DELTA Danish Electronics,
Light & Acoustics
Venlighedsvej 4
2970 Hørsholm
Denmark
Tel. (+45) 72 19 40 00
Fax (+45) 72 19 40 01
www.delta.dk
This report is issued under the rules of DANAK (Danish Accreditat ion) and ILAC (Internat ional Laboratory Accreditat ion Cooperat ion) including its MRA (Mutual Recognit ion Arrangement). Further information can be found at www.danak.dk and www.i lac.org. The report must not be reproduced, except in ful l, without the written approval of DELTA.
DELTA Test Report
Version m
TEST Reg. no. 19
W e h e l p i d e a s m e e t t h e r e a l w o r l d
Type approval testing of C6200 and C6250 Performed for Selco A/S DANAK-1910203 Project no.: A505341 Page 1 of 54 including 6 annexes 19 June 2008
DANAK-1910203 DELTA-A505341 Page 2 of 54
HFR/lko
Title Type approval testing of C6200 and C6250
Test object C6200 and C6250
Detailed information is given in Section 2.
The test objects were received on 25 March 2008.
Report no. DANAK-1910203
Project no. A505341
Test period 25 March - 16 June 2008
Client Selco A/S Betonvej 10 4000 Roskilde Denmark
Tel.: +45 70 26 11 22 Fax: +45 70 26 25 22
Contact person Mr Jesper Højland E-mail: [email protected]
Manufacturer Selco A/S
Specifications IACS E10: Rev. 5, Dec 2006. “Test Specification for Type Approval. Test specification applicable, but not confined to, all equipment used for: - Control, protection and safety; - internal communication”.
IEC 60945: Fourth edition, 2002 “Maritime navigation and radio communication equipment and systems - General requirements - Methods of testing and required test results”.
IEC 60533: Second edition, 1999. “Electrical and electronic installations in ships - Electromagnetic compatibility”.
Results No malfunctions were detected. The criteria for compliance are listed in Section 3.2.
Test personnel Karsten Kruse Jensen Henrik Egeberg Nielsen Poul Nørgaard Poul Terkelsen Olling Truelsen
DANAK-1910203 DELTA-A505341 Page 3 of 54
HFR/lko
Date 19 June 2008
Project manager
Henrik Funding Raun, B.Sc.E.E. DELTA
Responsible
Susanne Otto, B.Sc.E.E. DELTA
DANAK-1910203 DELTA-A505341 Page 4 of 54
HFR/lko
Table of contents Page
1. Summary of test 6 1.1 Test requirements 6 1.2 Conclusion 7
2. Test objects 8 2.1 Test object(s) 8 2.2 Auxiliary equipment 9
3. General test conditions 10 3.1 Test setup 10 3.2 Criteria for compliance 10 3.3 Functional test 10 3.4 Standard environment 11 3.5 Test sequence 11
4. Test and results 12 4.1 Power supply failure 12 4.2 Power supply variations (permanent) 12 4.3 Low temperature (cold) 13 4.4 Dry heat 13 4.5 Damp heat, cyclic 14 4.6 Insulation resistance 15 4.7 High voltage 15 4.8 Resonance search (4 g) 16 4.9 Endurance - random (4 grms) 16 4.10 Electrostatic discharge 17 4.11 Radiated radio frequency interference 18 4.12 Conducted low frequency interference 19 4.13 Conducted radio frequency interference 19 4.14 Fast transients (burst) 20 4.15 Slow transients (surge) 21 4.16 Radiated emissions 21 4.17 Conducted emissions 22 4.18 Enclosure protection, IP 2X 23
Annex 1 List of instruments 24
Annex 2 Photos 26
Annex 3 Test record sheets - Conducted emissions 35
Annex 4 Test record sheets - Radiated emissions 42
Annex 5 Measurement curves - Vibration 47
DANAK-1910203 DELTA-A505341 Page 5 of 54
HFR/lko
Annex 6 Functional test procedure (from Client) (This annex is informative and not part of the accredited report) 53
DANAK-1910203 DELTA-A505341 Page 6 of 54
HFR/lko
1. Summary of test
1.1 Test requirements Test Test method Power supply failure IACS E10:2006 Power supply variations IEC 60945:2002, IACS E10:2006 Low temperature (cold) IEC 60068-2-1:2007 Dry heat IEC 60068-2-2:2007 Damp heat (cyclic) IEC 60068-2-30:2005 Insulation resistance IACS E10:2006 High voltage IACS E10:2006 Vibration (resonance search) IEC 60068-2-6:2007 Vibration (endurance - random) IEC 60068-2-64:1993 Electrostatic discharges IEC 61000-4-2:2001 Radiated radio frequency interference IEC 61000-4-3:2006 Conducted low frequency interference IACS E10:2006 Conducted radio frequency interference IEC 61000-4-6:2004 Electrical fast transients (burst) IEC 61000-4-4:2004 Slow transients (surge) IEC 61000-4-5:2005 Radiated emissions CISPR 16-1:1999, CISPR 16-2:2002, Conducted emissions CISPR 16-1:1999, CISPR 16-2:2002, Enclosure protection, IP 2X IEC 60529:2001
DANAK-1910203 DELTA-A505341 Page 7 of 54
HFR/lko
1.2 Conclusion
The test objects mentioned in this report meet the relevant requirements of the standards stated below.
