conventional fire sstems contents - sms fire detection …

27
CONVENTIONAL FIRE SYSTEMS 1 CONTENTS FP585 Control Panel 2 ES Detect 4 Vision 2020P 6 Vision 2020PT 8 Vision 2020R 10 Vision 2020F 12 Vision 2020HF 14 Optical Smoke Detectors 16 Heat Detectors 17 Beam Smoke Detectors 18 Manual Call Points 19 Electronic Sounder and Strobe Range 22 Electronic Sounder 24 Bells 25 Door Holders 26 Duct Smoke Detector 27

Upload: others

Post on 08-Jun-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

1

CONTENTS

FP585 Control Panel 2

ES Detect 4

Vision 2020P 6

Vision 2020PT 8

Vision 2020R 10

Vision 2020F 12

Vision 2020HF 14

Optical Smoke Detectors 16

Heat Detectors 17

Beam Smoke Detectors 18

Manual Call Points 19

Electronic Sounder and Strobe Range 22

Electronic Sounder 24

Bells 25

Door Holders 26

Duct Smoke Detector 27

Page 2: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

2

ORDER CODES

2 Zone 75585-02NMB

4 Zone 75585-04NMB

8 Zone 75585-08NMB

Flush Surround 13270-29

8 Zone Repeat Panel 75586-08NMB

2.1Ah 12V SLA Battery 4015-502-Y

2.8Ah 12V SLA Battery 4015-509-Y

FP585 CONTROL PANEL

DIMENSIONS (mm)

395 87

89 89

197

19

274

For flush mounting, aperture size 378mm x 245mm x 60mm

TECHNICAL SPECIFICATION

No. of Zones 2 4 8 *8 Zone Repeat

Maximum Load per Zone 3mA N/A

No. of Sounder Circuits 2 4 8 N/A

Max. Sounder Circuit Load 0.5A per circuit Total load not to exceed 1A N/A

Batteries (not included) 2 x 12V, 2.1 Ah or 2 x 12V, 3.4 Ah2 x 12V, 3.4 Ah

2 x 12V, 2.1 Ah

Battery Standby (Using Batteries specified above)

72 hours plus 0.5 hours alarm load 72 hours

Aux. Relay Contacts 1 N/O and 1 N/C pair, 1A at 24V N/A

Approx Weight (with batteries) 5.8 Kg 6.2 Kg 5.8 Kg

Cable Entry 13 Top and 13 Rear

Cable Type BS 6387, 2 core, min 1.5mm2 CSA

Class Change FacilityVia normally open push button switch located no more than 100m from panel

N/A

Temperature Indoor, 0 - 40ºC

Standards EN54 Parts 2&4

Approvals BSI Approved

The FP585 panel complies fully

with the European standard

EN54 Parts 2 & 4 and can be

used on installations meeting

BS 5839: Part 1.

Each panel contains its own

integral power supply and

battery support for up to eight

alarm sounder circuits, two

auxiliary relay contacts, a zone

disablement facility and a one

man test and commission facility,

all simplifying system design,

installation and commissioning.

Page 3: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

3

FP585 CONTROL PANELSYSTEM ARCHITECTURE

Note: This schematic is for guidance only – please refer to product instructions during installation.

All cables are 2 core unless otherwise stated.

Repeat Panel

Smoke Detector

BeamTransmitter

AlarmSounder

SounderStrobe

AlarmSounder

AlarmSounder

SmokeDetector

HeatDetector

CallPoint

End ofLine

SmokeDetector

CallPoint

SmokeDetector

CallPoint

4 ZoneControl

Panel

SoundersCircuits

1 N/O, 1 N/C relay contactsto auxiliaryequipmentsuch as doorholders ormanned centrelink.

Class Change

DuctDetector

End ofLine

End ofLine

End of Line

BeamReceiver

End ofLine

End ofLine

3 Core Cable

Polarised Relay(to switch 230V equipment

eg. door holders)

24V

Beam Control Unit (24V required)

SounderStrobe

Page 4: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

4

Optical smoke detector:

Optical detector with software support to provide reliable detection and high degree of false

alarm resilience

Heat Detector Range

Range of Heat EN54-5 detectors:

