CURSO DE
CONVERSOR DE FREQUÊNCIA
DANFOSS DO BRASIL
![Page 2: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/2.jpg)
Danfoss do Brasil - Service
![Page 3: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/3.jpg)
Danfoss do Brasil - Service
CORRENTE ALTERNADA
![Page 4: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/4.jpg)
Danfoss do Brasil - Service
Nomes comumente encontrados que designam os Inversores
AFD adjustable frequency drive
VFD variable frequency drive
ASD adjustable speed drive
VSD variable speed drive
DRIVE
![Page 5: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/5.jpg)
Danfoss do Brasil - Service
Teoria & Partes de um AFD
• 4 Partes Compõem um AFD
• Retificador• Circuito Intermediário• Inversor• Controle & Regulação
![Page 6: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/6.jpg)
Danfoss do Brasil - Service
Retificador
![Page 7: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/7.jpg)
Danfoss do Brasil - Service
Retificador
![Page 8: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/8.jpg)
Danfoss do Brasil - Service
Retificador
![Page 9: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/9.jpg)
Danfoss do Brasil - Service
SCR
Retificador
![Page 10: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/10.jpg)
Danfoss do Brasil - Service
Princípio Da Partida Suave Princípio Da Partida Suave (Soft Starter)(Soft Starter)
Voltagem
Voltagem
Tempo
Tempo
controle do ângulo da Fase
Tensão Inicial
Tempo de Rampa
![Page 11: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/11.jpg)
Danfoss do Brasil - Service
Partida EsPartida Estrtrêlaêla--TriânguloTriângulo Versus Soft-start Versus Soft-start
M
M Y
I Y
I
M L
I s-s
M s-
s
M L
I Start 6 x InI Start 6 x In
I nI n
I nI n
I Start 4 x InI Start 4 x In
EsEstrtrêlaêla--TriânguloTriângulo
Soft-start
Torque/CurrentTorque/Current
Torque/CorrenteTorque/Corrente
VelocidadeVelocidade
VelocidadeVelocidade
![Page 12: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/12.jpg)
Danfoss do Brasil - Service
Retificador
![Page 13: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/13.jpg)
Danfoss do Brasil - Service
Circuito Intermediário - DC Link
![Page 14: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/14.jpg)
Danfoss do Brasil - Service
CORRENTE ALTERNADA
![Page 15: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/15.jpg)
Danfoss do Brasil - Service
CORRENTE ALTERNADA
![Page 16: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/16.jpg)
Danfoss do Brasil - Service
ω=2πf
f(t)= Vmax. sen ωt
veff²= 1 . ∫ f(t) ² dt T ti
tf
veff²=2π∫ V²max. sen²ωt0
2π1 .
2π
veff²=2π∫. sen²ωt0
1 . V²max
sen²a= 1- cos 2a2
veff²=2π1 . V²max 1 t
2
2π
0
veff²=2π1 . V²max 2π
2
veff²= V²max
2
veff =√ V²max
2
veff= Vmax
√2
rmsdt
dt
![Page 17: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/17.jpg)
Danfoss do Brasil - Service
Circuito Intermediário - DC Link
veff= Vmax
√2
} Vmax
220Vac 311,12 Vdc380Vac 537,40 Vdc
veff . Vmax= √2
![Page 18: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/18.jpg)
Danfoss do Brasil - Service
Redução das Correntes Harmônicas Pela Adição das Bobinas DC
“Choke=Bobina=reator=indutor”
Norma IEEE-519(THVD= Distorção Harmônica Total de Tensão)
![Page 19: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/19.jpg)
Danfoss do Brasil - ServiceO que são harmônicas?
Harmônica é a componente de uma onda periódica cuja frequência é um múltiplo inteiro da frequência fundamental (no caso da energia elétrica no Brasil, de 60 Hz)
Nesta figura, vemos duas curvas: uma onda senoidal normal, representando uma corrente de energia "limpa", e outra onda menor, representando uma harmônica.Esta segunda onda menor representa a harmônica de quinta ordem, o que significa que sua frequência é de 5 x 60 Hz, ou 300 Hz.
Somatória das duas curvas; ilustrando bem a distorção harmônica na curva de tensão
f =1T
![Page 20: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/20.jpg)
Danfoss do Brasil - Service
CIRCUITO INVERSOR
Alarme 30 Fase U ausente
Alarme 31 Fase V ausente
Alarme 32 Fase W ausente
Alarme 16 curto-circuito entre os enrolamentos do motor ou entre os terminais u,v,w.
