1.2-MVA-SOLAR-STATION (Concrete)
Container with DC-distribu on, Inverters,Medium-Voltage Transformer and Switchgear
The solar sta on HSC1200C is a new development for large photovoltaic power plants. The concrete container includes the DC-distribu on, the inverter, the medium voltage transformer and the medium voltage switchgear. The HSC1200C is a plug and play solu on for quick installa on with low total costs. The HSC1200C is a completely factory-assembled systemonly the DC-connec ons to the photovoltaic array and the AC-connec on to the medium-voltage grid have to be done on site.The photovoltaic array is linked via fuses or circuit breakers and an EMC-fi lter to the input of the inverter. As an op on, the current in each string can be measured separately.The inverter system consists of two iden cal inverters. These inverters operate independently and feed their output power into di erent low-voltage windings of a special medium voltage transformer T1 (please refer to the block diagram below), op mized for the photovoltaic array. The container is connected to the grid via the internal medium-voltage switchgear. Op onally, the auxiliaries of the inverter system and the hea ng can be fed by transformer T2 or from an external source.Each inverter is supplied with all necessary control systems and has its own maximum-power-point tracker. As standard, a PC-based monitoring system with an Ethernet interface provides all important informa on to the user. In the unlikely case of malfunc on, a failure message is generated and sent automa cally. Op onally the communica on can be real-ized via GSM modem.
HSC1200C
HSC1200C
Block diagram
-
Technical Data Version 1.8
Helios Systems Wind&Sun Technologies CompanyInverters made by FeCon GmbH
www.helios-systems.netTel.: 0049 461 430 122-0 Fax: 0049 461 430 122-11 E-Mail: [email protected]
Electrical Data
Rated AC-power at 10 % of rated grid voltage 1000 kW
Rated apparent power 1210 kVA
Rated grid voltage (other voltage levels and frequencies on request) 20 kV, 3~, 50 Hz/60 Hz
Short circuit level -
Maximum AC-current 34.9 A
Line power factor (cos ) at 20 % rated power > 0.98 at rated power
AC-current distor on (THD) at rated power < 3 %
Rated PV-power within 10 % of rated grid voltage 1028 kW
Maximum PV-power at rated grid voltage 1140 kW
Maximum PV-current 2460 A
Maximum PV no-load-voltage 1000 V=
MPP-area at rated PV-power 450 V= to 880 V=
Control strategy MPP-Tracking
E ciency at (10|30|50|75|100) % power (96.3|97.6|97.7|97.3|97.1) %
EU e ciency incl. transf. losses / inductor and auxiliary losses 97.1 %
EU e ciency incl. transf. losses / inductor, excl. auxiliary losses 97.3 %
EU e ciency excl. auxiliary losses -
Feed-in star ng at 1400 W
Standby losses / at night 80 W control power + 1100 W transformer loss
Maximum auxiliary power < 3000 W + hea ng power (if necessary)
General Data
Ambient temperature (others on request) -10 C to 45 C
Rela ve humidity non-condensing
Maximum al tude without dera ng in power 1500 m above sea level
Cooling type Forced air cooling
Minimum air quality acc. to EN 60721-3-3 Class 3S2
Protec on class IP54
Dimensions H x W x D 3200 mm x 7380 mm x 2680 mm
Weight < 38,000 kg
Container surface Concrete
Colour of cabinet / colour of container -
Approvals and cer fi cates BDEW-MSRL / FGW / TR8; EN 61000-6-2; EN 61000-6-4; EN 61000-3-12; EN 61000-3-11;EN 50178; Guida Enel
Features
DC-disconnec on DC-disconnector
AC-disconnec on Grid contactor
Display Industry PC with monitor
Earth leakage detec on Earth leakage monitor
Surge arresters With monitoring on AC- and DC-side
LVRT-Handling. Incl.
Communica on Cabinet Standard
Op ons
Display within control cabinet for display of status External heat exchanger for very dusty/moist ambients and extreme clima c condi- ons.
Separately fused DC-inputs Dehumidifi ers in converter room
Earthing of solar fi eld (posi ve or nega ve is grounded) MV-switchgear with vacuum circuit breaker or fuses for transformer
Measuring and monitoring of single input currents Change of 20 kV medium voltage design to other voltages
Hea ng Incl. thermostat
Technical Data HSC1200C