Helios Systems © Wind&Sun Technologies Company Inverters made by FeCon GmbH www.helios-systems.net Tel.: 0049 461 430 122-0 • Fax: 0049 461 430 122-11 • E-Mail: [email protected] 1.2-MVA-SOLAR-STATION (Concrete) Container with DC-distribuƟon, Inverters, Medium-Voltage Transformer and Switchgear The solar staƟon HSC1200C is a new development for large photovoltaic power plants. The concrete container includes the DC-distribuƟon, the inverter, the medium voltage transformer and the medium voltage switchgear. The HSC1200C is a plug and play soluƟon for quick installaƟon with low total costs. The HSC1200C is a completely factory-assembled system—only the DC-connecƟons to the photovoltaic array and the AC-connecƟon to the medium-voltage grid have to be done on site. The photovoltaic array is linked via fuses or circuit breakers and an EMC-lter to the input of the inverter. As an opƟon, the current in each string can be measured separately. The inverter system consists of two idenƟcal inverters. These inverters operate independently and feed their output power into dierent low-voltage windings of a special medium voltage transformer T1 (please refer to the block diagram below), opƟmized for the photovoltaic array. The container is connected to the grid via the internal medium-voltage switchgear. OpƟonally, the auxiliaries of the inverter system and the heaƟng can be fed by transformer T2 or from an external source. Each inverter is supplied with all necessary control systems and has its own maximum-power-point tracker. As standard, a PC-based monitoring system with an Ethernet interface provides all important informaƟon to the user. In the unlikely case of malfuncƟon, a failure message is generated and sent automaƟcally. OpƟonally the communicaƟon can be real- ized via GSM modem. HSC1200C HSC1200C Block diagram

Upload: chiana-petre

Post on 25-Nov-2015

9 views

Category:

Documents


1 download

DESCRIPTION

helios

TRANSCRIPT

  • Helios Systems Wind&Sun Technologies CompanyInverters made by FeCon GmbH

    www.helios-systems.netTel.: 0049 461 430 122-0 Fax: 0049 461 430 122-11 E-Mail: [email protected]

    1.2-MVA-SOLAR-STATION (Concrete)

    Container with DC-distribu on, Inverters,Medium-Voltage Transformer and Switchgear

    The solar sta on HSC1200C is a new development for large photovoltaic power plants. The concrete container includes the DC-distribu on, the inverter, the medium voltage transformer and the medium voltage switchgear. The HSC1200C is a plug and play solu on for quick installa on with low total costs. The HSC1200C is a completely factory-assembled systemonly the DC-connec ons to the photovoltaic array and the AC-connec on to the medium-voltage grid have to be done on site.The photovoltaic array is linked via fuses or circuit breakers and an EMC-fi lter to the input of the inverter. As an op on, the current in each string can be measured separately.The inverter system consists of two iden cal inverters. These inverters operate independently and feed their output power into di erent low-voltage windings of a special medium voltage transformer T1 (please refer to the block diagram below), op mized for the photovoltaic array. The container is connected to the grid via the internal medium-voltage switchgear. Op onally, the auxiliaries of the inverter system and the hea ng can be fed by transformer T2 or from an external source.Each inverter is supplied with all necessary control systems and has its own maximum-power-point tracker. As standard, a PC-based monitoring system with an Ethernet interface provides all important informa on to the user. In the unlikely case of malfunc on, a failure message is generated and sent automa cally. Op onally the communica on can be real-ized via GSM modem.

    HSC1200C

    HSC1200C

    Block diagram

  • Technical Data Version 1.8

    Helios Systems Wind&Sun Technologies CompanyInverters made by FeCon GmbH

    www.helios-systems.netTel.: 0049 461 430 122-0 Fax: 0049 461 430 122-11 E-Mail: [email protected]

    Electrical Data

    Rated AC-power at 10 % of rated grid voltage 1000 kW

    Rated apparent power 1210 kVA

    Rated grid voltage (other voltage levels and frequencies on request) 20 kV, 3~, 50 Hz/60 Hz

    Short circuit level -

    Maximum AC-current 34.9 A

    Line power factor (cos ) at 20 % rated power > 0.98 at rated power

    AC-current distor on (THD) at rated power < 3 %

    Rated PV-power within 10 % of rated grid voltage 1028 kW

    Maximum PV-power at rated grid voltage 1140 kW

    Maximum PV-current 2460 A

    Maximum PV no-load-voltage 1000 V=

    MPP-area at rated PV-power 450 V= to 880 V=

    Control strategy MPP-Tracking

    E ciency at (10|30|50|75|100) % power (96.3|97.6|97.7|97.3|97.1) %

    EU e ciency incl. transf. losses / inductor and auxiliary losses 97.1 %

    EU e ciency incl. transf. losses / inductor, excl. auxiliary losses 97.3 %

    EU e ciency excl. auxiliary losses -

    Feed-in star ng at 1400 W

    Standby losses / at night 80 W control power + 1100 W transformer loss

    Maximum auxiliary power < 3000 W + hea ng power (if necessary)

    General Data

    Ambient temperature (others on request) -10 C to 45 C

    Rela ve humidity non-condensing

    Maximum al tude without dera ng in power 1500 m above sea level

    Cooling type Forced air cooling

    Minimum air quality acc. to EN 60721-3-3 Class 3S2

    Protec on class IP54

    Dimensions H x W x D 3200 mm x 7380 mm x 2680 mm

    Weight < 38,000 kg

    Container surface Concrete

    Colour of cabinet / colour of container -

    Approvals and cer fi cates BDEW-MSRL / FGW / TR8; EN 61000-6-2; EN 61000-6-4; EN 61000-3-12; EN 61000-3-11;EN 50178; Guida Enel

    Features

    DC-disconnec on DC-disconnector

    AC-disconnec on Grid contactor

    Display Industry PC with monitor

    Earth leakage detec on Earth leakage monitor

    Surge arresters With monitoring on AC- and DC-side

    LVRT-Handling. Incl.

    Communica on Cabinet Standard

    Op ons

    Display within control cabinet for display of status External heat exchanger for very dusty/moist ambients and extreme clima c condi- ons.

    Separately fused DC-inputs Dehumidifi ers in converter room

    Earthing of solar fi eld (posi ve or nega ve is grounded) MV-switchgear with vacuum circuit breaker or fuses for transformer

    Measuring and monitoring of single input currents Change of 20 kV medium voltage design to other voltages

    Hea ng Incl. thermostat

    Technical Data HSC1200C