• IACS E10:2004
• IEC 60533:1999
• IEC 60945:2002
The test results relate only to the object tested.
DANAK-1910203 DELTA-A505341 Page 8 of 54
HFR/lko
2. Test objects
2.1 Test object(s)
Test object 2.1.1
Name of test object Generator Controller Model / type C6200 Part no. C6200.0010 Serial no. 413643 FCC ID - Manufacturer Selco A/S Supply voltage 24 VDC Comments The customer states as follows, regarding
modifications of the test object: “Modification 1: A capacitor of 10nF has been added to the reset pin 44 of the DSP (ADSP2184, IC8). Modification 2: A T-Filter 22nF has been added to the analogue output 1 and 2.”
Test object 2.1.2
Name of test object Hand Terminal for C6200 Model / type C6250 Part no. C6250.0010 Serial no. 409497 FCC ID - Manufacturer Selco A/S Supply voltage 24 VDC through CAN bus Comments -
DANAK-1910203 DELTA-A505341 Page 9 of 54
HFR/lko
2.2 Auxiliary equipment
Auxiliary equipment 2.2.1
Name of auxiliary equipment Sigma UI Module Model / type S6500 Part no. S6500.0010 Serial no. 381405 FCC ID - Manufacturer Selco A/S Supply voltage 24 VDC Comments -
DANAK-1910203 DELTA-A505341 Page 10 of 54
HFR/lko
3. General test conditions
3.1 Test setup
A drawing of the test setup is enclosed in Annex 6.
3.2 Criteria for compliance
No change of the actual operational states of the test objects is allowed. However, temporary change is allowed during the power supply failure test.
In addition, the following generic acceptance criteria for compliance were in force during the EMC immunity testing:
• Performance Criterion A: (For continuous phenomena): The EUT shall continue to operate as intended during and after the test. No degradation of performance or loss of function is allowed as defined in the relevant equipment standard and in the technical specification published by the manufacturer.
• Performance Criterion B: (For transient phenomena): The EUT shall continue to operate as intended after the tests. No degradation of performance or loss of function is allowed as defined in the technical specification published by the manufacturer. During the test, degradation or loss of function or performance which is self-recoverable is, however, allowed but no change of actual operating state or stored data is allowed.
• Performance Criterion C: Temporary degradation or loss of function or performance is allowed during and after the test, provided the function is self-recoverable, or can be restored by the operation of the controls as defined in the relevant equipment standard and in the technical specification published by the manufacturer.
3.3 Functional test
A functional test was performed before, during (if specified) and after each test. The functional test was carried out in accordance with the functional test procedure provided by the customer.
The functional test procedure is given in Annex 6.
DANAK-1910203 DELTA-A505341 Page 11 of 54
HFR/lko
3.4 Standard environment
Normal environmental condition:
Temperature : 15 °C - 35 °C Humidity : 25 %RH - 75 %RH Air pressure : 86 kPa - 106 kPa (860 mbar - 1060 mbar) Power supply voltage : Unom. ±3%
3.5 Test sequence
DANAK-1910203 DELTA-A505341 Page 12 of 54
HFR/lko
4. Test and results
4.1 Power supply failure
Test methods
IACS E10, Test No. 3.
Procedure
The power supply is interrupted 3 times within 5 minutes with a break time of 60 seconds.
Normal power-up procedure is to be obtained after each power break.
Results
No malfunction was observed during the exposure, and the function of the test objects was OK after each exposure.
One of the power supply failures was made during the boot sequence.
Performance criterion: C.
4.2 Power supply variations (permanent)
Test method
IACS E10, Test No. 4.
IEC 60945, Section 5.2.2.
Procedure (24 VDC input)
Unom. = Nominal supply voltage = 24 VDC
Exposures, each with a duration of 15 minutes, are performed at the following supply voltages:
U1 = Un +30 % = 31.2 VDC U2 = Un -25 % = 18.0 VDC
The test objects are observed during the exposures, and a functional test is performed at the end of each exposure.
An additional power supply variations test is performed as part of the functional test during the low temperature and the dry heat test profiles.
DANAK-1910203 DELTA-A505341 Page 13 of 54
HFR/lko
Results
No malfunction was observed during the exposure, and the function of the test objects was OK after the exposure.
Performance criterion: A.
4.3 Low temperature (cold)
Test method
IEC 60068-2-1:2007, Test Ad: Cold for heat-dissipating object with gradual change of temperature.
Severity and procedure
Temperature : -15 °C Duration : 16 hours
The test objects are de-energised during the exposure. However, during the last 2 hours of the exposure, the test objects are energised and a functional test is performed.
A power supply variations test ref. Section 4.2 is performed as part of the functional test during the low temperature test profile.
After recovery, a functional test and an insulation resistance test are performed in standard environment.
Results
No malfunction was observed during the exposure and the function of the test objects was OK during the last 2 hours of the exposure and after recovery.
4.4 Dry heat
Test method
IEC 60068-2-2:1974, Test Bd: Dry heat for heat-dissipating object with gradual change of temperature, Amendment 1 (1993), Amendment 2 (1994).
Severity and procedure
Temperature : +70 °C Duration : 16 hours Humidity : Below 50 %RH
DANAK-1910203 DELTA-A505341 Page 14 of 54
HFR/lko
The test objects are energised and in normal operating condition during the exposure. During the last hour of the exposure, a functional test is performed.
