cross reference ra part number: 194l-e32-1753 a · 2019. 8. 15. · product details and...
TRANSCRIPT
Product Details and Certifications
Cross Reference RA Part Number: 194L-E32-1753 A
Product: 194L-E32-1753Description: 194L IEC Control and Load Switch, OFF-ON 90°, 32 Amp,
3 Poles, Front / Door
Representative Photo Only (actual product may vary based on configuration sections)
SWITCH DATA
Bulletin 194E/L Control and Load Switches
Enclosure Type Open
Configuration OFF-ON 90°
Size 32 A
No. of Poles 3 Poles
Installation Front / Door
ACTUADOR
Actuador Selection Select actuator separately
CERTIFICATIONS AND APPROVALS
UL
CSA
IEC
CE
For UL Certifications Directory: http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
2 Rockwell Automation Publication 194-TD002B-EN-P
194 Control and Load Switches Product Overview
Bulletin 194E Bulletin 194L
Product Type Inductive load-rated load switch Inductive load-rated control/load switch
Current Range 16…100 A 12…40 A
Main Applications UL, CSA ratings "suitable as at-motor disconnect" UL, CSA ratings "suitable as at-motor disconnect"
Functionality� 3- or 6-pole switch configurations for OFF-ON or changeover
applications (16…100 A switches)
� 1- to 6-pole multifunction switch control configurations forOFF-ON, changeover, Star-Delta (Wye-Delta), reversing,ammeter, voltmeter, and step switch applications
� Also available in custom control configurations up to 16circuits for any unique control switching application.
Mounting Styles Front/door or base/DIN Rail mounting Front/door or base/DIN Rail mounting
Handles
� Handle colors in grey/black and red/yellow and padlockableversions
� Legend plates available in 0-I international markings and textstyles
� Uniformly styled handles: selector knob, disk style,rectangular style, and key-operated versions (Type 1/12, IP66)
� Handle colors in grey/black and red/yellow and padlockableversions
� Legend plates available in 0-I international markings and textstyles
Open Switch or Enclosed� Open switch (large frame Bul. 194E — open style only)� Enclosed: IP66 thermoplastic enclosure or UL/CSA rated
enclosureOpen switch
UL/CSA Electrical Ratings:Rated Voltage Ue 600V AC 600V AC
Rated Current Ie 16…100 A @ 600V 12…40 A @ 600V
Rated Power Pe [FLA] Varies w/ 1- or 3-phase switch, voltage Varies w/ 1- or 3-phase switch, voltage
Short-Circuit Ratings 5 kA 5 kA
Switching Rate [ops/h] 120 120
Mechanical Life [ops] 0.2 million (16…100 A switches) 1 million
IEC Rated Current Ie
AC-1 16…100 A @ 600V 12…40 A @ 600V
AC-21A 16…100 A @ 600V 12…40 A @ 600V
AC-22A 16…100 A @ 600V 12…40 A @ 600V
Ambient Operational Temp. -25…+60 °C (-13…+140 °F) -25…+60 °C (-13…+140 °F)
Ambient Enclosed Temp. -20…+60 °C (-4…+140 °F) -20…+60 °C (-4…+140 °F)
Ambient Storage Temp. -40…+80 °C (-40…+176 °F) -40…+80 °C (-40…+176 °F)
Protection class per IEC529 Switch bodies: IP2 Switch bodies: IP2
Optional Accessories� IP66 handles� Multi-length shafts and shaft extension kits� Terminal covers
� Multi-length shafts and shaft extension kits� Terminal covers
Standards/Certifications
� UL 508� CSA C22.2, No. 14� IEC 60947-3 Low Voltage Switchgear and Controlgear part 3� CE
� UL 508� CSA C22.2, No. 14� IEC 60947-3 Low Voltage Switchgear and Controlgear part 3� CE
Bulletin 194L
IEC Control and Load Switches
2-435www.ab.com/catalogs Preferred availability cat. nos. are bbold.
