24
Data Sheet 10/18-0.32-EN Electro-Pneumatic Positioner TZIDC-200 Pos: 1 /Titelblätter / Copyright/DB/Aktorik/Stellungsregler/Elektropneumatischer Stellungsregler TZIDC-200 @ 8\mod_1176719585890_3101.doc @ 82998 for 4 … 20 mA two-wire technology, flameproof enclosure Low operating cost Compact design Well-proven technology and intelligence Robust and environmentally ruggedized Wide operating temperature range -40 ... 85 °C (-40 ... 185 °F) Easy to commission, “single pushbutton” operating philosophy Mechanical position indicator ATEX, FM, CSA, GOST and IECEx approvals - flameproof enclosure - intrinsically safe For SIL2 safety loops Compact, well-proven, and flexible Pos: 2 /Inhaltsverzeichnis/Inhaltsverzeichnis für alle Dokumente @ 0\mod_1138710310890_3101.doc @ 3129 Contents

Upload: truongtuong

Post on 23-Sep-2018

251 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Data Sheet 10/18-0.32-EN

Electro-Pneumatic PositionerTZIDC-200

Pos: 1 /Titelblätter / Copyright/DB/Aktorik/Stellungsregler/Elektropneumatischer Stellungsregler TZIDC-200 @ 8\mod_1176719585890_3101.doc @ 82998

for 4 … 20 mA two-wire technology,flameproof enclosure

Low operating cost

Compact design

Well-proven technology and intelligence

Robust and environmentally ruggedized

Wide operating temperature range -40 ... 85 °C (-40 ... 185 °F)

Easy to commission, “single pushbutton” operating philosophy

Mechanical position indicator

ATEX, FM, CSA, GOST and IECEx approvals - flameproof enclosure - intrinsically safe

For SIL2 safety loops

Compact, well-proven, and flexible

Pos: 2 /Inhaltsverzeichnis/Inhaltsverzeichnis für alle Dokumente @ 0\mod_1138710310890_3101.doc @ 3129 Contents

Page 2: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

2

Contents 1 Description...........................................................................................................................................................3

1.1 Pneumatics.....................................................................................................................................................3 1.2 Operation........................................................................................................................................................3 1.3 Communication ..............................................................................................................................................3 1.4 Inputs and outputs..........................................................................................................................................3 1.5 Modular design...............................................................................................................................................3

2 Mounting versions...............................................................................................................................................5 2.1 To linear actuators in accordance with the standard .....................................................................................5 2.2 To rotary actuators in accordance with the standard .....................................................................................5 2.3 Integral mounting to control valves ................................................................................................................5 2.4 Special actuator-specific mounting ................................................................................................................5

3 Operation..............................................................................................................................................................7 3.1 General...........................................................................................................................................................7 3.2 Operator panel ...............................................................................................................................................8

4 Communication ...................................................................................................................................................9 4.1 DTM................................................................................................................................................................9 4.2 LKS adapter (RS-232 interface converter).....................................................................................................9 4.3 FSK Modem ...................................................................................................................................................9

5 Technical data....................................................................................................................................................10 5.1 Input..............................................................................................................................................................10 5.2 Output...........................................................................................................................................................10 5.3 Travel............................................................................................................................................................10 5.4 Air supply......................................................................................................................................................10 5.5 Transmission data and influences................................................................................................................10 5.6 Environmental capabilities ...........................................................................................................................11 5.7 Housing ........................................................................................................................................................11 5.8 Safety Integrity Level....................................................................................................................................11 5.9 Explosion protection .....................................................................................................................................12 5.10 Options .........................................................................................................................................................12 5.11 Accessories ..................................................................................................................................................13

6 Electrical connection ........................................................................................................................................14 7 Dimensions ........................................................................................................................................................16 8 Ordering information.........................................................................................................................................19

8.1 Ordering information (continued) .................................................................................................................20 8.2 Additional ordering information ....................................................................................................................20 8.3 Order information, accessories 1 .................................................................................................................21 8.4 Order information, accessories 2 .................................................................................................................22 8.5 Order information, accessories 3 .................................................................................................................23

Page 3: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

3

Pos: 3.1 /Überschriften/1/G - L/Kurzbeschreibung @ 7\mod_1175676881796_3101.doc @ 75993

1 Description Pos: 3.2 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828 Wechsel ein-auf zweispaltig Pos: 3.3 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Kurzbeschreibung TZIDC-2x0 @ 10\mod_1176706470984_3101.doc @ 81985

The TZIDC-200 is an electronically configurable positioner with communication capabilities, mounting to pneumatic linear or rotary actuators. It features a small and compact design, a modular construction, and an excellent cost-performance ratio. Fully automatic determination of the control parameters and adaptation to the final control element yield considerable time savings and an optimal control behavior. Pos: 3.4 /Überschriften/1.1/2-spaltig/Pneumatik @ 10\mod_1176211138453_3101.doc @ 76683

1.1 Pneumatics Pos: 3.5 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Pneumatik @ 10\mod_1173180645393_3101.doc @ 71139 a

An I/P module with subsequent pneumatic amplifier is used to control the pneumatic actuator. The well-proven I/P module proportionally converts the permanent electrical positioning signal from the CPU into a pneumatic signal used to adjust a 3/3-way valve. The air flow for pressurizing or depressurizing the actuator is continuously adjusted. As a result, excellent control is achieved. When reaching the set point, the 3/3-way valve is closed in center position to minimize the air consumption. Four different pneumatics versions are available: for single-acting or double-acting actuators, each with “fail-safe” or “fail-freeze” function. Pos: 3.6 /Überschriften/1.1.1/2-spaltig/Sicherheitsfunktion "entlüftend" @ 10\mod_1176211744343_3101.doc @ 76809

1.1.1 “Fail-safe” function Pos: 3.7 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Sicherheitsfunktion "entlüftend" @ 10\mod_1176211673796_3101.doc @ 76788

If the electrical power supply fails, the positioner output 1 is depressurized, and the pneumatic actuator’s return spring moves the valve to the defined safe position. In case of a double-acting actuator the second output 2 is additionally pressurized. Pos: 3.8 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Pos: 3.9 /Überschriften/1.1.1/2-spaltig/Sicherheitsfunktion "blockierend" @ 10\mod_1176211798765_3101.doc @ 76830

1.1.2 “Fail-freeze” function Pos: 3.10 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Sicherheitsfunktion "blockierend" @ 10\mod_1176211845484_3101.doc @ 76851

If the electrical power supply should fail, the positioner output 1 (and 2, if applicable) is closed and the pneumatic actuator stops (“freezes”) the valve in the current position. If compressed air supply should fail, the positioner depressurizes the actuator. Pos: 3.11 /Überschriften/1.1/2-spaltig/Bedienung @ 10\mod_1176211172234_3101.doc @ 76704

1.2 Operation Pos: 3.12 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Bedienung (Kommunikationsmöglichkeit) @ 10\mod_1173184631054_3101.doc @ 71160