A power supply variations test ref. Section 4.2 is performed as part of the functional test during the dry heat test profile.
After recovery the functional test is repeated in standard environment.
Results
No malfunction was observed during the exposure and the function of the test objects was OK during the last 2 hours of the exposure and after recovery.
4.5 Damp heat, cyclic
Test method
IEC 60068-2-30 (2005), Test Db: Damp heat cyclic (12 + 12 hours’ cycle), Variant 1.
Severity and procedure
Lower temperature : 25 °C Humidity at lower temperature : >95 %RH
Upper temperature : 55 °C Humidity at upper temperature : 93 %RH Number of cycles : 2
During the first cycle, the test objects are energised and in normal operational mode. A functional test is performed during the first 2 hours of the 55 °C phase.
During the second cycle, the test objects are de-energised. However, during the last 2 hours of the second 55 °C phase, the test objects are energised and a functional test is performed.
After recovery the test objects are energised and a functional test and an insulation resistance test are performed in standard environment.
Results
No malfunction was observed during the exposure, and the function of the test objects was OK during the first and second cycle at 55 °C and 93 %RH and after recovery.
No corrosion attack was observed after the exposure.
DANAK-1910203 DELTA-A505341 Page 15 of 54
HFR/lko
4.6 Insulation resistance
Test method
IACS E10, Test No. 9.
Procedure
The insulation resistance is measured between shorted supply terminals and earth with 50 VDC for 24 VDC power ports. The insulation resistance has to be above 10 MΩ initially, and above 1 MΩ after the cold, damp heat and high voltage exposures.
Results
Cable designation
Test condition
Test voltage[Vrms]
Duration [sec]
Insulation resistance
[MΩ] Initial 50 VDC 60 sec. > 10 MΩ
After Low temperature test
50 VDC 60 sec. > 1 MΩ
After Damp heat test
50 VDC 60 sec. > 1 MΩ
DC power port
After High voltage test
50 VDC 60 sec. > 1 MΩ
4.7 High voltage
Test method
IACS E10, Test No. 10.
Procedure
550 VAC, 50 Hz is applied between shorted supply terminals and earth for 1 minute for the 24 VDC supply line.
No flashover, breakdown etc. is acceptable.
Results
No flashover or breakdown was observed during the exposure. The insulation resistance was OK after the exposure.
DANAK-1910203 DELTA-A505341 Page 16 of 54
HFR/lko
4.8 Resonance search (4 g)
Test method
IEC 60068-2-6:2007, Test Fc: Vibration (sinusoidal).
Severity and procedure
Frequency range : 2 - 100 Hz Frequency / amplitude : 2 - 25 Hz : ± 1.6 mm 25 - 100 Hz : ± 4 g Sweep rate : Max. 0.5 octave/min. Number of axes : 3 mutually perpendicular
The test objects are de-energised during the exposure.
During the resonance search, the resonance frequencies are determined by means of stroboscopic light with slow motion facility and accelerometer measurements of the amplification factors (Q).
Resonance frequencies with an amplification factor above 2 are recorded.
Results
Amplification factor above 2 was recorded.
Place of measurement Axis Frequency [Hz]
Amplification factor
X 2 - 100 < 2 Y 2 - 100 < 2 C6200 Z 75 7.8 X 2 - 100 < 2 Y 2 - 100 < 2 C6250 Z 100 2.7
4.9 Endurance - random (4 grms)
The sinusoidal vibration test according to IACS E10 is replaced by random vibration test according to “Environmental test specification for instrumentation and automation equipment” No. 2.4, issued April 2006 by DNV.
This random vibration test will cover the requirements of the sinusoidal vibration test according to IACS E10.
DANAK-1910203 DELTA-A505341 Page 17 of 54
HFR/lko
Test method
IEC 60068-2-64:1993, Test Fh: Vibration, broadband random (digital control).
Severity and procedure
Frequency range : 2 - 100 Hz Acceleration spectral : 2 - 25 Hz : +12 dB/octave Density : 25 - 100 Hz : 0.2 g2/Hz Total RMS level : 4.0 g Duration : 150 minutes per axis Number of axes : 3 mutually perpendicular
The test objects are energised and in normal operational mode during the exposures. A functional test is performed during and after the exposure in each axis.
A visual inspection is performed after the exposure.
Results
No malfunction was observed during the exposure and the function of the test specimens was OK during and after the exposure in each axis.
No damage was observed after the exposures.
4.10 Electrostatic discharge
Test method
IEC 61000-4-2:2001: Testing and measurement techniques - Electrostatic discharge immunity test.
Severity and procedure
Air discharge : 2, 4 and 8 kV Contact discharge : 2, 4 and 6 kV Energy storage capacitance : 150 pF
Discharge resistance : 330 Ω Polarity : + and - Number of discharges : 10 per polarity at each test point
The discharges are applied only to such points and surfaces of the test objects, which are accessible to personnel during normal use.
DANAK-1910203 DELTA-A505341 Page 18 of 54
HFR/lko
Contact discharges are applied to conductive surfaces and coupling planes. Air discharges are applied to insulating surfaces.
The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure.
Results
No malfunction was observed during the exposure and the function of the test objects was OK after the exposure.
Performance criterion: B.
4.11 Radiated radio frequency interference
Test method
IEC 61000-4-3:2006: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test.
