DeltaV Distributed Control System Product Data Sheet October 2019 CTO CIOC CHARM Cabinets Delivers Electronic Marshalling enabled by CHARMs technology or controller cabinet for CHARM system Fast delivery Reduced system footprint Significantly reduce cabinet design engineering Fully documented package Introduction The DeltaV Configure To Order (CTO) Cabinets provide a predesigned solution for DeltaV CHARM I/O system, assembled in industry standard cabinets, ready to be installed on-site and connected to the field I/O. These cabinets are designed to meet CSA and CE personal safety requirements to help facilitate site installation and inspection. They seamlessly integrate into the overall hardware solution of your DeltaV project.

Upload: others

Post on 06-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

DeltaV Distributed Control System Product Data SheetOctober 2019

CTO CIOC CHARM Cabinets

�� Delivers Electronic Marshalling enabled by CHARMs technology or controller cabinet for CHARM system

�� Fast delivery

�� Reduced system footprint

�� Significantly reduce cabinet design engineering

�� Fully documented package

Introduction

The DeltaV™ Configure To Order (CTO) Cabinets provide a predesigned solution for DeltaV CHARM I/O system, assembled in industry standard cabinets, ready to be installed on-site and connected to the field I/O.

These cabinets are designed to meet CSA and CE personal safety requirements to help facilitate site installation and inspection. They seamlessly integrate into the overall hardware solution of your DeltaV project.

Page 2: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 2

CTO CICO CHARM Cabinets October 2019

Benefits

Standardized cabinet designs: The CTO cabinets deliver the full benefits of electronic marshalling. These cabinets meet recommended installation practices of the DeltaV system and each is tested before shipping. The flexibility of DeltaV CHARM I/O allows for 100% utilization of channels, regardless of the I/O signal mix. Late changes are easily accommodated with minimal re-engineering and no rewiring.

Fast delivery: Standard cabinets are available with short lead times when ordered for direct shipment to site.

Reduced system footprint: Equipment room footprint is reduced by eliminating the traditional marshalling cabinets with cross wiring to traditional I/O cards.

Significantly reduce cabinet design engineering: The CHARM I/O cabinets use DeltaV Electronic Marshalling, which allows any channel to be assigned to any one of four controllers. This eliminates the task of rationalizing I/O to specific controllers and preserves I/O flexibility to handle late changes to the system.

Fully documented package: Each cabinet is supplied with full documentation showing internal lay-out, bill of materials and internal wiring. Drawings can be incorporated into the project drawing package.

Description

The CTO CHARM Cabinets offering comprises a range of pre-engineered solutions based on industry accepted cabinet enclosures, preinstalled with CHARM I/O or DeltaV controllers and related equipment, ready to be installed in an equipment room and connected to process field instrumentation or CHARM I/O.

The cabinets are typical, free standing enclosures intended for floor mounting in equipment room areas, where temperature and humidity are controlled within the requirements for computer/electronic equipment. They come ready to receive incoming 24 VDC power or available plant AC power. All internal wiring to power distribution components and grounding conductors has been tested at the factory.

Before delivery, each cabinet undergoes a full in-house inspection, to assure that it is fully operational before shipping directly to site. Electronic Marshalling eliminates the need for any internal cross wiring and I/O rationalization there is typically no need for FAT at a staging facility.

The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O.

The CTO CHARM cabinets support all available low voltage CHARM I/O types with 24 VDC bussed field power. The standard cabinets are designed for easy bottom cable entry.

The CTO cabinets are ordered by selecting a base enclosure model, on top of which one or more predefined options are configured to meet specific project needs.

Base enclosure models are available:

� For different cabinet sizes / entry (Front Access or Front and Rear access).

� For different power distribution needs: DC powered or AC powered.

� For different world area design standards and regulations: EUR (Europe), NA (US/Canada) and NK (Asia Pacific and MEA).

Configurable options examples: type of CHARMs (I.S. or non I.S.), type of controllers, type of I/O cards, side panels, cabinet light, nameplate engraving and injected power.

All cabinets come with following equipment installed:

� Primary and secondary 24VDC power distribution for CHARM I/O Cards and field instrumentation

� Wire ducts or wire basket

� Grounding bars

� Wiring plan pocket

� Emerson Name Plate Holder and blank name plate insert

� DeltaV equipment based on your configuration (and priced separately): including CHARM I/O carriers, base plates, standard terminal block, address plugs and terminals.

The CHARM I/O cards and CHARMs are not included and are to be ordered separately.

The required number of (redundant) CHARM I/O cards and CHARM modules depends on the actual number and types of I/O that will be wired into the cabinet.

The following sections provide a more detailed specification for the CTO CHARM Cabinets and available options.