The positioner has a built-in operating panel providing a 2-line LCD and 4 pushbuttons for optimal local configuration, commissioning and operational monitoring. Alternatively, the appropriate configuration program and the available communication option can be used. Pos: 3.13 /Überschriften/1.1/2-spaltig/Kommunikation @ 10\mod_1176211201546_3101.doc @ 76725

1.3 Communication Pos: 3.14 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kurzbeschreibung/Kommunikation @ 10\mod_1176212225390_3101.doc @ 76893

The standard TZIDC-200 model has a local communication interface (LKS connector). Additionally, a “HART communication” option for communication via the 20 mA signal is available. Both communications are based on the HART Protocol. Pos: 3.15 /Überschriften/1.1/2-spaltig/Ein-/Ausgänge @ 10\mod_1176211233015_3101.doc @ 76746

1.4 Inputs and outputs Pos: 3.16 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kurzbeschreibung/Ein-/Ausgänge @ 10\mod_1176212290390_3101.doc @ 76914

In addition to its input for the analog position set point the TZIDC-200 positioner is equipped with a digital input which can be used to activate various protective functions in the device via the process control system. A digital output allows you to output collective alarms or fault messages. Pos: 3.17 /Überschriften/1.1/2-spaltig/Modularer Aufbau @ 10\mod_1176211317984_3101.doc @ 76767

1.5 Modular design Pos: 3.18 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/ModularerAufbau @ 10\mod_1173184783043_3101.doc @ 71181 q

The TZIDC-200 basic model can be enhanced at any time by retrofitting optional equipment. Option modules for analog or digital position feedback or a shutdown-module can be installed. Additionally, a mechanical position indicator, proximity switches or 24 V microswitches are available for indicating the position independently of the mother board function. Pos: 3.19 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829

Wechsel ein-auf zweispaltig Pos: 3.20 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 4: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

4

Pos: 3.21 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kurzbeschreibung/Schematische Darstellung @ 10\mod_1173185518080_3101.doc @ 71202

Basic model Optional upgrades

Fig. 1: TZIDC-200 schematic diagram Basic model Optional upgrades 1 LKS plug 9 Plug module for analog feedback (4 … 20 mA) 2 Positioning signal 4 … 20 mA 10 Plug-in module for safety shutdown (forced depressurization) 3 Digital input 11 Plug module for digital feedback 4 Digital output DO 12 Installation kit for mechanical position indicator 5 Supply, 1.4 … 6 bar 13 Installation kit for digital feedback with proximity switches 6 Exhaust 14 Installation kit for digital feedback with 24 V microswitches 7 I/P module with 3/3-way valve 8 Position sensor (optional up to 270° rotation angle)

Important With optional upgrades either the “Installation kit for digital feedback with proximity switches” (13) or the “Installation kit for digital feedback with microswitches 24 V” (14) can be used. In both cases, the “mechanical position indicator” (8) must be installed.

Pos: 4 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 5: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

5

Pos: 5.1 /Überschriften/1/A - F/Anbauversionen @ 9\mod_1180950395125_3101.doc @ 101275

2 Mounting versions Pos: 5.2 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828 Wechsel ein-auf zweispaltig Pos: 5.3 /Überschriften/1.1/2-spaltig/Genormter Anbau an pneumatische Linearantriebe @ 10\mod_1176212852312_3101.doc @ 76956

2.1 To linear actuators in accordance with the standard

Pos: 5.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Genormter Anbau an pneumatische Linearantriebe @ 10\mod_1176213091968_3101.doc @ 77040

Lateral attachment is in accordance with DIN / IEC 534 (lateral attachment to NAMUR). The required attachment kit is a complete set of attachment material, but does not include the screwed pipe connections and air pipes. Pos: 5.5 /Überschriften/1.1/2-spaltig/Genormter Anbau an pneumatische Schwenkantriebe @ 10\mod_1176212899953_3101.doc @ 76977

2.2 To rotary actuators in accordance with the standard

Pos: 5.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Genormter Anbau an pneumatische Schwenkantriebe @ 10\mod_1176213146937_3101.doc @ 77061

This attachment is designed for mounting according to the standard VDI/VDE 3845. The attachment kit consists of a console with mounting screws for mounting on a rotary actuator. The adapter for coupling the positioner feedback shaft to the actuator shaft has to be ordered separately. Screwed pipe connections and air pipes have to be provided on site. Pos: 5.7 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Pos: 5.8 /Überschriften/1.1/2-spaltig/Integrierter Anbau an Regelventile @ 10\mod_1176212940421_3101.doc @ 76998

2.3 Integral mounting to control valves Pos: 5.9 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Integrierter Anbau an Regelventile, TZIDC-2x0 @ 10\mod_1181809000968_3101.doc @ 105953

The TZIDC-200 positioner featuring standard pneumatic action is available as an option for integral mounting. The required holes are found at the back of the device. The benefit of this design is that the point for mechanical stroke measurement is protected and that the positioner and actuator are linked internally. No external tubing is required. Pos: 5.10 /Überschriften/1.1/2-spaltig/Besondere antriebsspezifische Anbauversionen @ 10\mod_1176212991062_3101.doc @ 77019

2.4 Special actuator-specific mounting Pos: 5.11 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Besondere antriebsspezifische Anbauversionen @ 10\mod_1173186727709_3101.doc @ 71265

In addition to the mounting methods described above, there are special actuator-specific attachments. Please contact us for details. Pos: 5.12 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829

Wechsel ein-auf zweispaltig Pos: 5.13 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 6: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

6

Pos: 5.14 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Anbauvarianten TZIDC-2x0 @ 10\mod_1178783906328_3101.doc @ 90413

Fig. 2: Mounting options 1 Mounting to linear actuators acc. to DIN / IEC 534 3 Integral mounting to control valves 2 Mounting to rotary actuators to VDI / VDE 3845 4 Integral mounting to control valves by using an adapter panel

Pos: 6 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 7: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

7

Pos: 7.1 /Überschriften/1/A - F/Betrieb @ 10\mod_1175678278921_3101.doc @ 76015

3 Operation Pos: 7.2 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828 Wechsel ein-auf zweispaltig Pos: 7.3 /Überschriften/1.1/2-spaltig/Allgemeines @ 10\mod_1176213970765_3101.doc @ 77124 A

3.1 General Pos: 7.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Allgemeines @ 10\mod_1176214294328_3101.doc @ 77292

Microprocessor-based position control in the TZIDC-200 provides for optimal results. The positioner features high-precision control functions and high operational reliability. Due to their elaborate structure and easy accessibility, the device parameters can be quickly adapted to the respective application.

The total range of parameters includes: - Operating parameters - Adjustment parameters - Monitoring parameters - Diagnosis parameters - Maintenance parameters Pos: 7.5 /Überschriften/1.1.1/2-spaltig/Betriebsparameter @ 10\mod_1176214001500_3101.doc @ 77145

3.1.1 Operating parameters Pos: 7.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Betriebsparameter @ 10\mod_1176214346265_3101.doc @ 77343

The following operating parameters can be set manually if required:

Signal Signal min. 4 mA, max. signal 20 mA (0 ... 100 %) freely selectable for split-range operation min. range 20 % (3.2 mA) recommended range > 50 % (8.0 mA)

Action (positioning signal) Increasing: Signal 4 ... 20 mA = position 0 ... 100 % Increasing: Signal 20 ... 4 mA = position 0 ... 100 %

Characteristic curve (travel = f signal) Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 or freely configurable with 20 reference points.

