Data SheetSS/AX4PH Issue 7
Single and Dual Input Analyzersfor pH/Redox (ORP)
AX460, AX466 and AX416
Cost effective
– select one or two pH/Redox (ORP) inputs or combine pH/Redox (ORP) and conductivity in one analyzer
Reduced installation cost
– easy access terminations; reduced panel space
High functionality at minimum cost
– three alarms and two fully isolated current outputs
– integral Water/Chemical sensor cleaner control
– integral PID controller (AX460)
Expanded monitoring and control
– add-on option board provides a total of five alarm relays and four current outputs
– service log-book providing historical data
On line assurance of reliability
– comprehensive sensor and instrument self-checking
Energy saving
– high visibility backlit display with auto switch-off function
Reduced yearly maintenance costs
– 12 to 30V DC option negates the need for costly safety tests
Wide range of applicability
– water and wastewater treatment– power, pure water– semiconductors– chemicals– pharmaceuticals– pulp & paper
More processing power, higherperformance
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
2
The AX400 SeriesAX400 analyzers incorporate the latest technology to providehighly reliable, flexible, feature-packed devices that satisfy adiverse range of process monitoring and control applications.The complete range encompasses solutions for pH/Redox(ORP), conductivity and dissolved oxygen.
AX46x analyzers enable continuous measurements of one ortwo pH or Redox (ORP) points with simultaneous local displayand retransmission. AX46x is used with glass, enamel andantimony pH electrodes and metal Redox sensors, providingmeasurements with exceptional accuracy and performance.
AX400 Series analyzers are available for either wall-/pipe- orpanel-mounting and are rated to IP66/NEMA 4X.
High Functionality as StandardAll versions are supplied with two, fully isolated current outputsas standard, that can be assigned to the measured parameter,sample temperature or any appropriate calculated variables.
Three programmable relay set points are available that can alsobe assigned as required.
Innovative features such as power-saving display and adiagnostic current output option all contribute to a low cost ofownership.
Plug-and-Produce Expanded ControlAn advanced function card provides an additional two currentoutputs and two further alarm relays that can be assigned toeither measured values or sample temperature.
ABB Plug-and-Produce software automatically reconfigures theanalyzer if an option board is added later. No user programmingis necessary.
A real-time clock and logbook are also included making thefull-facility versions extremely powerful and versatile.
Significantly Reduced Maintenance CostsThe AX400 analyzers are supplied as standard for 85 to 265VAC operation. There are no inner switches to set.
They can also be provided for 24V AC or 12 to 30V DC supplyand recognize automatically which of the two supplies is beingused. 24V DC operation reduces maintenance costssignificantly by negating the need for costly, yearly safety tests toensure compliance with safety procedures.
Energy Saving DisplayThe backlit display has been designed to operate in all types ofenvironments and shows both the measured parameter(s) and,on a separate 16-character display line, diagnostic andcomputed information.
On dual-input analyzers both measured parameters aredisplayed simultaneously.
For conservation of energy, the backlight can be set to switch offautomatically after 60s of inactivity.
Easy-Access Installation TerminalsEasy access to the terminations ensures rapid andcost-effective installation. The wall-/pipe-mount version hasbeen designed to ensure that cable connection is simple andconvenient. Ingress protection of the electronics section isretained even when the terminal compartment cover is opened.
AX400 Outputs
Backlight Can Be Set to Switch-off When Inactive
AX400 Termination Chamber Makes Access Easy
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
3
Dual Input Measurement for Critical DutiesThe AX400 enables two continuous measurements withsimultaneous local display and retransmission. This capabilityprovides an on-line validation of the process measurement.
Making two simultaneous measurements and configuring one ofthe set points as a difference alarm provides continuous on-linechecking and early warning of an invalid measurement.
Detecting breakthrough of ammonia in a chiller unit is madepossible with dual measurement. Comparison before and afterthe chiller ensures extremely rapid leakage detection, preventingdamage to the system.
Waste Treatment pH & Redox (ORP)pH and Redox (ORP) are essential control parameters whenremoving toxic chromium ions from waste water inmetal-finishing applications. Dual pH and Redox analyzers andintegral control simplifies installation and reduces investmentcosts.
Just-in-Time MaintenanceOne of the most vulnerable times for a pH electrode is duringreintroduction into the line. If used with a solution earth rod,AX46x analyzers with advanced diagnostic facilities can detectsensor breakages as they occur. In addition, they can detectsensors out-of-process and several reference faults for faultdiagnosis and reduced downtime.
Dual-input Comparator for Critical Measurements
Ammonia Leakage Detection in a Chiller Unit
!!"#$
%%
&'()*+
%%"
Waste Treatment pH and Redox (ORP)
Just-in-Time Maintenance
*%
,
, !!,
*
!-
.$
/'0,/
/100/
/( /
/2/
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
4
Reduced Maintenance Through In-line CleaningMany installed pH sensors benefit from regular cleaning. Whencarried out manually, this can be laborious and costly – so isoften ignored. Advanced AX400 pH analyzers make it possibleto automate sensor cleaning by using a programmablewash-timer contact to activate a cleaning agent valve or pump.
Pulsed water-wash and jet-wash chemical clean actions arestandard, user-selectable functions. The frequency and durationof the wash can be tuned to meet the requirements of theapplication.
For chemical cleaning a 60 liter (13 gallon) sensor cleaningstation can be supplied (model no. AA0010), complete withdelivery pump and low level alarm. Chemical cleaning hasproved particularly successful on potable drinking water plantswhere manganese and iron in the sample can createunacceptably high levels of maintenance. Effective cleaningreduces cost of ownership.
Combined Conductivity and pHThe AX416 version measures conductivity and pH with thesame analyzer. The option board provides the capability toretransmit pH, conductivity and both sample temperatures. Fiveprogrammable alarms can be assigned to suit the needs of theapplication, enabling even the most demanding requirements tobe met.
AX460 Integral P, PI and PID ControlThe single input AX460 analyzers incorporate three-term PIDControl, offering three modes of sophisticated control: analog,pulse length (time proportional) and pulse frequency. These aresupplied as standard and can be operated in direct- orreverse-acting mode, dependent upon the application.
Auto/Manual and Bumpless TransferAn auto/manual feature is incorporated for rapid manual accessto the control functions. The controller facilitates bumplesstransfer between manual and auto modes, providing themeasured variable is within the proportional band and someintegral action time has been programmed.
Current Output Proportional ControlIn this case, the control signal is provided by the 4 to 20mAoutput of the AX460 analyzers rather than using thealarm/control contacts. The magnitude of the current outputchanges in proportion to the deviation from set point. Thismethod is used generally with motorized valves or whencontrolling the speed of dosing pumps with a 4 to 20mAproportional input.
Efficient Auto-cleaning Control for One or Two Sensor Systems
Simultaneous Conductivity and pH Measurement
3
--+
++&'
'
!)$,%*
AX460 – Integral P, PI, and PID Control
Current Acting Control
+
+04'
(
3
!-$
+&0
&
-
56
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
5
Time Proportioning Control (Pulse Length)With time proportioning control, the AX460 analyzerÕs controlsignal output is in pulses, the duration of which changes inproportion to the system error. The pulses are delivered byvarying the length of time that the alarm/control contact isactivated.
Time Proportioning Control is used generally to control dosingby low-cost solenoid valves or metering pumps and is alsoknown as pulse-length proportional or Mark Space control.
Bi-directional ControlAs well as single set point control for both acid and baseaddition, the AX460 analyzer can be configured withindependent controllers.
To avoid control overlap, a minimum of 0.5pH difference (ordeadband) between the set points is essential. The differencebetween the set points varies depending upon the application.
Control of each set point can be configured independently aseither P or PI control in this mode. The setting of proportionalband or integral action can also be different for each set point.
Pulse-frequency Proportional ControlImpulse pumps dosing chemical reagents are controlled easilyby the AX460 analyzerÕs pulse-frequency proportional controloutput. In this case, the pulse length of the alarm/controlcontact is fixed and the frequency of the delivered pulsesincreases in proportion to the system error, as set by theproportional band. Diaphragm metering pumps must have aremote pulse input capability in order to utilize this function.
Pulse-frequency control in the AX460 analyzer operates bypulsing a relay on for 300ms and off for a period of timedetermined by the pulse frequency. The pulse frequency (PFr) isadjustable between 1 and 120 pulses per minute. The greaterthe difference between the measured variable and the set pointthe greater the pulse frequency.
Example
If the pulse frequency is set at 120 pulses per minute and thepercentage output is 100% then the pulse rate is 2 pulses persecond. If the percentage output is reduced to 50%, the pulserate falls to one pulse per second.
Power Failure RecoveryIn the event of a power failure the user can configure the controlmode to be Auto, Manual or Last. This optimizes controlconditions on power-up to ensure rapid recovery of processcontrol.
