data sheet 11b.16 - 18 diamix l - compamix...
TRANSCRIPT
COMPARATO NELLO SRL
1UNI EN ISO 9001: CERTIFIED COMPANY 2015
Not only have the Diamix L and Compamix L mixing/thermoregulating valves a fixed point regulation function, butthey also feature a specific software which allows the servocontrol to independently carry out all the thermal disinfection processesin plants with recirculation rings, thus significantly reducing the danger of outbreak and proliferation of legionella bacteria.There are so many variables connected to the construction of plants where our equipment can be implemented, that it isimpossible to totally rule out the risk.This version is completed by two semi-conductor temperature feelers: one on the mixed way - for normal regulation - and one on thefinal section of the recirculation ring - for sampling during the thermal disinfection process. The disinfection function can be startedmanually or be programmed weekly/daily: the default value is during the night between Sunday and Monday at 2:00 AM, because,statistically, this is the time users draw less water. This function can be turned off, if desired. The duration of the disinfection depends on the characteristics of the installation, becausethe Legionella bacterium reacts differently according to the maximum temperature reached in the final section of the ring. The higherthe temperature, the shorter the disinfection process: • more than 70°C - the disinfection takes 30 minutes • 65°C to 70°C - the disinfection takes 60 minutes • 60°C to 65°C - the disinfection takes 120 minutes • 57,5°C to 60°C - the disinfection takes 180 minutes • 65°C to 57.5°C - the disinfection takes 240 minutesThe valve features a relay which supplies the recirculation pump during the disinfection and outlet signals which trigger in case offailure, for instance if the disinfection process cannot be completed because the reached water temperature isn’t high enough. Thevalve carries out a test to check that the procedure has been properly carried out according to the set criteria. At the end of the di-sinfection process the valve resumes its mixing function. In order to avoid scalds, if water is drawn during the thermal disinfectionprocess, it is advisable to install an anti-scald safety device for each user.
OPERATION
Diamix L available for 1/2” • 3/4" • 1" diameters.Compamix L available for 1"1/4 • 1"1/2 • 2" diameters.
VERSIONS
Diamix L - Compamix LData Sheet 11B.16 - 18
USEThermoregulating/mixing motorized valves such asDiamix L and Compamix Lcan be used for:sanitary hot water mixing inplants with recirculation, whereit is necessary to carry out aprogrammed thermal disinfec-tion according to the nationalguidelines for Legionellosisprevention and control.
THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION
COMPARATO NELLO SRL
2UNI EN ISO 9001: CERTIFIED COMPANY 2015
Power supply (110 V and 60 Hz on request)Maximum power consumption
45 sec.8,9 VA (230V) • 9,4 VA (24V) 10 VA (230V) • 10,6 VA (24V)
Operating times (90° rotation) *Degree of protection IP 67
35 sec.
230V • 24V 50 Hz
-10°C to +50°C-15°C to +85°C
Operational room temperature for lowertemperatures, please contact out technical officeAdjustment rangeTemperature probe
TECHNICAL FEATURES Compamix LDiamix L
Diamix L - Compamix LData Sheet 11B.16 - 18
* more operating times available upon request
Valve bodies
3-WAY VERTICAL MIXED OUTLET,COMPARATO CONNECTION
FULL FLOWØ 3/4" • 1"
3-WAY VERTICAL MIXED OUTLETISO 5211 CONNECTION
FULL FLOWØ 1/2" • 3/4" • 1"• 1"1/4 • 1"1/2 • 2"
MATERIALI IMPIEGATI
THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION
YESAutomatic calculation of disinfection timeoptionalImmersion probe
daily / weeklyDisinfection cycle programming
contact-type NTC 10kΩPIDElectronic adjuster
1 BODY BRASS CW617N UNI 5705CHROMED NICKEL
2 COUPLING BRASS CW617N UNI 5705 3 BALL BRASS CW617N UNI EN
5705 CHROMED NIKEL 4 BALL SEAL P.T.F.E. 5 ANTI-FRICTION
SEAL P.T.F.E. 6 O-RING EPDM
1 BODY CW617N UNI EN 12165 2 COUPLING CW617N UNI EN 12165 3 BALL CW617N UNI EN 12165 4 BALL SEAL P.T.F.E. 5 ANTI-FRICTION
SEAL P.T.F.E. 6 ROD SEAL P.T.F.E. 7 BUSHING
PACKING CW614N UNI EN 12164 8 O-RING FKN
COMPARATO NELLO SRL
3UNI EN ISO 9001: CERTIFIED COMPANY 2015
Diamix L - Compamix LData Sheet 11B.16 - 18
DIAMIX L - COMPAMIX L MOUNTING
AB
C
D
EF
min.
