Data Center Energy Efficiency Opportunities What Managers Should Know
February 2015
Mike Walker President, AlterAction Inc.
(An ENERGY STAR Technical Support Contractor)
![Page 2: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/2.jpg)
Who are we?
• Work on behalf of EPA’s ENERGY STAR program as “technical support contractors”
• 3 core areas of expertise: – Large scale “human behavior change” – IT management & consulting – Energy efficiency, sustainability
• Vendor/product/solution neutral • Our services are free -- we get paid by EPA
![Page 3: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/3.jpg)
State Electronics Challenge
• Promotes lifecycle stewardship of computers & imaging equipment — Buying green — Operating efficiently
• Power management • Extending product life • Reducing paper usage
— Managing responsibly • Maximizing reuse & using certified recyclers
![Page 4: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/4.jpg)
SEC Best Practices Use
• Establish & promote policy/directive for power management & paper use reduction
• Ensure ENERGY STAR “sleep” function enabled on all computers & monitors – Power down features imaging equipment
• Extend life of equipment
• Ensure double-sided printing features used on 75% of printers, copiers, & multifunction devices
![Page 5: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/5.jpg)
We are here today because data centers...
1. Consume a lot of energy – Energy consumption grew:
• 200% from 2000-5 • 36% from 2006-10
– 2% of electricity in US 2. Can be made far more
efficient – Efficient data centers can
use up to 80% less power
5
![Page 6: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/6.jpg)
Server rooms/closets in commercial buildings
6
Typical office building:
23% of annual energy costs
High efficiency office building:
40-50% of annual energy costs
Major opportunity!
![Page 7: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/7.jpg)
Savings remain untapped…
Split incentives Risk aversion Some solutions require new
expertise
7
But YOU can overcome this, with a little help
![Page 8: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/8.jpg)
Presentation Goals
1. Identify drivers of energy costs 2. Provide non-technical overview of measures 3. Empower managers to spot opportunities 4. Next steps & helpful (free!) resources
8
![Page 9: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/9.jpg)
Server rack vs. barbecue grill
9
• Industrial Light & Magic deployed 84 blade servers/rack. Just 1 rack… – Uses 28 kW – Requires 8 tons of cooling per rack – Heat equivalent to 4 Weber Spirit gas grills
vs.
280 burgers/hour!
![Page 10: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/10.jpg)
Where does all the energy go?
10
Source: “Best Practices Guide for Energy-Efficient Data Center Design”, DOE, revised March 2011, prepared by Rumsey Engineering
PUE = 2.6 PUE = 1.6
![Page 11: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/11.jpg)
Data center energy savings: 3 areas of opportunity
1. IT equipment 2. Airflow management 3. HVAC adjustments
11
![Page 12: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/12.jpg)
The “cascade” effect
12 Source: The Green Grid, Emerson
1 W saved at the processor saves ~ 2.84 W total
![Page 13: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/13.jpg)
Eliminating unused servers & systems
• Opportunity: – 8-10% of servers performing no
useful function
• Why? – Good at provisioning, not so much
at decommissioning
• Solution? – Take inventory – Identify, remove comatose servers
• Eliminating one server can save $2500/year in energy, software licensing, & maintenance costs
13
“Bring out your dead!”
![Page 14: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/14.jpg)
Consolidating lightly utilized servers
• Due to traditional one workload, one box approach – More than 90% of all x86 servers run at <12% utilization – Typical server runs at < 6% utilization
• Four smarter approaches: – Combine apps onto a single server/operating system instance – Reduce redundancy by clustering servers – Downsize application portfolio – Virtualize servers
14
![Page 15: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/15.jpg)
What is a “virtual machine?”
• Software that simulates server hardware & OS
• Allows for multiple concurrent OS instances on a single “box”
• Improves scalability, reduces downtime, and enables faster deployments
15
![Page 16: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/16.jpg)
Virtualization, cont.