Page 3: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 3

CTO CICO CHARM Cabinets October 2019

Overview of CIOC/Controller Cabinets – Base Models for EUROPE World Area

Base Model Number Description# CHARM IO

Incoming Power Requirements (Prim and Sec)

Permitted Location / World Area

EU-CAB-800F-252-AC-CIOCAC Powered Electronic Marshalling Cabinet for 252 CHARM I/O; 800mm W x 600mm D;Front Access; Cable Entry - Bottom

252 230V ACSafe AreaEUR

EU-CAB-800FR-504-AC-CIOCAC Powered Electronic Marshalling Cabinet for 504 CHARM I/O; 800mm W x 800mm D;Front and Rear Access; Cable Entry - Bottom

504 230V ACSafe AreaEUR

EU-CAB-800F-168-AC-CIOCAC Powered Electronic Marshalling Cabinet for 168 CHARM I/O; 800mm W x 600mm D;Front Access; Cable Entry - Bottom

168 230V ACSafe Area EUR

EU-CAB-800FR-336-AC-CIOCAC Powered Electronic Marshalling Cabinet for 336 CHARM I/O; 800mm W x 800mm D;Front and Rear Access; Cable Entry - Bottom

336 230V ACSafe Area EUR

EU-CAB-800F-288-DC-CIOCDC Powered Electronic Marshalling Cabinet for 288 CHARM I/O; 800mm W x 600mm D;Front Access; Cable Entry - Bottom

288 24V DCSafe AreaEUR

EU-CAB-800FR-576-DC-CIOCDC Powered Electronic Marshalling Cabinetfor 576 CHARM I/O; 800mm W x 800mm D;Front and Rear Access; Cable Entry - Bottom

576 24V DCSafe AreaEUR

EU-CAB-800FR-AC-CNTR-288

AC Powered Controller and Electronic Marshalling Cabinet for 288 CHARM I/O; 800mm W x 800mm D; Front and Rear Access; Cable Entry - Bottom

288 230V ACSafe AreaEUR

EU-CAB-800F-AC-CNTRAC Powered Controller Cabinet; 800mm W x 600mm D; Front Access; Cable Entry - Bottom

N/A 230V ACSafe AreaEUR

EU-CAB-800FR-AC-CNTRAC Powered Controller Cabinet;800mm W x 800mm D; Front and Rear Access; Cable Entry - Bottom

N/A 230V ACSafe AreaEUR

Overview of CIOC/Controller Cabinets.

The CTO base model reference for cabinets uses the following naming convention: “EU-CAB-XXXYY-ZZZ-IP-DDDD”, where

• EU: Europe Design Standards and Regulations .

• XXX = cabinet width (mm), e.g. “800”, “1200”.

• YY = “F” for Front only access (600 mm deep), “FR” for Front and Rear access (800 mm deep).

• ZZZ = maximum I/O’s count in this CTO.

• IP =AC / DC Incoming Power, DC = 24V DC or AC = 120/230V AC.

• DDDD = short description of content and purpose.

Page 4: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 4

CTO CICO CHARM Cabinets October 2019

Overview of CIOC/Controller Cabinets – Base Models for US/CANADA World Area

Base Model Number Description# CHARM IO

Incoming Power Requirements (Prim and Sec)

Permitted Location / World Area

NA-CAB-800F-252-AC-CIOCAC Powered Electronic Marshalling Cabinet for 252 CHARM I/O; 800mm W x 600mm D;Front Access; Cable Entry - Bottom

252 120V ACSafeArea US/CANADA

NA-CAB-800FR-504-AC-CIOCAC Powered Electronic Marshalling Cabinet for 504 CHARM I/O; 800mm W x 800mm D; Front and Rear Access; Cable Entry - Bottom

504 120V ACSafeArea US/CANADA

NA-CAB-800F-288-DC-CIOCDC Powered Electronic Marshalling Cabinet for 288 CHARM I/O; 800mm W x 600mm D;Front Access; Cable Entry - Bottom

288 24V DCSafeArea US/CANADA

NA-CAB-800FR-576-DC-CIOCDC Powered Electronic Marshalling Cabinet for 576 CHARM I/O; 800mm W x 800mm D;Front and Rear Access; Cable Entry - Bottom

576 24V DCSafeArea US/CANADA

NA-CAB-800FR-AC-CNTR-288

AC Powered Controller and Electronic Marshalling Cabinet for 288 CHARM I/O; 800mm W x 800mm D; Front and Rear Access; Cable Entry - Bottom.

288 120V ACSafeArea US/CANADA

NA-CAB-800F-AC-CNTRAC Powered Controller Cabinet;800mm W x 600mm D; Front Access;Cable Entry - Bottom

N/A 120V ACSafeArea US/CANADA

NA-CAB-800FR-AC-CNTRAC Powered Controller Cabinet;800mm W x 800mm D; Front and Rear Access;Cable Entry - Bottom

N/A 120V ACSafeArea US/CANADA

Overview of CIOC/Controller Cabinets.

