2 | 362PMR-B Dead Tank Circuit Breaker
ABB (www.abb.com) is a leader in power and automation technologies that enables utility and industry customers to improve their performance while lowering environmental impact.
The ABB Group of companies operates in approximately 100 countries and employs around 145,000 people.
ABB innovations for changing demands
A complete range of high voltage circuit breakersABB offers the widest range of high voltage circuit breakers on the market. Our portfolio of dead tank circuit breakers ranges from 72.5 kV to 800 kV.
ABB has a long history of developing innovative technologies to address the changing demands of power systems. As these systems continue to evolve, switching solutions must be designed to meet present-day applications as well as anticipate the future state of the grid.
362PMR-B Dead Tank Circuit Breaker | 3
Engineered to reduce switching transients
ABB is proud to offer the type 362PMR-B SF6 power circuit breaker, based on the well-established 362PMI-B platform, for applications requiring closing resistors.
StandardsThe 362PMR-B Dead Tank Circuit Breaker is tested for high transient recovery voltage (TRV) performance, ultimate mechanical endurance and is certified for class C2 capacitive switching.
– ANSI/IEEE C37.09– ANSI/IEEE C37.04– ANSI/IEEE C37.06– ANSI/IEEE C37.06.1
Certifications– ISO 9001– ISO 14001– OHSAS 18001
ApplicationsThe 362PMR-B was designed for:– overhead transmission lines, especially long transmission applications, with a potential for transient overoltage – transformer applications with a potential for inrush current– capacitive switching applications
Type PM circuit breaker familyWith just under 50,000 breakers delivered to date, spanning voltages up to 800 kV, the ABB type PM dead tank circuit breakers remain the most purchased brand in the industry. This is due to their low cost of ownership and strong performance, backed by industry-leading service and support.
Benefits of ABB’s advanced technology
Endurance to reduce extreme transientsThe 362PMR-B circuit breaker is designed with integrated pre-insertion resistors providing overvoltage protection for capacitor bank, transmission line and transformer switching.
Pre-insertion resistors (closing resistors) are used to limit over-voltages in the network during switching operations. The pre-insertion resistors are only used during closing and consist of resistor blocks that are connected in parallel with the breaking chamber. The resistor blocks will close the circuit approximately 8-12 ms before the arcing contacts. Pre-insertion resistors are mainly used at higher system voltages (≥362 kV).
Simple and reliable HMB mechanismEach fully integrated hydraulic mechanism is self lubricating, hermetically sealed from the atmosphere and weather protected, affording excellent reliability and long term stability.
– Longer lifetime and ease of service due to reduced lead content, more interchangeability of parts– Higher reliability due to fewer pump starts – Robust, compact design with non anodized sealing surfaces and a minimum number of moving parts– Simple adaptation to breakers
ABB backs the HMB mechanism with an industry-best 10 year warranty.
Easy installation and retrofit, saving time and money Installation time of approximately 16 hours as the breaker is shipped in only 4 sections (3 pressurized poles with bushing and mechanism attached, and frame with associated control housing).
No external capacitors needed except for short line faultFor short-line fault, the type 362PMR-B does not require any external capacitors up to the maximum rated fault current of 63kA, saving cost, installation time, and further substation space. For special fast-rate-of-rise applications per ANSI/IEEE C37.06.1, the circuit breaker requires no capacitance for the 7% short circuit rating and 2 nF capacitors for the 30% short-circuit current rating.
Enhanced safetyABB supplies shatter-proof composite bushings and ASME pressure vessel code certified tanks. Overpressure relief devices, designed to rupture in case of internal pressure build up, are also included as an enhanced safety feature.
4 | 362PMR-B Dead Tank Circuit Breaker
Single-break interrupter with pre-insertion resistorOur single piece high performance puffer interrupter utilizes state-of-the-art technology with dual-motion contacts, allowing for greater reliability. For questions on pre-insertion resistor options, contact the factory.
TanksSingle-piece tanks are ultrasonically cleaned, then leak tested in a vacuum sealed chamber using highly accurate helium mass spectrometer leak detection. Each tank is ASME pressure vessel tested and certified.
Control cubicleABB prides itself on offering generously sized control cubicles at workable heights to vastly improve access to the equipment over its lifetime.
Insulating mediumThe type PMR-B uses SF6 as the insulating medium. ABB has invested in monitoring technology, manufacturing techniques, and innovative designs to reduce SF6 gas leaks.
Features
BushingsABB offers a variety of bushing options, including silicone and porcelain insulators, to meet customer application needs and environmental conditions. ABB utilizes tapered designs where feasible to reduce the SF6 volume and therefore installed inventory in our customer’s fleet.