• Cuts energy consumption by 10-40%
• Ubiquitous: – 92% of large data
centers – 37% of small data
centers
• BUT…not all systems are good candidates
16
![Page 17: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/17.jpg)
Virtualization reduces total cost of ownership
• SWIC had 35 physical servers
• Virtualization effort led to 35 virtual machines on 4 virtual hosts (physical servers)
17
![Page 18: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/18.jpg)
Right-size new servers
• Are you fully utilizing what’s already deployed? • Avoid “oversizing”
– Don’t buy a tour bus when the workload calls for golf cart
• Avoid the one-spec procurement trap
18
![Page 19: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/19.jpg)
Data storage – more efficient technology
• Lower speed disk drives, smaller drive platters
• Massive array of idle disks (MAID) – Only those disk drives in active use are
spinning at any given time • Solid state storage (SSDs)
– No mechanical parts – Startup (OS) disks are good candidates
• Tape
19
MAID
Right-size new storage hardware!
![Page 20: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/20.jpg)
Data Storage Resource Management (SRM) tools
• Deduplication removes duplicate files • Automated provisioning improves storage utilization • Thin provisioning provides just-enough, just-in-time storage • Tiered Storage matches storage technology to access
requirements
20
![Page 21: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/21.jpg)
What is a Uninterruptable Power Supply (UPS) system?
• Provides power until emergency generators come on line
• Corrects for power surges, voltage drops, and frequency distortions
21
![Page 22: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/22.jpg)
Exelon: UPS Change Improves Efficiency & Redundancy
• Increasing “load factor” boosts efficiency
• Example: Exelon – Before: two 1000 kVA
UPSs in parallel run at low load
– After: four smaller (750 kVA) UPSs run at higher load
– Protection from component AND system failure (increased redundancy)
![Page 23: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/23.jpg)
ENERGY STAR certified data center products
23
Large network equipment
Storage
Uninterruptible Power Supplies (UPS)
Servers
![Page 24: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/24.jpg)
New ES servers can consume 54% less power
24
![Page 25: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/25.jpg)
ENERGY STAR qualified servers
• Eligible servers: – Blade, multi-node, rack-mounted, and pedestal – ≤ 4 processor sockets per server (or blade/node)
• Requires: – Efficient power supplies – Low power draws when server is at “idle” – Advanced power management features – Server Efficiency Rating Tool (SERT) test results – Capabilities to measure real time power use,
processor utilization, and air temperature
25
![Page 26: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/26.jpg)
ES servers made by leading manufacturers
26
![Page 27: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/27.jpg)
ENERGY STAR certified data storage requirements
• Efficient power supplies and variable speed fans
• Making available thin provisioning, data de-duplication, lossless compression, and delta snapshots
• Reporting on energy consumption under different operating conditions
27
![Page 28: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/28.jpg)
Save energy with ENERGY STAR qualified UPSs
• ES qualified UPSs cut energy losses by 33 - 55%
• Different UPS types available: – Modular UPSs (pictured)
maximize the “load factor” – Traditional “double
conversion” UPSs – Multi-mode UPSs
28
![Page 29: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/29.jpg)
Data center energy savings: 3 areas of opportunity
1. IT equipment 2. Airflow management 3. HVAC adjustments
29
![Page 30: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/30.jpg)
Raised floor environment helps separate cold & hot air
30
(Photos courtesy of Tate and NIH)
![Page 31: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/31.jpg)
Proper hot aisle/cold aisle orientation can save 5-12%
(Photo courtesy of 42U.com)
31
![Page 32: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/32.jpg)
Cold aisle containment further reduces mixing
(Photos courtesy of 42U.com) 32
• Some hot air is still mixing with cold air
• Containment can save: – ~20% to 25%
in fan energy – ~20% at the
chiller
![Page 33: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/33.jpg)
Airflow management strategies
Sources: LBNL, Keyzone Computer Products, Ltd.
Properly located and sized vented tiles & diffusers
Grommets minimize air leaks in raised floor systems
Variable Speed fan Drives (VSDs)
in CRACs
Adequately sized return plenum or ceiling height
Adequately sized supply
Appropriate pressure in underfloor supply plenums; no obstructions
Rigid enclosures (“containment”) eliminate mixing
Hot aisle / cold aisle layout
33
![Page 34: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/34.jpg)
Airflow management devices: blanking panels
• Maintain the separation of hot and cold air in a rack
• A single 12” blanking panel can yield 1-2% energy savings per server rack
34 (Photos courtesy of PlenaForm Systems, EDP Europe, and 42U.com.)