- Rate of rise Type A1 for standard applications

- Fixed Temp Type A1S and high temp (Type BS) for higher ambient temperature applications

GENERAL SPECIFICATION

Operating voltage 8 to 42 V DC

Storage temperature -25 °C to 75 °C

Minimum operating temperature -20°C

Air humidity < 95 %

Type of protection IP43 (with base + option)

Material ABS

Color white, similar to RAL 9010

Weight800171, 800177, 800271 = 74g. 800371 = 110g

Dimensions Ø: 117 mm H: 49 mm (62 mm incl. base)

ES DETECT

Our ES Detect conventional range

offers a comprehensive range

of smoke and heat detectors.

The ES Detect automatic detector

is an non-addressable detector

specifically designed for operation

on conventional systems. The

range not only includes intelligent

algorithms for fire detection but

also a wide range of different

types of detectors.

Key Features

l Microprocessor controlled range of automatic fire detectors

l Software monitoring contamination, maintaining optimum sensitivity throughout the whole life

l Compatible with diode base allowing zone continuity while monitoring for detector removal

Page 5: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

5

ES DETECT

TECHNICAL SPECIFICATION

Type Heat - Fixed Temp Heat - Fixed Temp Type B Rate of Rise Optical smoke

Part number 800171 800177 800271 800371

Minimum reset time 100 m/sec

Alarm current @ 9 V DC typ. 9 mA

Air speed 0 to 25.4 m/s

Quiescent current approx. 25 μA approx. 30 μA

Application temperature

Up to 50 °C up to 65 °C up to 50 °C up to 72 °C

Detector category and approvals

EN 54-5 A1S EN 54-5 BS EN 54-5 A1R EN 54-7

ORDER CODES

Fixed heat detector 800171

Fixed heat detector, class B 800177

Rate-of-rise heat detector 800271

Optical smoke detector 800371

Standard Detector Base 805590

Detector base with diode 805590-D

Remote LED for ES Detect 781814

DIMENSIONS (MM)

Compatibility Statement:

The ES Detect range is only approved to be installed with FP585 Control Panels or with SenTRI via interface units. Refer to Technical Data sheet for details

FP585 Control Panels - 75585-02NMB, 75585-04NMB, 75585-08NMB

117

Z1

Z2

Z3

Z4

62

Page 6: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

6

VISION 2020P

Description

The 2020P Optical Smoke Detector is part of the Vision range of detectors. Vision is a range of

conventional detectors, which have been produced using the latest in manufacturing technology

and supplied with an array of installer-friendly advanced features, making them ideal for all your

conventional fire detection requirements.

The 2020P Optical Smoke Detector uses a state of the art optical chamber combined with an

application specific integrated circuit (ASIC) to provide quick and accurate detection of fires.

A combination of the unique chamber design and other technically advanced features will

significantly extend the service intervals before cleaning of the detector becomes necessary.

A hand held laser tool can also be used in conjunction with the Vision range of detectors for

triggering the Vision detector. With a range of several metres, the hand held unit provides an

effortless way of remotely triggering the Vision detector.

The 2020P Detector has an integral LED, which illuminates to provide a local alarm signal. This

latches on, and remains illuminated until the detector is reset by a momentary power interruption.

An optional remote LED annunciator may be used to repeat any alarm signal.

A variety of detector bases can be used with the 2020P Detector, providing application flexibility

and compatibility with a wide range of conventional fire alarm panels, including our SMS range.

All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and

have a tamper resistant feature, which when activated prevents removal of the detector without

the use of a tool.

Please note: the laser triggering tool does not negate the requirement to test the detector as

specified in BS 5839 Pt 1:2002.

CONVENTIONAL OPTICAL SMOKE DETECTOR

ORDER CODES

Optical Smoke Detector 2020P

Bases

Standard Base – adds 9.5mm to

detector height 2020B

Standard Base with Schottky diode 2020BSD

Deep Base – adds 21mm to

detector height 2020DB

Deep Base with Schottky diode 2020DBSD

Accessories

Laser Triggering Tool 2020LT

PRODUCT OVERVIEW

Features

l Low profile design

l Low current draw

l Automatic drift compensation

l Remote alarm trigger feature

l Easy maintenance

l Range of detector bases available

l Remote LED Option

l Approved to EN54–7:2000 (Amendment 1)

Page 7: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

7

VISION 2020P

NOTES

It is essential to ensure that only known

compatible components are used in a fire

detection system. If in doubt, always consult

the fire control panel supplier/manufacturer.