Time Proportioning Control
Bi-directional Control
78-9
7:89
;+$
(+$
;+$<8
:<8
88
:<8
7-
7-9
(+$
;+$
(+$
;+$
<8
789
-9
--9
-
=3
+*
Pulse-frequency Proportional Control
7-9
78-9
7--9
(+$
;+$
(+$
;+$
;+$
2>7-
-< -<:
-< -< -< -<
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
6
Specification
pH/Redox (ORP) – AX460 and AX466Inputs
One or two* pH or mV inputs and solution earth
One or two* temperature sensors
Enables connection to glass or enamel pH and reference sensors andRedox (ORP) sensors
*AX466 only
Input resistanceGlass >1 x 1013Ω
Reference 1 x 1013Ω
Range–2 to 16pH or –1200 to +1200mV
Minimum spanAny 2pH span or 100mV
Resolution0.01pH
Accuracy0.01pH
Temperature compensation modesAutomatic or manual Nernstian compensation
Range –10 to 200°C (14 to 392°F)
Process solution compensation with configurable coefficient
Range –10 to 200°C (14 to 392°F)
adjustable –0.05 to +0.02%/°C (–0.02 to +0.009%/°F)
Temperature sensorProgrammable Pt100, Pt1000 or Balco 3kΩ
Calibration RangesCheck value (zero point)
0 to 14pH
SlopeBetween 40 and 105% (low limit user-configurable)
Electrode Calibration ModesCalibration with auto-stability checking
Automatic 1 or 2 point calibration selectable from:
ABB
DIN
Merck
NIST
US Tech
2 x user-defined buffer tables for manual entry,
2-point calibration or single-point process calibration
Conductivity – AX416 OnlyRange
Programmable 0 to 0.5 to 0 to 10,000µS/cm (with various cell constants)
Minimum span10 x cell constant
Maximum span10,000 x cell constant
Units of measureµS/cm, µS/m, mS/cm, mS/m, MΩ-cm and TDS
AccuracyBetter than ±0.01% of span (0 to 100µS/cm)
Better than ±1% of reading (10,1000µS/cm)
Operating temperature range–10 to 200°C (14 to 392°F)
Temperature compensation–10 to 200°C (14 to 392°F)
Temperature coefficientProgrammable 0 to 5%/°C and fixed temperature compensationcurves (programmable) for acids, neutral salts and ammonia
Temperature sensorProgrammable Pt100 or Pt1000
Reference Temperature25°C (77°F)
DisplayType
Dual 5-digit, 7-segment backlit LCD
Information16-character, single line dot-matrix
Energy-saving functionBacklit LCD configurable as ON or Auto-Off after 60s
Logbook*Electronic record of major process events and calibration data
Real-time clock*Records time for logbook and auto-manual functions
*Available if option board is fitted
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
7
Relay Outputs – On/OffNumber of relays
Three supplied as standard or five with option board fitted
Number of set pointsThree supplied as standard or five with option board fitted
Set point adjustmentConfigurable as normal or failsafe high/low or diagnostic alert
Hysteresis of readingProgrammable 0 to 5% in 0.1% increments
DelayProgrammable 0 to 60s in 1s intervals
Relay contactsSingle-pole changeover
Rating 5A, 115/230V AC, 5A DC
Insulation2kV RMS contacts to earth/ground
Analog Outputs Number of current outputs (fully isolated)
Two supplied as standard or four with option board fitted
Output ranges0 to 10mA, 0 to 20mA or 4 to 20mA
Analog output programmable to any value between 0 and 22mA toindicate system failure
Accuracy±0.25% FSD, ±0.5% of reading (whichever is the greater)
Resolution0.1% at 10mA, 0.05% at 20mA
Maximum load resistance750Ω at 20mA
ConfigurationCan be assigned to either measured variable or either sampletemperature
Digital CommunicationsCommunications
Profibus DP (with option board fitted)
Control Function – AX460 OnlyController Type
P, PI, PID (configurable)
Control OutputsOutput
Can be assigned a maximum of two relays, two analog outputs, orone of each
AnalogCurrent output control (0 to 100%)
Time proportioning cycle time1.0 to 300.0s, programmable in increments of 0.1s
Pulse frequency1 to 120 pulses per minute, programmable in increments of 1 pulseper minute
Controller actionReverse, direct or bi-directional (programmable)
Proportional band0.1 to 999.9%, programmable in increments of 0.1%
Integral action time (Integral reset)1 to 7200s, programmable in increments of 1s (0 = Off)
Derivative0.1 to 999.9s programmable in increments of 0.1s, available only forsingle set point control
Auto/ManualUser-programmable
Access to FunctionsDirect keypad access
Measurement, maintenance, configuration, diagnostics and servicefunctions
Performed without external equipment or internal jumpers
Sensor Cleaning FunctionConfigurable cleaning action relay contact
Continuous
Pulse in 1s on and off times
Frequency5 minutes to 24 hours, programmable in 15 minute increments up to1 hour then in 1 hour increments for 1 to 24 hours
Duration15s to 10 minutes, programmable in 15s increments up to 1 minutethen in 1 minute increments up to 10 minutes
Recovery period30s to 5 minutes, programmable in 30s increments
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
8
Mechanical DataWall-/Pipe-mount versions
IP66/NEMA4X
Dimensions 192mm high x 230mm wide x 94mm deep(7.56 in. high x 9.06 in. wide x 3.7 in. deep)
Weight 1kg (2.2 lb)
Panel-mount versionsIP66/NEMA4X (front only)
Dimensions 96mm x 96mm x 162mm deep(3.78 in. x 3.78 in. x 6.38 in. deep)
Weight 0.6kg (1.32 lb)
Cable Entry Types
Power SupplyVoltage requirements
85 to 265V AC 50/60 Hz
24V AC or 12 to 30V DC (optional)
Power consumption<10VA
InsulationMains to earth (line to ground) 2kV RMS
Environmental DataOperating temperature limits
–20 to 65°C (–4 to 149°F)
Storage temperature limits–25 to 75°C (–13 to 167°F)
Operating humidity limits Up to 95%RH non condensing
EMCEmissions and immunity
Meets requirements of:
EN61326 (for an industrial environment)
EN50081-2
EN50082-2
Hazardous area approvals
SafetyGeneral safety
EN61010-1
Overvoltage Class II on inputs and outputs
Pollution category 2
LanguagesLanguages configurable:
English
French
German
Italian
Spanish
Standard 5 or 7 x M20 cable glands
North American 7 x knockouts suitable for 1/2 in. Hubble gland
CENELEC ATEX IIG EEx n IIC T4 Pending
FM non-incendive Class I Div. 2 Groups A to D Pending
CSA non-incendive Class I Div. 2 Groups A to D Pending
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
9
Overall Dimensions
Dimensions in mm (in.)
Wall-/Pipe-mount Version
856
-5?<:6@5:<8!6
@!5<:?6-5-< 6
A!<8-
5-<!6
5-<@6
856
!:<85<!!6 !:<85<!!6
85<::6 85<::6
<85-<??6
<85-<??6
@ 5<:6
:85!<@6
8-58<@6
@5:<8!6
Pipe-mount Detail
!5,?<6 $
Dimensions in mm (in.)
Panel-mount Version
@<!- 5<!-6
:<8- 58< 6 8 56 @!5<::6
@!5<::6
8< -5-<6
@<!- 5<!-6
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
10
Electrical Connections
&05+ 6
&0
&0
&*=
&
5''36
= =B
. .
( (*
8 .
! .
:
? .
@ .
-
.
.
# +
C
8 # +
! C
8
!
:
?
@
-
8
!
.
.
'D
'D
8 '(*
! .
:
? .
@ .
-
. 8
.
# +
C
8 # +
! C
&0 &0
&05+ 6
(*516
Terminal Block B pH/Redox (ORP) without Solution Earth‡
pH/Redox (ORP) with Solution Earth‡
ConductivitySensor B Sensor A
1 9Temperature Compensator common*
Link 1 & 2 / 9 & 10**Temperature Compensator common*
Link 1 & 2 / 9 & 10**Temperature Compensator common
Link 1 & 2 / 9 & 10**
2 10 Temperature Compensator third lead* Temperature Compensator third lead* Temperature Compensator third lead
3 11 Temperature Compensator* Temperature Compensator* Temperature Compensator
4 12 Not applicable Reference Electrode Screen
5 13 Not used Not used Cell (Cell Electrode)
6 14 Reference Electrode Solution Earth‡ Cell (Earth Electrode)
7 15 Screen* Screen* Not used
8 16 Glass/Metal Electrode Glass/Metal Electrode Not used
*If fitted. **When a 2-wire Pt100, Pt1000 or BALCO temperature compensator is fitted.‡Solution Earth also referred to as Ground Rod.
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416 SS/AX4PH Issue 7
11
Ordering Information
Single and Dual Input Analyzers for pH/Redox (ORP) and ConductivityModels AX460, AX466 & AX416
AX4 X X X X X 0 X
First Process Variable (PV1)
Conductivity 0 to 10,000µS cm–1 for 2-electrode sensorsConductivity 0 to 1,999mS cm–1 for 4 electrode sensorsConductivity USP<645> for 2-electrode sensorspH/Redox (ORP)Dissolved Oxygen
13568
Second Process Variable (PV2)*
No second process variable – select for PID control of PV1Conductivity 0 to 10,000µS cm–1 for 2-electrode sensorsConductivity 0 to 1,999mS cm–1 for 4-electrode sensors**Conductivity USP<645> for 2-electrode sensorspH/Redox (ORP)Dissolved Oxygen
013568
Enclosure Types
Wall-mount IP66/NEMA 4X, General
Wall-mount – cable glands fittedPipe-mount
12
Wall-mount NEMA 4X/IP66, North American
Wall-mountPipe-mount
67
Panel-mount, Universal
Panel-mount** 5
Advanced Functions & Communications
Basic (2 current outputs + 3 relays)Advanced (4 current outputs + 5 relays + logbook)Profibus DP, basic (2 current outputs + 3 relays)**Profibus DP, advanced (4 current outputs + 5 relays + logbook)**
0123
Power Supply
85 to 265V AC 45 to 65Hz24V AC/12 to 30V DC (auto-selection)85 to 265V AC 45 to 65Hz (tropicalized)‡24V AC/12 to 30V DC (auto-selection, tropicalized)‡
0123
Reserved 0
Manual
EnglishFrenchItalianGermanSpanish
12345
* When ordering units with a second process variable (PV2) the code digit for PV2 in the order code number must be equal to, or greater than, the code digit for PV1, e.g. AX416 permissible, AX461 not permissible.
** Profibus DP not available in panel-mount housing when 0 to 1,999mS/cm is selected as Second Process Variable (PV2).
‡ Check factory for availability of tropicalization.
SS
/AX4
PH
Issu
e 7
Single and Dual Input Analyzers for pH/Redox (ORP)AX460, AX466 and AX416
ABB has Sales & Customer Support expertisein over 100 countries worldwide
www.abb.com
The Company’s policy is one of continuous product improvement and the right is reserved to modify the
information contained herein without notice.