Publication A117-CA001A-EN-P
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Product Selection/Catalog Number Explanation
aInstallation Type
Code Description
A Base/DIN Mounting
E Front/Door Mounting
C Front/Door Mounting (For use with 32 A and 40 A switches only. Usewhen selecting 22.5 mm hole-mounting style handle.)
bLoad Size
Code Description Code Description
12 12 A 25 25 A
16 16 A 32 32 A
20 20 A 40 40 A
Bulletin 194L Control and Load Switches
Base/DIN Rail Mounting Front/Door Mounting Base/DIN Rail Mounting Front/Door Mounting Front/Door Mounting
12…25 A Base Mount 12…25 A Front Mount 32 A and 40 A Base Mount 32 A and 40 A Front Mount32 A and 40 A Front Mount,
for use with 22.5 mmmounting hole style handle
194L – A 16 – 175 3a b c d
cCode Function Configuration Use with Switch Style��: Circuit Diagram Ref. No.150
On/Off2-Position (60 degrees) 194L-E, 12…40 A, 1…6 poles 1501…1506
175 2-Position (90 degrees) 194L-E or 194L-A, 12…40 A, 1…6 poles 1751…1756178 2-Position (90 degrees-inverted) 194L-E or 194L-A, 12…40 A, 1…4 poles 1781…1784
225
Change-Over
1-2 (without 0, 45 degrees) 194L-E, 12…40 A, 1…5 poles or194L-A, 12…40 A, 1…2 poles 2251…2255
250 1-2 (without 0, 60 degrees) 194L-E, 12…40 A, 1…5 poles 2501…2505300 1-0-2 (with 0, 30 degrees, spring return) 194L-E, 12 A, 1…3 poles 3001…3003325 1-0-2 (with 0, 45 degrees) 194L-E or 194L-A, 12…40 A, 1…4 poles 3251…3254326 1-0-2 (with 0, 45 degrees, spring return) 194L-E, 12 A, 1…3 poles 3261…3263350 1-0-2 (with 0, 60 degrees)
194L-E, 12…40 A, 1…4 poles3501…3504
375 1-0-2 (with 0, 90 degrees) 3751…3754
425
Step Switch
1-2-3 (45 degrees) 194L-E or 194L-A, 12…40 A, 1 pole194L-E, 12…40 A, 2…3 poles 4251…4253
426 1-2-3-4 (45 degrees) 194L-E, 12…40 A, 1…3 poles194L-A, 12…40 A, 2 poles 4261…4263
427 1-2-3-4-5 (45 degrees)194L-E or 194L-A, 12…40 A, 1 pole
4271428 1-2-3-4-5-6 (45 degrees) 4281450 1-2-3 (60 degrees)
194L-E, 12…40 A, 1…3 poles4501…4503
451 1-2-3-4 (60 degrees) 4511…4513452 1-2-3-4-5 (60 degrees)
194L-E, 12…40 A, 1 pole4521
453 1-2-3-4-5-6 (60 degrees) 4531500 0-1-2-3-4 (30 degrees)
194L-E, 12…40 A, 1…3 poles5001…5003
501 0-1-2-3-4-5 (30 degrees) 5011…5013525 0-1-2 (45 degrees) 5251…5253526 0-1-2-3 (45 degrees)
194L-E or 194L-A, 12…40 A, 1 pole194L-E, 12…40 A, 2…3 poles
5261…5263527 0-1-2-3-4 (45 degrees) 5271…5273528 0-1-2-3-4-5 (45 degrees) 5281…5283550 0-1-2 (60 degrees)
194L-E, 12…40 A, 1…3 poles
5501…5503551 0-1-2-3 (60 degrees) 5511…5513552 0-1-2-3-4 (60 degrees) 5521…5523553 0-1-2-3-4-5 (60 degrees) 5531…5533725
Star-Delta(Wye-Delta)
0-Y-Δ (45/90 degrees)194L-E or 194L-A, 12…40 A, 3 poles
7253732 0-Y-Δ (45/90 degrees) 7323750 0-Y-Δ (60 degrees) 194L-E, 12…40 A, 3 poles 7503730
Reversing1-0-2 (45 degrees) 194L-E or 194L-A, 12…40 A, 3 poles 7303
754 1-0-2 (60 degrees) 194L-E, 12…40 A, 3 poles 7543825
Voltmeter0-RN-SN-TN-TR-ST-RS (45 degrees)
194L-E or 194L-A, 12 A, 1 pole
8251827 0-RS-ST-TR (45 degrees) 8271875
Ammeter0-1-2-3 (90 degrees) 8751
876 0-1-2-3-4 (90 degrees) 8761877 0-1 (90 degrees inverted) 8771
dNo. of Poles
Code Description
1 1 Pole
2 2 Poles
3 3 Poles
4 4 Poles
5 5 Poles
6 6 Poles
Catalog Number Explanation
� Not all possible configurations are available. Some configurations may have longer delivery times and minimum order quantities.�When choosing front mount style 194L-E for 32 A or 40 A, use the 194L-C code only if a 194L-HC style handle is being used.