TECHNICAL SPECIFICATION

ELECTRICAL

Operating Voltage Range 14 to 28VDC (Nominal 24VDC)

Maximum Standby Current @ 25ºC 60μA @ 24VDC

Maximum Alarm Current 70mA @ 28VDC

ENVIRONMENTAL

Application Temperature Range –30ºC to +70ºC

Humidity 5 to 95% Relative Humidity (non-condensing)

MECHANICAL

Height 32.5mm (plus 9.5mm for standard base)

Diameter 102mm

Weight 75g (plus 45g for standard base)

Max Wire Gauge for Terminals 0.4mm2 to 2.0mm2

Colour Approximates RAL9016

Material ABS

Standards EN54 part 7

Approvals LPCB Approved and CE Approved

CONVENTIONAL OPTICAL SMOKE DETECTOR

DIMENSIONS (mm)

42102

Page 8: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

8

VISION 2020PT

Description

The 2020PT Multi-functional Detector is part of the Vision range of detectors. Vision is a range of

conventional detectors, which have been produced using the latest in manufacturing technology

and supplied with an array of installer-friendly advanced features, making them ideal for all your

conventional fire detection requirements.

The 2020PT Multi-functional Detector uses a state of the art optical chamber and heat element

combined with sophisticated algorithms to provide quick and accurate detection of fires. The

combination of optical and heat detection provides a faster response to ‘real fire’ situations, while

at the same time reducing the risk of unwanted environmentally generated alarms.

A hand held laser tool can also be used in conjunction with the Vision range of detectors for

triggering the Vision detector. With a range of several metres, the hand held unit provides an

effortless way of remotely triggering the Vision detector.

The 2020PT Detector also has an integral LED, which illuminates to provide a local alarm signal.

This latches on, and remains illuminated until the detector is reset by a momentary power

interruption. An optional remote LED annunciator may be used to repeat any alarm signal.

A variety of detector bases can be used with the Vision Detector, providing application flexibility

and compatibility with a wide range of conventional fire alarm panels, including our SMS range.

All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and

have a tamper resistant feature, which when activated prevents removal of the detector without

the use of a tool.

Please note: the laser triggering tool does not negate the requirement to test the detector as

specified in BS 5839 Pt 1:2002.

OPTICAL HEAT DETECTOR

ORDER CODES

Optical Heat Detector 2020PT

Bases

Standard Base – adds 9.5mm to

detector height 2020B

Standard Base with Schottky diode 2020BSD

Deep Base – adds 21mm to

detector height 2020DB

Deep Base with Schottky diode 2020DBSD

Accessories

Laser Triggering Tool 2020LT

PRODUCT OVERVIEW

Featuresl Low profile designl Low current drawl Automatic drift

compensationl Remote alarm trigger featurel Easy maintenancel Range of detector bases

availablel Remote LED Optionl Approved to EN54 – 7:2000

(Amendment 1)l EN54 – 5:2000 (Amendment

1) Class A1R; CEA 4021

Page 9: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

9

VISION 2020PT

NOTES

1. To avoid unwanted alarm conditions being

triggered by class A1R detectors, the maximum

ambient operating temperature should not

exceed 45ºC.

2. It is essential to ensure that only known

compatible components are used in a fire

detection system. If in doubt, always consult

the fire control panel supplier/manufacturer.