Printed in UK (05.07)
© ABB 2007
ABB LimitedOldends Lane, StonehouseGloucestershireGL10 3TAUKTel: +44 (0)1453 826661Fax: +44 (0)1453 829671
ABB Inc.Analytical Instruments9716 S. Virginia St., Ste. EReno, Nevada 89521USATel: +1 775 850 4800Fax: +1 775 850 4808
pH/Redox (ORP) Sensors forProcess Monitoring
TB(X)5 Series
Next Step™ Solid State reference– eliminates poisoning, pumping and plugging
Advantage™ Series with solution ground rod– permits continuous sensor diagnostics
Comprehensive selection of measuringelectrodes– sensors designed to suit all application
requirements
Combination style construction– measuring, reference and temperature elements, all
in one compact body
Insertion, submersion, flow-throughand hot-tap– increases flexibility of installation
Integral potted cable– no in-process high impedance connections
Comprehensive selection of wetted materials– assures compatibility with design, budget and
process
Operating temperatures up to 140C (284F)– the highest glass temperature limit on the market
Operating pressures up to 21 bar (300 psi)and higher– the highest pressure limit on the market
The Most Durable pH/Redox (ORP)Sensors in the World
Data SheetSS/TBX5_3
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
2
The Most Durable pH/Redox (ORP) Sensorsin the WorldA well deserved reputation for ruggedness, longevity andaccuracy hallmark the TB(X)5 Series pH/Redox sensors. Thesensors are easily applied to most industrial measurementneeds. They are renowned for their ability to outperformconventional sensors in the industries’ toughest processapplications.
Solid-state Next Step™ reference technology is the foundationfor all TB(X)5 Series electrodes. The totally solid inner referencechamber is charged with potassium chloride (KCl). This non-liquid reference all but eliminates poisoning, plugging andpumping problems that plague conventional liquid, slurry andgel designs.
The Next Step Advantage™ series incorporates a solutionground rod that enables sensor diagnostics.
All measurement functions are combined in one compact body:reference, measuring electrode, temperature sensor and groundrod. Using an integral potted cable, a completely sealedassembly is provided without in-process high impedanceconnections.
These advances in reference design, combined with superiorglass electrode technology, result in an industrial sensor withunequalled durability and flexibility.
Electrode
Next Step Reference Electrode
Competing Gel orSlurry-filled Reference
Slurry orGel-filledReservoir
Ceramic orTeflon Junction
OptionalSecond Junction
Ag/AgClElement
Next StepSolid StateReference(Not Shown)
TemperatureCompensator
Ag/AgClElement
MetallicSupport Rodand Ground
Wood and TeflonLiquid Junction
Solution GroundInterface
edoC epyT noitpircseD
sgnitaR
egnaRserutarepmeTgnitarepO taecnadepmI
52 77(C )FC F
1 ssalgtalF .gniluofyvaehhtiwytudytisnedhgiHaNwoL.noitcnujdiuqilhtiwhsulfedortcelE + .rorre Hp41ot0 001ot01 212ot06 1 M056
2 esopruplareneGssalg
erutarepmetrewoldnaytudmuidemotthgilroF.HphgihroftoN.snoitacilppa Hp21ot0 001ot0 212ot23 M002
5 )PRO(xodeR .tnemele)tP(munitalP ot0 Vm0002 041ot0 482ot23 k1 6 )bS(ynomitnA .sessecorpFHroevisarbarofedortceleHplateM Hp11ot3 08ot02– 671ot4– k1
F dicA/ediroulF dnaFHtnecreplarevesotpuybgnihcteottnatsiseR.sdicagnorts Hp21ot0 08ot01 2 671ot05 2 M005
J tnatsisergnitaoCerutarepmethgiH
gnorts,HpwoldnahgihrofelbatiusdnaelitasreV.retawytiruphgihdnaslacimehc Hp41ot0 041ot01 482ot05 M005
setoN . 121ot0)1 052ot23(C selcycnoitaziliretsrof)F05)2 221(C noitartnecnocFHhgihrofdednemmocer.xam)F
Wide Variety of Sensorsfor Most Industrial ApplicationsABB offers a wide variety of standard sensors for mostapplications. These include variations in body style, measuringelectrode type and shape, temperature compensator, junctiontype and shape and cable. Next Step Advantage™ sensors alsoallow choice of solution ground and O-ring materials.
Durable ElectrodesThe TB(X)5 electrode design eliminates failures due to thermalstress caused by rapid temperature excursions. Unlike othersensors that use a large inner air bubble for expansionabsorption, TB(X)5 electrodes use a unique inner plunger;providing more effective protection against temperaturefluctuations.
The glass manufacturing process uses inoffensive components.The glass contains no barium, cobalt or uranium oxides. Theimpedance is low enough to maintain signal integrity, yet highenough to remain chemically durable with little or no sodium ion(Na+) error.
The electrodes are available in several measuring element typesensuring greatest process optimization.
Sensor Construction
Electrode Types and Ratings
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
3
Body StyleSensor bodies are constructed of Kynar (PVDF) or Ryton (PPS).TB5 Series sensors use Solid-State Next Step™ references. TheTB(X)5 Series denotes Next Step Advantage™ types withintegral solution ground.
Sensor Models and Applications
Reference Junction StylesTo promote TB(X)5 electrode process efficiency, referencejunctions are available as either wood or PTFE, each also offeredin flush, notched, or recessed forms.
The hardwood junction is recommended for all general purposeduties particularly those requiring high resistance to coating.PTFE junctions are promoted for continuous processes over11.0 pH or those containing known wood delignifiers such asstrong caustics, bleaches and other oxidizers.
Flush junctions have no process protrusions and thereforesupply excellent self-cleaning properties when used with flatglass and fitted at 90 in process pipelines.
Notched junctions provide an integral protection guard fornormal bulb-style glasses and are especially suited forretractable and immersion sensors.
Recessed junctions are also available. They place the glass bulbbehind a 'hood' giving it protection from abrasive or high velocityprocesses.
Consult factory for availability of recessed junctions.
NormalGlass
FlatGlass
Flush Notched
rebmuNledoMydoB noitacilppAetats-diloS
petStxeN petStxeNegatnavdA
155BT 155XBT SPP,kcol-tsiwT,enil-nI
noisrembuS
655BT 655XBT FDVP,dedaerhT,enil-nI
noisrembuS
755BT 755XBT FDVP pat-toH,rotcarterevlavllaB
165BT 165XBT FDVP elbaziliretS,enil-nI
265BT 265XBT FDVP elbaziliretS,yratinaS
465BT 465XBT FDVP,rotcartererusserphgiH
pat-toH
765BT 765XBT SPP erusserphgiH,enil-nI
Type 1 – Flat Glass
pH
Type 5 – Platinum
ORP
Type 6 – Antimony
pH
pH
Type 2 – General Purpose GlassType F – Fluoride/Acid Resistant GlassType J – Coating Resistant Glass
Electrodes Types
Junction Styles
Junction Styles
)X(BTrosneShsulF dehctoN
dooW EFTP sedortcelE dooW EFTP sedortcelE155 J,F,6,5,2,1
655 6,1 J,F,5,2,1755 6,1 J,F,5,2,1165 J,F,5,1 J,F,5,1265 J,F,5,2,1
465 6 J,F,5,2765 J,F,6,5,2
etoN . noitcelesdilaV= noitcelesdilavnI=
elytS noitpircseD noitacilppA
hsulF rosnesfodnehtiwhsulF sessecorpgniluofyvaeh,enil-nI
dehctoN noitcetorpedortcelegnidivorpnoitcnujdnoyebsdnetxE srosnesnoisremmidna)evlav-llab(pat-toH
Reference Junction Selection
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
4
Temperature CompensationTemperature compensators enable analyzers to adjust fortemperature effects on the glass pH electrode output (Nernst).Selected analyzers can also use this measurement tocompensate for solution pH temperature effects.
Sensors can be ordered with integral temperature sensors or asexternal units.
The integral temperature compensator is available in two forms;Balco 3k and Pt100.
Integral Temperature Compensator
0.4
pHError
0.3
0.20.1
0.0- 0.1
- 0.2
- 0.3
- 0.4
0-5
-10
-15
+ 5
+ 10
+ 15
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
TemperatureChange (C)From 25 C
Temperature CompensatorLocation (Typical)
ToJunction
Box
Black
Junction BoxWiring
(4TB5023-0088)
Pin Leads(Type 'T' cable)
Female BNC and SpadeLugs for Junction Box
Male BNC / Spade Lug to Pin Leads Extension(Cable 4TB 3011-8XXX)
RedWhiteGreenHeavy Green
WithTemperatureCompensator
(Type '0' Cable)
To TB82,TB84, 4630and AX46
Heavy Green
Pin Leads(Type 'T' cable)
Female BNC and SpadeLugs for Junction Box
Male BNC / Spade Lug to Pin Leads Extension(Cable 4TB 3011-7XXX)
ToJunction
Box
Junction BoxWiring
(4TB5023-0088)
Black
Green
WithoutTemperature
Compensator
(Type '0' Cable)
To TB82,TB84, 4630and AX46
pH Error without Temperature Compensation
Cable OptionsTB(X)5 sensors offer complete flexibility of cabling optionsthroughout the range. All cables are potted inside the sensorensuring environmental protection.
The standard cable length for most sensors is 1.5m(5 ft.). However, cables can be supplied as any continuous sizeup to 9m (30 ft.).
Standard accessories include junction boxes and submersion(immersion) couplers, typically used with extension cables fordirect connection to ABB-TBI instruments.
Extension cables also permit distances between sensor andinstrument of up to 30m (100 ft.) without external preamplifier.
A BNC/TC to pin terminal adapter is available for connection toTB82, TB84, 4630 and AX46 Series instruments.
Sensors with pin terminals are selected with code option ‘T’.Next Step Advantage Sensor Cablesand Junction Box Wiring (TBX5 Models)
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
5
Note.Junction box supplied without cable glands 4TB9515-0165for use with conduit.
