Contents
Safety.......................................................................... 4General.instructions. 4Safety.instructions. 4Intended.use. 5Intended.use.of.relay.(K1). 5
Description.................................................................. 6Function.and.application. 6Operating.modes. 6Connections. 8
Installation................................................................... 9Mounting.the.control.unit. 9Connecting.the.inputs. 12Connecting.the.outputs. 12
Expanding.the.system. 13Master-slave.circuit. 13Procedure. 13
Operation................................................................... 14Switching.the.lighting.on/off.centrally. 16Setting.the.brightness. 16Setting.the.colour.(RGB.mode). 16Sequence.play. 16Control.luminaires.groups. 16
User.interfaces.capabilities.overview. 17Troubleshooting. 18
Appendix................................................................... 19Technical.data. 19Dimensions. 21Important.definitions. 22Scene,.lighting.scene. 22Sequence. 22Group,.luminaire.group. 22Fade.time. 22Cycle.time. 22
4 XI.2011
DALI.EASY.SOSafety
SafetyGeneral instructionsThe.control.unit.must.only.be.installed.and.put.into.operation.by.a.qualified.electrician...The.applicable.safety.regulations.and.accident.prevention.regulations.must.be.observed.
Safety instructions
WARNING!Exposed,.live.cables..Danger.of.electric.shock!.Before.installation,.operation.on.dip.switches.or.any.maintenance.work.turn.off.the.main.switch.of.the.installation.CAUTION!Destruction.of.the.control.unit.and.other.devices.through.incorrect.installation!•. The.control.unit.must.not.be.opened.•. The.control.unit.is.intended.to.be.snap-mounted.on.a.35.mm.DIN.rail.within.an.electrical.cabinet.acc..DIN.43880,.in.dry.location.•. The.terminal.connection.areas.shall.be.properly.covered.and.not.accessible..Areas.other.than.the.front.cover.face.must.be.inaccessible..•. Cables.must.be.fixed.in.such.a.way.that,.in.case.of.disconnection,.they.will.not.reach.other.contacts.or.metal.parts.•. Only.connect.to.ballasts.with.a.DALI.compliant.interface.•. Do.not.connect.any.additional.control.unit.or.power.supply.to.the.DALI.control.lines.•. Do.not.connect.DALI/EASY/IN1-IN2.lines.to.mains,.or.any.mains.referred.voltage.or.to.any.other.external.voltage.•. Do.not.exceed.the.maximum.number.of.electronic.ballasts,.or.EASY.components.•. Respect.relay.contacts.rating..Contacts.are.not.suitable.for.lamp.load..Use.an.appropriate.external.power.relay.and.external.safety.fuse.•. Do.not.wire.IN1.or.IN2.to.other.DALI.EASY.SO.
5
DALI.EASY.SO
XI.2011
Safety
Intended useThe.DALI.EASY.SO.control.unit.may.only.be.operated.according.to.the.″Description″.section..All.other.applications.are.considered.to.be.inappropriate.use..If.the.DALI.EASY.SO.control.unit.is.not.used.as.intended,.there.is.no.guarantee.that.it.will.operate.safely.
Intended use of relay (K1)As.it.is.a.mechanical.device,.relay.output.is.not.intended.for.frequent.commutations..In.case.fast.scenes.recall.cycles.are.needed,.for.instance.in.Light.sequencer.mode,.decouple.relay.commutations.from.DALI.outputs.by.setting.dip.switch.1.to.ON.
6 XI.2011
DALI.EASY.SODescription
DescriptionFunction and applicationThe.DALI.EASY.SO.controls.indoor.lighting.systems.and.can.be.used.to.implement.static.scene.in.general.lighting.and.dynamic.lighting.concepts..It.enables.manual.and.automatic.control.of.up.to.four.DALI.luminaire.groups.on.separate.channels.and.one.relay..Up.to.4.x.16.lighting.scenes.can.be.programmed,.called.up.individually.or.run.through.cyclically.in.up.to.4.sequences.