![Page 35: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/35.jpg)
Airflow management devices: floor grommets
• Improve cooling efficiency by sealing areas where cables enter & exit plenums (e.g., a raised floor)
• Less leakage helps direct more cold air to the equipment that needs cooling
35
(Photos courtesy of PlenaForm Systems, EDP Europe, and 42U.com.)
![Page 36: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/36.jpg)
Airflow management devices: structured cabling
36
Vs.
![Page 37: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/37.jpg)
QTS conducted an extensive air flow assessment
• Removed obstructions to vented tiles, (e.g., cabling)
• Closed vented tiles that were not in use • Installed self–sealing grommets • Used vinyl covers to seal gaps in doors, pipes
and windows
37
Saved $60,000 over a 2-month period
![Page 38: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/38.jpg)
Variable Speed Drives (VSDs)
• CRAC fans use 5-10% total data center energy
• Fan/pump power varies with the cube of speed
• Translation: 1/2 the speed uses 1/8 the power
• Other EE measures need VSDs to reach full potential
38
Source: UR Energy
![Page 39: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/39.jpg)
VSD considerations
• Reduced fan speed in retrofits can cause condensation and freezing on the coils – New CRACs with VSDs have digital compressors that slow
down with fan speed
39
• VSDs can affect power quality w/ harmonics – eBay needed 16
225-KVA harmonic mitigating transformers
(Photo courtesy National Instruments )
![Page 40: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/40.jpg)
eBay installed VSDs on 83 CRAH units
40
![Page 41: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/41.jpg)
Data center energy savings: 3 areas of opportunity
1. IT equipment 2. Airflow management 3. HVAC adjustments
41
![Page 42: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/42.jpg)
Turn up the heat!
• Server inlet temps as low as 55°F??? That’s old school!
• In 2008, ASHRAE recommended 64 to 81°F
• Save 3% to 5% in energy costs for every 1°F increase in server inlet temp
42
(Drawing courtesy of Raritan )
![Page 43: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/43.jpg)
Today’s servers can stand the heat. Safe operating ranges:
• Sun Blade (40° to 90°F)
• Dell Blade (50° to 95°F)
• IBM Blade (50° to 95°F)
• NetAppStorage (50° to 104°F)
43
![Page 44: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/44.jpg)
Raising server inlet temps: considerations
• Can produce hot spots if not monitored properly
• Internal server fans may automatically turn on, raising energy costs
• Data centers with VSDs benefit the most
• Uncomfortable working conditions?
44
(Photo courtesy Infrared Imaging Services, LLC)
Hot spot (viewed from front of server rack)
![Page 45: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/45.jpg)
Humidity control in the past
• Tight relative humidity (RH) tolerances leads to: – CRAC #1 reads RH as too high:
• Over-cools air to remove moisture and then reheats to bring temp back up
– Results in CRAC #2 reading RH as too low:
• Adds moisture by generating steam and cools air to bring temp back down
• Termed “CRAC fighting”
45
![Page 46: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/46.jpg)
Solving humidity issues
• Use dew point (DP) instead of RH to measure humidity
• Maintain broader ASHRAE recommended humidity range (42 to 59 degrees °F DP)
• Use adiabatic humidification technologies – Misters, foggers, ultrasonic – Required in new CA DCs
46
![Page 47: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/47.jpg)
eBay: ½ year payback with ultrasonic humidification
47
Consideration: ultrasonic humidifiers require de-ionized water
![Page 48: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/48.jpg)
Free cooling with a water-side economizer • Evaporative cooling
of tower produces chilled water
• Heat exchanger used to bypass mechanical chiller
• Downside: high capital costs
• Added security
48
![Page 49: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/49.jpg)
Free cooling with an air-side economizer
Exhaust Air 85°F
Outside Air 65°F
In milder climates, outside air can be used for most of the year (SFO: all but ~10 days annually!)