Junction Box Wiring(4TB5023-0162)
Pin LeadsType 'T' cable
Junction Box Wiring(4TB5023-0162)
Male BNCType 'F'cable
Pin LeadsType 'T'cable
Pin Lead Extensionwith Temperature Compensator Connector
(Cable 4TB3011-4XXX)
to TB515, TB540,TBN580 andTB7
Male BNC –Female BNC –to Sensor or
Junction Box
Extension Cable(Cable 4TB3011-1XXX)
Female BNC –To Sensor orJunction Box
Pin LeadsTo TB82, TB84,4630 and AX46
Pin Extension Cable(Cable 4TB3011-3XXX)
To TB515,TB540,TBN580and TB7
To Sensor orJunction Box
To Sensor orJunction Box
Pin LeadsTo TB82, TB84,4630 and AX46
WithoutTemperatureCompensator
WithTemperatureCompensator
Male BNC and TinnedTemperature Compensator Leads
Type 'F' cable
Male BNC and ExtensionCable Connector on
Temperature Compensator LeadsType 'F' cable
Female BNC to Male BNC Extensionwith Temperature Compensator
Connector to Tinned Leads(Cable 4TB 3011-2XXX)
Solid State and Next Step Reference Sensor Cables and Junction Box Wiring (TB5 Models)
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
6
Models TB551 & TBX551 Ryton SensorsModels TB(X)551 sensors are in-line flow-through orsubmersible (immersion), general purpose, twist-lock stylesensors. The sensor body is molded from chemically resistantRyton (PPS).
The sensor can be adapted to 1 in. fittings by either a threadedRyton receptacle or a twist-lock receptacle. The twist-lockreceptacle is available in Kynar (PVDF) or stainless steel.
Optional electrode guards protect the electrode in submersion(immersion) applications.
Specification
Applications
In-line, flow-through, submersible (immersion)
Max. pressure/temperature
690kPa (100 psi) at 140C (284F)
Features
Low cost, universal type.
Adapter for twist-lock, or threaded-cap, insertion
Material
Body Ryton (Polyphenylene Sulphide)
Junction Wood or Teflon (PTFE)
Junction types Flush
Dimensions in mm (in.)
Models TB(X)551 Ryton Sensors
Overall Dimensions – Models TB(X)551
33.0(1.30)
Sensor
Ryton Body
167(6.57)
120.0(4.73)
2.5(0.10)64.5(2.54)
24.4 (0.96)
26.7 (1.05)
Sensor with Junction Box
95.0(3.74)
Electrode
3/4 in. NPT
64.5(2.54)
12 (0.47)
No. 118 Viton O-Rings2 Each
1 in. NPT Tee(CustomerSupplied)
Ryton ThreadedReceptacle
Flow
Safety CatchAssembly
Flex Conduit and Coupling (Customer Supplied)
Open toAllow Airto Escape
ScrewsTurn intoO-RingGroove
316 Stainless SteelSubmersible Guard
PVCSubmersible
Guard
Twist LockReceptacle
316 Stainless SteelKynar
167 (6,57) 71.1(2.80)
3/4 in. NPT
276.9 (10.90)
3/4 in. NPT Conduit Port (2 Typ.)
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
7
Ordering Information – Models TB(X)551
Notes.1) For direct connection to TB82, TB84, 4630/35 and AX46 transmitters or other supplier devices, using terminal blocks.
2) Not available for Platinum, Redox (ORP), or Antimony, pH, electrodes (codes 5 & 6).
3) Not available for fluoride-resistant electrodes (code F). Compatible with TB82, TB84, 4630/35 and AX46 instruments.
4) Kalrez O-rings only for solution ground sleeve. External O-rings are Viton. External Kalrez O-ring kits available separately.
5) TB551 only. There are 2 options to connect to TB82 or TB84 transmitters:
Option 1 – use BNC/TC to PIN adapter with conduit fitting or BNC/TC to PIN adapter. In either case temperature compensator code must be 2 or 4.
Option 2 – select T in integral cable code, not designed for use with extension cables or junction box.
6) TB551: junction box mounted on sensor. Cable length approx. 102mm (4 in.). Requires extension cable.
7) TB(X)551: when selecting JB or JS, cable length is approx. 102mm (4 in.). Requires extension cable. If junction box is ordered separately and longer cable lengthsare required, enter length under code for integral cable.
srosneSetats-diloSdradnatSdoRdnuorGnoituloSoN petStxeN )elbisrembus(noisremmI,kcol-tsiwT,enil-nI
041@isp001(ylbmessArosneSPRO/HpydoBnotyR )C155BT X X X X X X X X
edortcelEgnirusaeM
1256FJ
001ot01(ssalgtalF 09tawolfhtiwsetalucitraphgihrof)Hp41ot0,C 001ot0(Hp,ssalG )Hp21ot0,C
)PRO(xodeR,munitalP08ot02–(Hp,ynomitnA )Hp11ot3,C
08ot01(tnatsiser-ediroulF,Hp,ssalG )Hp21ot0,C041ot5(erutarepmethgih/ssalgtnatsiser-taoC )Hp41ot0,C
1256FJ
noitasnepmocomrehTlargetnI
01–3–
155XBTroftoN
155XBTroftoN
enoNk3 sdaeldenniT 2
k3 rotcennocelbacnoisnetxE 2
sdaeldenniT001tP 3,2
rotcennocelbacnoisnetxE001tP 3,2
01234
noitcnuJdiuqiL
AB
petStxeN,hsulf,dooWpetStxeN,hsulf,nolfeT
AB
lairetaMdoRdnuorGnoituloS
123
leetssselniats613muinatiT
2ByolletsaH
155BTroftoN155BTroftoN155BTroftoN
lairetaMgniR-O
1234
notiVMDPE
enociliSzerlaK 4
155BTroftoN155BTroftoN155BTroftoN155BTroftoN
elytSydoB
0 ydobnotyR 0
erawdraHyrosseccA
023456
enoN)8110-5025BT4(elcatpecerkcol-tsiwt,leetssselniatS
)9110-5025BT4(elcatpecerkcol-tsiwt,)FDVP(ranyK)0210-5025BT4(draugelbisrembuS,CVP
)1210-5025BT4(draugelbisrembus,leetssselniatS)0210-5159BT4(elcatpecerdedaerhT,)SPP(notyR
023456
elbaCrosneSlargetnI,erusaeMfostinU 5
–T0
155XBTroftoN teef,rotcennocCNBteef,sdaelniP/denniT 1
detcelesera)woleb(BJnehwesU 7,6
FT0
elbaCrosneSlargetnI,htgneL
–JJ
–BS
teefnihtgnelelohwretne)m8.8(tf03)m3.0(tf1xobnoitcnujhtiW 7,6
xobnoitcnujsseL 7,6
–JJ
–BS
155XBT X X X X X X X X X XegatnavdApetStxeN )noisremmI(elbisrembuS,kcol-tsiwT,enil-nI, 1
041@isp001(ylbmessArosneSPRO/HpydoBnotyR )C
rofsrosneSgnikcehc-flesnoituloShtiw()doRdnuorG
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
8
Specification
Applications3/4 in. NPT process connection, In-line,submersion (immersion)
Max. pressure/temperature
690kPa (100 psi) at 80C (176F)
276kPa (40 psi) at 140C (284F)
Material
Body Kynar (PVDF) as standardJunction Wood or Teflon (PTFE)
Junction types Flush (Antimony and flat glass only)
Notched (recommended)
Flow-through
Specify insertion depth in code
Submersion/Immersion
With notched junction
Models TB(X)556 Kynar Sensors
Models TB556 & TBX556 Kynar SensorsModels TB(X)556 Sensors are threaded style sensors suitablefor submersion (immersion) and insertion into the process pipes.
Mounting thread size is 3/4 in. NPT.
The sensor is available in several insertion lengths from thestandard 40mm (1.5 in.) to a maximum of 127mm (5 in.).
The sensor body is molded from chemically resistant Kynar(PVDF).
Sensor with Junction Box
238.1 (9.38)120.0 (4.73)
3/4 in.NPTConduit Port
(2 Typ.)
71.1(2.80)
95.0(3.74)
3/4 in. NPT Electrode
22.2 (0.80)
Note.27.9mm (1.1 in.)insertion depth notavailable on TBXAdvantage sensorswith solution grounds
27.9 (1.10) Min.38.1 (1.5) Standard
As Specified up to 127.0 (5.00) Max.(see Note)
Rear of Sensor andCable to be Sealedin Conduit or Pipe(Customer Supplied)
3/4 in. Coupling(Customer Supplied)
Kynar Body
Conduit(Customer Supplied)
3/4 in. NPT7/8 in.WrenchFlats
3/4 in. NPT
Notched Sensor
127.0(5.00)
Notched SensorSubmersible Application s
Notched SensorFlow Applications
SampleOutlet
SampleInlet
3/4 in. Tee(customer Supplied)
Dimensions in mm (in.)
Overall Dimensions – Models TB(X)556
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
9
Ordering Information – Models TB(X)556
Notes.1) Antimony pH electrodes supplied only with flush junctions (codes A & B).
2) Not available for, Redox (ORP), or Antimony, pH, electrodes (codes 5 & 6).
3) Not available for fluoride-resistant electrodes (code F). Compatible with TB82, TB84, 4630/35 and AX46 instruments.
4) Flush junctions for flat glass pH and Antimony electrodes only (codes 1 & 6).
5) Notched junctions not available for Antimony electrodes.
6) Manufactured as 1.5 in.depth, includes cable strain relief.
7) There are 2 options to connect TB556 to TB82 or TB84 transmitters:
Option 1 – use BNC/TC to PIN adapter with conduit fitting or BNC/TC to PIN adapter. In either case temperature compensator code must be 2 or 4.
Option 2 – select T in integral cable code, not designed for use with extension cables or junction box.
8) For direct conection to type TB82, TB84, 4630/35 and AX46 transmitters, or other supplier devices, using terminal blocks.
9) TB556: junction box or submersible (immersion) connector mounted on sensor. Cable length approx. 102mm (4 in.). Requires extension cable for Temperaturecompensator code must be 0, 2 or 4.