Operating modesDALI.EASY.SO.has.four.operating.modes:•. Lighting.control.mode:.Brightness.is.adjusted.manually..Lighting.scenes.are.recalled.or.stored.manually.•. Lighting.sequencer.mode:.The.stored.lighting.scenes.are.called.up.automatically.one.after.the.other.(play.sequence).•. Daylight.simulation:.The.lighting.scenes.are.called.up.automatically.to.simulate.light.conditions.as.they.change.during.the.course.of.a.day..Lighting.scenes.and.cycle.time.(=.duration.of.the.″day″).can.be.adjusted.by.EASY.RMC.
•. Lighting.timer.mode:.scenes.and.sequence.A.are.recalled.automatically.by.external.timer.switch.connect.to.IN2..Temporarily.manual.override.of.light-ing.(scene,.brightness,.etc.).is.allowed.by.EASY.components..
Action IN2 closed duration (time)
Action IN2 closed duration (time)
Action IN2 closed duration (time)
Go.to.next.scene 1' Stop.sequence.(recall.A16) 15' Recall.scene.A10 25"Recall.scene.A1 2' Recall.scene.A5 1" Recall.scene.A11 30"Recall.scene.A2 3' Recall.scene.A6 5" Recall.scene.A12 40"Recall.scene.A3 4' Recall.scene.A7 10" Recall.scene.A13 50"Recall.scene.A4 7' Recall.scene.A8 15"Play.sequence.A 10' Recall.scene.A9 20"
'.=.minute,.".=.second
7
DALI.EASY.SO
XI.2011
Description
Lighting.timer.mode:.Scenes.recall.example
A
B
C
D
2'
100%
0%
A B C D
3'
7'
2'
IN2 closed duration (time)
Scene 1 recall
Dim level
Scene 1
Scene 2
Scene 4Scene 1
time
Scene 2 recall
Scene 4 recall
Scene 1
Behaviour after a power failureThe.luminaires.connected.to.the.control.unit.behave.as.follows.if.there.is.a.power.failure:•. Lighting.control.mode:.The.last.state.prior.to.a.power.failure.is.automatically.restored.•. Lighting.sequencer.mode:.The.sequence.restarts.with.the.first.active.scene.•. Daylight.simulation:.The.simulation.restarts.with.the.first.active.scene.•. Lighting.timer.mode:.See.Lighting.control.mode.or.Lighting.sequencer.mode
8 XI.2011
DALI.EASY.SODescription
ConnectionsThe.wire.connections.are.push-in.type.terminals..The.wires.can.be.removed.with.a.tool...The.control.unit.has.the.following.connections:•. DALI.output.(A)•. K1.relay.(B)•. Mains.connection.(C)•. IN2.Input.for.timer.switch.(D)•. IN1.Input.for.push.button.(E)•. DIP.switches.(F).
.DIP2
ON Slave
OFF Master.DIP1
ON. K1 K1.controlled.by.IN1.(toggle.mode)
OFF.
IN1.=.ON/OFF/DimmingK1.controlled.by.CH4.(when.CH4.value.is.0.K1.open)
•. Input.for.EASY.signal.(G)..Note:.when.using.push-in.wires.be.careful.to.respect.EASY.numbering.(1..4).across.the.system.
•. LED.status.(H)
WARNING! IN1/IN2.are.suitable.only.for.potential.free.“clean.contact”.and.SELV.isolation.from.mains.electrical.components.(pushbuttons.or.time.switches)..
On
f : 0.5 - 1.5 ; s: 0. 5 - 2.5
10 - 12 mm
wire preparatio n: push in
EASY signal
2 134
Sync
Cmd DALI EASY SO
N LK1
240 V~ 3A0/50/60 Hz
110-240 V ~
ta = 0...50°C
CH1(R) CH2 (G) CH3 (B) CH4 (W)
IN 1
DALImax 64mA / 32 devices total
DA +- DA +- DA +- DA +-140-70 mA
IN 2
OFF: MasterDIP2
ON: DIP1
OFF:
K1
ON: Slave
A B C
E DG
H
F
9
DALI.EASY.SO
XI.2011
Installation
InstallationMounting the control unitMounting Dismounting
10 XI.2011
DALI.EASY.SOInstallation
White light
4
On
EASY signal
2 134
SyncCmd DALI EASY SO
Made in Italy by OSRAMAxxxxxx 0072
N LK1
240 V~ 3A 140-70 mA0/50/60 Hz
110-240 V ~
ta = 0...50°C
wire preparation0.5 – 2.5
10 – 12 mm
CH1(R) CH2 (G) CH3 (B) CH4 (W)
IN 1
DALImax 64mA / 32 devices total
DA +- DA +- DA +- DA +-
OFF: MasterDIP1
ON:
OFF: K1
ON: Slave
IN 2DIP2
USB Adapter
N L PE
~~DADA
~~DADA
~~DADA
+
-
+
-
3 2 1
GROUP Switching lights
GROUP Dimming lights
GROUP Dimming lights
GROUP Dimming lights
Warning: principle schematic only!Follow the applicable country regulations of installation.All the necessary fuses and safety devices must be added in the real application.
Push button coupler(optional)
Infra-red receiver
Y-Connector
EASY PC Kit
Y-Connector
(optional)
(optional)
EASY Hybrid control(optional)
Timer switch(optional)
General dimming / switching(optional)
Relay
Fluorescent
DALI ECG
DALI ECG
DALI transformer
Halogen
4
3
2
1
11
DALI.EASY.SO
XI.2011
Installation
Tunable white and colored light
DALI ECG~~DADA
DALI ECG~~DADA
N L PE
DALI ECG~~DADA
+
-
+
-
DALI ECG~~DADA
USB Adapter
On
EASY signal
2 134
SyncCmd DALI EASY SO
Made in Italy by OSRAMAxxxxxx 0072
N LK1
240 V~ 3A 140-70 mA0/50/60 Hz
110-240 V ~
ta = 0...50°C
wire preparation0.5 – 2.5
10 – 12 mm
CH1(R) CH2 (G) CH3 (B) CH4 (W)
IN 1
DALImax 64mA / 32 devices total
DA +- DA +- DA +- DA +-
OFF: MasterDIP1
ON:
OFF: K1
ON: Slave
IN 2DIP2
4 3 2 1
Warning: principle schematic onlyFollow the applicable country regulations of installationAll the necessary fuses and safety devices must be added in the real application.
EASY PC Kit (optional)
EASY Hybrid control(optional)
Infra-red receiver(optional)
Y-Connector
Y-Connector
Push button coupleroptional Timer switch
(optional)
General dimming / switching(optional)
In the schema, K1 function is extra energy saving: stand by power of ballast/luminaires is saved when lights are offTypical use of K1 is shown in previous principle schema
Relay
Fluorescent
Fluorescent
Fluorescent
Blue
White
Green
Red
Cold White
White
-
Warm white
RGB+W Tunable White
Lighting configuration
Colour!.
( )
12 XI.2011
DALI.EASY.SOInstallation
Connecting the inputsProceed.as.follows:
Step Task1 Disconnect.the.unit.from.the.mains.supply.
2 Connect.the.EASY.accessories.
3 Strip.the.power.cable,.remove.the.insulation.from.the.phase.and.neutral.wires.and.connect.to.the.terminals.
4 Connect.the.external.push.button.to.the.terminal.IN1.or.the.external.timer.switch.to.the.IN2.terminal,.if.applicable.
Connecting the outputsProceed.as.follows:
Step Task1 Strip.the.DALI.lines,.remove.the.insulation.and.connect.to.the.DALI.terminals.
2 Strip.the.lines.and.connect.K1.to.the.external.contactor,.if.necessary.
13
DALI.EASY.SO
XI.2011
Installation
Expanding the systemMaster-slave circuitIn.a.master-slave.circuit,.up.to.64.DALI.EASY.SO.can.be.controlled.simultaneously.
Note:.An.OSRAM.„EASY.System.Coupler“.is.required.every.8.DALI.EASY.SO.units.to.maintain.the.EASY.line.SELV.
ProcedureProceed.as.follows.to.set.up.a.master-slave.circuit:
Step Task1 Disconnect.all.control.units.from.the.mains.supply.2 Set.DIP2.to.OFF.(Master).to.one.unit.
Note:.In.Light.Timer.mode,.connect.an.external.timer.switch.to.IN2.of.the.master.unit..In.addressed.mode.(see.EASY.Touch.panel.instruction.sheet),.connect.additional.external.timers.to.IN2.of.every.DALI.EASY.SO.unit.that.operates.in.Light.timer.mode.
3 For.the.remaining.control.units,.which.operate.as.slaves,.set.DIP1.switch.to.ON.(Slave).4 Connect.the.control.units.via.EASY.by.Y-connectors.or.push-in.terminals.5 Connect.a.maximum.of.four.infrared.receivers,.two.push.button.couplers.and.one.EASY.RC.every.16.DALI.EASY.SO.units.
14 XI.2011
DALI.EASY.SOOperation
Operation
Note:.To.operate.via.an.EASY.PB.Coupler,.DALI.EASY.RMC,.EASY.Hrybrid.Remote,.EASY.Touch.panel.and.EASY.PC.Kit,.see.the.separate.instruc-tions.sheet.
Typical.commissioning.procedure.has.the.following.steps:
1. .Prepare.lighting.concepts.by.user.interface:.1.1. Adjust.brightness,.colors/color.temperature,.switch.on/off.single.channel1.2. Store.lighting.scene
2. .Operate.the.lighting.installation.in.two.ways:2.1. By.user.interface:.Control.each.channel.independently.or.recall.stored.scenes.and.sequences2.2. By.external.timer.switch:.recall.stored.scenes.and.sequences
15
DALI.EASY.SO
XI.2011
Operation
•. Main.functions.by.EASY.RMC.(refer.to.instruction.sheet.for.further.details.and.complete.functionality.description).
Ch 1
Ch 2
Ch 4
StartTime +
StopTime -
Ch 3
Scene 2
Scene 1
Scene 3
On/Off
Dimming
Scene 4
Button FunctionCH.1...CH.4 The.luminaires.of.a.group.(channels.1...4).are.switched.on.and.off.(short.press).and.their.brightness.
is.changed.(long.press).
Start/time.+ The.sequence.is.started.(short.press).or.the.fade.time.is.extended.(long.press).
Stop/time.- The.current.sequence.is.stopped.(short.press).or.the.fade.time.is.shortened.(long.press).
Scene.1.to.Scene.4 The.corresponding.scene.is.called.up.(short.press).or.stored.(long.press).
On/Off.dimming All.luminaires.are.switched.on.and.off.(short.press).and.their.brightness.is.changed.(long.press).
16 XI.2011
DALI.EASY.SOOperation
•. Main.functions.by.EASY.Hybrid.Remote.(refer.to.instruction.sheet.for.further.details.and.complete.functionality.description)
A
B
F2
CD
E
G
F1
F4F3
J
K
1 2 3 4
5 6 7 8
A B C D
Switching the lighting on/off centrallyPress.the.central.button.(C).briefly.
Setting the brightness�..Press.function.button.F2.briefly.
�..Turn.the.jog.wheel.(D).clockwise.(+)./.anti-clockwise.(–).
Setting the colour (RGB mode)�..Press.function.button.F1.briefly.
�..Turn.the.jog.wheel.(D).clockwise.(+)./.anti-clockwise.(–).
Sequence playPress.play.function.button.F3.briefly.
Control luminaires groups�..Press.F1.+.F2.simultaneously.
�..Choose.number.of.channels:.1.....8.channels.
�..Press.F4.to.return.
�..Press.F1.to.choose.the.channel.and.set.the.brightness.
17
DALI.EASY.SO
XI.2011
Operation
User interfaces capabilities overviewPRESENCE SENSING
DIMMING WIRELESS IR / RF"
SEQUENCES LIGHT SCENES
LIGHT SCENES STORE
Max. LIGHT GROUPS independentely controlled
EASY.RMC x IR 1 4 x 4
EASY.PB.Coupler x x 4 8 x 4
EASY.Color.Drive x IR/RF 4 8 8.(Up.to.2.DALI.EASY.SO)
EASY.Hybrid.Remote x IR/RF 4 8 x 8.(Up.to.2.DALI.EASY.SO)
EASY.Touch.Panel x 4 16 x 16.(Up.to.4.DALI.EASY.SO)
EASY.Color.Control.Software x >.4 >.16 x 256.(Up.to.64.DALI.EASY.SO)
Note:.PHM.is.available.only.in.combination.with.OSRAM.fluorescent.ballast.and.can.be.enabled/disabled.by.EASY.PC.KIT.
Permanent.Heating.Mode.(PHM):.Flicker.free.at.fluorescent.lamp.switch.on.and.during.sequences.