Severity and procedure
Frequency range : 80 - 2000 MHz Field strength : 10 V/m Modulation : 80 % AM, 1000 Hz sine wave
The test is performed in a semi anechoic room. The field is generated using linearly polarised broadband antennas.
The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure and a functional test is performed after the exposure.
Results
No malfunction was observed during the exposure and the function of the test objects was OK after the exposure.
Performance criterion: A.
DANAK-1910203 DELTA-A505341 Page 19 of 54
HFR/lko
4.12 Conducted low frequency interference
Test method
IACS E10:2006, Test No. 15.
Severity and procedure
Frequency range : 0.05 - 10 kHz Amplitude (DC-supplied) : 0.05 - 10 kHz : 10 % of Unom./ min. 3 Vrms Maximum applied power : 2.0 W
The impedance of the test generator is less than 1 Ω.
The test signal is superimposed on the power supply lines via a coupling transformer.
The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test objects was OK after the exposure.
Performance criterion: A.
4.13 Conducted radio frequency interference
Test method
IEC 61000-4-6:2004: Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields.
Severity and procedure
Frequency range : 150 kHz - 80 MHz Amplitude : 0.15 - 80 MHz : 10 Vrms Modulation : 80 % AM, 400 Hz sine wave Sweep rate : 0.15 - 80 MHz : 1.5 × 10−3 decades/s
The test objects are supplied with power via a coupling / decoupling network.
The test signal is coupled to the power lines and signal lines via coupling networks. The coupling impedance is 150 Ω.
DANAK-1910203 DELTA-A505341 Page 20 of 54
HFR/lko
The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test objects was OK after the exposure.
Performance criterion: A.
4.14 Fast transients (burst)
Test method
IEC 61000-4-4:2004: Testing and measurement techniques - Section 4: Electrical fast transient / burst immunity test.
Severity and procedure
Amplitude : 2 kV on power lines : 1 kV on signal lines Pulse rise time : 5 ns Pulse duration : 50 ns
Generator impedance : 50 Ω Repetition rate : 5 kHz Burst duration : 15 ms Burst period time : 300 ms
The test objects are supplied with power via a transient coupling network. The test signal is successively coupled to each power line and protective earth with reference to the ground plane.
The test signal is injected on the signal lines using a capacitive coupling clamp. The clamp is successively used on selected signal cables.
The test signal is injected on the power lines for 5 minutes, using each coupling mode and each polarity, and then on the signal lines for 5 minutes using each polarity.
The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure and a functional test is performed after the exposure.
DANAK-1910203 DELTA-A505341 Page 21 of 54
HFR/lko
Results
No malfunction was observed during the exposure and the function of the test objects was OK after the exposure.
Performance criterion: B.
4.15 Slow transients (surge)
Test method
IEC 61000-4-5:2005: Testing and measurement techniques - Surge immunity test.
Severity and procedure
Amplitude power ports : 1 kV line-to-earth, 0.5 kV line-to-line Voltage rise time : 1.2 µs (open circuit) Voltage decay time : 50 µs (open circuit)
The impedance of the test generator is 2 Ω for line-to-line coupling and 12 Ω for line-to-earth coupling.
The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure.
Results
No malfunction was observed during the exposure and the function of the test objects was OK after the exposure.
Performance criterion: B.
4.16 Radiated emissions
Test methods
CISPR 16-1:1999: Specification for radio disturbance and immunity measuring apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus.
CISPR 16-2:2002: Specification for radio disturbance and immunity measuring apparatus and methods. Part 2: Methods of measurement of disturbances and immunity.
DANAK-1910203 DELTA-A505341 Page 22 of 54
HFR/lko
Severity and procedure
General power distribution zone.
Frequency range : 0.15 - 2000 MHz
Limits (quasi-peak) : 0.15 - 30 MHz : 80 - 50 dBμV/m 30 - 100 MHz : 60 - 54 dBμV/m 100 - 2000 MHz : 54 dBμV/m, except for 156 - 165 MHz : 24 dBμV/m
The electric field is measured with antennas at a distance of 3 m.
The measuring bandwidth is 200 Hz in the frequency range 10 kHz - 150 kHz, 9 kHz in the frequency range 150 kHz - 30 MHz and 120 kHz in the frequency range 30 MHz - 2000 MHz, except for the frequency range 156 MHz - 165 MHz where the measuring bandwidth is 9 kHz.
The test objects are energised and in normal operational mode during the measurement.
Results
The radiated emissions were within the specified limits. Test record sheets of the radiated emission measurements are enclosed in Annex 4.
4.17 Conducted emissions
Test methods
CISPR 16-1:1999: Specification for radio disturbance and immunity measuring apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus.
CISPR 16-2:2002: Specification for radio disturbance and immunity measuring apparatus and methods. Part 2: Methods of measurement of disturbances and immunity.
Severity and procedure
General power distribution zone.
Frequency range : 0.01 - 30 MHz
Limits (quasi-peak) : 0.01 - 0.15 MHz : 120 - 69 dBμV 0.15 - 0.50 MHz : 79 dBμV 0.50 - 30 MHz : 73 dBμV
The radio frequency voltage is measured at the power supply terminals of the test object by a receiver through an artificial mains network.
DANAK-1910203 DELTA-A505341 Page 23 of 54
HFR/lko
The measuring bandwidth is 200 Hz in the frequency range 10 kHz - 150 kHz and 9 kHz in the frequency range 150 kHz - 30 MHz.