150
mm
1
234
Allowed positions
NOTES:The pipe section where the temperature probe will be installed has to be made of metal. The following part of the pipe can be of any type, provided it is suitable for its intended use.Once the valve body has been installed, the servocontrol can be rotated 180°. Mounting the servocontrol facing downwards is not allowed.
1 MIXING PROBE 2 ANTI-LEGIONELLA PROBE 3 CHECK VALVE 4 RECIRCULATION PUMP
A: hot sanitary water inlet from boilerB: cold sanitary water inlet/recirculation returnC: mixed water outlet to usersD: recirculation/cold water inlet to boilerE: recirculation returnF: cold sanitary water inlet
Diamix L • COMPARATO connection
OVERALL SIZE [mm]
Diamix L • ISO 5211 connection Compamix L
VERTICAL mixed COMPARATO connection
20 3/4" 1" 38 105 145 84 74 25 1" 1"1/4 42 117 164 94 82
MODEL øTANGSDN ø
VALVE BODIES A B C D EVALVE BODIES
D - E: dimensions refer to the valve body without tangs and caps.
VERTICAL mixed ISO 5211 connection
BR
AS
SVA
LVE
BODI
ES
15 1/2" 31 65 64 Diamix L 20 3/4" 42 82 74 Diamix L 25 1" 45 92 89 Diamix L 32 1"1/4 50 103 100 Compamix L 40 1"1/2 61 123 110 Compamix L 50 2" 67 140 130 Compamix L
MODEL DN Ø A B C
THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION
Diamix L
SERVOCONTROL
COMPARATO NELLO SRL
4UNI EN ISO 9001: CERTIFIED COMPANY 2015
Diamix L - Compamix LData Sheet 11B.16 - 18
SPACER FOR INSULATIONE
SPACER FOR INSULATION AND MANUAL OPENING
h 90 mm h 90 mm h 90 mm
h 90 mm h 90 mm h 60 mm
THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION
ACCESSORIESOPTIONAL SPACERS FOR INSULATION AND/OR MANUAL OPENING
DIAMIX L COMPARATO CONNECTION
COMPAMIX L
OPTIONAL INLETS/OUTLETS CABLESINLET DESCRIPTIONFUNCTION
1Manual
activationdisinfection cycle
2 Forcing towards hot
If you close the inlet for at least 2 seconds, the disinfectioncycle activates
If you close the inlet for at least 2 seconds, the disinfectioncycle activates towards the hot way (during this phase thetemperature control is disabled); the display showsthe“Man” message.
3 Forcing towards cold
If you close the inlet, the geared motor activates: the valveis turned clockwise (during this phase the temperaturecontrol is disabled); the display shows the “Man” message.
OUTLET DESCRIPTIONFUNCTION
1 Disinfection cycle
2 Disinfection alarm
The outlet is activated during the disinfection cycle. The outlet is activated if there is a power shortage (“Ald”) during the disinfection cycle.
