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

Company

Device

Customer

E-Mail: [email protected]

Phone: 01420 544433

Andy McGrath - Testo

Tester:

01790945Serial No.:Testo 875-2

Alton

Newman Lane

Testo Ltd

Various DatesMeasuring Date:

Trace & Access Heating SystemPipework

Demonstration Thermography Report

Measuring Site:

Demonstration Thermography Report to highlight the capabilities of theTesto 875 series Thermal Imaging cameras and IR software for theapplication of Tracing Heating System pipework and leaks.

Task

Alton, Hampshire, GU34 2QJ

Cheriton House, NewmanLane,

Testo Ltd

1/17Page

Page 2: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00283(1).BMT 10/11/2009

Measuring Time:

08:59:13

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20207780lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9519.5Measure point 1

-20.00.9525.4Measure point 2

-20.00.9520.5Measure point 3

Profile line:

Thermal and Digital Images taken with Testo 875 series Thermal Imaging camera. Images taken a property,during a Demonstration of the Thermal Imaging camera..The Images are of the Bathroom floor Tracing the Heating system pipework to the radiator in the Loungenext door and through to the Rear Bedroom.Spot temperature markers have been added to the thermal image along with a Temperature Profile LineGraph to indicate the temperature variation. The Thermal image is displayed in " Iron" Palette.

Remarks:

2/17Page

Page 3: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00282(1).BMT 10/11/2009

Measuring Time:

08:57:32

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20207780lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9517.7Measure point 1

-20.00.9521.4Measure point 2

-20.00.9517.4Measure point 3

-20.00.9521.4Measure point 4

-20.00.9517.6Measure point 5

Profile line:

Thermal and Digital Images taken with Testo 875 series Thermal Imaging camera. Images taken at aProperty, during a Demonstration of the Thermal Imaging Camera.The Images are of the Rear Bedroom floor Tracing the Heating system pipework to the radiator in the room.Spot temperature markers have been added to the thermal image along with a Temperature Profile LineGraph.The Thermal image is displayed in " Iron" Palette.

Remarks:

3/17Page

Page 4: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00278(1).BMT 10/11/2009

Measuring Time:

08:39:54

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20207780lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9518.5Measure point 1

-20.00.9521.2Measure point 2

-20.00.9519.0Measure point 3

-20.00.9522.0Measure point 4

-20.00.9519.4Measure point 5

Profile line:

Thermal and Digital Images taken with Testo 875 series Thermal Imaging camera. Images taken atProperty, during Demonstration of the Thermal Imaging Camera.The demonstration was used in part of an Investigation to Trace/Detect the Heating System pipework in theproperty and to ascertain if there were any more possible leaks from the Heating /Hot Water system in theGround Floor Flat.The Images are of the Bedroom floor Tracing the Heating system pipework to the radiator in the room andthrough to the bathroom & Rear Bedroom.Spot temperature markers have been added to the thermal image along with a Temperature Profile LineGraph to indicate the temperature variation.The Thermal image is displayed in " Iron" Palette.

Remarks:

4/17Page

Page 5: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00084(1).BMT 07/05/2010

Measuring Time:

09:45:50

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20211321lens serial no.:

Date:

A Thermal Survey of the Heating system pipework was conducted during a Demonstration of the Testo 875series Thermal Imaging cameras to show its capabilities in respect of Trace & Access and Flood Restoration.The Thermal survey was conducted to trace the Heating system pipework and to establish if there were anyapparent anomalies / leaks.The survey was conducted in conjunction with an ongoing Investigation regarding a suspected Water Leak atthe property.The thermal image highlights the trace of the Heating pipework running from under the floor in the hallway,now running under the floor into the bedroom.However, having established thermally the location of the heating pipework in this section of the hall /bedroom, there was no thermal evidence of a leak in this specific area.Thermal Image displayed in "Iron" Palette.

Remarks:

5/17Page

Page 6: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00085(1).BMT 07/05/2010

Measuring Time:

09:50:34

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20211321lens serial no.:

Date:

A Thermal Survey of the Heating system pipework was conducted during a Demonstration of the Testo 875series Thermal Imaging cameras to show its capabilities in respect of Trace & Access and Flood Restoration.The Thermal survey was conducted to trace the Heating system pipework and to establish if there were anyapparent anomalies, leaks in the system.The survey was conducted in conjunction with an ongoing Investigation regarding a suspected Water Leak atthe property.The thermal image highlights the trace of the Heating pipework under the floor in the en suite bathroom,However, having established thermally the location of the heating pipework in this section of the en suite,there was no thermal evidence of a leak in this specific area.Thermal Image displayed in "Iron" Palette.The thermal image has then been combined / blended with the Digital image in the "TwinPix" function in theTesto IR software to provide the combination image.