TECHNICAL SPECIFICATION

ELECTRICAL

Operating Voltage Range 14 to 28VDC (Nominal 24VDC)

Maximum Standby Current @ 25ºC 75μA @ 24VDC

Maximum Alarm Current 70mA @ 28VDC

ENVIRONMENTAL

Application Temperature Range (see note 1) –30ºC to +70ºC

Humidity 5 to 95% Relative Humidity (non-condensing)

MECHANICAL

Height 40.5mm (plus 9.5mm for standard base)

Diameter 102mm

Weight 78g (plus 45g for standard base)

Max Wire Gauge for Terminals 0.4mm2 to 2.00mm2

Colour Approximates RAL9016

Material ABS

Standards EN54 Part 7 and EN54 Part 5

Approvals LPCB Approved and CE Approved

OPTICAL HEAT DETECTOR

DIMENSIONS (mm)

50102

Page 10: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

10

VISION 2020R

Description

The 2020R Rate of Rise Heat Detector is part of the Vision range of detectors. Vision is a range of

conventional detectors, which have been produced using the latest in manufacturing technology

and supplied with an array of installer-friendly advanced features, making them ideal for all your

conventional fire detection requirements.

The 2020R Heat Detector uses a state of the art heat element combined with an application

specific integrated circuit (ASIC) to provide quick and accurate detection of fires. The detector

incorporates both rate of rise and static elements and is suitable for all areas where the ambient

conditions do not normally exhibit rapid changes in temperature.

A hand held laser tool can also be used in conjunction with the Vision range of detectors for

triggering the Vision detector. With a range of several metres, the hand held unit provides an

effortless way of remotely triggering the Vision detector.

The 2020R Detector also has an integral LED, which illuminates to provide a local alarm signal.

This latches on, and remains illuminated until the detector is reset by a momentary power

interruption. An optional remote LED annunciator may be used to repeat any alarm signal.

A variety of detector bases can be used with the 2020R Detector, providing application flexibility

and compatibility with a wide range of conventional fire alarm panels, including our SMS range.

All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and

have a tamper resistant feature, which when activated prevents removal of the detector without

the use of a tool.

Please note: the laser triggering tool does not negate the requirement to test the detector as

specified in BS 5839 Pt 1:2002.

RATE OF RISE HEAT DETECTOR

ORDER CODES

Rate of Rise Detector 2020R

Bases

Standard Base – adds 9.5mm to

detector height 2020B

Standard Base with Schottky diode 2020BSD

Deep Base – adds 21mm to

detector height 2020DB

Deep Base with Schottky diode 2020DBSD

Accessories

Laser Triggering Tool 2020LT

PRODUCT OVERVIEW

Features

l Low profile design

l Low current draw

l Remote alarm trigger feature

l Easy maintenance

l Range of detector bases available

l Remote LED Option

l Approved to EN54 – 5:2000 (Amendment 1) Class A1R

Page 11: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

11

VISION 2020R

NOTES

1. To avoid unwanted alarm conditions being

triggered by class A1R detectors, the maximum

ambient operating temperature should not

exceed 45ºC.

2. It is essential to ensure that only known

compatible components are used in a fire

detection system. If in doubt, always consult

the fire control panel supplier/manufacturer.

TECHNICAL SPECIFICATION

ELECTRICAL

Operating Voltage Range 14 to 28VDC (Nominal 24VDC)

Maximum Standby Current @ 25ºC 70μA @ 24VDC

Maximum Alarm Current 70mA @ 28VDC

ENVIRONMENTAL

Application Temperature Range (see note 1) –30ºC to +70ºC

Humidity 5 to 95% Relative Humidity (non-condensing)

MECHANICAL

Height 40.5mm (plus 9.5mm for standard base)

Diameter 102mm

Weight 70g (plus 45g for standard base)

Max Wire Gauge for Terminals 0.4mm2 to 2.0mm2

Colour Approximates RAL9016

Material ABS

Standards EN54 Part 5

Approvals LPCB Approved and CE Approved

RATE OF RISE HEAT DETECTOR

DIMENSIONS (mm)

102 50

Page 12: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

12

VISION 2020F

Description

The 2020F 58ºC Fixed Temperature Heat Detector is part of the Vision range of detectors. Vision

is a range of conventional detectors, which have been produced using the latest in manufacturing

technology and supplied with an array of installer-friendly advanced features, making them ideal

for all your conventional fire detection requirements.

The 2020F 58ºC Fixed Temperature Heat Detector uses a state of the art heat element combined

with an application specific integrated circuit (ASIC) to provide quick and accurate detection

of fires. The detector incorporates a static element and is suitable where ambient conditions

normally exhibit rapid changes in temperature e.g. kitchens.