The CTO base model reference for cabinets uses the following naming convention: “NA-CAB-XXXYY-ZZZ-IP-DDDD”, where

• NA : US/Canada Design Standards and Regulations.

• XXX = cabinet width (mm), e.g. “800”, “1200”.

• YY = “F” for Front only access (600 mm deep), “FR” for Front and Rear access (800 mm deep).

• ZZZ= maximum I/O’s count in this CTO.

• IP=AC/DC Incoming Power, DC=24VDC or AC=120/230VAC.

• DDDD= short description of content and purpose.

Page 5: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 5

CTO CICO CHARM Cabinets October 2019

Overview of CIOC Cabinets – Base Models for AP and MEA World Area

Base Model Number Description# CHARM IO

Incoming Power Requirements (Prim and Sec)

Permitted Location / World Area

NK-CAB-800F-252-AC-CIOCAC Powered Electronic Marshalling Cabinet for 252 CHARM I/O; 800mm W x 600mm D; Front Access; Cable Entry - Bottom

252 230 / 110 VACSafe Area MEA /AP

NK-CAB-800FR-504-AC-CIOCAC Powered Electronic Marshalling Cabinet for 504 CHARM I/O; 800mm W x 800mm D; Front and Rear Access; Cable Entry - Bottom

504 230 / 110 VACSafe Area MEA /AP

NK-CAB-800F-168-AC-CIOCAC Powered Electronic Marshalling Cabinet for 168 CHARM I/O; 800mm W x 600mm D; Front Access; Cable Entry – Bottom

168 230 / 110 VACSafe Area MEA /AP

NK-CAB-800FR-336-AC-CIOCAC Powered Electronic Marshalling Cabinet for 336 CHARM I/O; 800mm W x 800mm D; Front and Rear Access; Cable Entry - Bottom

336 230 / 110 VACSafe Area MEA /AP

Overview of CIOC/Controller Cabinets.

The CTO base model reference for cabinets uses the following naming convention: “NK-CAB-XXXYY-ZZZ-IP-DDDD”, where

• NK: Middle East and Africa and Asia Pacific Standards and Regulations.

• XXX = cabinet width (mm), e.g. “800”, “1200”.

• YY = “F” for Front only access (600 mm deep), “FR” for Front and Rear access (800 mm deep).

• ZZZ = maximum I/O’s count in this CTO.

• IP = Incoming Power, AC = 230/110VAC.

• DDDD = short description of content and purpose.

Page 6: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 6

CTO CICO CHARM Cabinets October 2019

Base Model

EU-C

AB-

800F

-252

-AC

-CIO

C

EU

-CA

B-80

0FR

-504

-AC

-CIO

C

EU-C

AB-

800F

-168

-AC

-CIO

C

EU

-CA

B-80

0FR

-336

-AC

-CIO

C

EU-C

AB-

800F

-288

-DC

-CIO

C

EU-C

AB-

800F

R-5

76-D

C-C

IOC

EU-C

AB-

800F

R-A

C-C

NTR

-288

EU-C

AB-

800F

-AC

-CN

TR

EU

-CA

B-80

0FR

-AC

-CN

TR

World Area EUR EUR EUR EUR EUR EUR EUR EUR EUR Power Input (DC: 24VDC, AC:120/230VAC) AC AC AC AC DC DC AC AC AC

Enclosure Access (F: Front, FR: Front-Rear) F F/R F F/R F F/R F/R F F/R

#CHARMI/O 252 504 168 336 288 576 288 Enclosure Options Type of CHARMS (to be specified for each row of CHARMS)

C 0 Non I.S. • • • • • • • NA 1 I.S. o o o o o o o

Enclosure Light S 0 Light with motion Sensor • o o o • • o o o

1 No o • • • o o • • o

Temperature Monitoring B 0 Yes • • • • • • • • • Door Fans R 0 Thermostat Controlled • • • • NA • • •

1 Continuous Run o o o o o o o

Side Panels - Installed D 0 No o o o o o o o o o

1 Yes • • • • • • • • •

Baying Kit I 0 No • • • • • • • • •

1 Yes o o o o o o o o o

Cable Clamps Rail F 0 No • • • • • • • • •

1 Yes o o o o o o o o o

Door Hinges - Front E 0 On Left • • • • • • • • •

1 On Right o o o o o o o o o

Door Hinges - Rear L 0 On Left NA • NA

• NA • • NA

1 On Right o o o o o

Plinth U 0 100 mm • • • • • • • • •

1 200 mm o o o o o o o o o

Field Cable Routing Z 0 Cable Duct • • • • • • • NA

1 Wire Basket o o o o o o o

Utility Socket P 0 No • • • • • • • • •

1 Yes o o o o o o o o o

Ethernet C 0 Copper • • • • • • NA 1 Fiber Optic o o o o o o

Certification A 0 CE • • • • • • • • •

1 None o o o o o o o o o

• : Default option setting

o : Configure To Order option setting, different from default blank :

option setting not possible for the base enclosure

o 1 : Options available for both front and rear side of the cabinet if rear side is configured as a NON DeltaV S IS side