3Rockwell Automation Publication 194-TD002B-EN-P
Specifications 194E Load Switches
Electrical Ratings
Performance Data 16 A 25 A 32 A 40 A 63 A 80 A 100 A Aux.ContactsIEC Applications
Rated operational voltage (Ue): IEC� [V] 690 690 690 690 690 690 690 690
Rated operational voltage (Ue): UL, CSA [V] 600 600 600 600 600 600 600 600
Rated isolation voltage (Ui): IEC/UL, CSA [V] 690/600 690/600 690/600 690/600 690/600 690/600 690/600 690/600
Rated impulse voltage (Uimp): UL, CSA [kV] 8 8 8 8 8 8 8 8
Test voltage, (Ui) 1 minute [kV] 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Lost power per pole [W] 0.58 1.0 1.5 1.6 2.4 3.6 5.5 0.4
Rated frequency [Hz] 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Conventional free air thermal current Ith� [A] 25 40 50 63 75 100 120 12
Conventional enclosed thermal current Ie� [A] 20 32 40 50 63 80 100 10
Rated current Ie�
[A] 16 25 32 40 63 80 100 10AC-1/ Non-inductive or only slightly inductive
loads
AC-21A Switching of resistive loads with slightoverload
Rated power Pe
AC-23A Occasional switching of 3Ø motors and other highly inductive loads (criterion for selecting main switches)
230V [kW] 5.5 7.5 7.5 15 18.5 22 30 —
400V [kW] 7.5 11 15 22 30 37 55 —
690V [kW] 7.5 11 15 18.5 22 37 45 —
AC-3 Squirrel-cage motors; starting andstopping of running motors
230V [kW] 4 5.5 7.5 11 15 18.5 22 —
400V [kW] 5.5 7.5 11 15 18.5 30 37 —
690V [kW] 5.5 7.5 11 15 18.5 30 22 —
Short circuit current (co-ordination type 2)Rated conditional short-circuit current Maximum fuse rating of circuit (type g,G) Rated short-time current Icw (1 s)
400/415V
[kA] 20 20 15 20 15 30 25 —
[A] 20 25 35 50 63 80 100 —
[A] 800 900 900 1300 1300 2500 2500 —
Rated breaking capacity AC23A (cosφ 0.45)
230V [A] 156 296 296 484 484 780 780 —
400V [A] 120 256 256 504 504 800 800 —
690V [A] 70 136 136 196 196 376 376 —
DC switching capacity
1 poleRated current Ie
24/48V [A] 20 25 32 40 63 80 100
—110V [A] 5 5 6 8 10 16 20
220V [A] 1 1 1 1.5 15 3 3
440V [A] 0.5 0.5 0.5 0.6 0.6 0.7 0.7
DC-21A For resistive loads,T ≤ 1 msUe max = 660V
2 polesin
series
96V [A] 20 25 32 40 63 80 100
—
110V [A] 20 23 25 32 50 70 80
220V [A] 5 5 6 8 10 16 20
440V [A] 1 1 1 1.5 1.5 3 3
600V [A] 0.6 0.6 0.6 0.8 0.8 1 1
3 polesin
series
110V [A] 20 25 32 40 63 80 100
—220V [A] 13 13 15 20 28 50 63
440V [A] 2.2 2.2 2.2 3.6 3.6 6.5 6.5
600V [A] 1.3 1.5 1.5 2 2 3 3
Rated power Pe
3 polesin
series—
DC-23A, DC-3, DC-5 90V [kW] 1 1.3 1.5 2.9 4.1 5.1 7.2
For inductive loads,T ≤ 15 ms 110V [kW] 1 1.1 1.3 2.2 3.3 5.5 7
220V [kW] 0.8 0.9 1.1 1.7 2 3.5 4.4
440V [kW] 0.6 0.6 0.6 0.9 0.9 1.1 1.1
600V [kW] 0.4 0.4 0.4 0.5 0.5 0.9 0.9
�See standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-Non-Fused-Disconnect-Switches#specifications
4 Rockwell Automation Publication 194-TD002B-EN-P
194E Load Switches Specifications
Performance Data 16 A 25 A 32 A 40 A 63 A 80 A 100 A Aux.ContactsUL/CSA Applications
Continuous current [A] 16 25 32 40 63 80 100 —
Heavy Pilot Duty [AC] A600 A600 A600 — — — — A600
Standard Duty [DC] — — — — — — — Q600
Motor rating 60 Hz120V, 1P
[FLA] 16 16 16 24 34 56 80
—Single-phase (2poles)
[Hp] 1 1 1 2 3 5 7.5
240V, 1P[FLA] 12 12 17 17 28 50 68
[Hp] 2 2 3 3 5 10 15
480V, 1P[FLA] 8.5 8.5 14 21 26 34 68
[Hp] 3 3 5 7.5 10 15 30
600V, 1P[FLA] 11.2 11.2 11.2 16 20 27 44
[Hp] 5 5 5 7.5 10 15 25
Three-phase
120V, 3P[FLA] 13.6 13.6 19.2 30.4 40 56 84
—
[Hp] 2 2 3 5 7.5 10 15
240V, 3P[FLA] 9.6 15.2 22 28 42 68 80
[Hp] 3 5 7.5 10 15 25 30
480V, 3P[FLA] 11 14 21 27 34 52 65
[Hp] 7.5 10 15 20 25 40 50
600V, 3P[FLA] 11 11 17 22 27 52 52
[Hp] 10 10 15 20 25 50 50
Mechanical Data
Performance Data 16 A 25…32 A 40…63 A 80…100 AAux.