A hand held laser tool can also be used in conjunction with the Vision range of detectors for

triggering the Vision detector. With a range of several metres, the hand held unit provides an

effortless way of remotely triggering the Vision detector.

The 2020F Detector also has an integral LED, which illuminates to provide a local alarm

signal. This latches on, and remains illuminated until the detector is reset by a momentary

power interruption. An optional remote LED annunciator may be used to repeat any

alarm signal.

A variety of detector bases can be used with the 2020F Detector, providing application flexibility

and compatibility with a wide range of conventional fire alarm panels, including our SMS range.

All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and

have a tamper resistant feature, which when activated prevents removal of the detector without

the use of a tool.

Please note: the laser triggering tool does not negate the requirement to test the detector as

specified in BS 5839 Pt 1:2002.

58ºC FIXED TEMPERATURE HEAT DETECTOR

ORDER CODES

58º Fixed Temperature

Heat Detector 2020F

Bases

Standard Base – adds 9.5mm to

detector height 2020B

Deep Base – adds 21mm to

detector height 2020DB

Standard Base with Schottky diode 2020BSD

Deep Base with Schottky diode 2020DBSD

Accessories

Laser Triggering Tool 2020LT

PRODUCT OVERVIEW

Features

l Low profile design

l Low current draw

l Easy maintenance

l Range of detector bases available

l Remote LED Option

l Approved to EN54 – 5:2000 (Amendment 1) Class A2S

l Remote alarm trigger feature

Page 13: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

13

VISION 2020F

NOTES

1. To avoid unwanted alarm conditions being

triggered by class A2S detectors the maximum

ambient operating temperature should not

exceed 45ºC.

2. It is essential to ensure that only known

compatible components are used in a fire

detection system. If in doubt, always consult

the fire control panel supplier/manufacturer.

TECHNICAL SPECIFICATION

ELECTRICAL

Operating Voltage Range 14 to 28VDC (Nominal 24VDC)

Maximum Standby Current @ 25ºC 70μA @ 24VDC

Maximum Alarm Current 70mA @ 28VDC

ENVIRONMENTAL

Application Temperature Range (see note 1) -30ºC to +70ºC

Humidity 5 to 95% Relative Humidity (non-condensing)

MECHANICAL

Height 40.5mm (plus 9.5mm for standard base)

Diameter 102mm

Weight 70g (plus 45g for standard base)

Max Wire Gauge for Terminals 0.4mm² to 2.0mm2

Colour Approximates RAL9016

Material ABS

Standards EN54 part 5

Approvals LPCB Approved and CE Approved

58ºC FIXED TEMPERATURE HEAT DETECTOR

DIMENSIONS (mm)

102 50

Page 14: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

14

VISION 2020HF

Description

The 2020HF 78ºC Fixed Temperature Heat Detector is part of the Vision range of detectors. Vision

is a range of conventional detectors, which have been produced using the latest in manufacturing

technology and supplied with an array of installer-friendly advanced features, making them ideal

for all your conventional fire detection requirements.

The 2020HF 78ºC Fixed Temperature Heat Detector uses a state of the art heat element combined

with an application specific integrated circuit (ASIC) to provide quick and accurate detection

of fires. The detector incorporates a static element and is suitable where ambient conditions

normally exhibit rapid changes in temperature above 45ºC e.g. boiler houses.

A hand held laser tool can also be used in conjunction with the Vision range of detectors for

triggering the Vision detector. With a range of several metres, the hand held unit provides an

effortless way of remotely triggering the Vision Detector.

The 2020HF Detector also has an integral LED, which illuminates to provide a local alarm signal.

This latches on, and remains illuminated until the detector is reset by a momentary power

interruption. An optional remote LED annunciator may be used to repeat any alarm signal.

A variety of detector bases can be used with the 2020HF Detector, providing application flexibility

and compatibility with a wide range of conventional fire alarm panels, including our SMS range.

All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and

have a tamper resistant feature, which when activated prevents removal of the detector without

the use of a tool.

Please note: the laser triggering tool does not negate the requirement to test the detector as

specified in BS 5839 Pt 1:2002.

