data sheet 3va1150-4gd46-0aa0

6
Data sheet 3VA1150-4GD46-0AA0 CIRCUIT BREAKER 3VA1 IEC FRAME 160 BREAKING CAPACITY CLASS S ICU=36KA @ 415 V 4-POLE, LINE PROTECTION TM210, FTFM, IN=50A OVERLOAD PROTECTION IR=50A FIXED SHORT CIRCUIT PROTECTION II=10 X IN NEUTRAL PROTECTION 100% CABLE CONNECTION Model product brand name SENTRON Product designation Molded case circuit breaker Design of the product Line protection Product variations General Applications Ground fault monitoring version Without Design of the auxiliary release Without auxiliary release Design of the auxiliary switch Without Design of the operating mechanism toggle handle Type of the driving mechanism / motor drive No Design of the overcurrent release TM210 General technical data Number of poles 4 Trip class / of the L-trip / with I2t characteristic / initial value 1 Trip class / of the L-trip / with I2t characteristic / Full- scale value 1 Electrical endurance (switching cycles) ● at AC-1 / at 380/415 V / at 50/60 Hz 8 000 circuit-breaker / Design 3VA Mechanical service life (switching cycles) / typical 15 000 Voltage Insulation voltage / Rated value V 800 Protection class 3VA1150-4GD46-0AA0 Changes preserved Page 1/ 6 20.03.2015 © Copyright Siemens AG

Upload: others

Post on 19-Nov-2021

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Data sheet 3VA1150-4GD46-0AA0

Data sheet 3VA1150-4GD46-0AA0CIRCUIT BREAKER 3VA1 IEC FRAME 160 BREAKINGCAPACITY CLASS S ICU=36KA @ 415 V 4-POLE,LINE PROTECTION TM210, FTFM, IN=50AOVERLOAD PROTECTION IR=50A FIXED SHORTCIRCUIT PROTECTION II=10 X IN NEUTRALPROTECTION 100% CABLE CONNECTION

Modelproduct brand name SENTRONProduct designation Molded case circuit breakerDesign of the product Line protectionProduct variations General ApplicationsGround fault monitoring version WithoutDesign of the auxiliary release Without auxiliary releaseDesign of the auxiliary switch WithoutDesign of the operating mechanism toggle handleType of the driving mechanism / motor drive NoDesign of the overcurrent release TM210

General technical dataNumber of poles 4Trip class / of the L-trip / with I2t characteristic / initialvalue

1

Trip class / of the L-trip / with I2t characteristic / Full-scale value

1

Electrical endurance (switching cycles)

● at AC-1 / at 380/415 V / at 50/60 Hz 8 000

circuit-breaker / Design 3VAMechanical service life (switching cycles) / typical 15 000

VoltageInsulation voltage / Rated value V 800

Protection class

3VA1150-4GD46-0AA0 Changes preservedPage 1/6 20.03.2015 © Copyright Siemens AG

Page 2: Data sheet 3VA1150-4GD46-0AA0

Protection class IP IP40Protection class IP / on the front IP40Protective function of the overcurrent release LI

Switching capacitySwitching capacity class of the circuit breaker S

DissipationActive power loss

● maximum W 14.6

ElectricityContinuous current / Rated value / maximum A 160Continuous current / Rated value A 50Adjustable response value current

● of the current-dependent overload release /Full-scale value

A 1

● of the instantaneous short-circuit release / initialvalue

A 10

Main circuitOperating voltage

● with AC / at 50/60 Hz / Rated value V 690

● for DC / Rated value V 600

Operating current

● at 40 °C / Rated value A 50

● at 50 °C / Rated value A 50

● at 55 °C / Rated value A 49

● at 60 °C / Rated value A 48

● at 65 °C / Rated value A 46

● at 70 °C / Rated value A 45

Auxiliary circuitNumber of CO contacts / for auxiliary contacts 0

SuitabilitySuitability for use system protection

Adjustable parametersAdjustable response value current

● of I-trip / Full-scale value A 10

● for N-conductor protection / initial value A 100

● for N-conductor protection / Full-scale value A 100

Adjustable response value current / of the current-dependent overload release / initial value