49
![Page 50: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/50.jpg)
Hours of air-side economizer use per year
50
![Page 51: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/51.jpg)
Info available on energystar.gov/lowcarbonit
• Non-technical descriptions
• Impartial information about – Costs – Savings – Implementation
considerations
Top 12 Data Center Opportunities
1. Virtualization of Servers 2. Decommissioning of Unused
Servers 3. Consolidation of Lightly Utilized
Servers 4. Data Storage Opportunities 5. Efficient Equipment Purchase 6. Hot Aisle/Cold Aisle Arrangement 7. Containment/Enclosures 8. Variable Speed Drives 9. Housekeeping: Blanking Panels,
Cabling and Gaps 10. Server Inlet Temperature and
Humidity Adjustments 11. Air Side Economizer 12. Water Side Economizer
51
![Page 52: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/52.jpg)
Utilities often help pay for energy saving measures
Note: "C" indicates a customized measure, and "P" indicates a prescriptive measure. Some programs also incentivize the removal of existing servers through a customized approach. (Data current as of April 2012). Source: Utility websites and personal communications with utility energy efficiency program managers and industry groups, April 2012.
Utility Programs
Virtu
aliza
tion
ENER
GY ST
AR
Serve
rMa
ssive
Arra
y of
Idle D
isks
Unint
errup
tible
Powe
r Sup
plyCh
illers/
Coo
ling
Towe
rsTh
ermal
Energ
y St
orag
eSt
orag
e Co
nsoli
datio
nAi
rflow
Varia
ble
Freq
uenc
y Driv
eAi
r-Side
Ec
onom
izer
Water
-Side
Ec
onom
izer
Pump
s/Mot
ors
HVAC
/ CRA
C
DC Po
wer
Arizona Public Service Company (APS) C C C C/P C P P C P PAustin Energy C C C C C P P C/P
AVISTA Utilities C P P C/PBritish Colombia Hydro (BC Hydro) C C C C C C C C C C C CCommonwealth Edison C C C C C C C C P CDuke Energy (NC, SC, OH) C C C/P C C C C/P C C P P CEfficiency Vermont C C C P C C P PEnergy Trust of Oregon P C C C C C C/PFocus on Energy (WI) C/P C C P C C C P C C P CIdaho Power P P PNevada Power P PNew York State Energy Research and Development Authority (NYSERDA) C C C C C C/P C C C/P C/P CPacific Gas & Electric Company (PG&E) C C C C C C P C C P P CPuget Sound Energy (PSE) C C C C CSacrament Municipal Utility District (SMUD) C C/P C C/P C C P C/PSalt River Project P P PSan Diego Gas & Electric (SDG&E) C P P PSeattle City Light P C/P C C C C C P C C C C CSilicon Valley Power C C C P C C P PSnohomish County Public Utility District C C C CSouthern California Edison (SCE) C C C C C C C C C C C
52
![Page 53: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/53.jpg)
ENERGY STAR rating for data centers
• Rewards data centers in the top 25 % of their peers in energy efficiency
• Uses Power Usage Effectiveness (PUE) • Allows you to compare your data center to others across
the U.S. • Limited to stand-alone data centers or buildings that
house large data centers
53
NetApp Data Center in Research Triangle Park, NC
![Page 54: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/54.jpg)
Suggested next steps
1. Schedule a walk-thru to look for potential savings opportunities
2. Counter technical concerns/questions with… – “You might be right: why don’t we ask an expert?” – Schedule a (free) conference call with a vendor-neutral
ENERGY STAR technical advisor
3. Estimate project ROI – Emphasize increased reliability and redundancy as direct
benefits – Don’t forget $ from utility incentive programs
4. Build a coalition for change – Share opportunities with friends in Finance, Facilities
54
![Page 55: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/55.jpg)
Questions & Answers
55
![Page 56: Data Center Energy Efficiency Opportunities · 2015-02-11 · Data Center Energy Efficiency Opportunities What Managers Should Know February 2015 Mike Walker President, AlterAction](https://reader033.vdocuments.mx/reader033/viewer/2022042712/5f96fa1a1c3cb42d77729b04/html5/thumbnails/56.jpg)