Contacts
Protection class according to IEC 529
Motor rating 60 Hz
handles IP66 IP66 IP66 IP66 IP66
switch bodies IP20 IP20 IP20 IP20 IP20
Mechanical life [million operations] 0.2 0.2 0.2 0.2 0.2
Max wire gauges
Terminal size per IEC 947-1 A4 A6 A7 A9 2xA2
rigid wire [AWG][mm2]
16…101…10
14…81.5…16
12…42.5…25
10…14…50
18…140.75…2.5
fine strands [AWG][mm2]
16…81.5…6
14…81.5…10
12…42.5…16
10…14…35
18…140.5…2.5
Tightening torque [N•m]/[lb•in] 1.4/12.2 1.4/12.2 2.8/24.5 5.6/50 1/8.8
Environmental Data
Storage -40…+80 °C (-40…+176 °F)
Operation -25…+60 °C (-13…+140 °F)
Electrical Ratings, Continued
17Rockwell Automation Publication 194-TD002B-EN-P
Specifications 194L Control and Load Switches
Performance Data 12 A 16 A 20 A 25 A 32 A 40 AIEC Applications
Rated voltage Ue � IEC-947 [V] 690 690 690 690 690 690
Isolating conditions acc. to VDE fulfilled up torated impulse voltage Uimp [kV] 6 6 6 6 8 8
Thermal rated current Ith� 40 °C IEC-947 [A] 16 20 25 30 32 45
Thermal rated current Ithe 60 °C IEC-947 [A] 12 16 20 25 32 45
Rated current Ie�
IEC-947 690V [A] 12 16 20 25 32 40AC-1/AC-21A
Non-inductive or slightlyinductive loads/switching of resistive loadswith slight overload
AC-1 Non-inductive or slightlyinductive loads SEV 660V [A] 12 16 20 25 32 40
AC22ASwitching of mixed resistiveand inductive loads with slightoverload
IEC-947 220…500V690V
[A][A]
1212
1616
2020
2525
3232
4040
AC-15Switching of inductive drives,motors, valves, andelectromagnets.