The test objects are energised and in normal operational mode during the measurement.
Results
The conducted emissions were within the specified limits. Test record sheets of the conducted emission measurements are enclosed in Annex 3.
4.18 Enclosure protection, IP 2X
Test method
IEC 60529:2001: Degrees of protection provided by enclosures (IP Code).
Severity and procedure
The test specimen was subjected to a test corresponding to IEC 60529:2001, table 1, first characteristic numeral 2 (IP 2X): “Protection against access to hazardous parts with a finger”, and thus IEC 60945:2001, clause 12.1: “Protection against access to dangerous voltages”.
Results
The test objects have adequate protection against access to hazardous parts with a finger, i.e. no openings greater than 12 mm Ø were measured.
DANAK-1910203 DELTA-A505341 Page 24 of 54
HFR/lko
Annex 1
List of instruments
DANAK-1910203 DELTA-A505341 Page 25 of 54
HFR/lko
List of instruments
NO. DESCRIPTION MANUFACTURER TYPE NO. Y221A EL.DYN SHAKER LING DYNAMICS V875-440 Acc. 91 ACCELEROMETER BRÜEL & KJÆR 4371 22617 ACCELEROMETER BRÜEL & KJÆR 4393 Acc. 72 ACCELEROMETER BRÜEL & KJÆR 4393 22603 ACCELEROMETER BRÜEL & KJÆR 4393 22604 ACCELEROMETER BRÜEL & KJÆR 4393 22585 ACC. PRE-AMP. BRÜEL & KJÆR 2626 22613 ACC. PRE-AMP. 4-CHAN. BRÜEL & KJÆR 2692 22631 VIBR. CONTROLLER SIGNALSTAR VECTOR U2 22601 VOLTMETER HEWLETT-PACKARD 34401A 22616 OSCILLOSCOPE ISOTECH ISR620 EVFGT-19 CLIMATIC CHAMBER DELTA VKF875-3 EVFGT-28 CLIMATIC CHAMBER DELTA VF 10 29223 CURRENT PROBE SINGER 91550-4 29342 REFLECTOMETER COUPLER, 600-4200 MHz ROHDE & SCHWARZ ZPD
29410 CURRENT PROBE AMPLIFIER FOR 29707 AND 49035 TEKTRONIX TM501 & AM503T
29691 0.01 - 20 GHz. SYNTH. SWEEPER HEWLETT-PACKARD 83620A 29694 1-12 GHz. HORN ANTENNA. LOGIMETRICS AN 8200 F 29696 HF CURRENT INJ. CLAMP LUTHI EM 101 29703 LF POWER AMPLIFIER BRÜEL & KJÆR 2708 29781 DIGITAL MULTIMETER W. HPIB HEWLETT-PACKARD 34401A 29800 RF ATTENUATOR, 50 OHM, 10 dB, DC-12.4 GHz SUHNER 6810.17.A
29806 BROADBAND POWER AMPLIFIER, 10 kHz-220 MHz, 75 W AMPLIFIER RESEARCH 75A220
29813 2-LINE CDN NETWORK, IEC 61000-4-6 MEB M2 29815 3-LINE CDN NETWORK, IEC 61000-4-6 MEB M3
29844 -40 dBc VOLTAGE SAMPLER, DC-100 MHz DELTA EMC DEPT. SAMPLER_VER_2
29846 RF GENERATOR, 9 kHz-2.4 GHz MARCONI 2024 29864 CAPACITIVE COUPLING CLAMP DELTA EMC IEC 1000-4-4 29865 CAPACITIVE COUPLING CLAMP DELTA EMC IEC 1000-4-4 29879 DIFFERENTIAL HIGH VOLTAGE PROBE, DC-25 MHz TEKTRONIX P5200 29911 DIGITAL MULTIMETER W. HPIB HEWLETT-PACKARD 34401A
29913 ELECTRICAL FAST TRANSIENT (BURST) GENERATOR EM TEST EFT 500
29914 ELECTRONIC SURGE GENERATOR EM TEST VCS 500 29936 SAMPLING OSCILLOSCOPE, 100 MHz, 500 MS/s TEKTRONIX TDS 340A 29977 RF POWER ATTENUATOR, 50 OHM, 6 dB, 150 W NARDA 769-6 29984 RF POWER AMPLIFIER, 0.8-2.2 GHz, 200W MILMEGA AS0822-200
29994 ESD GENERATOR, AIR AND CONTACT DISCHARGE EM TEST ESD 30, P18 & P30
49000 SINGLE CHANNEL POWER METER DISPLAY UNIT ROHDE & SCHWARZ NRVS
49009 CABLE#36, 3,25 M, 50 OHM, COAX CABLE, N(STRAIGHT)-7/16, ROOM1 SUHNER RG 214/U
49035 ACTIVE CURRENT PROBE HEAD FOR 29410 TEKTRONIX A6302
49521 SHIELD-LINE CDN NETWORK, IEC 61000-4-6 DELTA EMC DEPT. SHIELD-LINE CDN
49526 COAX RF DIODE DETECTOR, NEG. OUTPUT, CS TEST AGILENT 8471D 49527 COAX RF DIODE DETECTOR, NEG. OUTPUT, CS TEST AGILENT 8471D
49552 15 MHz FUNCTION / ARBITRARY WAVE GENERATOR HEWLETT-PACKARD 33120A
DANAK-1910203 DELTA-A505341 Page 26 of 54
HFR/lko
Annex 2
Photos
DANAK-1910203 DELTA-A505341 Page 27 of 54
HFR/lko
Photo 1. Vibration, resonance search, C6200.
Photo 2. Vibration, resonance search, C6250.
DANAK-1910203 DELTA-A505341 Page 28 of 54
HFR/lko
Photo 3. Vibration, endurance, e.g. Z-axis.
Photo 4. Radiated emissions (0.15 - 30 MHz).
DANAK-1910203 DELTA-A505341 Page 29 of 54
HFR/lko
Photo 5. Radiated emissions (30 - 2000 MHz).
Photo 6. Conducted emissions.
DANAK-1910203 DELTA-A505341 Page 30 of 54
HFR/lko
Photo 7. Radiated radio frequency interference (80 - 1000 MHz).
Photo 8. Radiated radio frequency interference (1000 - 2000 MHz).
DANAK-1910203 DELTA-A505341 Page 31 of 54
HFR/lko
Photo 9. Conducted radio frequency interference.
Photo 10. Conducted low frequency interference.
DANAK-1910203 DELTA-A505341 Page 32 of 54
HFR/lko
Photo 11. Electrostatic discharge.
Photo 12. Slow transients (surge).
DANAK-1910203 DELTA-A505341 Page 33 of 54
HFR/lko
Photo 13. Fast transients (burst).
Photo 14. Climatic testing, in test chamber.
DANAK-1910203 DELTA-A505341 Page 34 of 54
HFR/lko
Photo 15. Climatic testing, test setup.
DANAK-1910203 DELTA-A505341 Page 35 of 54
HFR/lko
Annex 3
Test record sheets - Conducted emissions
DANAK-1910203 DELTA-A505341 Page 36 of 54
HFR/lko
DELTA Electronics Testing, EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Line: Line. Power input: BUSBAR Voltage, 230 VAC Test Site: EMC - 4 Operator: KKJ - A505341 Test Specification: IEC 60945, E10 Comment: Sheet 06 Start of Test: 2008-03-28 SCAN TABLE: "CE 0.01-30 PK" Unit: dBµV Detector: Mode: Curve 1: MaxPeak ClearWrite
0
20
40
60
80
100
Level [dBµV]
10k 30k 100k 300k 1M 2M 4M 10M 30MFrequency [Hz]
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
MES CE 0.01-30 PK MaxPk x MES CE 0.01-30 QP QPk
LIM CE, IEC 60945, QP Conducted EmissionLIM CE, E-10 deck bridge Conducted Emission
DANAK-1910203 DELTA-A505341 Page 37 of 54
HFR/lko
DELTA Electronics Testing, EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Line: Neutral. Power input: BUSBAR Voltage, 230 VAC Test Site: EMC - 4 Operator: KKJ - A505341 Test Specification: IEC 60945, E10 Comment: Sheet 07 Start of Test: 2008-03-28 SCAN TABLE: "CE 0.01-30 PK" Unit: dBµV Detector: Mode: Curve 1: MaxPeak ClearWrite
0
20
40
60
80
100
Level [dBµV]
10k 30k 100k 300k 1M 2M 4M 10M 30MFrequency [Hz]
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
MES CE 0.01-30 PK MaxPk x MES CE 0.01-30 QP QPk
LIM CE, IEC 60945, QP Conducted EmissionLIM CE, E-10 deck bridge Conducted Emission
DANAK-1910203 DELTA-A505341 Page 38 of 54
HFR/lko
DELTA Electronics Testing, EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Line: Line. Power input: Generator Voltage, 230 VAC Test Site: EMC - 4 Operator: KKJ - A505341 Test Specification: IEC 60945, E10 Comment: Sheet 08 Start of Test: 2008-03-28
0
20
40
60
80
100
Level [dBµV]
10k 30k 100k 300k 1M 2M 4M 10M 30MFrequency [Hz]
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
MES CE 0.01-30 PK MaxPk x MES CE 0.01-30 QP QPk
LIM CE, IEC 60945, QP Conducted EmissionLIM CE, E-10 deck bridge Conducted Emission
DANAK-1910203 DELTA-A505341 Page 39 of 54
HFR/lko
DELTA Electronics Testing, EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Line: Neutral. Power input: Generator Voltage, 230 VAC Test Site: EMC - 4 Operator: KKJ - A505341 Test Specification: IEC 60945, E10 Comment: Sheet 09 Start of Test: 2008-03-28
0
20
40
60
80
100
Level [dBµV]
10k 30k 100k 300k 1M 2M 4M 10M 30MFrequency [Hz]
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxx
MES CE 0.01-30 PK MaxPk x MES CE 0.01-30 QP QPk
LIM CE, IEC 60945, QP Conducted EmissionLIM CE, E-10 deck bridge Conducted Emission
DANAK-1910203 DELTA-A505341 Page 40 of 54
HFR/lko
DELTA Electronics Testing, EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Line: Pos. Power input: AUX Supply, 24VDC Test Site: EMC - 4 Operator: KKJ - A505341 Test Specification: IEC 60945, E10 Comment: Sheet 10 Start of Test: 2008-03-28
0
20
40
60
80
100
Level [dBµV]
10k 30k 100k 300k 1M 2M 4M 10M 30MFrequency [Hz]
MES CE 0.01-30 PK MaxPk LIM CE, IEC 60945, QP Conducted EmissionLIM CE, E-10 deck bridge Conducted Emission
DANAK-1910203 DELTA-A505341 Page 41 of 54
HFR/lko
DELTA Electronics Testing, EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Line: Neg. Power input: AUX Supply, 24VDC Test Site: EMC - 4 Operator: KKJ - A505341 Test Specification: IEC 60945, E10 Comment: Sheet 11 Start of Test: 2008-03-28
0
20
40
60
80
100
Level [dBµV]
10k 30k 100k 300k 1M 2M 4M 10M 30MFrequency [Hz]
MES CE 0.01-30 PK MaxPk LIM CE, IEC 60945, QP Conducted EmissionLIM CE, E-10 deck bridge Conducted Emission
DANAK-1910203 DELTA-A505341 Page 42 of 54
HFR/lko
Annex 4
Test record sheets - Radiated emissions
DANAK-1910203 DELTA-A505341 Page 43 of 54
HFR/lko
DELTA Electronics Testing EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Ant: Activ loop 0 Deg. Voltage: 24 VDC and 230 VAC Test Site: EMC - 5 Operator: PFN - A505341 Test Specification: E10 & IEC 60945 & IEC 60533 Comment: Sheet 04 Start of Test: 27-03-2008 / 13:20:40
0
10
20
30
40
50
60
70
80
Level [dBµV/m]
150k 300k 500k 1M 2M 3M 5M 7M 10M 30MFrequency [Hz]
MES ME IEC 945 (0 MaxPk LIM ME, IEC60533, QP Magnetic EmissionLIM ME, IEC 60945, QP Magnetic EmissionLIM ME, E10, QP Magnetic Emission
DANAK-1910203 DELTA-A505341 Page 44 of 54
HFR/lko
DELTA Electronics Testing EMC Section EUT: C6200 & C6250 Manufacturer: Selco A/S Operating Condition: Ant: Activ loop 90 Deg. Voltage: 24 VDC and 230 VAC Test Site: EMC - 5 Operator: PFN - A505341 Test Specification: E10 & IEC 60945 & IEC 60533 Comment: Sheet 05 Start of Test: 27-03-2008 / 13:20:40
0
10
20
30
40
50
60
70
80
Level [dBµV/m]
150k 300k 500k 1M 2M 3M 5M 7M 10M 30MFrequency [Hz]
x
MES ME IEC 945 (90 MaxPk x MES mfield 0001_fin QP
LIM ME, IEC 60945, QP Magnetic EmissionLIM ME, E10, QP Magnetic Emission
DANAK-1910203 DELTA-A505341 Page 45 of 54
HFR/lko
DELTA Electronics Testing EMC Section EUT: C6200 and C6250 Manufacturer: Selco A/S Operating Condition: Ant. 1 m vertical Test Site: EMC - 5 Operator: HEN - A505341 Test Specification: IEC 60945, E10 and IEC 60533 Comment: Sheet 12 Start of Test: 27-05-2008
0
10
20
30
40
50
60
Level [dBµV/m]
30M 50M 70M 100M 200M 300M 500M 1G 2GFrequency [Hz]
x
xx
x x x
x MES Maximering_fin QP MES IEC945 1m 30 MaxPk 1 LIM RE, IEC 60945 Radiated Emission
MEASUREMENT RESULT: "Maximering_fin QP" 27-05-2008 15:07 Frequency Level Transd Limit Margin Height Azimuth Polarisation MHz dBµV/m dB dBµV/m dB cm deg 69.600000 41.50 8.0 54.0 12.5 124.0 18.00 VERTICAL 160.015000 15.00 12.7 24.0 9.0 167.0 214.00 HORIZONTAL 162.000000 18.00 12.7 24.0 6.0 101.0 181.00 VERTICAL 400.050000 49.40 18.9 54.0 4.6 124.0 318.00 VERTICAL 500.060000 49.10 20.8 54.0 4.9 104.0 27.00 VERTICAL 550.070000 48.00 21.8 54.0 6.0 104.0 25.00 VERTICAL
DANAK-1910203 DELTA-A505341 Page 46 of 54
HFR/lko
DELTA Electronics Testing EMC Section EUT: C6200 and C6250 Manufacturer: Selco A/S Operating Condition: Ant. 4 m horizontal Test Site: EMC - 5 Operator: HEN - A505341 Test Specification: IEC 60945, E10 and IEC 60533 Comment: Sheet 13 Start of Test: 27-05-2008
0
10
20
30
40
50
60
Level [dBµV/m]
30M 50M 70M 100M 200M 300M 500M 1G 2GFrequency [Hz]
x
xx
x x x
MES IEC945 4m 30 MaxPk 1 MES IEC945 4m 30 MaxPk 3
x MES Maximering_fin QP LIM RE, IEC 60945 Radiated Emission
DANAK-1910203 DELTA-A505341 Page 47 of 54
HFR/lko
Annex 5
Measurement curves - Vibration
DANAK-1910203 DELTA-A505341 Page 48 of 54
HFR/lko
2.0 10.0 100.010.0m
100.0m
1.0
10.0
100.0
Frequency, Hz
LogM
ag, R
atio
CH1
Mea1/Mea5 X: 99.9553 Y : 1.83774
test date 09-04-2008SKIB_4_RES start 09:07:13
Curve 1 Resonance search, X-axis (max. ampl. fact.), C6200.