Alarme 14 fuga ao terra ou curto-circuito entre as fases do motor e o terra ou fuga para a massa.Alarme 12 Excesso
de corrente no motorAlarme 13 Excesso de corrente no conversor
![Page 21: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/21.jpg)
Danfoss do Brasil - Service
PWM - Pulse Width Modulation (Modulação em Largura de Pulso)
![Page 22: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/22.jpg)
Danfoss do Brasil - Service
Operação do Conversor
![Page 23: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/23.jpg)
Danfoss do Brasil - Service
Controle e Regulação
![Page 24: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/24.jpg)
Danfoss do Brasil - Service
Torque Constante(Esteira / Correia transportadora)
![Page 25: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/25.jpg)
Danfoss do Brasil - Service
Torque Variável (Bomba & Ventiladores)
![Page 26: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/26.jpg)
Danfoss do Brasil - Service
Freio Dinâmico ou Reostático
VLT6000 não tem
![Page 27: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/27.jpg)
Danfoss do Brasil - Service
O Freio é necessário?
• 3 opções– Standard - no brake ST– Standard with Brake SB– Extended with Brake EB
VLT6000 não tem
![Page 28: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/28.jpg)
Danfoss do Brasil - Service
Extended com freio
• Loadsharing= compartilhar a carga• Conexão do DC bus entre os VLT’s• Resistores de freio podem dividir a carga• Entrada de 24Vcc para alimentar o controle
VLT6000 não tem
![Page 29: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/29.jpg)
Danfoss do Brasil - Service
Filtro RFI(interferência em rádio frequência)
![Page 30: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/30.jpg)
Danfoss do Brasil - Service
Filtro LC
![Page 31: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/31.jpg)
Danfoss do Brasil - Service
Resposta da Tensão e da Corrente sem Filtro, e com a
inclusão do
Filtro LC
Filtro LC
![Page 32: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/32.jpg)
Danfoss do Brasil - Service
Refrências
De Velocidades
![Page 33: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/33.jpg)
Danfoss do Brasil - ServiceSistema em Malha Fechada
Controlador
1-10bar
Sinal de Controle
1-10bar
Bomba com o VLT
Controlador Processo campoSet point
Transmissor
Erro
Feed back-
+
Atu
ad
or
![Page 34: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/34.jpg)
Danfoss do Brasil - Service
U V W
60
4 – 20 mA
PI
0 – 100 MCA
VLT
FeedBackSetpoint(=~4,2Bar)
Par 211=42% Para VLT6000
0 – 10 Bar
55
38 até 42 MCA
3,8 até 4,2 bar
60Hz----42 Mca
xxHz----38 Mca38 MCA -- 9,12 mA 42 MCA-- 10,08 mA
Loop Fechado
Ajuste do P.I.D.
![Page 35: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/35.jpg)
Danfoss do Brasil - Service
MOTOR ASSÍNCRONOEstator
Rotor
![Page 36: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/36.jpg)
Danfoss do Brasil - Service
PLAQUETA
DO
MOTOR
![Page 37: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/37.jpg)
Danfoss do Brasil - Service
Tensão Alternada Trifásica
Campo Girante
Pm = n.Pe
![Page 38: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/38.jpg)
Danfoss do Brasil - Service
f
U
T
RPM
60Hz P = U x I
![Page 39: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/39.jpg)
Danfoss do Brasil - Service
Torque do motor acima da velocidade síncrona
![Page 40: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/40.jpg)
Danfoss do Brasil - Service
L1 T1
L2 T2
L3 T3
Esquema Básico de Potência dos Soft Starters
![Page 41: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/41.jpg)
Danfoss do Brasil - Service
Esquema Elétrico de um SoftStarter
L1
L2
L3
T1
T2
T3
Módulo deIdentidade
Placa de Controle
Módulo Snubber/
Sobretensão
CTs •SCRs
PT
Ventilador
Sete Componentes Principais
• Placa de Controle• SCRs• Módulo de Identidade• Módulo Snubber/Sobretensão• Ventilador(es)• Transformador de Potência• Transformador de Corrente
![Page 42: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/42.jpg)
Danfoss do Brasil - Service
Princípio Da Partida SuavePrincípio Da Partida Suave
Voltagem
Voltagem
Tempo
Tempo
controle do ângulo da Fase
Tensão Inicial
Tempo de Rampa
![Page 43: Conversor Aula](https://reader035.vdocuments.mx/reader035/viewer/2022081412/5449cf3aaf795978188b45f6/html5/thumbnails/43.jpg)
Danfoss do Brasil - Service
Esquema Geral de um Soft Starter
L1
L2
L3
T1
T2
T3
Módulo deIdentidade
•Módulo de Controle Principal
Módulo Snubber/
Sobretensão
CTs SCRs
PT
Fan
Áreas mais expostas a danos;
• SCRs
• Módulo de Controle Principal
• Transformadores de Potência