Bushing current transformersABB utilizes slipover bushing current transformer (BCT) designs for our dead tank product line which allow for cost effective, efficientand safe removal or exchange without removing the bushings.
HMB 4.1 mechanismThe moving contacts of each separate pole unit are driven by a type HMB-4 spring hydraulic mechanism that is mounted at one end of each interrupter tank. Mechanical energy is stored in a column of compression disk springs and is translated hydraulically to the pole’s operating shaft. Spring charge is automatically maintained by the operation of a universal motor and hydraulic pump.
362PMR-B Dead Tank Circuit Breaker | 5
Rated per ANSI and IEC standards
Maximum continuous voltage kV 380
Operating frequency Hz 50 / 60
Interrupting time 2 cycles
Impulse withstand voltage
2 µ-sec chopped wave kV Peak 1680
Full wave lightning impulse (BIL) kV Peak 1300
Switching impulse close / open kV Peak 825 / 900
Power frequency withstand voltage
60 Hz 1 minute dry withstand kV 555
Continuous current A 2000, 3000, 4000, 4400, 5000, 5500 (1)
Close and latch current kA 170
Short circuit breaking current kA 63
Minimum operating gas pressure @ 20° C psig 72
Normal operating gas pressure @ 20° C psig 87
Permissible ambient temperature °C -55 to +50 (2)
Interrupter enclosure dead tank
Configuration 3 pole units on individual frames
Design outdoor
Expected lifetime yrs ≥30
Dimensions (H x W x L) ft / mm 19.91 x 27.72 x 17.94 / 6069 x 8448 x 5469
Weight, SF6 gas lbs / kg 621 / 282
Operating mechanism
Type spring-hydraulic, type HMB-4.1
Quantity per breaker 3
Energy storage spring column, disc spring
Standard operating duty O-0.3s-CO-180s-CO
Stored operations 2
Seismic rating 0.5g value per IEEE 693
Charging source universal motor
Charging motor
Available voltages
VDC VAC
110 - 125220 - 250
110 - 125220 - 250
Power 650 W 1000 W
Operating current6 A @ 125 3 A @ 250
9 A @ 1254.5 A @ 250
Starting current 30 / 20 A 40 / 25 A
Max recharge time 88 seconds
Trip and close coils
Available voltages110-125 VDC220-250 VDC
Current
Trip3.5 A @ 120 V1.6 A @ 240 V
Close3.5 A @ 120 V1.6 A @ 240 V
Technical data
Above are not necessarily limiting values; further information available upon request.
Notes(1) 5000 A and above requires polymer insulators(2) Requires tank heaters on applications with ambient temperatures less than 30º C(3) Typical weight includes porcelain bushings and the maximum BCT load
6 | 362PMR-B Dead Tank Circuit Breaker
Physical data
Dimensions and specifications
Phase spacing 12 ft (5657.6 mm)
Height - installed 19.91 ft (6069 mm)
Width - installed 27.72 ft (8448 mm)
Length - installed 17.94 ft (5469 mm)
Shipping weight 22,473 lbs (10193.58 kg)
Footprint of frame 26.62 ft (8113 mm) x
7.98 ft (2433 mm)
Centerline to centerline 12 ft (3657.6mm)
Minimum height to live parts 19.30 ft (5884 mm)
Typical installed weight with porcelain bushings and maximum BCT’s
25,000 lbs (11,339.81 kg)
12’ (3657.6)
Phase Spacing12’ (3657.6)
Phase Spacing
27.38’ (8348)Installed
10.77’ (3283)Metal to Metal
5.55’ (1693)
2.5’ (762)Bottom of
Cabinet
13.03’ (3973)Clearance to Remove Interrupter
6.79’
10.77’ (3283)Metal to Metal
(2069)
4.50’(1371)
6.48’(1975)
7.64’ (2328)Center
Lineof
Breaker10.54’ (3214)Height
toUngrounded
Parts
19.30’ (5884)Height
toLiveParts
19.91’ (6069)8.96’
(2730)Strike
BushingCreep
9.87’ (3008)Metal to Metal
11.09’ (3381)Shipping Length
16.65’ (5075)
17.94’ (5469)
12’ (3657.6)
Phase Spacing12’ (3657.6)
Phase Spacing
27.38’ (8348)Installed
10.77’ (3283)Metal to Metal
5.55’ (1693)
2.5’ (762)Bottom of
Cabinet
13.03’ (3973)Clearance to Remove Interrupter
6.79’
10.77’ (3283)Metal to Metal
(2069)
4.50’(1371)
6.48’(1975)
7.64’ (2328)Center
Lineof
Breaker10.54’ (3214)Height
toUngrounded
Parts
19.30’ (5884)Height
toLiveParts