: Intentionally left blank to fill in your configuration choices

Overview of CIOC/Controller Cabinets Options for EUROPE World Area

Page 7: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 7

CTO CICO CHARM Cabinets October 2019

• : Default option setting

o : Configure To Order option setting, different from default blank :

option setting not possible for the base enclosure

o 1 : Options available for both front and rear side of the cabinet if rear side is configured as a NON DeltaV S IS side

: Intentionally left blank to fill in your configuration choices

Base Model

NA

-CA

B-80

0F-2

52-A

C-C

IOC

NA

-CA

B-80

0FR

-504

-AC

-CIO

C

NA

-CA

B-80

0F-2

88-D

C-C

IOC

NA

-CA

B-80

0FR

-576

-DC

-CIO

C

NA

-CA

B-80

0FR

-AC

-CN

TR-2

88

NA

-CA

B-80

0F-A

C-C

NTR

NA

-CA

B-80

0FR

-AC

-CN

TR

World Area US/CAN US/CAN US/CAN US/CAN US/CAN US/CAN US/CAN Power Input (DC: 24VDC, AC:120/230VAC) AC AC DC DC AC AC AC

Enclosure Access (F: Front, FR: Front-Rear) F F/R F FR FR F F/R

#CHARMI/O 252 504 288 576 288 Enclosure Options Type of CHARMS (to be specified for each row of CHARMS)

C 0 Non I.S. • • • • • NA 1 I.S. o o o o o

Enclosure Light L 1 Light with motion Sensor • o • • o o o

2 No o • o o • • o

Temperature Monitoring T 0 Yes • • • • • • • Door Fans F 0 Continuous Run • • NA • • •

1 Thermostat Controlled o o o o o

Side Panels - Installed S 0 No o o o o o o o

1 Yes • • • • • • •

Baying Kit B 0 No • • • • • • •

1 Yes o o o o o o o

Cable Clamps Rail R 0 No • • • • • • •

1 Yes o o o o o o o

Utility Socket U 0 No • • • • • • •

1 Yes o o o o o o o

Ethernet E 0 Copper • • • • NA 1 Fiber Optic o o o o

CIOC Injected Power Distribution

V 0 No • • • • • NA

1 Yes o o o o o

Certification Z 0 None • • • • • • •

1 CSA o o o o o o o

Overview of CIOC/Controller Cabinets Options for US/CANADA World Area

Page 8: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 8

CTO CICO CHARM Cabinets October 2019

Base Model

NK

-CA

B-80

0F-2

52-A

C-C

IOC

NK

-CA

B-80

0FR

-504

-AC

-CIO

C

NK

-CA

B-80

0F-1

68-A

C-C

IOC

NK

-CA

B-80

0FR

-336

-AC

-CIO

C

World Area MEA/AP MEA/AP MEA/AP MEA/AP Power Input (AC:230/110VAC) AC AC AC AC

Enclosure Access (F: Front, FR: Front-Rear) F F/R F F/R

#CHARMI/O 252 504 168 336

Enclosure Options Nameplate Engraving A 1 No o o o o

2 Yes • • • • Type of CHARMS

(to be specified for each row of CHARMS) B 1 Non I.S. • • • •

2 I.S. o o o o

Enclosure Light C 1 With Door Switch • • • •

2 With Motion Sensor o o o o

3 No o o o o Temperature Monitoring D 1 Yes • • • •

Door Fans E 1 Thermostat Controlled • • • •

2 Continuous Run o o o o 2 With Fan Flow Switch o o o o

Plinth F 1 100mm • • • • 2 200mm o o o o

Side Panels G 1 No o o o o

2 Yes • • • •

Baying Kit H 1 No • • • •

2 Yes o o o o

Cable Clamps Rail I 1 No • • • •

2 Yes o o o o

Input Voltage

Input Voltage

J P

1 230V AC • • • • 2 110V AC o o o o

Utility Socket K 1 No • • • •

2 Yes o o o o

Field Cable Routing L 1 Cable Duct • • • • 2 Wire Basket o o o o

Ethernet M 1 Copper • • • •

2 Fiber Optic o o o o

Door Fan Location N

1 Top • • • •

2 Bottom o o o o

24VDC for Injected Power O

1 No • • • •

2 Yes o o o o

• : Default option setting

o : Configure To Order option setting, different from default blank

: option setting not possible for the base enclosure

: Intentionally left blank to fill in your configuration choices

Overview of CIOC/Controller Cabinets Options for AP and MEA World Area

Following more detailed options can be specified upon order (if applicable):

� Disconnect switches for DC power feeds can be configured separately for CIOC power and for injected power inputs.

