ct saturation tutorial
Post on 27-Apr-2015
620 views
Embed Size (px)
TRANSCRIPT
CT Saturation TutorialPresented by Tony Giuliante
Bushing CT
IS
IP
N Turns
Copyright ATG Consulting 2003
1
Physical Properties of CoreLength L Area A
B-H Characteristic
Copyright ATG Consulting 2003
2
B-H CharacteristicB
H
Flux to Volts per Turn=
s B
dA
= B A sin (t) V = d = B A cos (t) N dt
Copyright ATG Consulting 2003
3
Flux to Volts per Turn
V = BA N
Electric Field to Ampere Turns =
H
dL
= H L
Copyright ATG Consulting 2003
4
Convert B-H CharacteristicB V = BA N
= H L
H
V/N vs. NIV N
NI
Copyright ATG Consulting 2003
5
CT Exciting Characteristic2000:5
300:5
VS
IS
Simplified Bushing CT CircuitIS
IPN
REB
REB = RLEADS + RDEVICES
Copyright ATG Consulting 2003
6
Simplified Bushing CT CircuitRCT IS
IPN
XM IM
REB
Simplified Bushing CT CircuitIS
IPN
XM IM
V = IS RTB
RTB
Copyright ATG Consulting 2003
7
Flux vs VoltageV = N d dt 1 = N 1 = N
V
dt
IS RTB
dt
Flux vs Voltage1 = N
IS RTB
dt
Flux equals the AREA under the Voltage
Copyright ATG Consulting 2003
8
Voltage Demand IS RTB
Voltage & Flux WaveformsIS RTB
Copyright ATG Consulting 2003
9
Flux Design Limits+ S
- S
Secondary CurrentNo Saturation
Copyright ATG Consulting 2003
10
Increased Voltage Demand Five times IS RTB5*IS RTB
Flux for Ideal CTNo Saturation
5*IS RTB
Copyright ATG Consulting 2003
11
Current Output for Ideal CTNo SaturationPrimary Current Secondary Current
Amperes
Time (Seconds)
Flux Design Limits+ S - S
Copyright ATG Consulting 2003
12
Flux Design Limits+ S - S
Flux Excursion
Copyright ATG Consulting 2003
13
Current vs Flux
AC Saturation
Copyright ATG Consulting 2003
14
AC Saturation Large Fault Current Large Burden Low CT Kneepoint Voltage
AC SaturationRelay Applications Large Fault Current Unit Auxiliary Transformers
Large Burden High Impedance Bus Differentials
Low CT Kneepoint Voltage Compact Distribution Switchgear
Copyright ATG Consulting 2003
15
Unit Auxiliary TransformersG
87UAT
DC OffsetTransformer
Fault current includes a dc component, or offset, that makes the current asymmetrical. L/R = 100 ms X/R = 37.7
Copyright ATG Consulting 2003
16
Offset Current vs FluxPrimary Current Flux Sec. Amperes or Flux Density
Time (Seconds)
Secondary CurrentPrimary Current Secondary Current
Amperes
Time (Seconds)
Copyright ATG Consulting 2003
17
Secondary Current Observations Secondary current is distorted due to the core flux saturation Secondary current distorts after a short time (time-to-saturation) Distortion slowly dissipates as primary dc offset decays
Secondary Current 100 Amps 50 0 -50 0 2 Tesla 1 0 -1 0 1 2 3 4 Cycles 5 6 7 I SEC 1 2 3 4 5 6 Magnetic Flux Density (B) 7 I PRIM
Copyright ATG Consulting 2003
18
Large Differential CurrentSecondary Current Primary Current
Amperes
Differential Current
Time (Seconds)
DC Saturation Factors Large DC Time Constant Large Burden Low CT Kneepoint Voltage High Remanent Flux
Copyright ATG Consulting 2003
19
Remanent Flux Trapped magnetic flux in core if a previous offset current is interrupted before reaching a symmetrical state High X/R ratios make remanent flux more likely due to the slow decay rates of offset current
Remanent Flux SurveyRemanent flux in % of saturation 0 - 20 21 - 40 41 - 60 61 - 80 Percentage of cts 39 18 16 27
Copyright ATG Consulting 2003
20
Remanent Flux Example CT data 1200:5, C800, burden = 1.6 +j 0.7 ohm
Fault current 24,000 amps with dc offset X/R ratio = 19 Display ct secondary output current for remanence of 0%, 50% and 75% of saturation
0% Remanent FluxPrimary Current Secondary Current
Amperes
Time (Seconds)
Copyright ATG Consulting 2003
21
50% Remanent FluxPrimary Current Secondary Current
Amperes
Time (Seconds)
75% Remanent FluxPrimary Current Secondary Current
Amperes
Time (Seconds)
Copyright ATG Consulting 2003
22
Remanent Flux ResultsRemanent flux 0% 50% 75% Time-to-saturation 1+ cycles 1/2 cycle 1/3 cycle
IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes C37.110-1996
Copyright ATG Consulting 2003