Travel limit The positioning travel, i.e. the stroke or angle of rotation, can be reduced as required within the full range of 0 ... 100 %, provided that a minimum value of 20 % is observed.

Shut-off function This parameter can be set separately for each end position. When the respective configured limit value is exceeded, the shut-off function causes immediate travel of the actuator until reaching the set end position. When the shut-off value is set to “0”, the position is further controlled, even in the respective end position.

Travel time prolongation This function can be used to increase the max. travel time for full travel. This time parameter can be set separately for each direction.

Important This function can only be used with the pneumatics with the safety function “fail-safe”.

Switching points for the position This parameter allows you to define two position limits for signaling (see option “Module for digital position feedback”).

Digital output The alarms generated in the TZIDC-200 positioner can be polled via the digital output as a collective alarm. The desired information can be selected via the operator panel or remotely via the configuration program. The output can be set to “active high” or “active low”, as required.

Digital input For the digital input, one of the following safety options can be selected. You may use the operator’s panel or configuration program to select an option. - No function (default) - Move to 0 % position - Move to 100 % position - Hold previous position - disable local configuration - Disable local configuration and operation - Disable any access (no local or remote access via a PC) The selected function is activated once the 24 V DC signal is no longer applied (< 11 V DC).

Pos: 7.7 /Überschriften/1.1.1/2-spaltig/Justageparameter @ 10\mod_1176214036515_3101.doc @ 77166

3.1.2 Adjustment parameters Pos: 7.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Justageparameter @ 10\mod_1176214397515_3101.doc @ 77364

The TZIDC-200 positioner has a special function for automatic adjustment of the parameters. Additionally, the control parameters can be set automatically (in adaptive control mode) or manually to optimally adapt them to the process requirements.

Tolerance band When reaching the tolerance band the position is considered as corrected. From this point on, the position is further slowly re-adjusted until the dead band is reached. The factory setting for this parameter is 0.3 %.

Dead band (sensitivity) When reaching the dead band, the position is held. The factory setting for this parameter is 0,1 %.

Actuator spring action Selection of the sensor shaft rotating sense (looking into the open case), if the valve is moved to the safe position by the actuator spring (actuator is depressurized via Y1/OUT1). For double-acting actuators the actuator spring action corresponds to pressurizing the pneumatic output (OUT2).

Display 0 ... 100 % Adjusting the display (0 ... 100 %) according to the direction of action for opening or closing the valve. Pos: 7.9 /Überschriften/1.1.1/2-spaltig/Betriebsüberwachungsparameter @ 10\mod_1176214071453_3101.doc @ 77187

3.1.3 Monitoring parameters Pos: 7.10 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Betriebsüberwachungsparameter @ 10\mod_1176214447375_3101.doc @ 77385 B

Various functions for permanent operational monitoring are implemented in the TZIDC-200 operating program. The following states will be detected and indicated, e.g.: - 4 ... 20 mA signal out of range - position out of the adjusted range - positioning time-out (adjustable time parameter) - position controller inactive - counter limits (settable in the diagnosis phase) exceeded While automatic commissioning is in progress, the current state is continuously indicated on the integrated LCD. During operation, the LCD shows the most important process variables: - current position (in %), - malfunctions, alarms, messages (as code) Access to extended monitoring parameters is possible via HART communication and the DTM. Pos: 7.11 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 8: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

8

Pos: 7.12 /Überschriften/1.1.1/2-spaltig/Diagnoseparameter @ 10\mod_1176214111046_3101.doc @ 77208

3.1.4 Diagnosis parameters Pos: 7.13 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Diagnoseparameter @ 10\mod_1176214500906_3101.doc @ 77406

The diagnosis parameters of the TZIDC-200 program inform the operator about the operating conditions of the valve. From this information the operator can derive which maintenance works are required, and when. Additionally, limit values can be defined for these parameters. When they are exceeded, an alarm is reported. The following values are e.g. determined: - Number of movements performed by the valve - Total travel The diagnosis parameters and limit values can be called up, set, and reset via HART communication, using the configuration program.

Pos: 7.14 /Überschriften/1.1/2-spaltig/Bedienpanel @ 10\mod_1176214143953_3101.doc @ 77229

3.2 Operator panel Pos: 7.15 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Bedienpanel TZIDC-2x0 @ 10\mod_1178871475703_3101.doc @ 90683

The TZIDC-200 positioner’s operator panel with four pushbuttons allows for - operational monitoring - manual control - configuration - fully automatic commissioning The operator panel is protected by a hinged cover which can be opened during operation even in hazardous areas, i.e. the positioner can be locally operated any time as required. Pos: 7.16 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Pos: 7.17 /Überschriften/1.1.1/2-spaltig/Ein-Tasten-Inbetriebnahme @ 10\mod_1176214193156_3101.doc @ 77250

3.2.1 Single-button commissioning Pos: 7.18 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Ein-Tasten-Inbetriebnahme @ 10\mod_1176214842843_3101.doc @ 77448

Commissioning the TZIDC-200 positioner is especially easy. The standard Autoadjust function for automatic adaptation of the device parameters can be started by simply pressing a single front panel button, and without knowing parameterization details. Depending on the selected actuator type (linear or rotary), the displayed zero position is automatically adapted: - for linear actuators counter-clockwise (CTCLOCKW) - for rotary actuators clockwise (CLOCKW). Besides this standard function, a customized “Autoadjust” function is available. The function is launched either via the operator’s panel or HART communication.

Pos: 7.19 /Überschriften/1.1.1/2-spaltig/Anzeigen @ 10\mod_1176214259859_3101.doc @ 77271

3.2.2 Display Pos: 7.20 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Anzeigen @ 10\mod_1176214873937_3101.doc @ 77469

The information indicated by the 2-line LC display is permanently updated and adapted during operation, to inform the operator in an optimal way. During control operation (control with or without adaptation) the following TZIDC-200 data can be called up by pressing the pushbuttons briefly: - Up button: Current setpoint (mA) - Down button: Temperature in device - Up + Down buttons: Current control deviation Pos: 7.21 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829

Wechsel ein-auf zweispaltig Pos: 7.22 /==== Leeres Modul mit einer Absatzmarke ==== @ 2\mod_1153381574375_0.doc @ 35553

Pos: 7.23 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828 Wechsel ein-auf zweispaltig Pos: 7.24 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Abb. TZIDC-2x0 und Bedienelemente @ 10\mod_1176707111062_3101.doc @ 82068

M00261 Fig. 3: TZIDC-200 with removed cover, view of the operator panel

M00235

conf

mA

ENTER

MODE

%°C

Fig. 4: TZIDC-200 operating elements and display

Pos: 7.25 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829

Wechsel ein-auf zweispaltig Pos: 8 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 9: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