19.91’ (6069)8.96’
(2730)Strike
BushingCreep
9.87’ (3008)Metal to Metal
11.09’ (3381)Shipping Length
16.65’ (5075)
17.94’ (5469)
362PMR-B Dead Tank Circuit Breaker | 7
Typical electrical drawings
Protection and control interfaces
Popular CT options
Accessory Tier 1 Tier 2 Tier 3
Dual trip coils
125 VDC
AC / DC transfer
Mini-monitor (Qty.) 3 3 3
Emergency trip
EB-27 CT terminal blocks
Cabinet light - door activated
20 A GFI (cabinet exterior)
20 A receptacle (panel mounted)
Non-insulated wire terminals
Circuit breakers
Push buttons
Undervoltage relays
DC visible disconnect
Local remote switch
Screw down device nameplates
Fiber optic merging unit
SF6 monitor
Ratio
Accuracy
ANSI
IECRelaying Metering
600:5 MR C-400 / C-800 0.3B-0.5 5P10@15VA
1200:5 MR C-400 / C-800 0.3B-1.0 CLASS 0.5@30VA
2000:5 MR C-400 / C-800 0.3B-1.0 10P20@50VA
3000:5 MR C-400 / C-800 0.3B-1.8 CLASS 0.5@30VA
4000:5 MR C-400 / C-800 0.3B-2.0 CLASS 0.2@15VA
Typical controls features
125 / 250 VDC
(+)
52X152Y1 52CC-1
(LOW GAS)
52X1 52X1
52Y1
5A
5B
52Y152B
52B
52Y1
63
63 (LOW SPRING)
(-)
1
2
52B
DC close - pole 152X1 X relay, closing52Y1 Y relay, anti pump52B Auxiliary switch contact5A – 5B Remote close and reclose52CC-1 Close coil63 Permissive contact / alarm contact
125 / 250 VDC
/ (+)
11A
9A 9B 9C
52A
52A
52TC1
11B
52A
52A
52TC2
11C
52A
52A
52TC3
(-)
21
22
Primary DC trip9A – 11A Remote trip pole 19B – 11B Remote trip pole 29C – 11C Remote trip pole 352A Auxiliary switch contact52TC1, 52TC2, 52TC3 Trip coil
Notes:1) Secondary trip is same as primary2) DC close for poles 2 and 3 is same as pole 1
AC schematic42-1, 42-2, 42-3 Motor contactor88-1, 88-2, 88-3 Motor23-1 Non-adjustable thermostat
120 / 240 VAC
88-1MECH
HEATER70 W
4 2 - 1
4 2 - 1
4 2 - 2
4 2 - 2
4 2 - 3
4 2 - 3
88-2 88-3MECH
HEATER70 W
MECH HEATER
70 WCABINET HEATER
75 W
23-1
CABINET HEATER
75 W
CABINET HEATER
75 W
CABINET HEATER
75 W
8 | 362PMR-B Dead Tank Circuit Breaker
Installation and commissioningThe compact design is ideal for new or existing substation layouts for voltages up to 362 kV. The breaker fits within most existing footprints and can be used to quickly address the need for greater protection for minimal cost.
Those familiar with the PM line of breakers can typically install and commission the breaker within 2 days given a prepared foundation. The pole assemblies are shipped complete with positive SF6 pressure, and are installed on frames with control cabinet on site.
ABB offers supervision, installation, commissioning, and maintenance service on all ABB breakers.
The type 362PMR-B is shipped with completely assembled pole units filled with positive SF6 pressure. For domestic deliveries, all components are transported to the customer on a double-drop, air ride trailer. For non-domestic deliveries, the bushings are removed and packaged for shipping. Weight of gas at shipping pressure is provided with test report.
Shipping and installation
Representative installation of a 362 kV PMR breaker in the United States.
Note:We reserve the right to make technical changes or modify the contents of thisdocument without prior notice. With regard to purchase orders, the agreedparticulars shall prevail. ABB does not accept any responsibility whatsoever forpotential errors or possible lack of information in this document. We reserveall rights in this document and in the subject matter and illustrations containedtherein. Any reproduction–in whole or in parts–is forbidden without ABB’s priorwritten consent.
Copyright 2014 ABB.
All rights reserved.
Contact us
Doc
umen
t N
umb
er:
2G
NM
1101
50 /
Feb
ruar
y 20
15
ABB Inc. High Voltage Products - Dead Tank Breakers100 Distribution Circle Mount Pleasant, Pennsylvania 15666, USA Phone: +1 (724) 696-1500 Fax: +1 (724) 696-1502 www.abb.us/highvoltage