18 XI.2011
DALI.EASY.SOOperation
TroubleshootingIf.you.cannot.remedy.the.fault,.please.contact.the.Customer.Service.department.of.the.luminaire.manufacturer.
Fault Cause RemedyLuminaire.does.not.function No.mains.voltage.present. Check.the.mains.supply.fuses.
Illuminant.defective. Replace.illuminant.Control.unit.does.not.respond.to.the.remote.control No.mains.voltage.present. Check.the.mains.supply.fuses.
Illuminant.defective. Replace.illuminant.Remote.control.batteries.are.too.weak. Check.the.display..Replace.the.batteries.if.neces-
sary.Remote.control.is.outside.the.range.of.the.infrared.receiver.
Reduce.the.distance.
Wrong.IR.coding. Check.the.IR.coding.on.the.EASY.RMC.Infrared.receiver.is.exposed.to.direct.light. Shade.the.receiver.or.select.another.installation.
location.Control.unit.does.not.respond.to.the.external.push.button
No.mains.voltage.present. Check.the.mains.supply.fuses.Illuminant.defective. Replace.illuminant.
Luminaire.does.not.react.as.expected.to.the.press.of.a.button
Button.was.pressed.too.long.or.too.short. See."Operation".No.mains.voltage.present. Check.the.mains.supply.fuses.
Sequence.in.the.master-slave.mode.is.not.synchro-nous
Slaves.have.already.been.programmed.and.have.their.own.scenes.
Perform.a.reset.and.create.the.sequence.again.
19
DALI.EASY.SO
XI.2011
Appendix
AppendixTechnical data
Operating.voltage 110-240.V./.0/50/60.Hz.(DC.operation.permissible)Supply.connection L,.NInputs •. EASY.signal.input,.SELV
.– Maximum.of.4.infrared.receivers.and.two.push.button.couplers.are.connectable•. IN1/IN2.input.for.potential-free.contact,.SELV
.– sharing.the.same.reference.potential.of.EASY.signal
.– must.be.connected.to.a.potential.free.“clean.contact”.with.SELV.isolation.from.mains..The.contacts.must.be.suitable.for.signal.commutation.(gold.contact.plating.is.suggested).
Outputs •. DALI.broadcast.channels,.basic.insulation.as.per.IEC.664.– Max..32.DALI.devices.are.connectable.(in.total.64.mA.max..total.current.capability,.shared.between.all.outputs).– Max..300.m.DALI.line.length.(total.across.all.channels)..– All.lines.shares.a.common.„-DA“.signal
•. K1.relay.output.– Normally.open.contact,.240.V.AC,.3.A.resistive;.36.VA.cosφ.0.4.50/60Hz;.for.external.power.relay.control..– Endurance:.40000.switching.cycles.
Master-slave.connection •. Max..total.line.length:.100.m•. Max..50.m.to.push.button.coupler•. Max..1.master.and.63.slaves.are.connectable
20 XI.2011
DALI.EASY.SOAppendix
Push.–.in.connection.termi-nals
Insulation.strip.length.10.....12.mmPermitted.conductor.cross.sections:..0.5.....2.5.mm².single.core..0.5.....1.5.mm².finely.stranded,.with.connector.sleeve..0.5.....1.5.mm².finely.stranded,.untreated
Power.consumption Max..10.W.(typical.5.W)Operating.temperature 0.°C.….+50.°CProtection.type Front.panel:.IP.20Protection.class IIDimensions.(L.x.W.x.H) 96.x.108.x.61.mm
21
DALI.EASY.SO
XI.2011
Appendix
Dimensions
10890
22 22
61
95
22 XI.2011
DALI.EASY.SOAppendix
Important definitionsScene, lighting sceneA.lighting.scene.defines.the.lighting.situation.of.luminaire.groups.in.a.room.
SequenceA.sequence.is.the.automatic.retrieval.of.stored.lighting.scenes.and.their.cyclic.playback..
Group, luminaire groupA.group.is.a.collection.of.luminaires.with.the.same.brightness..Luminaires.can.be.connected.to.the.same.DALI.output.channel.or.the.relay.
Fade timeThe.fade.time.is.the.time.in.which.the.lighting.system.changes.from.one.lighting.scene.to.the.next.in.sequencer.mode.