78ºC FIXED TEMPERATURE HEAT DETECTOR

ORDER CODES

78º Fixed Temperature

Heat Detector 2020HF

Bases

Standard Base – adds 9.5mm to

detector height 2020B

Standard base with Schottky diode 2020BSD

Deep Base – adds 21mm to

detector height 2020DB

Deep Base with Schottky diode 2020DBSD

Accessories

Laser Triggering Tool 2020LT

PRODUCT OVERVIEW

Features

l Low profile design

l Low current draw

l Easy maintenance

l Range of detector bases available

l Remote LED Option

l Approved to EN54 – 5:2000 (Amendment 1) Class BS

l Remote alarm trigger feature

Page 15: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

15

VISION 2020HF

NOTES

1. To avoid unwanted alarm conditions being

triggered by class BS detectors the maximum

ambient operating temperature should not

exceed 65ºC.

2. It is essential to ensure that only known

compatible components are used in a fire

detection system. If in doubt, always consult

the fire control panel supplier/manufacturer.

TECHNICAL SPECIFICATION

ELECTRICAL

Operating Voltage Range 14 to 28VDC (Nominal 24VDC)

Maximum Standby Current @ 25ºC 75μA @ 24VDC

Maximum Alarm Current 70mA @ 28VDC

ENVIRONMENTAL

Application Temperature Range (see note 1) –30ºC to +70ºC

Humidity 5 to 95% Relative Humidity (non-condensing)

MECHANICAL

Height 40.5mm (plus 9.5mm for standard base)

Diameter 102mm

Weight 70g (plus 45g for standard base)

Max Wire Gauge for Terminals 0.4mm² to 2.0mm2

Colour Approximates RAL9016

Material ABS

Standards EN54 Part 5

Approvals LPCB Approved and CE Approved

78ºC FIXED TEMPERATURE HEAT DETECTOR

DIMENSIONS (mm)

102 50

Page 16: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

16

ORDER CODES

Optical Smoke Detector 72441-25NM

Low profile base 17800-02

Low profile base

with diode 17801-02

Base less diode 17800-01

(surface cabling)

Base with diode 17801-01

(surface cabling)

Remote LED Module 72499-24NM

Repeat Relay 17899-44

OPTICAL SMOKE DETECTORS

DIMENSIONS (mm)

104

1046 73

wit

h b

ase

TECHNICAL SPECIFICATION

Operating Voltage Range 8 - 28V dc

Quiescent Current 60μA @ 28V

Alarm Current 26mA - 34mA

Ambient Temperature 0oc to +50oc

Colour White (comparable to RAL9010)

Ingress Protection IP30

Approx. Weight 0.11 Kg

Operating Temperature -10ºC to +50ºC

Standards EN54 Part 7

Approvals LPCB Approved

SPECIAL FEATURE

The use of the Diode Base

allows monitoring of a

removed detector to comply

with BS 5839.

N.B. Maximum of 20 per zone.

Possibly the earliest form of

smoke detection, optical smoke

detectors are ideal at detecting

visually smoky fires which are

likely to be slow, smouldering

fires.

ABS casing with red LED fire

indicator.

Page 17: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

17

DIMENSIONS (mm)

ORDER CODES

Fixed Temperature 72451-25NM

Rate of Rise 72461-25NM

High Fixed Temperature 72470-25NM

Low profile base 17800-02

Low profile base

with diode 17801-02

Base less diode 17800-01

(surface cabling)

Base with diode 17801-01

(surface cabling)

Remote LED Module 72499-24NM

Repeat Relay 17899-44

HEAT DETECTORS

TECHNICAL SPECIFICATION

Fixed Temp. Rate of Rise High Fixed Temp.

Operating Voltage Range 8-28V dc

Quiescent Current 30μA @28V dc

Ingress Protection IP30

Approx. Weight 0.07 Kg

Operating Temperature 0ºC to +85ºC

Trigger Temperature 58ºCNA (Factory preset 58ºC)

85ºC

Sensitivity Grade 1 Grade 2

Standards EN54 Part 5

Approvals LPCB Approved

97

1044

Heat detectors operate when a certain temperature is reached and are better suited to smokey, dusty or steamy environments than smoke detectors.

High fixed temperature devices are advised for kitchens or boiler rooms. Standard fixed temperature devices are suitable for areas where the temperature fluctuates for natural reasons or due to certain industrial processes.