9

Pos: 9.1 /Überschriften/1/G - L/Kommunikation @ 0\mod_1139412848859_3101.doc @ 3153 Communication

4 Communication Pos: 9.2 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828 Wechsel ein-auf zweispaltig Pos: 9.3 /Überschriften/1.1/2-spaltig/DTM @ 10\mod_1176215310421_3101.doc @ 77511

4.1 DTM Pos: 9.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kommunikation/DTM @ 10\mod_1176215507046_3101.doc @ 77595

The DTM (Device Type Manager) for TZIDC-200 is based on the FDT/DTM technology (FDT 1.2) and can be integrated in a process control system or loaded in a PC with the DSV401 (SMART VISION) program. This allows you to work with the same user interface in the commissioning phase, during operation, and for service tasks for monitoring the device, setting parameters, and uploading data. Communication is based on the HART protocol. It occurs via a local interface connection (LKS) or in frequency-modulated mode using an FSK-modem connected at any chosen point of the 20 mA signal line. Communication has no effect on operation. Newly set parameters are saved in the non-volatile memory directly upon the download into the device, and become active immediately. Pos: 9.5 /Überschriften/1.1/2-spaltig/LKS-Adapter (RS-232 Schnittstellenwandler) @ 10\mod_1176215338250_3101.doc @ 77532

4.2 LKS adapter (RS-232 interface converter) Pos: 9.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kommunikation/LKS-Adapter (RS-232 Schnittstellenwandler) @ 10\mod_1176215612828_3101.doc @ 77616

You can easily connect your TZIDC-200 positioner to a PC, e.g., in the workshop or in the commissioning phase, by using the positioner’s LKS adapter (LKS = local communication interface). An RS-232 interface converter adapts the signals on the serial PC port to the level of the positioner’s LKS.

Pos: 9.7 /Überschriften/1.1/2-spaltig/FSK-Modem @ 10\mod_1176215390421_3101.doc @ 77553

4.3 FSK Modem Pos: 9.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kommunikation/FSK-Modem @ 10\mod_1176215656328_3101.doc @ 77637

The FSK modem establishes a digital frequency-modulated communication (Frequency Shift Keying) with the TZIDC-200 positioner. Tapping is possible at any chosen point of the 20 mA signal line. We recommend that you use an electrically isolated FSK modem. It is bus-compatible when used with isolating amplifiers. Even connecting explosion-protected field devices is possible, on condition that the FSK modem is run outside the hazardous area.

Fig. 5: Local communication via LKS adapter

1 TZIDC-200 2 LKS adapter

3 Controller

Fig. 6: HART communication with FSK modem via 20 mA signal line

1 TZIDC-200 2 FSK modem

3 Controller

Pos: 9.9 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829

Wechsel ein-auf zweispaltig Pos: 10 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 10: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

10

Pos: 11.1 /Überschriften/1/S - Z/Technische Daten @ 0\mod_1132904574837_3101.doc @ 3169

5 Technical data Pos: 11.2 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828 Wechsel ein-auf zweispaltig Pos: 11.3 /Überschriften/1.1/2-spaltig/Eingang @ 0\mod_1139395051468_3101.doc @ 3221

5.1 Input Pos: 11.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Eingang / Stellsignal (Zweileitertechnik) @ 10\mod_1176272560140_3101.doc @ 77936

Output signal (two-wire technology) Nominal range 4 ... 20 mA Split range configuration between 20 ... 100 %

of the nominal range Max. 25 mA Min. 3.6 mA Starting at 3,8 mA Load voltage at 20 mA 9,7 V Impedance at 20 mA 485 Ω

Digital input Control voltage 0 ... 5 V DC logical switching

state "0" 11 ... 30 V DC logical switching

state "1" Current max. 4 mA Pos: 11.5 /Überschriften/1.1/2-spaltig/Ausgang @ 10\mod_1176215873937_3101.doc @ 77658

5.2 Output Pos: 11.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Ausgang / Druckluftausgang @ 10\mod_1176272620812_3101.doc @ 77957

Compressed air output Range 0 ... 6 bar (0 ... 90 psi)

Air capacity 5.0 kg/h = 3.9 Nm³/h = 2.3 sfcm

at 1.4 bar (20 psi) supply pressure

13 kg/h = 10 Nm³/h = 6,0 sfcm

at 6 bar (90 psi) supply pressure

Output function For single or double-acting actuators, air is vented from actuator or actuator is blocked in case of (electrical) power failure

Shut-off values End position 0 % = 0 ... 45 %

End position 100 % = 55 ... 100 %

Digital output (control circuit to DIN 19234/NAMUR) Supply voltage 5 ... 11 V DC Current > 0.35 mA … < 1.2 mA Switching state logical "0" Current > 2.1 mA Switching state logical "1" Effective direction (configurable) normally logical "0" or logical "1" Pos: 11.7 /Überschriften/1.1/2-spaltig/Stellweg @ 10\mod_1176215894234_3101.doc @ 77679

5.3 Travel Pos: 11.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Stellweg / Drehwinkel @ 10\mod_1176272774203_3101.doc @ 77978

Rotation angle Used range 25 ... 120 (rotary actuators,

optional 270°) 25 ... 60 ° (linear actuators) Travel limit Min. and max. limits, freely

configurable between 0 ... 100 % of total travel (min. range > 20 %)

Travel time prolongation Range of 0 ... 200 seconds, separately for each direction

Dead band time limit Range 0 ... 200 seconds (monitoring parameter for control until the deviation reaches the tolerance band)

Pos: 11.9 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Pos: 11.10 /Überschriften/1.1/2-spaltig/Luftversorgung @ 10\mod_1176215914875_3101.doc @ 77700

5.4 Air supply Pos: 11.11 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Technische Daten/Luftversorgung TZIDC-2x0 @ 10\mod_1180951671703_3101.doc @ 101588

Instrument air free of oil, water and dust acc. to DIN / ISO 8573-1 pollution and oil content according to Class 3 (purity: max. particle size: 5 µm, max. particle density: 5 mg / m3; oil content: max. concentration: 1 mg / m3; pressure dew point: 10 K below operating temperature

Supply pressure 1.4 ... 6 bar (20 ... 90 psi)

Note: Do not exceed the max. operating pressure of the actuator!

Air consumption < 0.1 kg/h / 0.05 scfm (independent of supply pressure)

Pos: 11.12 /Überschriften/1.1/2-spaltig/Übertragungsdaten und Einflussgrößen @ 10\mod_1176215939812_3101.doc @ 77721

5.5 Transmission data and influences Pos: 11.13 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Übertragungsdaten und Einflussgrößen @ 10\mod_1176272844734_3101.doc @ 78020

Output Y1 Increasing Increasing output signal 0 ... 100 % Increasing pressure at output

Decreasing Increasing output signal 0 ... 100 % Decreasing pressure at output

Action (positioning signal) Increasing Signal 4 ... 20 mA =

actuator position 0 ... 100 % Decreasing Signal 20 ... 4 mA =

actuator position 0 ... 100 %

Characteristic curve (travel = f signal) Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 and freely configurable with 20 reference points. Characteristic deviation < 0,5 % Tolerance band 0.3 ... 10 %, adjustable Dead band 0,1 ... 10 %, adjustable Resolution (A/D conversion) > 4000 steps Sample rate 20 ms Influence of ambient temperature < 0.5 % per 10 K Influence of vibration < ± 1 % to 10 g and 80 Hz

Seismic requirements Meets requirements of DIN / IEC 68-3-3 Class III for strong and strongest earthquakes.