A 1

Product detailsProduct component

3VA1150-4GD46-0AA0 Changes preservedPage 2/6 20.03.2015 © Copyright Siemens AG

Page 3: Data sheet 3VA1150-4GD46-0AA0

● Trip indicator No

● display No

● Voltage trigger No

● undervoltage release No

● undervoltage release with leading contact No

Product property

● for neutral conductors /upgradeable/retrofittable / Short-circuit andoverload proof

No

Product expansion / optional / motor drive Yes

Product functionProduct function

● Intrinsic device protection Yes

● communication function No

● Phase failure detection No

● other measurement function No

AccessoriesManufacturer article number / of the supplied basicswitch

3VA1150-4GD46-0AA0

Short circuitOperational short-circuit current breaking capacity(Ics)

● at 240 V / Rated value kA 55

● at 415 V / Rated value kA 36

● at 440 V / Rated value kA 25

● at 500 V / Rated value kA 15

● at 690 V / Rated value kA 5

Maximum short-circuit current breaking capacity (Icu)

● at 240 V / Rated value kA 55

● at 415 V / Rated value kA 36

● at 440 V / Rated value kA 25

● at 500 V / Rated value kA 16

● at 690 V / Rated value kA 7

Short-circuit current making capacity (Icm)

● at 240 V / Rated value kA 121

● at 415 V / Rated value kA 75.6

● at 690 V / Rated value kA 7.5

ConnectionsArrangement of electrical connectors / for maincurrent circuit

Front terminal

Type of connectable conductor cross-section

3VA1150-4GD46-0AA0 Changes preservedPage 3/6 20.03.2015 © Copyright Siemens AG

Page 4: Data sheet 3VA1150-4GD46-0AA0

● of the round conductor terminal / stranded 1 x (1.5 - 70 mm²)

Type of electrical connection / for main current circuit Box terminal

Mechanical DesignHeight mm 130Width mm 101.6Depth mm 70Mounting type fixed mounting

Environmental conditionsAmbient temperature

● during operation / minimum °C -25

● during operation / maximum °C 70

● during storage / minimum °C -40

● during storage / maximum °C 80

CertificatesEquipment marking

● acc. to DIN EN 61346-2 Q

● acc. to DIN EN 81346-2 Q

GeneralProductApproval

EMC Declaration ofConformity

Shipping Approval other

other other

Further informationInformation- and Downloadcenter (Catalogs, Brochures,…)http://www.siemens.com/lowvoltage/catalogs

Industry Mall (Online ordering system)https://eb.automation.siemens.com/mall/en/WW/Catalog/Product/3VA11504GD460AA0

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)http://support.automation.siemens.com/WW/view/en/3VA11504GD460AA0/all

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA11504GD460AA0

CAx-Online-Generatorhttp://www.siemens.com/cax

Tender specificationshttp://ausschreibungstexte.siemens.com/tiplv

3VA1150-4GD46-0AA0 Changes preservedPage 4/6 20.03.2015 © Copyright Siemens AG

Page 5: Data sheet 3VA1150-4GD46-0AA0

38.1

101.6

130

107.

8

25.4

25.425.4

11.1

11.1

13

20

20

70

75.8

88

45

70

17.5

9517

.5

17.7

17.7

12.7

25.4

50.8

57.2

5

114.

57.

75

4.2

12.7

25.4

18.8

18.8 18.8

18.8

-Q 1

2

I> I> I> I>

3 5

4 6

N

N.

3VA1150-4GD46-0AA0 Changes preservedPage 5/6 20.03.2015 © Copyright Siemens AG

Page 6: Data sheet 3VA1150-4GD46-0AA0

last modified: 11.03.2015

3VA1150-4GD46-0AA0 Changes preservedPage 6/6 20.03.2015 © Copyright Siemens AG