2.0 10.0 100.010.0m
100.0m
1.0
10.0
100.0
Frequency, Hz
LogM
ag, R
atio
CH1
Mea1/Mea5 X: 99.9553 Y : 1.80966
test date 09-04-2008SKIB_4_RES start 12:30:27
Curve 2 Resonance search, Y-axis (max. ampl. fact.), C6200.
DANAK-1910203 DELTA-A505341 Page 49 of 54
HFR/lko
2.0 10.0 100.010.0m
100.0m
1.0
10.0
100.0
Frequency, Hz
LogM
ag, R
atio
CH1
Mea1/Mea5 X: 75.4316 Y : 7.80534
test date 09-04-2008SKIB_4_RES start 16:09:20
Curve 3 Resonance search, Z-axis (max. ampl. fact.), C6200.
2.0 10.0 100.010.0m
100.0m
1.0
10.0
100.0
Frequency, Hz
LogM
ag, R
atio
CH4
Mea4/Mea5 X: 99.9553 Y : 0.940748
SKIB_4_RES start 09:07:13
test date 09-04-2008
Curve 4 Resonance search, X-axis (max. ampl. fact.), C6250.
DANAK-1910203 DELTA-A505341 Page 50 of 54
HFR/lko
2.0 10.0 100.010.0m
100.0m
1.0
10.0
100.0
Frequency, Hz
LogM
ag, R
atio
CH4
Mea4/Mea5 X: 99.9553 Y : 1.67339
SKIB_4_RES start 09:23:51
test date 09-04-2008
Curve 5 Resonance search, Y-axis (max. ampl. fact.), C6250.
2.0 10.0 100.010.0m
100.0m
1.0
10.0
100.0
Frequency, Hz
LogM
ag, R
atio
CH4
Mea4/Mea5 X: 99.9553 Y : 2.71566
SKIB_4_RES start 16:09:20
test date 09-04-2008
Curve 6 Resonance search, Z-axis (max. ampl. fact.), C6250.
DANAK-1910203 DELTA-A505341 Page 51 of 54
HFR/lko
2.0 10.0 100.01.0u
10.0u
100.0u
1.0m
10.0m
100.0m
1.0
10.0
Frequency, Hz
LogM
ag, g
²/Hz
RMS: 3.94583
SKBDNV4GRMS start 09:36:13 test date 09-04-2008
Curve 7 Endurance vibration, X-axis, 4 g rms.
2.0 10.0 100.01.0u
10.0u
100.0u
1.0m
10.0m
100.0m
1.0
10.0
Frequency, Hz
LogM
ag, g
²/Hz
RMS: 3.9663
SKBDNV4GRMS start 12:41:53 test date 09-04-2008
Curve 8 Endurance vibration, Y-axis, 4 g rms.
DANAK-1910203 DELTA-A505341 Page 52 of 54
HFR/lko
2.0 10.0 100.01.0u
10.0u
100.0u
1.0m
10.0m
100.0m
1.0
10.0
Frequency, Hz
LogM
ag, g
²/Hz
RMS: 3.9679
SKBDNV4GRMS start 16:25:01 test date 09-04-2008 Curve 9 Endurance vibration, Z-axis, 4 g rms.
DANAK-1910203 DELTA-A505341 Page 53 of 54
HFR/lko
Annex 6
Functional test procedure (from Client)
(This annex is informative and not part of the accredited report)
DANAK-1910203 DELTA-A505341 Page 54 of 54
HFR/lko
C6200 Test description 1. Attach 9VDC batteries to the 3 wire’s ALARM, PROT TRIP and PROGRAMMABLE OUTPUTS 2. Attach 24VDC to AUX SUPPLY on C6200 and see AUX SUPPLY led light up 3. Attach CANBUS connection between C6200 and S6500 4. Attach 24VDC to S6500 AUX module, after a few seconds it will show the BUS and GEN
Voltage on the display. 5. Attach C6250, after a few seconds it will show data on the display 6. Attach 220VAC to GENERATOR VOLTAGE and BUSBAR VOLTAGE and see the GENERATOR
VOLTAGE and BUSBAR VOLTAGE led’s light up, and see 220VAC in the display’s of the S6500 and the C6250
7. The green SYNC led on C6200 will now light up 8. Bridge C/B and see the C/B led on the C6200 and the C/B CLOSED led on the S6500 light up 9. Bridge PROGRAMMABLE INPUTS and see led 1 on PROGRAMMABLE INPUTS and
PROGRAMMABLE OUTPUTS light up. 10. Attach a voltmeter on PAR LINES and measure 5VDC 11. Attach a voltmeter on ANA OUT and measure 5VDC 12. Attach a voltmeter on GOV CONTROL and measure 5VDC 13. Attach a voltmeter on AVR CONTROL and measure 500HZ with a duty cycle at 50% 14. Bridge ANA IN 15. Attach the RS485 cable from laptop to RS485 on the C6200 16. Run the C6200_RS485 test on the laptop 17. push the start button on the C6200_RS485 test program on the laptop 18. The unit are now ready for test 19. It is consider an error if any of the led’s on the C6200 alters its state