Remarks:

6/17Page

Page 7: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00089(1).BMT 07/05/2010

Measuring Time:

10:01:42

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20211321lens serial no.:

Date:

A Thermal Survey of the Heating system pipework was conducted during a Demonstration of the Testo 875series Thermal Imaging cameras to show its capabilities in respect of Trace & Access and Flood Restoration.The Thermal survey was conducted to trace the Heating system pipework and to establish if there were anyapparent anomalies, leaks in the system.The survey was conducted in conjunction with an ongoing Investigation regarding a suspected Water Leak atthe property.The thermal image highlights the trace of the Heating pipework under the floor in the en suite bathroom,However, having established thermally the location of the heating pipework in this section of the en suite,there was no thermal evidence of a leak in this specific area.Thermal Image displayed in "Iron" Palette.The thermal image has then been combined / blended with the Digital image in the "TwinPix" function in theTesto IR software to provide the combination image.

Remarks:

7/17Page

Page 8: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00068(1).BMT 06/10/2009

Measuring Time:

09:31:58

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20207780lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9521.0Measure point 1

-20.00.9532.3Measure point 2

-20.00.9523.6Measure point 3

-20.00.9529.6Measure point 4

-20.00.9522.3Measure point 5

Profile line:

Thermal and Digital Images taken with Testo 875 series Thermal Imaging camera. Images during aDemonstration of the camera asPart of an Investigation to Trace/Detect the Heating System pipework and a possible leak from the system inthe Ground Floor of the premises.Images of Radiator and Floor area ajacent to the doorway .The Thermal image highlights the heatingpipework for the radiator / Heating system.A temperature profile graph has been added to highlight the temperature variation across the floor along withspot Temperature Markers. Thermal image in "Iron" Palette.

Remarks:

8/17Page

Page 9: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00070(1).BMT 06/10/2009

Measuring Time:

09:37:02

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20207780lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9521.7Measure point 1

-20.00.9526.2Measure point 2

-20.00.9521.1Measure point 3

Profile line:

Thermal and Digital Images taken with Testo 875 series Thermal Imaging camera.Images taken during aDemonstration of the camera as part of an Investigation to Trace/Detect the Heating System pipework and apossible leak from the system in the Ground Floor of the premises.Images of Radiator and Floor area in the shower room.The Thermal image highlights the heating pipeworkfor the radiator / Heating system.A temperature profile graph has been added to highlight the temperature variation across the floor along withspot Temperature Markers. Thermal image in "Iron" Palette.

Remarks:

9/17Page

Page 10: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00412.BMT 18/08/2010

Measuring Time:

10:21:42

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20221059lens serial no.:

Date:

Thermal Survey of Heating and Hot water system pipework, conducted during a Demonstration of the Testo875 series Thermal Imaging camera.Thermal Survey conducted of the Ground Floor area to ascertain if any anomalies / leaks can be detectedfrom the Heating and Hot Water system pipework.Images of the Kitchen / Utility Room area, the heating system pipework that can be thermally seen in thebackground is the main heating supply pipe from the boiler to the heating system pump located in acupboard in the hall. The other visible Heating system pipework is for the supply to the radiators in thekitchen and lounge.There are no visible Thermal anomalies or evidence of any possible leaks.

Remarks:

10/17Page

Page 11: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00422.BMT 18/08/2010

Measuring Time:

10:33:43

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20221059lens serial no.:

Date:

Thermal Survey of Heating and Hot water system pipework, conducted during a Demonstration of the Testo875 series Thermal Imaging cameras.Thermal Survey conducted of the Ground Floor area to ascertain if any anomalies / leaks can be detectedfrom the Heating and Hot Water system pipework.Images of the Kitchen / Utility Room area, the heating system pipework that can be seen in the backgroundis the main heating supply pipe from the boiler to the heating system pump located in a cupboard in the hall.The other Heating system pipework is for the supply to the radiators in the kitchen and lounge.There are no visible thermal anomalies or evidence of any possible leaks.

Remarks:

11/17Page

Page 12: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00425.BMT 18/08/2010

Measuring Time:

10:44:44

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20221059lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9519.0Measure point 1

-20.00.9520.0Measure point 2

-20.00.9519.4Measure point 3

-20.00.9519.5Measure point 4

-20.00.9524.8Measure point 5

-20.00.9518.9Measure point 6

Profile line:

Thermal Survey of Heating and Hot water system pipework, conducted during a Demonstration of the Testo875 series Thermal Imaging camera.Thermal Survey conducted of the Ground Floor area to ascertain if any thermal anomalies / leaks can bedetected from the Heating and Hot Water system pipework.Images of the Hall area, looking from the front door in the direction of the kitchen. The heating has beenswitched on for a short time and the heating system pipework for the supply and return to the radiators in thehallway, is now visible, (the supply pipework to the foreground). The other pipes that can be seen are comingfrom the lounge on the left, supplying the radiator in the hallway behind (adjacent to the front door) and thengoing on to supply to and return from the radiators in the bedrooms.There is no Thermal evidence of any anomalies / leaks.