10) TB(X)556: junction box mounted on sensor. Cable length approx. 102mm (4 in.). Requires extension cable for connection to transmitter. If junction box is orderedseparately and longer cable lengths are required, enter cable length in code for integral cable.
srosneSetats-diloSdradnatSdoRdnuorGnoituloSoN
petStxeN )noisremmI(elbisrembuS,dedaerhT,enil-nIylbmessArosneSPRO/HpydoBranyK
041@isp04( 09@isp001;C )C 655BT X X X X X X X X
edortcelEgnirusaeM
1256FJ
001ot01(ssalgtalF 09tawolfhtiwsetalucitraphgihrof)Hp41ot0,C 1
001ot0(Hp,ssalG )Hp21ot0,C)PRO(xodeR,munitalP08ot02–(Hp,ynomitnA )Hp11ot3,C 1
08ot01(tnatsiser-ediroulF,Hp,ssalG )Hp21ot0,C041ot5(erutarepmethgih/ssalgtnatsiser-taoC )Hp41ot0,C
1256FJ
noitasnepmocomrehTlargetnI
01
655XBTroftoN3
655XBTroftoN
enoNk3 sdaeldenniT 2
k3 rotcennocelbacnoisnetxE 2
sdaeldenniT001tP 3,2
rotcennocelbacnoisnetxE001tP 3,2
01234
noitcnuJdiuqiL
ABDE
ecnereferpetStxeN,hsulf,dooW 4
ecnereferpetStxeN,hsulf,nolfeT 4
ecnereferpetStxeN,dehcton,dooW 5
ecnereferpetStxeN,dehcton,nolfeT 5
ABDE
lairetaMdoRdnuorGnoituloS
123
leetssselniats613muinatiT
yolletsaH 2B
655BTroftoN655BTroftoN655BTroftoN
lairetaMgniR-O
1234
notiV
MDPEenociliS
zerlaK
655BTroftoN655BTroftoN655BTroftoN655BTroftoN
elytSydoB
0–15
0–50
655XBTroftoNeborp)noisremmI(elbisrembuS 6
htpednoitresnI.ni1.1htpednoitresni.ni5.1htpednoitresni.ni0.5
0115
0150
elbaCrosneSlargetnI 7
–T0
655XBTroftoN teef,rotcennocCNBteef,sdaelniP/denniT 8
detcelesera)woleb(BJnehwesU 01,9
FT0
elbaCrosneSlargetnI,htgneL
–JJ
–BS
teefnihtgnelelohwretne)m8.8(tf03ot)m3.0(tf1xobnoitcnujhtiW 01,9
xobnoitcnujsseL 01,9
–JJ
–BS
655XBT X X X X X X X X X X egatnavdApetStxeN )noisremmI(elbisrembuS,dedaerhT,enil-nI,ylbmessArosneSPRO/HpydoBranyK
isp04( 041@ 09@isp001C )C
rofsrosneSgnikcehc-flesnoituloShtiw()doRdnuorG
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
10
Models TB557 & TBX557 Hot-Tap Retractable SensorsModels TB(X)557 sensors are hot tap, ball valve insertionsensors. They enable sensor maintenance or replacementwithout interrupting the process.
An integral safety anti-blowout lip is incorporated into the sensordesign, preventing accidental sensor removal. Unlike chainrestraints, this safety-by-design is an integral part of the sensors'construction.
The sensor is inserted through a standard 11/2 in. or 11/4 in. fullport ball valve. Ease of disassembly aids sensor replacement.
Connection to a ball valve is by compression fitting available ineither hand-tight with 11/4 in. NPT threads or wrench-tight with1 in. NPT threads.
Additional fittings enable the assembly to be flushed and drainedin situ and uses a 11/2 in. NPT threads for connection to the ballvalve.
Specification
Applications
Insertion, Hot-tap
Max. pressure/temperature
690kPa (100 psi) at 80C (176F)276kPa (40 psi) at 140C (284F)
Features
Insert/retract without disturbing process flow
Replaceable electrodeAnti-blowout lip
No internal high-impedance connection
Material
Electrode Body Kynar (PVDF) as standardSensor sheath variants 316 stainless steel
Hastelloy or Titanium
External O-rings Viton
Junction Wood or Teflon (PTFE)Junction types Flush (Antimony only)
Notched (recommended)
Lengths Standard 400mm (16 in.)
Maximum 910mm (36 in.)
Overall Dimensions – Compression Fittings
11/4 in. Full Post Ball Valveor 11/2 in. Ball Valve
Compression Fitting
Process Line / Vessel
1/4 in. NPT Flushing Port21/2 in. Dia.
Hand-tight
13/4 in. Hex.
11/4 in. NPT
11/2 in. Hex.13/8 in. Hex.
1 in. NPT
97.8(3.85)
66.7(2.63)
Wrench-tight
Wrench-tightcompression fitting
Hand-tightcompression fitting
1/4 in. NPT Flushing Port
11/2 in. NPT184.7(7.27)
Wrench-tight flush and draincompression fitting
11/2 in. NPT
Hand-tight flush and draincompression fitting
199.4(7.85)
Dimensions in mm (in.)
Models TB557 and TBX557 Sensors
Overall Dimensions – Ball Valve
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
11
…Overall Dimensions – Models TB(X)557
Viton O-Rings Sheath Replaceable SensorKynar Back Piece
Hand-tight Compression Fitting
Installation Detail
26.7 Dia(1.05)22.9 Dia
(0.90)
21.0 Dia(0.83)
ReferenceJunction
Electrode
188(7.40)
No. 019 VitonO-Rings
222.9 (8.78) (Other Lengths Available)27.9(1.10)
Replacement Sensor Detail
Kynar BodyNo 019 VitonO-Rings
316 Stainless SteelTitanium or Hastelloy-CSheath
3/4 in. NPT
95.0 (3.74)
71.1(2.80)
120.0 (4.73)
3/4 in ConduitPort (2 Typ.)
25.4 Dia(1.00) Kynar Back Piece Anti-Blowout Lip
11/4 in. NPT
Optional Compression FittingHand-tight 316 Stainless Steelor Titanium
97.8 (3.85)
11/4 in. NPT Full Port Ball Valve
11/4 in. 316 Stainless SteelClose Nipple
Sensor
Optional Compression FittingWrench-tight 316 Stainless Steel,Titanium or Hastelloy-C
66.7(2.63)
27.9(1.10)
26.7 Dia(1.05) 3/4 in. NTP 1 in. NTP
11/4 in. NPT Full Port Ball ValveReducing Bushing
11/4 in. Close NippleSensor
Installation Detail
Wrench-tight Compression Fitting 28.6(1.13)
Dimensions in mm (in.)
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
12
Ordering Information – Models TB(X)557
srosneSetats-diloSdradnatSdoRdnuorGnoituloSoN petStxeN ,ydoBranyK,paTtoH,noitresnIevlaVllaB
041@isp04(ylbmessArosneSPRO/Hp 09@isp001;C )C 755BT X X X X X X X X
edortcelEgnirusaeM
1256FJ
001ot01(HpssalgtalF 09tawolfhtiwsetalucitraphgihrof)Hp41ot0,C 001ot0(Hp,ssalG )Hp21ot0,C
)PRO(xodeR,munitalP08ot02–(Hp,ynomitnA )Hp11ot3,C 1
08ot01(tnatsiser-ediroulF,Hp,ssalG )Hp21ot0,C041ot5(erutarepmethgih/ssalgtnatsiser-taoC )Hp41ot0,C
1256FJ
rotasnepmocerutarepmeTlargetnI
01–3–
755XBTroftoN
755XBTroftoN
enoNk3 sdaeldenniT 2
k3 rotcennocelbacnoisnetxE 2
sdaeldenniT001tP 3,2
rotcennocelbacnoisnetxE001tP 3,2
01234
noitcnuJecnerefeR
ABDE
ecnereferpetStxeN,hsulf,dooW 4
ecnereferpetStxeN,hsulf,nolfeT 4
ecnereferpetStxeN,dehctoN,dooW 5
ecnereferpetStxeN,dehctoN,nolfeT 5
ABDE
lairetaMdoRdnuorGnoituloS
123
leetssselniats613muinatiT
2ByolletsaH
755BTroftoN755BTroftoN755BTroftoN
lairetaMgniR-O
1234
notiVMDPE
enociliSzerlaK 6
755BTroftoN755BTroftoN755BTroftoN755BTroftoN
elytSydoB
07ABFGHJKLMNPRS
ylnoedortcele755)X(BTtnemecalpeRhtaehsmuinatiT.ni61
htaehsCyolletsaH.ni61htaehsleetSsselniatS613.ni61
htaehsmuinatiT.ni02htaehsmuinatiT.ni42htaehsmuinatiT.ni03
htaehsCyolletsaH.ni02htaehsCyolletsaH.ni42htaehsCyolletsaH.ni03
htaehsleetSsselniatS613.ni02htaehsleetSsselniatS613.ni42htaehsleetSsselniatS613.ni03
htaehsmuinatiT.ni63htaehsleetSsselniatS613.ni06
07ABFGHJKLMNPRS
erawdraHyrosseccA 7
01234
enoN 8
thgit-hcnerw,gnittifnoisserpmocleetSsselniatS613thgit-hcnerw,gnittifnoisserpmocCyolletsaH
thgit-dnah,gnittifnoisserpmocleetSsselniatS613thgit-dnah,gnittifnoisserpmocmuinatiT
01234
elbaCrosneSlargetnI 9
–T0
755XBTroftoN teef,rotcennocCNBteef,sdaelniP/denniT 01
detcelesera)woleb(5Jot1JroBJnehwesU 21,11
FT0
elbaCrosneSlargetnI,htgneL
–JJJJJJ
–B12345
teefnihtgnelelohwretne)m8.8(tf92ot)m3.0(tf1 31
xobnoitcnujhtiW 41
htaehs.ni61rofrosnestnemecalpeR 51
htaehs.ni02rofrosnestnemecalpeR 51
htaehs.ni42rofrosnestnemecalpeR 51
htaehs.ni03rofrosnestnemecalpeR 51
htaehs.ni63rofrosnestnemecalpeR 51
–JJJJJJ
–B12345
755XBT X X X X X X X X X X petStxeN ,egatnavdA ,paTtoH,noitresnIevlaVllaBylbmessArosneSPRO/HpydoBranyK
041@isp04( 09@isp001;C )C
rofsrosneSgnikcehc-fles
dnuorGnoituloShtiw()doR
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
13
10) For direct connection to type TB82, TB84, 4630/35 and AX46 transmitters,or other supplier devices, using terminal blocks.