Influence of mounting orientation Not measurable.

Meets the requirements of the following directives - EMC Directive 89 / 336 / EWG as of May 1989 - EC Directive for CE conformity marking

Communication - HART Protocol 5.1 - Local connector for LKS (local communication interface) adapter - HART communication via 20 mA signal line with (optional) FSK

modem Pos: 11.14 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Page 11: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

11

Pos: 11.15 /Überschriften/1.1/2-spaltig/Klimatische Beanspruchung @ 10\mod_1176215985578_3101.doc @ 77742

5.6 Environmental capabilities Pos: 11.16 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Technische Daten/Klimatische Beanspruchung @ 10\mod_1176272943953_3101.doc @ 78041

Ambient temperature For operation, storage and transport:

-40 … 85 °C (-40 ... 185 °F)

When using proximity switches SJ2-S1N (NO):

-25 … 85 °C (-13 ... 185 °F)

Relative humidity Operational (with closed housing and air supply switched on):

95 % (annual average), condensation permissible

Transport and storage: 75 % (annual average), non-condensing

Pos: 11.17 /Überschriften/1.1/2-spaltig/Gehäuse @ 10\mod_1176216027484_3101.doc @ 77763

5.7 Housing Pos: 11.18 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Gehäuse TZIDC-200 @ 10\mod_1176708472718_3101.doc @ 82221

Material/Protections Aluminum, protection class IP 65 / NEMA 4X Surface/color Electrostatic dipping varnish with epoxy resin, stove-hardened. Case varnished black, RAL 9005, matte, housing cover Pantone 420. Electrical connections Screw terminals: Max. 1.0 mm2 for options,

Max. 2.5 mm2 for analog signal. Note: Do not expose the terminals to strain. Cable entry: 2 tap holes 1/2-14 NPT or

M20 x `1.5 (cable gland or pipe plug must be ordered separately)

Pneumatic connections Threads G 1/4 or 1/4-18 NPT Weight 3,0 kg Mounting orientation any orientation allowed Dimensions see dimensional drawings Pos: 11.19 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Pos: 11.20 /Überschriften/1.1/2-spaltig/Sicherheitsintegritätslevel @ 10\mod_1176216055937_3101.doc @ 77784

5.8 Safety Integrity Level Pos: 11.21 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Sicherheitsintegritätslevel @ 13\mod_1191309977312_3101.doc @ 126333

Important Applies to applications with single-acting and depressurizing pneumatics.

The positioner TZIDC-200 and the emergency shutdown module for TZIDC-200 meet the requirements regarding: - functional safety in accordance with IEC 61508 / IEC 61511-1 - explosion protection (depending on the model) - electromagnetic compatibility in accordance with EN 61000 In case of a failure of electrical power or compressed air supply or when a positioner malfunction occurs, the actuator is depressurized by the positioner, and the return spring in the actuator moves the valve to a pre-defined, safe end position (either OPEN or CLOSED). SIL specific safety-related characteristics:

TZIDC-200 Emergency shutdown module for TZIDC-200

Category SIL2 SIL2 SFF 85 % 94 % PFDav 6.89 x 10-4 1.76 x 10-4 λdd + λs 925 FIT 718 FIT λdu 157 FIT 40 FIT

For details refer to the Management Summary in the SIL-Safety Instructions 37/18-79XA.

Pos: 11.22 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Page 12: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

12

Pos: 11.23 /Überschriften/1.1/2-spaltig/Explosionsschutz @ 10\mod_1176216136218_3101.doc @ 77805

5.9 Explosion protection Pos: 11.24 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Explosionsschutz TZIDC-200 @ 10\mod_1176711825609_3101.doc @ 82410

Important The values indicated here are taken from the respective approval certificates. Always observe the specifications and supplements in the certificates. (see operating instructions).

FM Approval HLC 8/02 3010829 Explosion proof; enclosure 4X; T5, max. 82 °C CL I; Div 1; Grp. C-D

Intrinsically safe; enclosure 4X; T5, max. 82 °C CL I, II, III; Div 1; Grp. A-B-C-D-E-F-G

Non-incendive, enclosure 4X; T4, max. 85 °C CL I; Div 2; Grp. A-B-C-D CL II, III; Div 2; Grp. F-G

Dust ignition-proof; enclosure 4X; T5, max. 82 °C CL II, III; Div 1; Grp. E-F-G CSA Certification 1393920 Explosion proof; enclosure 4X; T5, max. 85 °C CL I; Div 1; Grp. C-D CL II; Div 1; Grp. E-F-G CL III

Intrinsically safe; enclosure 4X; T5, max. 82 °C CL I; Div 1; Grp. A-B-C-D CL II; Div 1; Grp. E-F-G CL III ATEX / GOST Russia / GOST Ukraine

II 2G EEx d II C T4/T5/T6

Prototype test certificate: DMT 02 ATEX E 029 X

Type: Flameproof enclosure

Device class: II 2G (EEx ib IIC)

Temperature class: T4, T5, T6

Permissible ambient temperature:

T4: -40 °C < Tamb < 85 °C

T5: -40 °C < Tamb < 80 °C

T6: -40 °C < Tamb < 65 °C

ATEX II 2G EEx ib IIC T6 Prototype test certificate: TÜV 98 ATEX 1370 X

Type: Intrinsically safe equipment

Device class: II 2G (EEx ib IIC)

Temperature class: T4, T5, T6

Permissible ambient temperature:

T4: -40 °C < Tamb < 85 °C

T5: -40 °C < Tamb < 50 °C

T6: -40 °C < Tamb < 35 °C

IECEx Ex ib IIC T6 Prototype test certificate: IECEx TUN 04.0015X, Issue no.:

0

Type: Intrinsically safe

Temperature class: T4, T5, T6

Permissible ambient temperature:

T4: -40 °C < Tamb < 85 °C

T5: -40 °C < Tamb < 50 °C

T6: -40 °C < Tamb < 35 °C

Pos: 11.25 /Überschriften/1.1/2-spaltig/Optionen @ 10\mod_1176216171890_3101.doc @ 77826

5.10 Options Pos: 11.26 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Optionen TZIDC-200 @ 10\mod_1180689072031_3101.doc @ 100723

Module for analog position feedback1) Signal range 4 ... 20 mA (configurable split

ranges)

Supply, 2-wire circuitry 24 V DC (10 ... 30 V DC)

48 V DC (20 ... 48 V DC,

no ignition protection)

Characteristic curve (configurable)