� Power supply configuration: Power for CIOC and/or injected power (with diode), Front and Rear position in cabinet.

� 24VDC for injected power: optionally prewired (according specification to be provided).

� Wiring color scheme different from default: US (L- Black, N- White) / EUR (L- Brown, N- Blue)/ NK ( L- Brown, N- Blue)

� Input Voltage different from default: US (120VAC) / EUR (230VAC)/ NK (230/110V AC)

Page 9: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 9

CTO CICO CHARM Cabinets October 2019

Cabinet SpecificationsEU-CAB-800F-252-AC-CIOC

Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front Access – single door, right/left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~200 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Input Power Primary and Secondary 230 VAC

Power Supply Rating Configurable as 2 X 20A or 2 X 40A

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View

Top View

3 CHARM IO rails, for total of 252 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 7 x CHARM Base Plate

� 7 x CHARM Address Plug

� 84 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 10: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 10

CTO CICO CHARM Cabinets October 2019

EU-CAB-800F-252-AC-CIOC

Front View

Top View

Page 11: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

11

CTO CICO CHARM Cabinets October 2019

www.emersonprocess.com/deltav

NA-CAB-800F-252-AC-CIOC

Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth

Access Front Access – single door, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~200 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: None;Optional: CSA (US/Canada)

Input Power Primary and Secondary 120 VAC

Power Supply Rating Configurable as 2 X 20A or 2 X 40A

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View

Top View

Example BOM:

� Power Supply subassembly

3 CHARM IO rails, for total of 252 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 7 x CHARM Base Plate

� 7 x CHARM Address Plug

� 84 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 12: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 12

CTO CICO CHARM Cabinets October 2019

NA-CAB-800F-252-AC-CIOC

Front View

Top View

Page 13: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 13

CTO CICO CHARM Cabinets October 2019

NK-CAB-800F-252-AC-CIOC

Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front Access – single door, right/left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~200 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous Run, Thermostat Controlled or With Fan Flow switch

Temperature Monitoring Thermostat

Other Fan and louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications None)

Input Power Primary, Secondary and Utility; Default Input Power: 230 VAC ; Optional: 110 VAC

Power Supply Rating Fixed 2 X 40A

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View

Top View

3 CHARM IO rails, for total of 252 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 7 x CHARM Base Plate

� 7 x CHARM Address Plug

� 84 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 14: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 14

CTO CICO CHARM Cabinets October 2019

EU-CAB-800FR-504-AC-CIOCDimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front and Rear Access, single doors, Right/Left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Input Power Primary and Secondary 230 VAC

Power Supply Rating Individually configurable as 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View Rear View

Example BOM:

� Power Supply subassembly

6 CHARM IO rails, for total of 504 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 7 x CHARM Base Plate

� 7 x CHARM Address Plug

� 84 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

� Rear: same configuration as front

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 15: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 15

CTO CICO CHARM Cabinets October 2019

NA-CAB-800FR-504-AC-CIOCDimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm Plinth

Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: None;Optional: CSA (US/Canada)

Input Power Primary and Secondary 120 VAC

Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View Rear View

Example BOM:

� Power Supply subassembly

6 CHARM IO rails, for total of 504 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 7 x CHARM Base Plate

� 7 x CHARM Address Plug

� 84 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

� Rear: same configuration as front

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 16: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 16

CTO CICO CHARM Cabinets October 2019

NK-CAB-800FR-504-AC-CIOCDimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front and Rear Access, single doors, Right/Left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous Run, Thermostat Controlled or With Fan Flow Switch

Temperature Monitoring Thermostat

Other Fan and louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications None

Input Power Primary, Secondary and Utility; Default Input Power: 230 VAC ; Optional: 110 VAC

Power Supply Rating Fixed 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View Rear View

Example BOM:

� Power Supply subassembly

Front: 3 CHARM IO rails for total of 216 I/O, Rear: 3 CHARM IO rails for total of 288 I/O

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 6 x CHARM Base Plates on front & 8 x CHARM Base Plates on Rear

� 6 x CHARM Address Plugs on front & 8 x CHARM Address Plugs on Rear

� 216 x CHARM terminal blocks -Screw type on front & 288 x CHARM terminal blocks -Screw type on Rear

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 17: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

17

CTO CICO CHARM Cabinets October 2019

www.emersonprocess.com/deltav

EU-CAB-800F-168-AC-CIOC

Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth

Access Front Access, single door, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~200 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE(Europe); Optional: None

Input Power Primary and Secondary 230 VAC

Power Supply Rating Fixed 2 X 40A

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between both 2 CIOC carriers is included (can be changed if required).