11) TB557: junction box mounted on sensor. Cable length varies to match bodylength style. Order code for body style and accessory hardware anythingexcept zero. Requires extension cable. Order code for temperaturecompensator must be 0, 2 or 4.
12) TB(X)557: junction box mounted on sensor. Cable length approx. 102mm (4in.). Order code for body style and accessory hardware anything exceptzero. Code – # # # # # # # 0, J, B. Requires extension cable. If junction boxis ordered separately and longer cable lengths are desired, enter cablelength in integral sensor code.
13) Standard cable length of 4 ft (1.2m) as measured from rear of sensorassembly with 16 in. sheath only. Max. 29 ft (8.8m) cable only available with16 in. sheath. Longer sheaths decrease length accordingly.
14) Applicable to sensors with junction boxes only.
Notes.1) Antimony pH electrodes supplied only with flush junctions (codes A & B).
2) Not available for, Redox (ORP), or Antimony, pH, electrodes (codes 5 & 6).
3) Not available for fluoride-resistant electrodes (code F).Compatible with TB82, TB84, 4630/35 and AX46 instruments.
4) Flush junctions for Antimony electrodes only (code 6).
5) Not available for Antimony electrodes (code 6).
6) Kalrez O-rings only for solution ground sleeve. External O-rings are Viton.External Kalrez O-ring kits available separately.
7) Standard hardware kits have Viton O-rings.
8) Applicable for all body styles. Mandatory for replacement sensors
(code 0 in Body Style section).
9) There are 2 options to connect TB557 to TB82 or TB84 transmitters:
Option 1 – use BNC/TC to PIN adapter with conduit fitting or BNC/TC toPIN adaptor. In either case temperature compensator code must be2 or 4.
Option 2 – select T in integral sensor code, not designed for use withextension cables or junction box.
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
14
Models TB561 & TBX561 Sterizable SensorsModels TB(X)561 sensors are designed for sterilizable or in-lineapplications and for measurements in process vessels or linesrequiring periodic sterilization or cleaning. They are also used inthe TB18 Safe-T-Clean valve and 4TB9515-0190 stainless steelflow cell.
The sensors are available with a bushing and union nut but canalso be retro-fitted into standard DN25 bushings with 0.983 in.to 0.995 in. internal diameters. All hardware required for use withthe TB18 Safe-T-Clean or 4TB9515-0190 Flowcell is includedwith valve or Flowcell when purchased.
Specification
Applications
Batch processing with steam or chemical sterilization, fermenters,glass-lined reactors, pharmaceuticals, food and beverage
Max. pressure/temperatures
690kPa (100 psi) at 90C (176F)
448kPa (65 psi) at 121C (250F)
276kPa (40 psi) at 140C (284F)
Material
Electrode body Kynar (PVDF) as standard
Junction Wood or Teflon (PTFE)
Junction types Flush
Notched
Insertion depths
70mm, 100mm, 150mm or 200mm
(100mm required for TB18 Safe-T-Clean valve and Flowcell)
Models TB561 and TBX561 Sensors
Overall Dimensions – Models TB(X)561
L
Kynar SensorBody
Holder Nut
Flow cell (Requires 100 mm sensor)
No. 020 VitonO-Ring
152.4 (6.00)
Order Code 070:L = 70.0 (2.76)Order Code 100:L = 100.0 (3.94)Order Code 150:L = 150.0 (5.91)Order Code 200:L = 200.0 (7.87)
Front View
Vessel WallWeld
11/4 in. BSP
15
38.1(1.50)
Tank Bushing
11/4 in. BSP
Note.Holder nut slides over sensorand threads onto tank bushing
198.1(7.8)
166.4(6.55)
38.1(1.50)71.9(2.83)134.9(5.31)
NOTES.1. DASHED LINES REPRESENT DIMENSIONS OF FLOW CELL KIT
WITH SWAGE LOCK FITTINGS.2. FLOW CELL KIT WITHOUT SWAGE LOCK FITTINGS 4TB9515-0223
FLOW CELL KIT WITH SWAGE LOCK FITTINGS 4TB9515-0190
Safe-T-CleanSensor Valve TB18(Requires 100mmsensor with flushliquid junction)
1/2 in. NPT x 1/4 in.Swage Lock Fitting
(3 Typ)83.5(3.29)
38.5 (1.52)
Dimensions in mm (in.)
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
15
Ordering Information – Models TB(X)561
Notes.1) For direct connection to type TB82, TB84, 4630/35 and AX46 transmitters or other supplier devices, using terminal blocks.
2) Not available for Platinum, Redox (ORP), electrodes (code 5).
3) Kalrez O-rings only for solution ground sleeve. External O-rings are Viton. External Kalrez O-ring kits available separately.
4) Insertion depth measured from wetted face of sensor flange to tip of guard.
5) TB561only. There are two options to connect to TB82 or TB84 transmitters:
Option 1 – use BNC/TC to PIN adapter with conduit fitting or BNC/TC to PIN adapter. In either case temperature compensator code must be 2 or 4.
Option 2 – select T in integral cable code, not designed for use with extension cables or junction box .
6) TB561: junction box mounted on sensor. Cable length approx. 102mm (4 in.). Requires extension cable. If junction box is ordered separately and longer cable lengthsare required enter length under code position for integral cable.
7) Not compatible with all TB18 Safe-T-Clean valve styles.
8) Required for use in most TB18 Safe-T-Clean valves.
9) Required for use with TB18 Safe-T-Clean valves and 4TB9515-0190 Flowcell. Consult TB18 Product Specification sheet for comprehensive measuring electrodeselection.
srosneSetats-diloSdradnatSdoRdnuorGnoituloSoN petStxeN ylbmessArosneSPRO/HpydoBranyKelbaziliretS
121@isp56( )C165BT X X X X X X X X X
edortcelEgnirusaeM
125FJ
001ot01(ssalgtalF 09tawolfhtiwsetalucitraphgihrof)Hp41ot0,C 8
001ot0(Hp,ssalG )Hp21ot0,C)PRO(xodeR,munitalP
08ot01(tnatsiser-ediroulF,Hp,ssalG )Hp21ot0,C041ot5(erutarepmethgih/ssalgtnatsiser-taoC )Hp41ot0,C
125FJ
rotasnepmoCerutarepmeTlargetnI
01
165XBTroftoN3
165XBTroftoN
enoNk3 sdaeldenniT 2
k3 rotcennocelbacnoisnetxE 2
sdaeldenniT001tP 2
rotcennocelbacnoisnetxE001tP 2
01234
noitcnuJecnerefeR
ABDE
petStxeN,hsulf,dooWpetStxeN,hsulf,nolfeT
petStxeN,dehcton,dooW 7
petStxeN,dehcton,nolfeT 7
ABDE
lairetaMdoRdnuorGnoituloS
123
leetssselniats613muinatiT
2ByolletsaH
165BTroftoN165BTroftoN165BTroftoN
lairetaMgniR-O
1234
notiVMDPE
enociliSzerlaK 3
165BTroftoN165BTroftoN165BTroftoN165BTroftoN
htpeDnoitresnI 4
0112
7050
0000
mm07mm001 9
mm051mm002
0112
7050
0000
elbaCrosneSlargetnI,erusaeMfostinU 5
–T0
165XBTroftoN teef,rotcennocCNBteef,sdaelniP/denniT 1
detcelesera)woleb(SJ/BJnehwesU 7,6
FT0
elbaCrosneSlargetnI
–JJ
–BS
teefnihtgnelelohwretnem8.8)tf03(ot)m3.0(tf1xobnoitcnujhtiW 7,6
relpuocelbisrembus/xobnoitcnujsseL ,6 7
–JJ
–BS
165XBT X X X X X X X X X X X egatnavdApetStxeN elbaziliretS, 1
121@isp56(ylbmessArosneSPRO/HpydoBranyK )C rofsrosneS
htiw(gnikcehc-fles)doRdnuorGnoituloS
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
16
Models TB562 & TBX562 Sanitary SensorsModels TB(X)562 sensors are designed for processes needingthe use of sanitary (hygienic) fittings. These sensors have a11/2 in. tri-clamp flange fitting and are suitable for processesusing steam or chemical cleaning.
Specification
Applications
Food & Beverage, Dairy,Pharmaceuticals
Max. pressure/temperature
690kPa (100 psi) at 90C (176F)
448kPa (65 psi) at 121C (250F)276kPa (40 psi) at 140C (284F)
Material
Electrode body Kynar as standard
External O-ring Viton
Junction Wood or Teflon (PTFE)Junction types Flush
Mounting 11/2 in. polished sanitary tube flange
1 in. and 11/2 in. tri-clamp for flush style
Models TB(X)562 Sensors
Overall Dimensions – Models TB(X)562
29.0 (1.14) Dia.Standard Style
4.6 (0.18)46.2(1.82)
53.3 (2.10)139.7 (5.50)
86.4 (3.40)
34.3 (1.35) Dia.
69.9 (2.75)
52.1 (2.05)Flange Gasket(Customer Supplied)
Standard Style
3/4 in. NPT
11/2 in. Tri-Clamp Tee(Customer Supplied)
No. 216 VitonO-Ring
3/4 in. NPT
Liquid Junction
Flush Style
Kynar Body3.6 (0.14)Radius
SanitaryFlange
50.5 (1.99)
34.3 (1.35) Dia.
147.3 (5.80)
Flush Style
SanitaryFlange Gasket(Customer Supplied)
Vessel(CustomerSupplied)
Wall
26.7(1.05)
Dia.Front View
69.9(2.75)
139.7(5.50)
11/2 in. Kynar Tri-ClampFlange Mount Sensorwith TemperatureCompensator
ElectrodeGroove forSanitary Gasket
139.7 (5.50)
Dimensions in mm (in)
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
17
Ordering Information – Models TB(X)562
Notes.1) For direct connection to type TB82, TB84, 4630/35 and AX46 transmitters or other supplier devices using terminal blocks.