Rising or falling

Characteristic deviation < 1 %

Important Without a signal from the positioner (e.g., “no energy” or “initializing”) the module sets the output to > 20 mA (alarm level)

Module for digital position feedback1) Two switches for digital position feedback (position adjustable within the range of 0 ... 100%, ranges cannot overlap)

Current circuits acc. to DIN 19234 / NAMUR

Supply voltage 5 ... 11 V DC

Signal current < 1.0 mA Switching state logical “0“

Signal current > 2,0 mA Switching state logical “1“

Direction of action normally logical “0“ or logical “1“ (configurable)

Module for the emergency shutdown function2) Supply voltage 24 V DC (20 ... 30 V DC)

(galvanically isolated from input signal)

Safe position is activated when voltage < 5 V Explosion protection see certificate (operating

instructions) SIL See “Explosion protection”

A separate 24 V DC signal is normally applied to the emergency shutdown module, which connects through the signal from the microprocessor to the I/P module. When the 24 V DC signal is interrupted, the pneumatic module executes the respective safety function, depending on the mechanical construction:

The positioner output 1 is depressurized, and the valve is moved to the safe position. In case of a double-acting actuator the second output 2 is additionally pressurized.

Important The emergency shutdown module can only be used with pneumatics with the safe position “fail-safe”.

Page 13: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

13

The emergency shutdown module works independently of the mother board, i.e. all information from the final control element is available in the supervisory process control system at any time. 1) The module for analog position feedback and the module for

digital position feedback plug in separate slots and can be used together.

2) The module for the emergency shutdown function uses the same space as the module for analog feedback and the module for analog or digital feedback and cannot be plugged in and run together with any of them.

Digital position feedback with proximity switches Two proximity switches for independent position signaling. Switching points adjustable between 0 … 100 %

Current circuits acc. to DIN 19234 / NAMUR

Supply voltage 5 ... 11 V DC

Signal current < 1.0 mA Switching state logical “0“

Signal current > 2,0 mA Switching state logical “1“

Direction of action (logical state)

Position Proximity switch < Lim. 1 > Lim. 1 < Lim. 2 > Lim. 2

SJ2-SN (NC) 0 1 1 0

SJ2-S1N (NO) 1 0 0 1

Important When using SJ2_S1N (NO), the TZIDC-200 positioner may only be used at an ambient temperature range from -25 ... 85 °C (-13 ... 185 °F).

Digital position feedback with 24 V microswitches

Important Only approved for Ex d version!

Two microswitches for independent position signaling. Switching points adjustable between 0 … 100 %.

Voltage max. 24 V AC / DC

Load rating max. 2 A

Contact surface 10 µm Gold (AU) Mechanical position indicator Indicator disk in enclosure cover, linked with positioner feedback shaft through magnetic coupling.

Important These options are also available for retrofitting by Service.

Pos: 11.27 /======= Spaltenumbruch ======== @ 0\mod_1132937966324_3101.doc @ 3831

Pos: 11.28 /Überschriften/1.1/2-spaltig/Zubehör @ 10\mod_1176216204812_3101.doc @ 77847

5.11 Accessories Pos: 11.29 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Zubehör TZIDC-200 @ 10\mod_1176713261968_3101.doc @ 82461

Mounting material Attachment kit for linear actuators to DIN/IEC 534 / NAMUR

Attachment kit for rotary actuators to VDI/VDE 3845

Attachment kit for integral mounting to control valves

Attachment kit for actuator-specific attachment upon request

EEx d cable glands Cable gland and pipe plug approved for Ex d, securing adhesive

Pressure gauge block With pressure gauges for supply and output pressure. Pressure gauges with housing ø 28 mm,, with connection block in aluminum, black with installation material for mounting toTZIDC-200.

Filter regulator All metal version in brass, varnished black, bronze filter element, 40 µm, with condensate drain.

max. pre-pressure 16 bar, output adjustable to 1.4 ... 6 bar

PC adapter for communication LKS adapter f. plug conn. to TZIDC-200

FSK modem for HART communication

(see data sheet 63_6.71 DE)

PC software for remote configuration and operation DSV401 (SMART VISION) with DTM for TZIDC/TZIDC-200 available on CD ROM (see data sheet 63_1.20 EN) Pos: 11.30 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829

Wechsel ein-auf zweispaltig Pos: 12 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 14: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

14

Pos: 13.1 /Überschriften/1/A - F/Elektrischer Anschluss @ 0\mod_1140620471687_3101.doc @ 3143

6 Electrical connection Pos: 13.2 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Elektrischer Anschluss/Elektrischer Anschluss 200 @ 11\mod_1183551089984_3101.doc @ 109643

M00313

1

2

36

7

4

5

+41

-42

Lim

it2

+51

-52

Lim

it1

+11

-12

+81

-82

+83

-84

+51

-52

+41

-42

+31

-32

8

9

Fig. 7: Screw terminals, overview 1 Module for analog position feedback 2 Module for digital feedback or service switch of emergency

shutdown module 3 Module for digital feedback or terminals for emergency

shutdown module 4 Digital position feedback, either proximity switches or 24 V

microswitches

5 Digital position feedback, either proximity switches or 24 V microswitches

6 Digital output DO 7 Digital input 8 Signal 4 ... 20 mA 9 Grounding screw

Page 15: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

15

Fig. 8: Pin configuration A Basic model B Options

1 Analog input 2 Digital input 3 Digital output DO 4 Digital feedback 5 Analog feedback 6 Proximity switches 7 Microswitches 8 Emergency shutdown module

Pos: 14 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 16: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

16

Pos: 15.1 /Überschriften/1/M - R/Maßbilder @ 2\mod_1151313449156_3101.doc @ 31849

7 Dimensions Pos: 15.2 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Maßbilder/Maßbilder TZIDC-2x0 @ 10\mod_1176714385562_3101.doc @ 82545

All dimensions in mm (inch)

Fig. 9: Top view A Tap hole M8 (10 mm low) B Tap hole M6 (8 mm low)

C Tap hole M5 x 0.5 (air connections in version for integral mounting) D Sensor shaft (larger than scale)

Fig. 10: Left and right side view A NPT ½” or M20 x 1.5 B Pneumatic connections, NPT ¼“ -18 or G1/4“

Page 17: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

17

Fig. 11: Bottom view A Pneumatic connections, NPT 1/4"-18 or G1/4"

M00300

45

/7

5(1

.77

/2

.95

)

25

(0.9

9)

75

(2.9

5)

30 / 53

(1.18 / 2.09)

B*

A*

Mounting to linear actuators to DIN/IEC 534 Mounting to rotary actuators to VDI/VDE 3845

*) Dimensions A and B are dependent on the rotary actuator Fig. 12: Mounting drawings

Page 18: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

18

M00301

40 (1.58)120 (4.73)

97

(3.8

2)

Fig. 13: Positioner TZIDC-200 with pressure gauge block and filter regulator Pos: 16 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 19: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

19

Pos: 17.1 /Überschriften/1/A - F/Bestellinformationen @ 0\mod_1139397854370_3101.doc @ 3141 Order information