Remarks:

12/17Page

Page 13: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

File: IV_00390.BMT 08/12/2008

Measuring Time:

13:37:01

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9519.1Measure point 1

-20.00.9519.0Measure point 2

-20.00.9515.4Measure point 3

-20.00.9515.8Measure point 4

-20.00.9521.5Hot spot 1

Profile line:

Demonstration Thermal survey conducted with Testo 875 series Thermal Imaging camera.Conducted in Glazed walkway between Lounge and Kitchen extension.The homeowner is complaining of possible water leak under the tiled floor.At the time that this Thermal and Digital image were taken, the heat pattern effect from the hot water pipesunder the floor were able to be seen in the the Thermal image, travelling the length of the walkway and nowa hot spot can be seen clearly.Spot Temperatures have been added to the image to indicate the temperatures along the path of the pipes.A Auto Hot spot indicator HS1 has been added to pinpoint the hottest point on the Thermal image. Atemperature profile line graph has been added to the thermal image, to highlight the temperature variationacross the tiled floor.As can be seen, the temperature in this area has increased and is indicating an anomaly that requiresinvestigation.

Remarks:

13/17Page

Page 14: Demonstration thermography report of trace & access of heating pipework & leaks

A Thermal Survey of the Heating / Hot Water System pipework was conducted at a property as part of ademonstration of the Testo 875 series Thermal Imaging cameras.The thermal survey was conducted on the Heating / Hot Water system on the Ground Floor of the dwelling toestablish if there are any anomalies in the system. This survey was conducted in conjunction with an ongoingInvestigaton regarding a suspected Water Leak at the Property. As can be seen, substantial areas of thefloor had been dug up to expose the pipework in order to try to find the leak. However no leak had beenfound.Thermal images were taken of the Heating system pipework in the Kitchen, adjacent to the refrigerator andnext to the area of floor that had been exposed.. As can be seen, the Thermal Imaging camera has beenused to Trace / Highlight the Heating system pipework, located under the floor. There is a Thermal anomalyin this section of the kitchen, Heating system pipework, which it was felt could be a leak and thereforenecessitated further investigation.Spot temperature markers have been added to the thermal image to show the temperature variation acrossthe section of the floor above the heating system pipework. A Temperature Profile Line Graph has also beenadded to provide further visual verification of the temperature variation across the floor / Heating systempipework. The Auto Hot Spot indicator has also been applied to the thermal image, (HS1), to automaticallyidentify the hottest point in a defined area. Subsequent investigation found a jointed section of the heatingpipework which was leaking.

Demonstration Thermography Report

File: IV_00039.BMT 16/03/2010

Measuring Time:

16:22:41

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20221059lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9522.4Measure point 1

-20.00.9530.7Measure point 2

-20.00.9523.7Measure point 3

-20.00.9531.4Hot spot 1

Profile line:

Remarks:

14/17Page

Page 15: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

A Thermal Survey of the Heating / Hot Water System pipework was conducted at a property as part of ademonstration of the Testo 875 series Thermal Imaging cameras.The thermal survey was conducted on the Heating / Hot Water system on the Ground Floor of the dwelling toestablish if there are any anomalies in the system. This survey was conducted in conjunction with an ongoingInvestigaton regarding a suspected Water Leak at the Property. As can be seen, substantial areas of thefloor had been dug up to expose the pipework in order to try to find the leak. However no leak had beenfound.Thermal images were taken of the Heating system pipework in the Kitchen, adjacent to the refrigerator andnext to the area of floor that had been exposed.. As can be seen, the Thermal Imaging camera has beenused to Trace / Highlight the Heating system pipework, located under the floor. There is a Thermal anomalyin this section of the kitchen, Heating system pipework, which it was felt could be a leak and thereforenecessitated further investigation.Spot temperature markers have been added to the thermal image to show the temperature variation acrossthe section of the floor above the heating system pipework. A Temperature Profile Line Graph has also beenadded to provide further visual verification of the temperature variation across the floor / Heating systempipework. The Auto Hot Spot indicator has also been applied to the thermal image, (HS1), to automaticallyidentify the hottest point in a defined area. Subsequent investigation found a jointed section of the heatingpipework which was leaking.