IEC-947220…240V380…415V
500V
[A][A][A]
532
64
2.5
753
864
— —
DC switching capacityRated current Ie
Contacts in series
Rated Voltage [V] 1 2 3 4 5 6 824 48 72 96 120 144 192 [A] 12 16 20 22 — —48 96 144 192 240 288 384 [A] 10 12 16 18 — —60 120 180 240 300 360 450 [A] 8 10 12 14 32 40
DC-21A For resistive loads, T ≤ 1ms 110 220 330 440 550 660 — [A] 2 2.5 4 5 — —
220 440 660 — — — — [A] 0.5 0.6 0.7 0.8 — —Ue max = 600V 440 — — — — — — [A] 0.4 0.4 0.5 0.5 — —
Rated making/breaking capacity (= 1.5 x Ie)
25.2 50.4 75.6 100.8 126 151.2 201.6 [A] 18 24 30 33 — —1.05 x Rated voltage [V] 50.4 100.8 151.2 201.6 252 302.4 403.2 [A] 15 21 24 27 — —
For resistive loads, T Ith 1ms 63 126 189 252 315 378 504 [A] 12 18 18 21 48 60
115.5 231 346.5 462 577.5 — — [A] 3 4.5 6 7.5 — —Ue max = 600V 231 462 — — — — — [A] 0.75 1.12 1.05 1.2 — —
462 — — — — — — [A] 0.52 0.78 0.47 0.75 — —Rated current Ie
Rated voltage [V] 24 48 72 96 120 144 192 [A] 8 10 12 14 16 1630 60 90 120 150 180 240 [A] 4.5 5.5 7 8 — —
For inductive loads T = 50 ms 48 96 144 192 240 288 384 [A] 1.5 2 2.5 3 8 8Rated voltage [V] 60 120 180 240 300 360 450 [A] 1 1.2 1.5 1.8 4.8 4.8
110 220 330 440 550 660 — [A] 0.4 0.5 0.6 0.7 2 2220 — — — — — — [A] — — — — 0.6 0.6
Rated making/breaking capacity (= 1.1 x Ie)
1.1 x Rated voltage [V] 26.4 52.8 79.2 105.6 132 158.4 184.8 [A] 8.8 11 13.2 1.54 — 17.633 66 99 132 165 198 231 [A] 4.95 6.05 7.7 8.8 — —
For inductive loads T = 50 ms 52.8 105.6 158.4 211.2 264 316.8 369.6 [A] 1.65 2.2 2.75 3.3 8.8 8.8
Ue max = 600V 66 132 198 264 330 396 462 [A] 1.1 1.32 1.65 1.98 5.28 5.28
121 242 363 484 605 — — [A] 4.95 6.05 7.7 8.8 2.2 2.2Power Lost [W] 0.3 0.5 0.6 0.9 0.8 1.4
Rated powerPe Contacts in series
Rated voltage [V]DC-23A, DC-3, DC-5For inductive loads, T ≤1 ms
24 1 [kW] 0.12 0.15 0.20 0.25 0.30 0.3024 2 [kW] 0.20 0.25 0.30 0.37 — —48 2 [kW] 0.25 0.30 0.37 0.50 0.50 0.5048 3 [kW] 0.30 0.37 0.50 0.75 — —60 2 [kW] 0.25 0.30 0.37 0.50 1.00 1.0060 4 [kW] 0.37 0.50 0.75 1.00 — —110 4 [kW] 0.50 0.75 1.00 1.20 — —110 6 [kW] 1.00 1.20 1.40 1.60 — —220 4 [kW] 0.37 0.50 0.75 1.00 — —220 6 [kW] 1.00 1.20 1.40 1.50 — —
�See standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-Non-Fused-Disconnect-Switches#specifications
Electrical Ratings
18 Rockwell Automation Publication 194-TD002B-EN-P
194L Control and Load Switches Specifications
Performance Data, Continued 12 A 16 A 20 A 25 A 32 A 40 A
IEC Applications, Continued
Rated making/breaking capacity (= 4 x Ie) Contacts in series
Rated Voltage [V] 25.225.250.450.46363115.5115.5231231
1223244646
[A][A][A][A][A][A][A][A][A][A]
20.033.321.025.016.624.618.136.46.7
18.1
25.041.625.030.820.033.327.243.69.1
21.8
33.350.030.842.024.650.036.451.013.625.2
41.661.641.662.433.266.444.058.218.227.2
50.0—
41.6—
66.6—————
50.0—
41.6—
66.6—————
DC-23A, DC-3, DC-5
For inductive loads, T ≤ 7.5 ms
Rated breaking capacity
at 220V0.45 [cos j]
at 380V0.45 [cos j]
at 660V0.45[cos j]
[A]
[A]
[A]
72
72
53
96
96
72
128
128
86
176
176
112
296
280
196
296
336
196
Rated power Pe� IEC-947
AC-2 Slip-ring motors: starting, reversing andelectric braking; star/delta starting
3-phase3-pole
240V380V415V440V500V660V
[kW][kW][kW][kW][kW][kW]
35.55.55.57.57.5
47.57.57.51010
5.5999
1111
5.51313131515
——————
——————
AC-3 Squirrel-cage motors: starting and stoppingof running motors