8 Ordering information Pos: 17.2 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Bestellinformationen/Bestellinformationen TZIDC-200 @ 10\mod_1176714838156_3101.doc @ 82613

Electro-Pneumatic Positioner Variant digit No. 1 - 7 8 9 10 11 12 13 14 CodeTZIDC-200 with Flameproof Enclosure Catalog No. V18348- 0intelligent, software-configurable with local communicationinterface (LKS) and HART communicationCase / MountingCase made of aluminium, varnished, protection IP 65 (NEMA 4X)

for mounting to linear actuators acc. to DIN/IEC 534 / NAMUR or to rotary actuators acc. to VDI/VDE 3845 1

as above, but with mechanical position indicator 2for integral mounting to control valves 3

as above, but with mechanical position indicator 4for mounting to rotary actuators acc. to VDI/VDE 3845with extended rotation angle up to 270° 5

as above, but with mechanical position indicator 6

See Options/Accessories for customer-specific mountingPlease specify the actuator type and type of mounting

Note:Special mounting material is required

(see "Accessories")Operation

with operator panel and display integrated in the enclosure cover 1Explosion protection

ATEX Ex II 2 G EEx d IIC T4, T5, T6 1FM/CSA Class 1, Div. 1, Group C-D (explosion-proof) 1) 2ATEX EEx ib and EEx d IIC T6 3FM/CSA intrinsically safe and explosion-proof 1) 4IECEx Ex ib IIG T6 5GOST Russia Ex d IIC T4/T5/T6 Dother explosion protection certificates upon request

Output / safe position (in case of an electrical power failure)Single acting, fail safe 1

fail freeze 2Double acting, fail safe 3

fail freeze 4Connections 2)

Cable: Thread M20 x 1.5 Air pipe: Thread G 1/4 1Cable: Thread M20 x 1.5 Air pipe: Thread 1/4-18 NPT 2Cable: Thread 1/2-14 NPT Air pipe: Thread 1/4-18 NPT 3

Option modules for analog or digital position feedbackwithout 0

Plug-in module analog position feedback, sign. range 4...20 mA,for two-wire 1

digital position feedback 3analog position feedback, sign. range 4...20 mA,

two-wire, and digital position feedback 4shutdown module 3) 5

Continued on next page1) only with cable connection NPT thread2) EEx d cable glands see accessories3) only for fail safe pneumatic Pos: 17.3 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 20: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

20

Pos: 17.4 /Überschriften/1.1/1-spaltig/A - F/Fortsetzung Bestellinformationen @ 6\mod_1169193551531_3101.doc @ 61633

8.1 Ordering information (continued) Pos: 17.5 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Bestellinformationen/Fortsetzung Bestellinformationen TZIDC-200 @ 10\mod_1176714848265_3101.doc @ 82655

Electro-Pneumatic Positioner Variant digit No. 1 - 7 12 13 14 15 16 17 18 CodeTZIDC-200 with Flameproof Enclosure Catalog No. V18348-intelligent, software-configurable with local communication interface (LKS) and HART communicationOptional mechanical kit for digital position feedback

without 0Mechanical kit for digital position feedback

with proximity switches SJ2-SN (NC or logical 1) 1with proximity switches SJ2-S1N (NO or logical 0) 4) 2with 24 V DC/AC microswitches (change-over contacts) 5) 3

Parameter setting / bus addressFactory setting for HART devices 1Customized parameter setting for HART devices 2

Design (varnish / coding)Standard 1As specified (on request) 2

Device identification label (provide list, if available)without 0label including text (plain text, max. 16 letters)

with separate sticker 1with separate stainless steel label 18.5 x 65 mm 2 os: 17.6 /==== Leeres Modul mit zwei Absatzmarken ==== @ 3\mod_1159257408468_0.doc @ 42813

Pos: 17.7 /Überschriften/1.1/1-spaltig/S - Z/Zusätzliche Bestellinformationen @ 8\mod_1175766342062_3101.doc @ 76273

8.2 Additional ordering information Pos: 17.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Bestellinformationen/Zusätzliche Bestellinformationen TZIDC-200 @ 10\mod_1176714852671_3101.doc @ 82676

CodeCertificates

SIL2 - Declaration of conformity 6) CS2

Certificate of compliance with the order acc. to EN 10204-2.1 (DIN 50049-2.1) CF1Certificate of compliance with the order acc. to EN 10204-2.1 (DIN 50049-2.1) with item description CF2Test Report acc. to EN 10204-2.2 (DIN 50049-2.2) CF3

Inspection certificate 3.1 acc. to EN 10204 with max. deviation CBA

4) only for ambient temperature range -25...+85 °C5) only for Ex d version6) only for single acting and fail safe pneumatic Pos: 17.9 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 21: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

21

Pos: 17.10 /Überschriften/1.1/1-spaltig/A - F/Bestellinformationen, Zubehör 1 @ 8\mod_1175763415390_3101.doc @ 76189 Bestellangaben

8.3 Order information, accessories 1 Pos: 17.11 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Bestellinformationen/Bestellinformationen TZIDC-200, Zubehör 1 @ 10\mod_1176714842796_3101.doc @ 82634

TZIDC-200 Catalog No.Mounting material and costAttachment kit for linear actuators(lateral attachment to DIN/IEC 534 / NAMUR) stroke 10 ... 35 mm 7959125

stroke 20 ... 100 mm 7959126Attachment kit for rotary actuators (mounting to VDI/VDE 3845)consisting of:

a) Adapter (shaft coupler) 7959110b) Mounting bracket dimension A/B = 80/20 mm 319603

dimension A/B = 80/30 mm 319604dimension A/B = 130/30 mm 319605dimension A/B = 130/50 mm 319606

Pressure gauge block including attachment materialfor single acting TZIDC-200 with 2 pressure gauges Ø 28 mm(1 x for air supply and 1 x for output pressure)G 1/4 connections Supply pressure range

0...10 bar/ 0...140 psiOutput pressure range 0...4 bar/ 0...60 psi 7959111

0...10 bar/ 0...140 psi 79591121/4-18 NPT connections Supply pressure range

0...10 bar/ 0...140 psiOutput pressure range 0...4 bar/ 0...60 psi 7959113

0...10 bar/ 0...140 psi 7959114for double acting TZIDC-200 with 3 pressure gauges Ø 28 mm(1 x for air supply and 2 x for output pressure)G 1/4 connections Supply pressure range

0...10 bar/ 0...140 psiOutput pressure range 0...4 bar/ 0...60 psi 7959115

0...10 bar/ 0...140 psi 79591161/4-18 NPT connections Supply pressure range

0...10 bar/ 0...140 psiOutput pressure range 0...4 bar/ 0...60 psi 7959117

0...10 bar/ 0...140 psi 7959118(Pressure gauge blocks are delivered as separate units for mounting by the customer)Filter regulator, brass incl. material for mounting

to pressure gauge blockconnections thread G 1/4 7959119

thread 1/4-18 NPT 7959120(Filter regulators are delivered as separate units for mounting by the customer)Adapter and operating program for digital communication