15/17Page

Page 16: Demonstration thermography report of trace & access of heating pipework & leaks

A Thermal Survey of the Heating / Hot Water System pipework was conducted at a property as part of ademonstration of the Testo 875 series Thermal Imaging cameras.The thermal survey was conducted on the Heating / Hot Water system on the Ground Floor of the dwelling toestablish if there are any anomalies in the system. This survey was conducted in conjunction with an ongoingInvestigaton regarding a suspected Water Leak at the Property. As can be seen, substantial areas of thefloor had been dug up to expose the pipework in order to try to find the leak. However no leak had beenfound.Thermal images were taken of the Heating system pipework in the Kitchen, adjacent to the refrigerator andnext to the area of floor that had been exposed.. As can be seen, the Thermal Imaging camera has beenused to Trace / Highlight the Heating system pipework, located under the floor. There is a Thermal anomalyin this section of the kitchen, Heating system pipework, which it was felt could be a leak and thereforenecessitated further investigation.Spot temperature markers have been added to the thermal image to show the temperature variation acrossthe section of the floor above the heating system pipework. A Temperature Profile Line Graph has also beenadded to provide further visual verification of the temperature variation across the floor / Heating systempipework. Subsequent investigation found a jointed section of the heating pipework which was leaking.

Demonstration Thermography Report

File: IV_00024.BMT 16/03/2010

Measuring Time:

16:15:41

20.0Refl. temp. [°C]:

0.95Emissivity:

Picture parameters:

lens type: Standard 32° 20221059lens serial no.:

Date:

Picture markings:

RemarksRefl. temp. [°C]Emiss.Temp. [°C]Measurement Objects

-20.00.9526.0Measure point 1

-20.00.9529.8Measure point 2

-20.00.9527.1Measure point 3

-20.00.9522.5Measure point 4

Profile line:

Remarks:

16/17Page

Page 17: Demonstration thermography report of trace & access of heating pipework & leaks

Demonstration Thermography Report

A Thermal Survey of the Heating / Hot Water System pipework was conducted at a property as part of ademonstration of the Testo 875 series Thermal Imaging cameras.The thermal survey was conducted on the Heating / Hot Water system on the Ground Floor of the dwelling toestablish if there are any anomalies in the system. This survey was conducted in conjunction with an ongoingInvestigaton regarding a suspected Water Leak at the Property. As can be seen, substantial areas of thefloor had been dug up to expose the pipework in order to try to find the leak. However no leak had beenfound.Thermal images were taken of the Heating system pipework in the Kitchen, adjacent to the refrigerator andnext to the area of floor that had been exposed.. As can be seen, the Thermal Imaging camera has beenused to Trace / Highlight the Heating system pipework, located under the floor. There is a Thermal anomalyin this section of the kitchen, Heating system pipework, which it was felt could be a leak and thereforenecessitated further investigation.Spot temperature markers have been added to the thermal image to show the temperature variation acrossthe section of the floor above the heating system pipework. A Temperature Profile Line Graph has also beenadded to provide further visual verification of the temperature variation across the floor / Heating systempipework. Subsequent investigation found a jointed section of the heating pipework which was leaking.

Demonstration Thermography Report to highlight the capabilities of the Testo 875 series Thermal Imaging camera and the Testo IR software.This is an example report for Demonstration purposes only. The Report format is the "standard" template from the selection of Report Templates available in the software.The images used in this report were taken with a Testo 875-2 Thermal Imaging camera.The Thermal images and this report are compiled to demonstrate the capability of the camera and the software and its suitability for Trace and Access Applications, tracing the Heating and Hot Water System pipework and locating leaks in these systems.

It should be noted that the Emissivity of individual materials / components were not taken into consideration for the purpose of the Demonstration and therefore the indicated (Apparent),temperatures may not be truely representative in this instance.For this application the accuracy of the temperatures indicated is not relevant.

The purpose of the Report is to Demonstrate the capabilities of the Thermal Imaging camera and its suitability for this application and to show the quality / Resolution of images taken and how they can be easily transferred into a Report.

The images taken were not of any specific areas or conditions/anomalies, the images taken/used were purely for the Demonstration of the camera and the software.The images taken were solely for the purpose of Demonstrating the Equipment and the software, not for specific fault finding in this instance.Testo do not provide Consultancy /Conclusions for any of the images taken during the course of the Demonstration.It is not the purpose of this report to specifically identify any faults found or comment on the images, it is to highlight the capabilities of the camera / software and its use for various applications.

Some of the features of the camera and software have been applied to the images, such as:Spot Temperature Markers have been added to the Thermal images to indicate temperatures.

Auto Hot / Cold Spot Indicator has been applied, which automatically highlights the Hottest or Coldest temperature point in a defined area.

Temperature Profile Line Graph shows the temperature variation in graph form across the subject.

The images are automatically Time and Date stamped to verify the time and date when the image was taken.The report also details the Emissivity Value relating to the image taken.

Andy McGrath - Testo

,05/10/2010

Review: