data center airflow: a predictive model - 7x24 exchange 3 data center airflow.pdf · data center...

39
Data Center Airflow: A Predictive Model Roger R. Schmidt [email protected] Chief Thermal Architect, IBM Corporation Suhas V. Patankar [email protected] President, Innovative Research, Inc.

Upload: hoangque

Post on 13-Mar-2018

218 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Center Airflow:A Predictive Model

Roger R. [email protected]

Chief Thermal Architect, IBM Corporation

Suhas V. [email protected]

President, Innovative Research, Inc.

Page 2: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Agenda

• Product Heat Load Trends• Data Center/Equipment Cooling• Data Center Flow Measurements• Data Center Predictive Model/

Comparison with Measurements

Page 3: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Microprocessor Power Trends

1995 2000 2005 2010 2015Year

60

80

100

120

140

160

180

200

Max

imum

chi

p po

wer

(W) 1994 NTRS 1997 NTRS 1999 ITRS

26 - 43 W/cm2

30 - 88 W/cm2

Page 4: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Consortium of Computer and Telecom ManufacturersWill be published by Site Uptime Group

• Amdahl • Compaq• Cisco • Cray • Dell • HP

• IBM • Lucent • Nortel • Sun • Unisys

Heat Load Trends

Page 5: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Processing/Telecom Equipment Heat Load Trends

Year of Announcement1992 1994 1996 1998 2000 2002 2004 2006 2008 2010

Hea

t Loa

d pe

r Mac

hine

/Equ

ipm

ent A

rea

- wat

ts/ft

2

6080

200

400

600800

2000

4000

60008000

100

1000

10000

Hea

t Loa

d pe

r Mac

hine

/Equ

ipm

ent A

rea

- wat

ts/m

2

800

2000

4000

60008000

20000

40000

6000080000

1000

10000

100000

TapesWorkstationsServers & DASD(tall racks)

Communication Equipment(Frames)

Projections for Heat Loads

The Site Uptime Group

Page 6: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

IBM’s xSeries Servers

1 frame7.7 sq. ft. 7.6 kW max Max 982 watts/ft2

1800 lbs(133 lbs/sq.ft.)

Environmental Facts

Page 7: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

IBM’s zSeries Servers

1 or 2 frames14.4 sq. ft. for 1 fr.7.6 kW max for 1 fr.Max 527 watts/ft2

60 Amp dual power plugs2621 lbs(121 lbs/ft2)

Environmental Facts

Page 8: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Product Family Heat Density Trend Chart

Year of Product First Shipment1992 1994 1996 1998 2000 2002 2004 2006 2008 2010

Hea

t Loa

d pe

r Pro

duct

Foo

tprin

t - w

atts

/ft2 -fo

otpr

int

6080

200

400

600800

2000

4000

60008000

100

1000

10000

Hea

t Loa

d pe

r Pro

duct

Foo

tprin

t - w

atts

/m2 -fo

otpr

int

800

2000

4000

60008000

20000

40000

6000080000

1000

10000

100000

CommunicationEquipment(Frames)

Workstations(standalone)

Tape Storage SystemsServers & Disk Storage Systems (1.8-2.2m tall)

xx

The Site Uptime Group

Page 9: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

zSeries Cluster

8 tiles

16 tiles

527 watts/ft2

based on systemfootprint

263 watts/ft2

based on minimumsystem service clearances

Page 10: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Typical Functional Allocation within Data Center

Electrically active IT hardware - 30%Service Clearances around products - 30%Site infrastructure support equipment - 20%Main aisles and other inactive areas - 20%

Page 11: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Complete Data Center

0.30 x 527 watts/ft2 = 158 watts/ft2

Partially Configured Systems(Ave. of 50% total load) 0.50 x 158 watts/ft2=79 watts/ft2

Page 12: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Agenda

• Product Heat Load Trends• Data Center/Equipment Cooling• Data Center Flow Measurements• Data Center Predictive Model/

Comparison with Measurements

Page 13: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

CRAC CRAC

Servers/Storage

Servers/Storage

Servers/Storage

Servers/Storage

Subfloor

Raised Floor

Computer Data Center Cooling

Perforated Floor Tiles (6, 11, 25, 40, 60% open)

Page 14: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Center Cooling

Page 15: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Center Characteristics

Raised Floor

Sub floor

zSeries

EPO Panel

dT

cfm

Power Dissipated P

dT = fcn(cfm,P)

Perforated Floor Tile

Objective: Maintain EPO panel thermistors below 35C

Page 16: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Chiller Air Flowrate Required for zSeries

Area of Floor Tiles to SupplyChilled Air to Freeway System

zSeries

Other Computer Systems

Centerline ofAisle Walkway

29.5" to 32.6"

65.4"

(depends on whether side covers are installed)

Rear

Front

Chilled Air Flow Requirements

Underfloor Air Temperature(C)8 10 12 14 16 18 20 22 24 26

Air F

low

Rat

e(cf

m) f

or c

ross

-hat

ched

are

a

200

400

600

800

1000

1200

1400

1600

4.0 kW

6.5 kW

9.0 kW

Page 17: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Agenda

• Product Heat Load Trends• Data Center/Equipment Cooling• Data Center Flow Measurements• Data Center Predictive Model/

Comparison with Measurements

Page 18: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Center Floor Plan - Test Area

30'

26'

L

L

Current Flow Test Area

66'

20'

CRAC Units

Page 19: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Test Area Perforated Tile Test CasesA

B

AB

AB

4 x

15 ti

les

2 x

15 ti

les

AB

1 x

10 ti

les

1 x

10 ti

les

1 x

10 ti

les

2 x 7 tiles

Case 1 Case 2 Case 3 Case 4

2 x 7 tiles

2 x 7 tiles

2 x 7 tiles

AB

4 x

15 ti

les

4 x

4 ti

les

Case 5

1 x 7 tiles

Page 20: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Calibrated Flow Tool

Page 21: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Boxed-In Test Area

Page 22: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

“25%” Open Floor Tile

Page 23: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Center Test - Case 1

AB

4 x

15 ti

les

1 2 3 4 5 6 7 8 9 10 1112 1314 15

Tile Row no.

-300

-100

100

300

Air F

low

rate

(cfm

)

Flow Distribution - Test #10

Page 24: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Center Test - Case 4

Wes

t 1W

est 2

Wes

t 3W

est 4

Wes

t 5W

est 6

Wes

t 7W

est 8

Wes

t 9W

est 1

0W

est 1

1W

est 1

2C

hille

r 1 2 3 4 5 6 7 8 910 11 12 13 14 15

Tile Row no.

-200-100

0100200300400500

Air F

low

rate

(cfm

)

AB

2 x 7 tiles2 x 7 tiles

2 x 7 tiles

2 x 7 tiles

1 x 7 tiles

Page 25: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Data Center Test - Case 5

Wes

t 1W

est 2

Wes

t 3W

est 4

Wes

t 5W

est 6

Wes

t 7W

est 8

Wes

t 9W

est 1

0W

est 1

1W

est 1

2C

hille

r 1 2 3 4 5 6 7 8 910 11 12 13 14 15

Tile row no.

-200-100

0100200300400500

Air F

low

rate

(cfm

)

AB

1 x

10 ti

les

1 x

10 ti

les

1 x

10 ti

les

Page 26: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Agenda

• Product Heat Load Trends• Data Center/Equipment Cooling• Data Center Flow Measurements• Data Center Predictive Model/

Comparison with Measurements

Page 27: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Objectives of the Model

• Calculation of airflow distribution through the floor tiles for the whole data center

• Ability to vary chiller flow, tile perforations, and raised-floor height

• Easy-to-use, fast, flexible• Intended for routine use by data-center

designers and operators

Page 28: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Basis of the Model

• A two-dimensional (depth-averaged) calculation of the velocity and pressure fields under the raised floor is performed.

• The chiller flow is specified as inflow.• The outflow through the perforated tiles is

calculated from:∆p = A Q2

where ∆p is the pressure drop andQ is the volumetric flow rate

Page 29: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

The Cause of Flow Maldistribution

Page 30: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Results of the Model

Page 31: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Comparison With Measurements

Page 32: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Comparison With Measurements

Page 33: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Comparison With Measurements

Page 34: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Comparison With Measurements

Page 35: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Flow Maldistribution Revisited

Page 36: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Effect of Tile Open Area

Page 37: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Effect of Plenum Height

Page 38: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Industry Needs

• Heat loads of Data Processing Equipment are increasing.

• Sufficient chilled airflow must be supplied to maintain high reliability.

• Complex layouts of systems, chillers, and perforated tiles present extra challenges.

• A validated predictive tool is needed to aid in balancing/optimizing airflow distribution throughout the data center.

Page 39: Data Center Airflow: A Predictive Model - 7x24 Exchange 3 Data Center Airflow.pdf · Data Center Airflow: A Predictive Model Roger R. Schmidt ... Chiller Air Flowrate Required for

Our Contribution

• Detailed airflow measurements have been conducted on a data center with a variety of chiller and tile arrangements.

• A computational model has been developed for the prediction of the flow through the perforated tiles.

• The model predictions give good agreement with the measurements.

• One run of the model requires 1-2 minutes on a 300MHz Pentium computer.