ABS casing with red LED fire indicator.

Page 18: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

18

BEAM SMOKE DETECTORS

ORDER CODES

Transmitter / Receiver Beam pair 07011-41

Combined Reflective Beam 07011-40

(includes 1x Detector Head

Assembly, 4x prisms, 1x Test filter,

1x cable Interface)

Power Supply 05214-24-EN

TECHNICAL SPECIFICATION

Transmitter / Receiver Beam Pair

Combined Reflective Beam

Operating Voltage Range 11.5V dc to 28V dc 10.2V dc to 30V dc

Quiescent Current @ 24VdcReceiver and Controller <8mA <4mA

Transmitter: - 5.6mA

Alarm Current @24V: Controller and Receiver <16.5mA <15mA

Approx WeightControl Unit: 1.8KgTransmitter + Receiver inc. brackets: 650 gms.

0.67 Kg

IP Rating IP50

Ambient Temperature -10oC to 50oC -30oC to 55oC

Beam Length 10m - 100m 50m - 100m

Standards EN54 Part 12

DIMENSIONS (mm)

DIMENSIONS (mm)

65 101

140

210

210

85

100 9.5

260

9512

0

126 10

0

Transmitter / Receiver Beam Smoke Detector

Combined Reflective Beam

Prisms

Optical beam smoke detectors

are ideally suited for large open

areas such as warehouses, atria,

leisure centres and shopping

centres where the installation

of single point detectors may be

difficult and uneconomical.

These are also perfect for

applications such as churches

and museums that require an

unobtrusive fire safety system.

Beam detectors can be installed

with separate transmitter and

receiver or combined transceiver

unit and reflector.

Features:

l Low current consumption

l Automatic self check drift compensation

l Selectable sensitivity/threshold levels

l Small, unobtrusive detectors allow for a discreet installation.

Note: An additional 24V dc

power supply is required.

Page 19: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

19

ORDER CODES

Surface Mounted c/w back box

EN54 version 71150-52NMA-EN

Surface Mounted with cover and

back box EN54 version 71150-55NMA-EN

Key Operated, Surface Mounted

c/w back box 14115-08

Flush Mounted Call Point 71150-51NMA

Red Surface Mounted for NO

and NC connections 71150-62NM

MCP Square Glasses with ref to

EN54 Pt 11 (pack 10) 71150-90NM-EN

MCP Square Glasses without

ref to standards (pack 10) 71150-91NM

MCP Square Glasses branded

Senator II (pack 10) 78150-91NM

Plastic Test Keys (pack 10) 71150-92NM

MCP Surface Weather

Resistant Kit 71150-93NM

MCP Semi Flush Spacer 14112-20

MCP Semi-Flush Kit, current

range onto 1102 box 14112-29

MCP Flush Fixing Plate 19289-01

Round Glasses (1102 range)

(pack 10) 14111-99

MANUAL CALL POINTS

DIMENSIONS (mm)

TECHNICAL SPECIFICATION

Nominal Voltage 24V dc

Ingress Protection IP54 with gasket

Approx. Weight 0.15 Kg

Operating Temperature 0ºC to 50ºC

Standards EN54 Part 11

87

87

55 20

Surface Flush

Accessories & Spares

Key Operated Call Point – Preventing unauthorised operation for use in areas with a high risk

of tampering or vandalism.

Test Keys – For testing call points without breaking the glass.

Weather Resistant Kit – Allowing a call point to be used externally, providing weather resistance

to IP54.

Semi-flush Spacing Kit – For part recessing call points.

NB: this range will be discontinued from 31st December 2012.

Manual call points are

manufactured from ABS with

plastic covered push break glasses

for safe and simple operation.

No hammer is required.

A polycarbonate cover version

is available for applications

susceptible to inadvertent

operation, such as sports halls.

Note: All manual call points can

be flush mounted by using a

flush fixing plate.