2) Not available for Platinum, Redox (ORP), electrodes (code 5).
3) TB562 only. There are two options to connect to TB82 or TB84 transmitters:
Option 1 – use BNC/TC to PIN adapter with conduit fitting or BNC/TC to PIN adapter. In either case temperature compensator code must be 2 or 4.
Option 2 – select T in integral cable code, not designed for use with extension cables or junction box.
4) TB562: junction box mounted on sensor. Cable length approx. 102mm (4 in.). Requires extension cable. Temperature compensator code position must be 0, 2 or4.
5) TB(X)561: when selecting JB or JS cable length is approx. 102mm (4 in.). Requires extension cable. If junction box is ordered separately and longer cable lengths arerequired enter length under code position for integral cable.
srosneSetats-diloSdradnatSdoRdnuorGnoituloSoN petStxeN rosneS)PRO(xodeR/HpelbaziliretS
121@isp56(ylbmessArosneSydoBranyK )C265BT X X X X X X X X
edortcelEgnirusaeM
125FJ
001ot01(HpssalgtalF 09tawolfhtiwsetalucitraphgihrof)Hp41ot0,C 001ot0(Hp,ssalG )Hp21ot0,C
)PRO(xodeR,munitalP08ot01(tnatsiser-ediroulF,Hp,ssalG )Hp21ot0,C
041ot5(erutarepmethgih/ssalgtnatsiser-taoC )Hp41ot0,C
125FJ
rotasnepmocerutarepmeTlargetnI
01–3–
265XBTroftoN
265XBTroftoN
enoNk3 sdaeldenniT 2
k3 rotcennocelbacnoisnetxE 2
sdaeldenniT001tP 2
rotcennocelbacnoisnetxE001tP 2
01234
noitcnuJecnerefeR
AB
petStxeN,hsulf,dooWpetStxeN,hsulf,nolfeT
AB
lairetaMdoRdnuorGnoituloS
1 leetssselniats613 265BTroftoN
lairetaMgniR-O
123
notiVMDPE
enociliS
265BTroftoN265BTroftoN265BTroftoN
lairetaMydoB
0 )FDVP(ranyK 265BTroftoN 0
elytSydoB
01
pmalc-irT.ni5.1,dradnatSpmalc-irT.ni5.1/0.1,hsulF
01
elbaCrosneSlargetnI,erusaeMfostinU 3
–T0
265XBTroftoN teef,rotcennocCNBteef,sdaelniP/denniT 1
detcelesera)woleb(SJroBJnehwesU 5,4
FT0
elbaCrosneSlargetnI
–JJ
–BS
teefnihtgnelelohwretne)m8.8(tf92ot)m3.0(tf1xobnoitcnujhtiW 5,4
xobnoitcnujsseL 5,4
–JJ
–BS
265XBT X X X X X X X X X XegatnavdApetStxeN rosneS)PRO(xodeR/HpelbaziliretS, 1
121@isp56(ylbmessArosneSydoBranyK )C rofsrosneSgnikcehc-flesnoituloShtiw()doRdnuorG
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
18
Specification
Applications
High pressure, hazardous materials
Max. pressure/temperature
2065kPa (300psi) at 140C (284F)
Features
Insert/Retract without disturbing process
Retraction housing for safety
Taps for flushing or pressurizing
Material
Electrode body Kynar (PVDF)
Ball-valve/hardware 316 stainless steel(other materials on request)
External O-rings VitonJunction Wood or Teflon (PTFE)
Junction Types Flush (Antimony only)Notched (recommended)
Models TB564 and TBX564 Sensors
Overall Dimensions – Models TBX564
41(1.60)
38(1.50)
41(1.61)
334(13.1)
174(6.85)
13(0.50)
3/4 in. Conduit Port (2 Typ.)
Note.All pipe threads have Loctite PST sealant applied at the Factory.
120.0 (4.73)
3/4 in. NPT
95.0 (3.74)
71.1(2.80)
63.5 Max.(2.50)
3/4
O-Ring
21/8 in.Wrench Flats
11/4 in. NPT
43.2(1.70)
110 (4.33)268 (10.6)
Weld
11/2 in.316 Stainless SteelBall Valve
Reducing Coupling Guide
ReplaceableKynar Sensor
ExtractionHousing
End Cap
CompressionFitting with N o. 014Viton O-Ring
CompressionFitting1/2 in. NPT
1/2 in.Elbow
19/16 in.Wrench Flats (not shown)
No. 217 Viton
in. NPT
Insertion Assembly1/2 in. Tube, 1/8 in. Wall
1/4 in. 316 Stainless SteelPipe Plug (2 Typ.)
Interior O-Ring No. 115 Viton
Dimensions in mm (in.)
Models TB(X)564 are high pressure, hot-tap, ball-valve, insertionsensors. They permit sensor maintenance or replacementwithout interrupting the process.
A retraction housing is provided for isolating the sensor bodyfrom the operator. Using 1/4 in. taps, the housing can be flushedduring retraction or pressurized before insertion.
Models TB564 & TBX564 High Pressure Hot-tap Retractable Sensors
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
19
Ordering Information – Models TBX564
Notes.1) For direct connection to type TB82, TB84, 4630/35 and AX46 transmitters or other supplier devices using terminal blocks.
2) Antimony electrodes only supplied with flush junctions (code A and B).
3) Not available for Platinum, Redox (ORP), or Antimony, pH, electrodes (code 5 and 6).
4) Not available for fluoride-resistant electrodes (code F). Compatible with TB82, TB84, 4630/35 and AX46 instruments.
5) Not available for Antimony electrodes (code 6).
6) Kalrez O-rings for solution ground sleeve only. External O-rings are Viton. External Kalrez O-ring kits available separately.
7) Requires installation of BNC connector kit.
8) There are two options to connect TB564 to TB82 or TB84 transmitters:
Option 1 – use BNC/TC to PIN adapter with conduit fitting or BNC/TC to PIN adapter. In either case temperature compensator code must be 2 or 4.Option 2 – select T in sensor cable code, not designed for use with extension cables or junction box.
9) Junction box mounted on insertion rod. Cable length approx. 254mm (10 in.). Requires extension cable to connect to transmitter. Order code for temperaturecompensator must be 0, 2 or 4. If sensor is ordered without accessory hardware a junction box must be ordered separately.
10) Requires BNC field mount for replacement sensors.
11) Maximum pressure: 690 kPa (100 psi).
srosneSetats-diloSdradnatSdoRdnuorGnoituloSoN petStxeN , )PRO(xodeR/Hppat-toHerusserPhgiH 1 rosneS
041@isp003(ylbmessA )C465BT X X X X X X X X
edortcelEgnirusaeM
1256FJ
001ot01(ssalgtalF 09tawolfhtiwsetalucitraphgihrof)Hp41ot0,C 11
001ot0(Hp,ssalG )Hp21ot0,C)PRO(xodeR,munitalP08ot02(Hp,ynomitnA )Hp11ot3,C 2
08ot01(tnatsiser-ediroulFHp,ssalG )Hp21ot0,C041ot5(erutarepmethgih/ssalgtnatsiser-gnitaoC )Hp41ot0,C
1256FJ
rotasnepmocerutarepmeTlargetnI
01–3–
465XBTroftoN
465XBTroftoN
enoNk3 sdaeldenniT 3
k3 rotcennocelbacnoisnetxE 3
sdaeldenniT001tP 4,3
rotcennocelbacnoisnetxE001tP 4,3
01234
noitcnuJecnerefeR
ABCDE
petStxeN,hsulF,dooW 2
petStxeN,hsulF,nolfeT 2
ecnerefeRpetStxeN,desseceR,nolfeT 3
petStxeN,dehctoN,dooW 5
petStxeN,dehctoN,nolfeT 5
ABCDE
lairetaMdoRdnuorGnoituloS
123
leetssselniats613muinatiT
2ByolletsaH
465BTroftoN465BTroftoN465BTroftoN
lairetaMgniR-O
1234
notiVMDPE
enociliSzerlaK 6
465BTroftoN465BTroftoN465BTroftoN465BTroftoN
elytSydoB
0 ydobrosnesranyK,dradnatS 0
erawdraHyrosseccA
09A
enoN 7
ylbmessarosnes465)X(BTledoMetelpmoC htiw htiw htiw htiw htiw evlav-llaberawdrahrosnes465)X(BTledoM tuohtiw tuohtiw tuohtiw tuohtiw tuohtiw evlav-llab
09A
elbaCrosneSlargetnI,erusaeMfostinU 8
–T0
465XBTroftoN teef,rotcennocCNB 01
teef,sdaelniP/denniT 1 )dednemmoceR(detcelesera)woleb(SJ/BJnehwesU 9
FT0
elbaCrosneSlargetnI
–JJ
–BS
teefnihtgnelelohwretne)m8.8(tf03ot)m3.0(tf1xobnoitcnujhtiW 9
xobnoitcnujsseL 9
–JJ
–BS
465XBT X X X X X X X X X X egatnavdApetStxeN pat-toHerusserPhgiH)PRO(xodeR/Hp
041@isp003(ylbmessArosneS )C
rofsrosneSgnikcehc-fles
dnuorGnoituloShtiw()doR
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
20
Specification
Applications
High pressure insertion
Max. pressure/temperature
1380kPa (200 psi) at 140C (284F)
1725kPa (250 psi) at 100C (212F)
Features
2-piece sensor, double O-ring
Sealed body with stainless steel sleeve
Materials
Electrode body Ryton (Polyphenylene sulphide)
Outer sleeve 316 stainless steel(other materials available)
External O-rings Viton
Reference junction Wood or Teflon (PTFE)Junction type Flush
3/4 in. NPT Conduit Port (2 Typ.)