3 Temperaturealarm
The outlet is activated if the set point temperature is not reached within P2 time (“AL t”)
BRASS IMMERSION PROBE WITH CONNECTOR
Ø 5,5
1711,5G 1/8” NOTE:well not included
8 x 0,25 mm2
DIAMIX L ISO 5211CONNECTION
COMPARATO NELLO SRL
5UNI EN ISO 9001: CERTIFIED COMPANY 2015
Diamix L - Compamix LData Sheet 11B.16 - 18
APPLICATION EXAMPLES
Hot water production system with return connection for recirculation pipelines
Hot water production system without return connectionfor recirculation pipelines
12
3 3
12
1 SANITARY SURGE CHAMBER 2 BUFFER TANK 3 TEMPERATURE CONTROL PROBE
RECIRCULATION ONLY FOR DIAMIX L ANDCOMPAMIX L PRO
Tank capacityØ1/2" 10÷20 litres 3/4" 10÷20 litres 1" 20÷30 litres 1"1/4 25÷40 litres 1"1/2 30÷50 litres 2" 40÷60 litres
Warning: for a proper operation, you need to choose the right valve body diameter accordingto the flow. You can download our DimMix software at www.comparato.com,: it will help youmake the right choice.When replacing thermostatic mixers in existing systems, you need to check the presence ofsanitary recirculation, as per the diagram, and choose the valve body diameter according tothe Kvs values (see the table of fluid-dynamic features).BUFFER TANKIf necessary, it is possible to mount a buffer tank (2) on the outlet pipeline. This will avoidany fluctuation of the reference temperature value when the drawing flow is very low. Its useis recommended when the water volume inside the recirculation plant is limited.Here you can find the capacity values of the buffer tank recommended based on the diame-ters of the mixing valves.
THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION
PROBE
EARTH
BLUE
BROWN
PHASE
NEUTRAL
1
2
1 MIXING PROBE 2 ANTI-LEGIONELLA PROBE
ELECTRICAL CONNECTIONS
Should power fail, the actuator remains in the position it waswhen the power outage occurred.When the power is restored, the servocontrol resumes its normaloperation keeping the programmed settings.
1 : 2-pole terminal block for connection(free contact)
1
Anti-legionella cycle control of sanitary recirculation pump:the contact closes when the anti-legionella bacterium disinfectioncycle is active. This allows to force the activation of the recircu-lation pump, which must be ON while the cycle is carried out.Caution: Diamix L and Compamix L can work with the sanitarywater recirculation pump active 24h a day. It is possible to ma-nage the recirculation pump according to a time schedule, usingthe relevant timer (not included).
RECIRCULATIONPUMP
CARATTERISTICHE FLUIDODINAMICHEKvS (m3/h with ∆p = 100kPa = 1bar)
In order for the mixing process to run properly, make sure that the pressure values at the two inlets of the mixing valve areas constant and similar as possible.
KvSm3/hModel DNVERTICALmixedCOMPARATOconnection
VERTICALmixedISO 5211connection
Diamix L - Compamix LData Sheet 11B.16 - 18
Model Spacer WITH manualcontrol / opening
- 10° C ÷ +100° C
Spacer WITHOUT manualcontrol / opening
VERTICAL mixedCOMPARATO connection - 20° C ÷ +120° C
- 10° C ÷ +100° CVERTICAL mixedISO 5211 connection - 20° C ÷ +120° C
FLUID TYPE AND TEMPERATURESWater
20 11,5
25 18,315 620 11,525 18,332 27,240 47,350 73
Δp max[bar]Model PNDN
15 25 25 20 16 16 25 16 16 32 10 10 40 10 6 50 10 4
20 16 16 25 16 16
VERTICALmixedCOMPARATOconnection
PRESSURES
VERTICALmixedISO 5211connection
THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION
• Operating torque: Torque which can be occasionally provided by the actuator, with no risk of breaks nor permanent deformation of the actuator components.
• : Flow coefficient when the valve is completely open (2-way valve) or when the flow is completely deviated on a perpendicular (3-way valve).
• PN: Nominal operating pressure.
• ∆p max: Maximum differential operating pressure.
In o
rder
to p
rovid
e an
up-
to-d
ate
serv
ice, C
ompa
rato
Nell
o S.
r.l. re
serv
es th
e rig
ht to
mod
ify te
chnic
al da
ta, d
rawi
ngs,
grap
hs a
nd p
hoto
s of
this
instru
ction
man
ual a
t any
time,
with
out p
rior n
otice
. and
pho
togr
aphs
of th
is ca
talog
ue a
t any
time
and
with
out p
rior n
otice
.
6
HYDROTHERMAL SYSTEMS
COMPARATO NELLO SRL17014 CAIRO MONTENOTTE (SV) ITALIA VIALE DELLA LIBERTÀ • LOCALITÀ FERRANIA • Tel. +39 019 510.371 - FAX +39 019 517.102
www.comparato.com e-mail:[email protected] UNI EN ISO 9001: CERTIFIED COMPANY 2015
UPDATED DATA SHEETS AVAILABLE AT www.comparato.com