Front View

Example BOM:

� Power Supply subassembly

2 CHARM IO rails, for total of 168 I/Os.

Each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper

� Ethernet connectors

� 7 x CHARM Base Plate

� 7 x CHARM Address Plug

� 84 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 18: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 18

CTO CICO CHARM Cabinets October 2019

EU-CAB-800F-168-AC-CIOC

Front View

Top View

Top View

Page 19: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 19

CTO CICO CHARM Cabinets October 2019

EU-CAB-800FR-336-AC-CIOCDimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front and Rear Access, single doors, Right/Left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Input Power Primary and Secondary 230 VAC

Power Supply Rating Individually configurable as 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 4 CIOC carriers is included (can be changed if required).

Front View Rear View

Example BOM:

� Power Supply subassembly

Front: 2 CHARM IO rails for total of 144 I/O,Rear: 2 CHARM IO rails for total of 192 I/O

Each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper

� Ethernet connectors

� 6 x CHARM Base Plates on front and 8 x CHARM Base Plates on Rear

� 6 x CHARM Address Plugs on front and 8 x CHARM Address Plugs on Rear

� 72 x CHARM terminal blocks -Screw type on front and 96 x CHARM terminal blocks -Screw type on Rear

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 20: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 20

CTO CICO CHARM Cabinets October 2019

NK-CAB-800FR-336-AC-CIOCDimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front and Rear Access, single doors, Right/Left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous Run, Thermostat Controlled or With Fan Flow Switch

Temperature Monitoring Configurable: Thermostat

Other Fan and louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications None

Input Power Primary, Secondary and Utility; Default Input Power: 230 VAC ; Optional: 110 VAC

Power Supply Rating Individually configurable as 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 4 CIOC carriers is included (can be changed if required).

Front View Rear View

Example BOM:

� Power Supply subassembly

Front: 2 CHARM IO rails for total of 144 I/O,Rear: 2 CHARM IO rails for total of 192 I/O

Each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 6 x CHARM Base Plates on front and 8 x CHARM Base Plates on Rear

� 6 x CHARM Address Plugs on front and 8 x CHARM Address Plugs on Rear

� 72 x CHARM terminal blocks -Screw type on front and 96 x CHARM terminal blocks -Screw type on Rear

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 21: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

21

CTO CICO CHARM Cabinets October 2019

www.emerson.com/deltav

EU-CAB-800F-288-DC-CIOCDimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front Access – single door, right/left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~200 kg

Color Cabinet RALl7035, Plinth RAL7022

Temperature Monitoring Not included, Configurable option: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Power Requirements – Internal Power Distribution

Primary and secondary 24VDC power to be supplied from outside the cabinet(e.g. from adjacent cabinet or dedicated Power Supply Cabinet).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in left side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View

Top View

Example BOM:

3 CHARM IO rails, for total of 288 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 8 x CHARM Base Plate

� 8 x CHARM Address Plug

� 96 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 22: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 22

CTO CICO CHARM Cabinets October 2019

Front View

Top View

Page 23: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 23

CTO CICO CHARM Cabinets October 2019

NA-CAB-800F-288-DC-CIOCDimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth

Access Front Access – single door, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~200 kg

Color Cabinet RAL7035, Plinth RAL7022

Temperature Monitoring Not included, Configurable option: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: None;Optional: CSA (US/Canada)

Power Requirements – Internal Power Distribution

Primary and secondary 24VDC power to be supplied from outside the cabinet(e.g. from adjacent cabinet or dedicated Power Supply Cabinet).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in left side)

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View

Top View

Size of Wire Baskets: 150mm H x 54mm D

Example BOM:

3 CHARM IO rails, for total of 288 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 8 x CHARM Base Plate

� 8 x CHARM Address Plug

� 96 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 24: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 24

CTO CICO CHARM Cabinets October 2019

NA-CAB-800F-288-DC-CIOC

Front View

Top View

Page 25: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 25

CTO CICO CHARM Cabinets October 2019

EU-CAB-800FR-576-DC-CIOC

Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front and Rear Access, single doors, right/left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Temperature Monitoring Not included, Configurable option: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Power Requirements – Internal Power Distribution

Primary and secondary 24VDC power to be supplied from outside the cabinet(e.g. from adjacent cabinet or dedicated Power Supply Cabinet).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in sides).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained Primary and secondary control network between all 6 CIOC carriers is included (can be changed if required).

Front View

Top View

Example BOM:

6 CHARM IO rails, for total of 576 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 8 x CHARM Base Plate

� 8 x CHARM Address Plug

� 96 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 26: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 26

CTO CICO CHARM Cabinets October 2019

NA-CAB-800FR-576-DC-CIOC

Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm Plinth

Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Temperature Monitoring Not included, Configurable option: Thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: None;Optional: CSA (US/Canada)

Power Requirements – Internal Power Distribution

Primary and secondary 24VDC power to be supplied from outside the cabinet(e.g. from adjacent cabinet or dedicated Power Supply Cabinet).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in sides).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained Primary and secondary control network between all 6 CIOC carriers is included (can be changed if required).