LKS adapter see Data Sheet 10/63-6.71 ENFSK modem see Data Sheet 10/63-6.71 ENDSV401 (SMART VISION) on CD-ROM see Data Sheet 10/63-1.20 EN

EEx d cable glands 7)1 x EEx d cable gland M20 x 1.5,

1 pipe plug M20 x 1.5, securing adhesive 79592442 x EEx d cable glands M20 x 1.5,

securing adhesive 79592451 x EEx d cable gland 1/2" NPT,

1 pipe plug 1/2" NPT, securing adhesive 79592462 x EEx d cable glands 1/2" NPT,

securing adhesive 7959247

7) for cable diameter 7.2...11.7 mm Pos: 17.12 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 22: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

22

Pos: 17.13 /Überschriften/1.1/1-spaltig/A - F/Bestellinformationen, Zubehör 2 @ 8\mod_1175763510500_3101.doc @ 76210 Bestellangaben

8.4 Order information, accessories 2 Pos: 17.14 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Bestellinformationen/Bestellinformationen, Zubehör 2 @ 10\mod_1175763138078_3101.doc @ 76126

TZIDC , TZIDC-110, TZIDC-120, TZIDC-200, TZIDC-210, TZIDC-220 Catalog No.Attachment kit for Manufacturer / TypeAir Torque SC 30 9) 319604Air Torque SC-P-60-4 9) 319604Air Torque SR 30 9) 319603ARI DP32, DP33, DP34 7959125AMG SAD 010 ... SAF 040 9) 319603AMG SAD 040 ... SAF 050 9) 319605ARCA 812 stroke 30 mm 7959107ARCA 812 stroke 60 mm 7959106ARCA 813 stroke 30 mm 7959109ARCA 813 stroke 60 mm 7959108Automax DA 85 ... DA150 9) 319603Badger Meter ATC 754/755 7959123bar GTE / GTD 045 ... 127 9) 319604bar GTE / GTD 143 ... 254 9) 319605Bray 92 / 93 series 9) 319603Conovalve Series 740.000 / 750.000 / 770.000 / 795.000 7959125El-O-Matic ED / ED / PE / PD 500 ... 4004 9) 319605El-O-Matic ED / ED / PE / PD 25 ... 350 9) 319603FESTO DRD-4-F05 ... DRD-50F10 9) 319603FESTO DRD-77-F10 ... DRD-255-F14 9) 319605Fisher 1051-30, 1052-30 7959214Fisher 1061 size 130 7959206Fisher 471 7959195Fisher 585 C 7959250Fisher 657 / 667 Size 10 ... 30 mm 7959177Flow Serve DA 85 ... 150 9) 319603Foxboro FoxPak IP127 / V725 7959168Foxboro V713 stroke 10 ... 35 mm 7959125Foxboro V713 stroke 25 ... 90 mm 7959126GEFA AC 020 ... AC 1750 9) 319604GEFA MC 063 FA 9) 319603GEMÜ 690/25 and 50 7959103GEMÜ CleanStar 7959125Gulde DK 7959161

9) need additional Adapter (Shaft Coupler), Catalog No. 7959110 Pos: 17.15 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830

Page 23: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure

23

Pos: 17.16 /Überschriften/1.1/1-spaltig/A - F/Bestellinformationen, Zubehör 3 @ 8\mod_1175763567703_3101.doc @ 76231 Bestellangaben

8.5 Order information, accessories 3 Pos: 17.17 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Bestellinformationen/Bestellinformationen, Zubehör 3 @ 10\mod_1175763193171_3101.doc @ 76147

TZIDC , TZIDC-110, TZIDC-120, TZIDC-200, TZIDC-210, TZIDC-220 Catalog No.Attachment kit for Manufacturer / TypeHoneywell 600-11, 600-15 7959126Hytork XL26 ... XL680 9) 319603Hytork XL1125, XL1370, XL2585, XL4580 9) 319605Keystone 79U/E-002(S) ... 79U/E-181(S) 7959147Mapag A/F 30 ... A/F 500 9) 319603Masoneilan CAMFLEX II, VARIMAX, MINITORK II 7959144Masoneilan VariPak 28000 series 7959163MaxFlo MaxFlo 7959140NAF 791290 7959207NAMUR stroke 10 ... 35 mm 7959125NAMUR stroke 25 ... 90 mm 7959126NAMUR stroke 100 ... 170 mm 7959339NELES B1JU8, B1J8U, B1CU9/20E, B1CU17/55, B1CU13-32, 9) 319603

B1C6U-20U, 1JAU10/20, BC6U-20UNELES BC6-20, B1C6-20, BJ8-20, B1J8-20 7959146Norbro 10AR40, 20BR40, 20AR40, 20RDA40, 15AR40, 15BR40 9) 319603Norbro 25AR40, 25BR40, 35AR40, 35BR40, 33-40, 30AR40 9) 319604Norbro 45BR40, 45AR40 9) 319606Prisma PP10, PP20 9) 319604Prisma PPW 9) 319603Remote Control RCD 05-DA/SR ... RCD 60-DA/SR 9) 319603Revo FD/FS 12, 25, 50 9) 319603Revo FD/FS 90, 130, 180, 205, 306 9) 319605Richter RA-1/2 046 ... RA-1/2 127 9) 319604Richter RA-1/2 185 ... RA-1/2 300 9) 319605Samson 241, 271, 3271 7959145Samson 3277 7959136Schubert&Salzer GS 8020 / 8021 / 8023 7959200SED SED stroke 100 mm 7959141VDI / VDE 3845 80 / 20 mm 9) 319603VDI / VDE 3845 80 / 30 mm 9) 319604VDI / VDE 3845 130 / 30 mm 9) 319605VDI / VDE 3845 130 / 50 mm 9) 319606

9) need additional Adapter (Shaft Coupler), Catalog No. 7959110 Pos: 18 /Rückseiten/Minden_Aktorik @ 2\mod_1151575081640_3101.doc @ 32243 ===== Ende der Stückliste =====

Page 24: Data Sheet Electro-Pneumatic Positioner TZIDC-200 18348.pdf · Electro-Pneumatic Positioner TZIDC-200 10/18-0.32-EN for 4 … 20 mA two-wire technology, flameproof enclosure 2 Contents

ABB has Sales & Customer Support expertise in over 100 countries worldwide. www.abb.com/instrumentation

The Company’s policy is one of continuous productimprovement and the right is reserved to modify the

information contained herein without notice.

Printed in the Fed. Rep. of Germany (10.2007)

© ABB 2007

3KXE341004R1001

10/1

8-0.

32-E

N

Rev

. E

ABB Limited Salterbeck Trading Estate Workington, Cumbria CA14 5DS UK Tel: +44 (0)1946 830 611 Fax: +44 (0)1946 832 661

ABB Inc. 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183

ABB Automation Products GmbH Schillerstr. 72 32425 Minden Germany Tel: +49 551 905-534 Fax: +49 551 905-555 [email protected]