23
CT Classification
CT Accuracy Class ANSI defines accuracy rating classes by a letter and number C100, C800 or T100, etc. Letter designates how the accuracy can be determined Number designates the minimum secondary terminal voltage under a standard burden
Copyright ATG Consulting 2003
24
Accuracy Class Letter C means by Calculation non-gapped cores with negligible leakage flux, such as bushing cts
T means by Test cts with leakage flux, such as cts with wound primaries
Old classes H and LH T and L C
Accuracy Class Number Minimum secondary terminal voltage produced at 20 times rated current into a standard burden without exceeding a 10% ratio correction factor
Copyright ATG Consulting 2003
25
What is a Standard Burden? IEEE Standard Requirements for Instrument Transformers C57.13-1993 the standard relaying burdens are 1, 2, 4 and 8 ohms at a lagging 0.5 p.f. 20 times rated secondary current of 5 A is 100 A, and 100 A times the standard burdens yield C ratings of 100, 200, 400 and 800 V
CT Knee Point Voltages45o Tangent A B 300:5 2000:5
VS
IS
Copyright ATG Consulting 2003
26
Knee Point Definitions Point A is the ANSI knee point voltage point tangent to 45 degree slope line
Point B is the IEC knee point where a 10% increase in voltage causes a 50 % increase in current
IEC knee point is higher than ANSI knee point
CT Excitation Impedance Excitation curve represents the exciting impedance in terms of voltage and current The ANSI knee point (A) represents the point of maximum permeability of the iron core
Copyright ATG Consulting 2003
27
Examples Determine Accuracy Class Selecting CT Ratings Calculating Time to Saturation
Example - Find Accuracy Class Find the approximate ct accuracy class from the excitation curve the C class is defined for a 10% ratio correction factor at 20 times rated current 10% of (20 X 5 A) is 10 A for IE = 10 A, use the excitation curve to find VS as about 500 V
next find the ct terminal voltage by subtracting the internal voltage drop from VS (continued)
Copyright ATG Consulting 2003
28
Example - Equivalent CircuitIP VS = 500 IS = 100 A IE = 10 A VB = ? ZB
Example - continued VB (voltage to the burden)VB = VS - (IS X RS) VB = 500 - (100 X 0.61) VB = 439 V
The approximate ct accuracy class is the next lowest ANSI class number (C400)
Copyright ATG Consulting 2003
29
Examples Determine Accuracy Class Selecting CT Ratings Calculating Time to Saturation
Avoiding CT SaturationVX > IS ZTB (1 + X/R)VX = saturation voltage IS = secondary current ZTB = total ct secondary burden
Copyright ATG Consulting 2003
30
CTs for Generator Differentials For generators, typically cts cannot be sized to avoid saturation because of: high fault current high X/R ratio
Common applications would: select adequate ct primary rating select highest practical C class match manufacturer and types of cts
Examples Determine Accuracy Class Selecting CT Ratings Calculating Time to Saturation
Copyright ATG Consulting 2003
31
Transient Response of Current TransformersPower Systems Relaying Committee
Time to Saturate Equation
VK I F R TB
( I - KR )
=
TCT TST CT - T S
{
e
-t TCT
-e
-t TS
}
+1
Copyright ATG Consulting 2003
32
VKVK 2000:5 Tangents Intersect 300:5
VS
IS
Saturation ParametersR TB = RCT + R LEADS +R DEVICES I F = FAULT CURRENT (SEC RMS AMPS) KR =
{
.5 - .75 IRON CORE .1 AIR GAP
= 377L TCT = M R TB
Copyright ATG Consulting 2003
33
VM & I M45o Tangent VM 300:5 2000:5
VS
IM
IS
CT InductanceLM TCT = RTB VM
XM =
IMXM
LM =
Copyright ATG Consulting 2003
34
DC Offsets
DC Offset Current Depends on where in the voltage wave the fault occurs. Fault time is defined as: F I A => Fault Initiation Angle
Copyright ATG Consulting 2003
35
Voltage WaveformFIA
0
45
90 4.16
135 180 225 270 345 360 8.33 12.5
Degrees
60 Hz
0
16.67 Time ms
Voltage WaveformFIA
0
45
90 5
135 180 225 270 345 360 10 15
Degrees
50 Hz
0
20 Time ms
Copyright ATG Consulting 2003
36
Power SystemR L
G
Z = R2 + X2 = ARCTAN ( L / R)
Power SystemR L
G
= Characteri