Front View

Top View

Size of Wire Baskets: 150mm H x 54mm D

Example BOM:

6 CHARM IO rails, for total of 576 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 8 x CHARM Base Plate

� 8 x CHARM Address Plug

� 96 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 27: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 27

CTO CICO CHARM Cabinets October 2019

EU-CAB-800FR-AC-CNTR-288

Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front and Rear Access, single doors, right/left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Switch or thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Input Power Primary and Secondary 230 VAC

Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View

Top View

Example BOM front:

� 2 x Power Supply subassembly

� 24 VDC Power Distribution

� 2 x S-series 2-Wide controller carrier

� 2 x S-series 8-Wide carrier

� DeltaV Network switch Pri & Sec

� VIM Network switch Pri & Sec

� 4 x S-series 2-Wide Carrier for VIM I/O modules

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 28: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 28

CTO CICO CHARM Cabinets October 2019

EU-CAB-800FR-AC-CNTR-288

Rear View

Example BOM Rear:

3 CHARM IO rails, for total of 288 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 8 x CHARM Base Plate

� 8 x CHARM Address Plug

� 96 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 29: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 29

CTO CICO CHARM Cabinets October 2019

NA-CAB-800FR-AC-CNTR-288

Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm Plinth

Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Switch or thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations ; Default Certification: None; Optional: CSA (US/Canada)

Input Power Primary and Secondary 230 VAC

Power Supply Rating Individually configurable as 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.

Daisy chained primary and secondary control network between all 3 CIOC carriers is included (can be changed if required).

Front View

Top View

Size of Wire Baskets: 150mm H x 54mm D

Example BOM front:

� 2 x Power Supply subassembly

� 24 VDC Power Distribution

� 2 x S-series 2-Wide controller carrier

� 2 x S-series 8-Wide carrier

� DeltaV Network switch Pri & Sec

� VIM Network switch Pri & Sec

� 4 x S-series 2-Wide Carrier for VIM I/O modules

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 30: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 30

CTO CICO CHARM Cabinets October 2019

NA-CAB-800FR-AC-CNTR-288

Rear View

Example BOM Rear:

3 CHARM IO rails, for total of 288 I/O, each rail containing:

� 1 x CHARM I/O Carrier with redundant Copper Ethernet connectors

� 8 x CHARM Base Plate

� 8 x CHARM Address Plug

� 96 x CHARM terminal blocks -Screw type

� 1 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 31: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 31

CTO CICO CHARM Cabinets October 2019

EU-CAB-800F-AC-CNTR

Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front Access, single door, right/left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Switch or thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Input Power Primary and Secondary 230 VAC

Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors

Front View

Top View

Example BOM front:

� Power Supply subassembly

� 24 VDC Power Distribution

� VIM Network switch Pri & Sec.

� 4 x S-series 2-Wide Carrier for VIM I/O modules

� 2 x S-series 2-Wide controller carrier

� 2 x S-series 8-Wide carrier

� DeltaV Network switch Pri & Sec

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 32: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 32

CTO CICO CHARM Cabinets October 2019

EU-CAB-800F-AC-CNTR

Front View

Top View

External Layout Drawing for EU-CAB-800F-AC-CNTR: Front and Top View.

Page 33: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 33

CTO CICO CHARM Cabinets October 2019

NA-CAB-800F-AC-CNTRDimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth

Access Front Access, single door, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Switch or thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: None; Optional: CSA (US/Canada)

Input Power Primary and Secondary 120 VAC

Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors

Front View

Top View

Example BOM front:

� Power Supply subassembly

� 24 VDC Power Distribution

� VIM Network switch Pri & Sec.

� 4 x S-series 2-Wide Carrier for VIM I/O modules

� 2 x S-series 2-Wide controller carrier

� 2 x S-series 8-Wide carrier

� DeltaV Network switch Pri & Sec

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 34: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 34

CTO CICO CHARM Cabinets October 2019

Front View

Top View

Page 35: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 35

CTO CICO CHARM Cabinets October 2019

EU-CAB-800FR-AC-CNTR

Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable

Access Front and Rear Access, single doors, right/left hand hinged configurable, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Switch or thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None

Input Power Primary and Secondary 230 VAC

Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors

Front View

Top View

Example BOM Front:

� 2 x Power Supply subassembly

� 24 VDC Power Distribution

� 2 x S series 2-Wide controller carrier

� 2 x S series 8-Wides carrier

� DeltaV Network switch Pri & Sec

� VIM switch Pri & Sec

� 4 x S-series 2-Wide Carrier for VIM I/O modules

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools

Page 36: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 36

CTO CICO CHARM Cabinets October 2019

EU-CAB-800FR-AC-CNTR

Rear View

Example BOM Rear:

� 24 VDC Power Distribution

� 2 x SZ Controller Carrier with redundant Copper Ethernet connectors

� LSN Switch Pri & Sec

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 37: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 37

CTO CICO CHARM Cabinets October 2019

NA-CAB-800FR-AC-CNTRDimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm Plinth

Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans Configurable: Continuous run or with thermostat control

Temperature Monitoring Configurable: Switch or thermostat

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.