IEC-947
3-phase3-pole
220…240V380…440V
500V660V
[kW][kW][kW][kW]
2.24
5.55.5
35.57.57.5
4.57.5108
5.5111311
7.515—
18.5
7.518.5—
18.5
1-phase2-pole
110V220…240V380…440V
[kW][kW][kW]
0.751.32.2
1.12.23.7
1.22.54.5
1.63.25.5
—48
—416
AC-4 Squirrel-cage motors: starting, reversing,electric braking, inching
IEC-947
3-phase3-pole
220…240V380…415V440…550V
[kW][kW][kW]
0.751.51.5
1.52.22.2
33.73.7
45.55.5
5.57.57.5
5.57.511
1-phase2-pole
110V240V380V440V
[kW][kW][kW][kW]
0.180.370.750.75
0.370.751.11.1
0.551.51.81.8
0.752.233
————
————
�See standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-Non-Fused-Disconnect-Switches#specifications
19Rockwell Automation Publication 194-TD002B-EN-P
Specifications 194L Control and Load Switches
Performance Data, Continued 12 A 16 A 20 A 25 A 32 A 40 A
IEC Applications, Continued
AC-23A
Occasional switching ofmotors and other highlyinductive loads(criterion for selecting mainswitches)
IEC-9473-phase3-pole
220…240V380…440V
500V660V
[kW][kW][kW][kW]
2.24
5.55.5
35.57.57.5
4.57.5108
5.5111311
1118.5—22
1122—22
1-phase2-pole
110V220…240V380…440V
[kW][kW][kW]
0.751.32.2
1.12.23.7
1.22.54.5
1.63.25.5
—5.511
—5.511
Short-circuit ratings
Rated short-time current(1s)Strongest series fuse, not inenclosureConditional rated short-circuit
(gL characteristic)
[kArms][A]
[kA]
0.4820�
6
0.4820�
6
0.620�
5
0.7525�
5
0.835
5
0.840
5
Switch Rate electrical [ops/h] 120 120 120 120 120 120
CSA and UL Applications
Rated Voltage Ue [V AC] 600 600 600 600 600 600
AmpereRating
Pilot DutyGeneral Use
Contact classNon-inductive or slightly inductive load‡ [A] A600
12A600
16—20
—25
—32
—40
Rated power Pe§ UL (CSA) (FLA) (FLA) (FLA) (FLA)
Standard motor DOL rating(similar to AC-3)
3-phase3-pole
120V240V480V600V
[Hp][Hp][Hp][Hp]
1 (7.2)2 (6.8)5 (7.6)5 (6.1)
1.5 (12)3 (9.6)
7.5 (11)7.5 (9)
2 (13.6)4 (12.4)8 (11.6)10 (11)
3 (19.2)6 (18)
12 (17)15 (17)
5 (30.4)7.5 (22)20 (27)20 (22)
5 (30.4)10 (28)25 (34)25 (27)
1-phase2-pole
120V240V480V600V
[Hp][Hp][Hp][Hp]
0.5 (9.8)1 (8.0)2 (6.0)3 (6.8)
.75 (13.8)1.5 (10.0)
3 (8.5)3 (6.8)
1 (16)2 (12)
4 (11.2)5 (11.2)
1.5 (20)3 (17)6 (17)
7.5 (16)
2 (24)5 (28)
7.5 (21)10 (20)
2 (24)5 (28)10 (26)15 (27)
Heavy motor load, reversing Rating (similarto AC-4)Max. back-up fuse
3-phase3-pole(gG characteristic)
120V240V
[Hp][Hp]
[A]
——35
——55
——60
——80
Short CircuitRatings
Maximum Short CircuitProspective Fault CurrentMaximum Fuse Size
[kA]
[A]
5
35
5
55
5
60
5
80
Switching Rate electrical [ops/h] 120 120 120 120 120 120
Mechanical Data
Performance Data 12/16 A 20/25 A 32/40 A
Protection class acc. to IEC 529 HandlesSwitch Bodies
IP66IP20
IP66IP20
IP66IP20
Mechanical Endurance [mil.ops] 1 1 1
Switching rate mechanical [ops/h] 1200 1200 1200
Maximum Wire Gauges
rigid wire
fine strands
AWG[mm2]AWG
[mm2]
(2)18…12(2)1…2.5(2)18…12(2)1…2.5
(2)16…10(2)1.5…6(2)16…10(2)1.5…4
(2)12…8(2)4…10
(2)14…10(2)2.5…6
Environmental Data
Performance Data 12/16/20/25 A 32/40 A
Ambient temperature
Operation -25…+60 °C(-13…+140 °F)
-25…+60 °C(-13…+140 °F)
Storage -40…+80 °C(-40…+176 °F)
-40…+80 °C(-40…+176 °F)
�Does not apply to switches in enclosure.‡ Suitable for switching off-load (AC-20) above 660V, but only up to 660V for switches with screws at the rear.§ See standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-Non-Fused-Disconnect-Switches#specifications