Quick Installation Guide
DC Power Supply System Integrated Applications
Minipack 1U System, Integrated DC Distribution
Torque RecommendationsType& Size
Torque(Nm)
T1 Screws M6 2.5T2 Screws M3 0.3
T3 AC, I/O 0.4T4 Battery 1.2T5 Load 0.5
Note: General tolerance: ±10%
ToolsPZ2
PH1
Flat 3.5mmFlat 6mm
Minipack 1U System, Integrated DC Distribution2 Rectifiers, Compack Controller, LVBD Contactor & 2 Battery MCBs, 6 Load Fuses
249.0mm
44.5mm(1U)
482.5mm (19”)
A1: 263043
Parts Overview
A2: (option)241117.120, (48VDC, 400W) 241117.130, (48VDC, 800W WIR)
(1-2) (1-2)
A4: (option)239128
Blind Cover
A3:242100.400
Quick Installation Guide Minipack 1U System, Integrated DC Distribution 356824.103, Issue 1 2009-11 2
Remove Top Lock Cover 1-2
Fasten to Cabinet 1-4
A(M3)
A1
A1
2
Top Lock Cover A(M3)
1.5cm0.5cm
1 PH1(2x)
ccw
Compack controller (A3)not inserted
A1
Cabinet
B(~M6)
B(~M6)
Cabinet
A1
Sliding Drawer Shelf inMaintenance Position
2
PZ2 (2x)(T1)
cw
3
PZ2 (2x)
(1/2 turn) ccw
1
4
CAUTION: Slide/rail mounted equipment is not to be usedas a shelf or a work space. To comply with UL requirements and supportthe sliding drawer shelf, always fasten theMinipack 1U system to the cabinet, rightbelow a rigid, supporting surface (plate orcabinet mounted equipment).
Quick Installation Guide Minipack 1U System, Integrated DC Distribution 356824.103, Issue 1 2009-11 3
Electrical Connections 1-8
Mains Protection Cover
–,–,+,+
BatteryTerminalsFlat 6mm (T4)
Fasten All Cables
8
A1Sliding Drawer Shelf in Maintenance Position
AC Earth (PE) Screw M6 (Chassis) PZ2
LN
TBY(Mains Input 1, Internal use)
AC Mains Input 1Flat 3.5mm (T3)
L N
TBX (AC Mains
Input 2)
N L
DC Earth (TE) Flat 6mm (Mounted M4 screw connects AC Earth (PE) to Positive DC Output (TE))
Internal 3 wiresMains Loom, ML
(blue, black, yellow& green)
F1, Load Fuse
DC Load Terminals (E)Flat 3.5mm (T5) (Plug-in Terminals)
External AC FusesRecommended Rating
16A-C Type Hy/Mag (Europe)20A-C Type Hy/Mag (USA)
1
AC Mains (OFF)
Max 2.5mm2(12AWG)
2(+,–)1(+,–)
6(+,–)
A3
FB1, Battery FuseLVBD
CAN1
7
2 FB1&FB2
OFF(0)
CAUTION: When using “Dual Mains Input”(two feeds 1phase 100-250VAC),turn AC mains OFF, remove theinternal 3 wires Mains Loom MLbetween TBY and TBX and connectthe second Mains feed to TBX.
4
Batteries
Correct Polarity
3 Max 10mm2(6AWG)
For installations in USA and Canada only!
– An AC Overvoltage Protec-tion Device (OVP) must be installed in the system’s AC input. The device must comply with overvoltage category II according to IEC60950-1, Class II by IEC61643-1 or Class C by DIN VDE0675 – For supply connectors, use wire suitable for at least 75ºC, type: FEPW, RH, RHW, THHW, YHW, THWN, ZHHW, USE, ZX or similar. Use copper conductors only
5
Max 4mm2(10AWG)DC Load
Electric Shock
WARNING: Do NOT unscrew theload fuses while poweris ON and the loadcables connected! To disconnect the loadwhile power is ON,always unplug the loadterminals (E). The loadfuse can then beunscrewed.
CAUTION:This equipment has aconnection between theearthed conductor of theDC supply circuit and theearthing conductor.
I/O TerminalsFlat 3.5mm (T3)
(Plug-in Terminals)
6 I/O Alarms
Max 1.5mm2 (14AWG)
FlatHandle in
lockedposition
A3A3
Handle raised in open position
Locked Compack Controller
A3
Ethernet
Pin 1
Pin 16=Dig 3– 5=Dig 3+ 4=Dig 2– 3=Dig 2+ 2=Dig 1– 1=Dig 1+
9=AL3-nc 8=AL3-no 7=AL3-c 6=AL2-nc 5=AL2-no 4=AL2-c 3=AL1-nc 2=AL1-no 1=AL1-c
Out
puts
In
puts
Contacts shown with de-energized coil (Alarm)
www.eltekvalere.com
Headquarters:Eltek Valere
Gråterudv. 8, Pb 2340 Strømsø, 3003 Drammen, NorwayPhone: +47 32 20 32 00 Fax: +47 32 20 32 10
This product is CE marked and complies with all currentrequirements for relevant standards and directives.
Copyright © Eltek Valere, 2009 This document may be changed without notice Art. No. 356824.103, Issue 1.0, 2009 Nov (draft5) Published 2009-12-dd
Start Up 1-4
Drawer Shelf in Operation Position 1-5
3
AC MainsON
A2
A1
PH1cw
CAUTION: Double Pole / Neutral Fusing. There is a Mains fuse in each line.
A2
A1
4
FB1&FB2ON(1)
1 A1
A2 2 CabinetA2
Electric Shock
WARNING: Mount blind covers in unused rectifier slots! Blind
Cover
A4
Technical Specifications AC Input 100-250V, 14.8A max Frequency 45-66Hz DC Output 43.5-57.6V, 33.3A max Suitable for connection to IT systems
Top Lock Cover
A1
1 A(M3) A(M3)
2 PH1(2x) (T2)
cw
Cabinet
4
PZ2 (2x)(T1) cw
5
PZ2 (2x)
(1/2 turn)cw
3
A1
C(~M6)
C(~M6)