26k INTUMASTIC HP FIRE ALARM CABLE BUNDLE AIRCON PIPES PEX PIPES PEX-AL GAS PIPES HDPE PIPES CORE HOLE APPLICATIONS WITHIN: 2 HR MASONRY/CONCRETE OR HEBEL FLOOR SLAB TPS ELECTRICAL CABLE BUNDLE CPVC SPRINKLER PIPES SIMPLY SQUIRT THE INTUMASTIC HP INTO THE ANNULAR GAP BETWEEN THE OUTSIDE OF THE SERVICE PENETRATION AND THE INSIDE OF THE HOLE. FILL TO THE FULL DEPTH OF THE: MINIMUM 100mm THICK- CONCRETE/MASONRY OR HEBEL FLOOR SLAB. PHONE: (07) 5411 4209 OR (02) 8004 3333 (Option 2) WEBSITE: tbafirefly.com.au EMAIL: [email protected] TBA FIREFLY

Upload: others

Post on 25-Nov-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CORE HOLE APPLICATIONS WITHIN: 2 HR …

26kINTUMASTIC HP

FIRE ALARM CABLE BUNDLE

AIRCON PIPES PEX PIPES PEX-AL GAS PIPES HDPE PIPES

CORE HOLE APPLICATIONS WITHIN:

2 HR MASONRY/CONCRETE OR HEBEL FLOOR SLAB

TPS ELECTRICAL CABLE BUNDLE CPVC SPRINKLER PIPES

SIMPLY SQUIRT THE INTUMASTIC HP INTO THE ANNULAR GAP BETWEEN THE OUTSIDE OF THE SERVICE PENETRATION AND THE INSIDE OF THE HOLE. FILL TO THE FULL DEPTH OF THE: MINIMUM 100mm THICK-CONCRETE/MASONRY OR HEBEL FLOOR SLAB.

PHONE: (07) 5411 4209OR (02) 8004 3333 (Option 2)

WEBSITE: tbafirefly.com.auEMAIL: [email protected]

TBA FIREFLY

Page 2: CORE HOLE APPLICATIONS WITHIN: 2 HR …

FRL -/120/120

FRL -/120/120

FRL -/120/120

FRL -/120/120

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

H3

BUNDLE OF UP TO 12 FIRE ALARM CABLES

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

Warringtonfire Report No:FAS190236 RIR Specific ID No:

H3

Warringtonfire Report No:FAS190236 RIR Specific ID No:

H9a

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

H10a

BUNDLE OF UP TO 12 TPS ELECTRICAL CABLES

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

33.4mm CPVC FIRE SPRINKLER PIPE

48mm CPVC SPRINKLER PIPETBA FIREFLY

Page 3: CORE HOLE APPLICATIONS WITHIN: 2 HR …

FRL -/120/120

FRL -/120/120

FRL -/120/120

FRL -/120/120

Warringtonfire Report No:FAS190236 RIR Specific ID No:

H11

25mm COPPER PIPE LAGGED WITH 25mm ARMAFLEX FR THERMAL INSULATION

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

H27

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

H14

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

H15

Up to 43mm OD PEX PIPE

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

Up to 43mm OD PEX-AL GAS PIPE

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 50mm) and sealed to the full depth of the substrate.

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

40mm HDPE PIPETBA FIREFLY

Page 4: CORE HOLE APPLICATIONS WITHIN: 2 HR …

FRL -/120/120

FRL -/120/120

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

H16

Warringtonfire Report No:

FAS190236 RIRSpecific ID No:

H17

22mm uPVC PIPE

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate.

Up to 9 x 13mm ARMAFLEX LAGGED COPPER PIPES + up to 20 x TPS CABLES + with or without 16mm FLEXIDRAIN PIPE + with or without STEEL CABLE TRAY

Protected with TBA Firefly Intumastic HP in the annular gap (Min 10mm Max 40mm) and sealed to the full depth of the substrate. Then the whole bundle is wrapped with TBA Firefly 12mm Penowrap 300mm to either side of the seal or 600mm to the Top Side only.

All service penetrations must be treated in strict accordance with the concise construction details contained within the referenced compliance Reports. These Reports meet Specification A2.3 of NCC2016 Amendment 1 (Including prior versions) & Schedule 5 of NCC2019 (Including amendment 1) for determination of an FRL.

TBA FIREFLY