345.1(13.59)
71.1(2.80)
95.3 (3.74)
120.0(4.73)
Junction Box(see Note)
Kynar Adapter
Assembled Sensor
13/16 in. Wrench Flats1 in. NPT
3/4 in. NPT
Electrode
19.1(0.75)
Assembled Sensor
1 in. NPT 1 3/16 in. Wrench Flats 1 in. NPT
196.9 (7.75)6.4 (0.25)
12.7 (0.50)
28.6 (1.13)
Replaceable Body
Ryton BodyNo. 118 VitonO-Rings (2 Typ)
Stainless SteelSleeve
165.1 (6.50)30.1
(1.19)
26.67 (1.05)
316 StainlessSteel Body
Models TB567 and TBX567 Sensors
Overall Dimensions – Models TB(X)567
Dimensions in mm (in.)
Models TB(X)567 sensors are high pressure, in-line sensors.Their permissible pressure and temperature ratings are unique inthe industry.
After consultation with ABB, customers have exceeded thestandard ratings of 1724kPa (250 psi) at 100C (212F). Manyinstallations are operating at over 6895kPa (1000 psi).
The assembly comprises two parts: a 316 stainless steelhousing and a molded Ryton sensor body.
Models TB567 & TBX567 High Pressure In-Line Sensors
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
21
Ordering Information – Models TB(X)567
Notes.1) For direct connection to type TB82, TB84, 4630/35 and AX46 transmitters or other supplier devices using terminal blocks.
2) Antimony pH electrodes only supplied with flush junctions (code A and B).
3) Not available for Platinum, Redox (ORP), or Antimony, pH, electrodes (code 5 and 6).
4) Not available for fluoride-resistant electrodes (code F). Compatible with TB82, TB84, 4630/35 and AX46 instruments.
5) Kalrez O-rings for solution ground sleeve only. External O-rings are Viton. External Kalrez O-ring kits available separately.
6) There are two options to connect TB567 to TB82 or TB84 transmitters:
Option 1– use BNC/TC to PIN adapter with conduit fitting or BNC/TC to PIN adapter. In either case temperature compensator code must be 2 or 4.
Option 2 – select T in sensor cable code, not designed for use with extension cables or junction box.
7) Junction box mounted on sensor. Cable length approx. 254mm (10 in.). Requires extension cable to connect to transmitter. Order code for temperature compensatormust be 0, 2 or 4. If sensor is ordered without accessory hardware a junction box must be ordered separately.
srosneSetats-diloSdradnatSdoRdnuorGnoituloSoN petStxeN )PRO(xodeR/HperusserPhgiHeniL-nI
041@isp002(ylbmessArosneS )C765BT X X X X X X X X
edortcelEgnirusaeM
256FJ
001ot0(Hp,ssalG )Hp21ot0,C)PRO(xodeR,munitalP08ot02(Hp,ynomitnA )Hp11ot3,C 2
08ot01(tnatsiser-ediroulFHp,ssalG )Hp21ot0,C041ot5(erutarepmethgih/ssalgtnatsiser-taoC )Hp41ot0,C
256FJ
rotasnepmocerutarepmeTlargetnI
01–3–
765XBTroftoN
765XBTroftoN
enoNk3 sdaeldenniT 3
k3 rotcennocelbacnoisnetxE 3
sdaeldenniT001tP 4,3
rotcennocelbacnoisnetxE001tP 4,3
01234
noitcnuJecnerefeR
ABC
petStxeN,hsulf,dooWpetStxeN,hsulf,nolfeT
ecnerefeRpetStxeN,dessecer,nolfeT 9
ABC
lairetaMdoRdnuorGnoituloS
123
leetssselniats613muinatiT
2ByolletsaH
765BTroftoN765BTroftoN765BTroftoN
lairetaMgniR-O
1234
notiVMDPE
enociliSzerlaK 5
765BTroftoN765BTroftoN765BTroftoN765BTroftoN
elytSydoB
0 ydobrosneS765)X(BTledoM 0
erawdraHyrosseccA
0D
enoNgnisuohrosnesleetssselniats613765)X(BTledoM
0D
elbaCrosneSlargetnI,erusaeMfostinU 6
–T0
765XBTroftoN teef,rotcennocCNBteef,sdaelniP/denniT 1
detcelesera)woleb(SJ/BJnehwesU 7
FT0
elbaCrosneSlargetnI
–JJ
–BS
teefnihtgnelelohwretne)m8.8(tf03ot)m3.0(tf1xobnoitcnujhtiW 7
xobnoitcnujsseL 7
–JJ
–BS
765XBT X X X X X X X X X X egatnavdApetStxeN , )PRO(xodeR/HperusserPhgiHeniL-nI 1
041@isp002(ylbmessArosneS )C gnikcehc-flesrofsrosneS
dnuorGnoituloShtiw()doR
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
22
Accessories
Automatic CleanersABB sensors are designed to resist fouling and pluggingespecially when placed in sufficient velocity.
Sometimes a lack of velocity or the precipitative properties of theliquid require the use of an automatic cleaner.
ABB supplies jet-wash type cleaning facilities for submersion(immersion) TB556 sensors with 11/2 in. insertion depth.
When coupled to a customer-supplied solenoid valve deliveringwash fluid, effective cleaning can be initiated by ABB pHinstrumentation such as the TB84PH or AX46 Series. Forexample, the TB84PH can be configured:
• Wash cycle time 0 to 99.99 hours
• Wash on time 0 to 999 seconds
• Wash recovery time 0 to 999 seconds
• Hold function ON or OFF
Hydraulic Cleaner with Models TB(X)556 Sensor
Corrosion Resistant Tubing(Customer Supplied)
Solenoid Valve(Customer Supplied)
CleaningSolution
1/4 in. Union(Customer Supplied)
1/4 in. 316 Stainless Steel
1/4 in. Polypropylene
2 in. NPT Threads
Set Screw to SecureDelivery Tube
Hydraulic CleanerHousing
(PVC)
3/4 in. NPT
pH Sensor with anInserton Depth of 1.5 in.
PCV or Stainless Steel3/4 in. Coupling
(Customer Supplied)
PCV or Stainless Steel3/4 in. Conduit
(Customer Supplied)
Configurable ParametersInclude: Cycle Time, On Time,Recovery Time and Hold Outputs
Hydraulic Cleaner Application Example
Specification
Model
4TB5205-0232
Materials
PVC, Polypropylene
316 stainless steel
Max. pressure/temperature
690kPa (100 psi) at 40C (104F)
276kPa (40 psi) at 60C (140F)
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
23
pH/Redox (ORP) Transmitters
Model Description
TB82PH Advantage Series – 2-wire 24V d.c. 4 to 20mA
pH/Redox/pIon Transmitter – Certified intrinsically safe
– SMART-key programming
– On-line sensor diagnostics
– Configurable output
– Multi-temperaturecompensations
– Adjustable damping
– Hold output
– Configurable security code
– HART communication
– NEMA 4X/IP65 housing
– CE approved
TB84PH Advantage Series – AC-powered instrument
pH/Redox/pIon Transmitter – SMART-key programming
– On-line sensor diagnostics
– Configurable output
– Multi-temperaturecompensations
– Adjustable damping
– Hold output
– Configurable security code
– NEMA 4X/IP65 housing
– CE approved
– 3-relay outputs
– 2 analog outputs
– Wash control function
AX460 – AC-powered instrument
pH/Redox Transmitter – Simple menu programming
– Configurable output
– Multi-temperaturecompensations
– Hold output
– Configurable security code
– NEMA4/IP65 housing
– 1/4 DIN panel-mount housing
– CE approved
– 3 relay outputs
– 2 analog outputs
– Wash control function
…Accessories
Ball-Valves for TB(X)557 Sensors
Model Description
4TB5205-0174 11/4 in. 316 stainless steelIncludes 11/4 in. to 1 in. reducingbushing with 11/4 in. nipple.For wrench-tight compressionhardware 4TB4953-0024 only.
4TB5205-0175 11/2 in. Kynar (PVDF)Includes 11/2 in. to 1/4 in. reducingbushing with 11/2 in. nipple.For wrench-tight compressionhardware 4TB4953-0019 only.
4TB5205-0217 11/4 in. 316 stainless steelIncludes 11/4 in. nipple.For hand-tight compressionhardware 4TB4953-0006 only.
4TB5205-0218 11/2 in. Kynar (PVDF)Includes 11/2 in. to 11/4 in.reducing bushing with 11/2 in.nipple.For hand-tight compressionhardware 4TB4953-0060 or4TB4953-0065 only.
4TB5205-0254 11/2 in. 316 stainless steelIncludes 11/2 in. to 11/4 in.reducing bushing with 11/2 in.nipple.For hand-tight compressionhardware 4TB4953-0060 only.
4TB5205-0255 11/2 in. 316 stainless steelIncludes 11/2 in. to 1 in. reducingbushing with 11/2 in. nipple.For hand-tight compressionhardware 4TB4953-0024 only.
Acknowledgements
Hastelloy® is a registered trademark of Haynes International Inc.
Halar® is a registered trademark of Ausimont USA Inc.
Kalrez® and Viton are registered trademarks of DuPont Dow Elastomers L.L.C.
Kynar® is a registered trademark of Elf Atochem North America Inc.
LOCTITE® is a registered trademark of Loctite Corporation
Ryton® is a registered trademark Chevron Phillips Chemical Company
Teflon® is a registered trademark of E.I. DuPont de Nemours Company Inc.
Next Step™ and Next Step Advantage™ are trademarks of ABB Automation Inc.
pH/Redox (ORP) Sensors for Process MonitoringTB(X)5 Series SS/TBX5_3
SS
/TB
X5Is
sue
3
ABB Inc.Analytical Instruments9716 S. Virginia St., Ste. EReno, Nevada 89521USATel: +1 775 850 4800Fax: +1 775 850 4808
ABB Inc.125 E. County Line RoadWarminsterPA 18974USATel: +1 215 674 6000Fax: +1 215 674 7183
ABB has Sales & Customer Supportexpertise in over 100 countries worldwide
www.abb.com
ABB LimitedOldends Lane, StonehouseGloucestershireGL10 3TAUKTel: +44 (0)1453 826661Fax: +44 (0)1453 829671
The Company’s policy is one of continuous productimprovement and the right is reserved to modify the
information contained herein without notice.
Printed in UK (11.05)
© ABB 2005