Certifications Installation in Safe Area locations; Default Certification: None; Optional: CSA (US/Canada)

Input Power Primary and Secondary 230 VAC

Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear

Internal Power Distribution AC Distribution subassembly (mounted in left side).

Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).

Control Network Redundant 100BASE-FX, RJ45 connectors

Front View

Top View

Example BOM Front:

� 2 x Power Supply subassembly

� 24 VDC Power Distribution

� 2 x S series 2-Wide controller carrier

� 2 x S series 8-Wides carrier

� DeltaV Network switch Pri & Sec

� VIM switch Pri & Sec

� 4 x S-series 2-Wide Carrier for VIM I/O modules

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 38: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 38

CTO CICO CHARM Cabinets October 2019

NA-CAB-800FR-AC-CNTR

Rear View

Example BOM Rear:

� 24 VDC Power Distribution

� 1 x SZ Controller Carrier with redundant Copper Ethernet connectors

� LSN Switch Pri & Sec

No DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 39: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

www.emerson.com/deltav 39

CTO CICO CHARM Cabinets October 2019

How to order a CTO Cabinet?

Configure To Order CHARM Cabinets are pre-engineered solutions developed by Emerson’s Project Management Office (PMO) and made available from Emerson Supply Chain. Basically, the following steps are followed to obtain a CHARM Cabinet:

1. Specify the CHARM Cabinet by selecting the base model and the options required for the project.

Specifying tools are available to aid in the selection of the right combination of optioned CTOs.

2. Based on the specification, you will then receive:

• A quotation for the fully assembled Cabinet.

• The detailed specification (drawing package) matching your configuration, including the Bill of Materials.

3. Approve the drawing package for construction.

4. Order the CHARM Cabinet as per provided quotation and approved drawings.

5. The CHARM Cabinet is assembled, factory tested and delivered to site. The delivery includes the as-built drawing package (AutoCAD).

For questions related to specific project quotations or order processing, please contact your local Emerson Sales office or your regional Emerson assembly center:

For US/Canada St. Louis iCenter: [email protected]

For Europe Cluj iCenter: [email protected]

For Asia Pacific Singapore iCenter: [email protected]

For Middle East and Africa iCenter: [email protected]

Project Customizations“…What if a CTO CHARM Cabinet is 90% what I need, but I really need my Cabinet to have…”

Minor customizations as a variation or addition to the standard CTO offering can often be developed in such a way that the additional effort is incremental.

In case your project would require a customer witnessed Factory Acceptance Test, this can also be accommodated.

Please work with your local Emerson Sales office or regional Emerson assembly center to evaluate any impacts of requested customizations to cost, delivery time and certifications.

System Compatibility

CHARM Cabinets are compatible with DeltaV version 11.3.1 and above.

CHARM I/O cards require S-series Controllers.

Certifications

The CTO CHARMs Cabinet designs are designed to meet CE and CSA personal safety and EMC requirements. The designs have been submitted for the following certifications:

� Conformity to the relevant European directives, including EMC (CE Marking)

� CSA Mark for US and Canada

For Europe Design Standards and Regulations, the cabinet default comes with CE Certification. Optionally, no certification can be specified.

For US/Canada Design Standards and Regulations, the cabinet default does not come with certification. The CSA Certification is optional.

Refer to the DeltaV S-series Electronic Marshalling or to the DeltaV S-series IS Electronic Marshalling Product Data Sheet for certification information on the DeltaV system components.

Page 40: CTO CICO CHARM Cabinets - Emerson Electric€¦ · The CTO controller cabinets are designed to house your controllers, device net, vim, serial and fieldbus I/O. The CTO CHARM cabinets

October 2019CTO CICO CHARM Cabinets

EmersonNorth America, Latin America:

+1 800 833 8314 or +1 512 832 3774

Asia Pacific: +65 6777 8211

Europe, Middle East:

+41 41 768 6111

www.emerson.com/deltav

©2019, Emerson. All rights reserved.

The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.

Related Products

� CHARM I/O Cards must be ordered separately

� CHARMs must be ordered separately

� CHARMS requiring other terminal blocks than the standard terminal block should be ordered with the non-standard terminal block