Page 20: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

20

ORDER CODES

Flush Call Point with

470 Ohm resistor and

NO contact c/w glass MCP1A-R470FG -01

Surface Outdoor Call Point with

470 Ohm resistor and

NO contact c/w glass WCP1A-R470SG-01

Key Operated Surface Mounted WR9102

Surface call point with

470ohm resistor and

NO Contact

c/w resettable element MCP1A-R470SF-01

Surface call point c/o

comes with

glass element MCP3A-R000SG-01

Spare Glasses for MCP1A and

WCP1A (Pack of 10) XENS-891

Resettable element for

MCP1A (pack of 10) XENS-890

Hinged protective cover

(pack of 10) XENS-892

Surface Backbox for MCP1A

range of MCP (pack of 10) XENS-895

Pack of test keys (pack of 10)

for use with MCP1A and

WCP1A range XENS-899

MANUAL CALL POINTS

The Manual Call Points from SMS are both with a 470 Ohm resistor and Normally Open contact,

complete with glass. Available in semi-flush mounting or surface mounting options. The Call

Points are designed to provide a manual alarm interface to non addressable fire alarm control

panels. Both call points are supplied in the standard red colour.

Installation time is significantly reduced by the two part connector located at the back of the

device.

Both break glass, supplied, and resettable operating elements can be used in the standard unit

by a yellow strip on the element which becomes visible when activated. With the addition of a

hinged transparent cover the element may be protected against accidental operation. A specialist

test key may be inserted into the bottom of the unit to lower the glass and release the micro-

switch and thus a full functional test is achieved.

l Certified to EN54, Part 11

l Re-settable operating element option

l Resistive and clean contact connections

l Semi-flush or surface mounting

l Backward compatibility

Page 21: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

21

TECHNICAL SPECIFICATION – SURFACE MOUNTED WATERPROOF MANUAL CALL POINT

Operating Voltage 30V dc maximum

Current Rating 2A (switching only)

Ingress Protection IP67

Approx. Weight 0.24 Kg

Operating Temperature -30ºC to 70ºC

Relevant Humidity Up to 95% non-condensing

Standards Certified to EN54 Part 11

TECHNICAL SPECIFICATION – FLUSH MOUNTED MANUAL CALL POINT AND SURFACE RESETTABLE CALL POINT

Operating Voltage 30V dc maximum

Current Rating 2A (switching only)

Ingress Protection IP24D

Approx. Weight 0.11 - 0.16 Kg

Operating Temperature -10ºC to 55ºC

Relevant Humidity 93± 3% non-condensing

Standards Certified to EN54 Part 11

MANUAL CALL POINTS

DIMENSIONS (mm)

89

93

27.5 32

DIMENSIONS (mm)

93

97.5 71

Page 22: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

22

ORDER CODES

IP55 Electronic Sounder

red (100 dBA) CONV-IP-SN-R

IP31 Electronic Sounder

red (100 dBA) CONV-SN-R

IP55 Electronic Sounder Strobe

red body, red lens 100 dBA* CONV-SN-ST-RR

IP55 Ultra low current Strobe

red body, red lens* CONV-IP-ST-RR

IP55 Voice Enhanced Electronic

Sounder red (100 dBA) CONV-IP-VP-R

IP55 Voice Enhanced Electronic

Sounder and Strobe red body

red lens (100 dBA)* CONV-IP-VP-ST-RR

ELECTRONIC SOUNDER AND

The Electronic Sounder and Strobe range incorporates sound, speech and strobe effects all in one

range of alarm devices. The range offers all variants in the choice of 2 colours, red or white, with

either a shallow base version sealed to IP31 or a deep base version sealed to IP55. All the low

profile sounders have the option of an integral strobe.

STROBE RANGE

TECHNICAL SPECIFICATION

Sounder Sounder/Strobe Strobe Only

Sound Output at 1m See Tone Table See Tone Table N/A

Strobe Flash Rate See Tone Table See Tone Table Variable

Strobe Output N/AEquivalent to a 3W Xenon flasher

Equivalent to a 3W Xenon flasher

Average Current See Tone Table See Tone Table 6 mA

Operating Voltage Range 10.8V – 28.8V 10.8V – 28.8V 10.8V – 28.8V

Maximum Reverse Monitoring Voltage

30V/20μA 30V/20μA <20μA @30V

Ingress Protection IP55 with the Deep Base, IP31 with the Shallow Base

Approx Weight 0.3Kg 0.3Kg 0.3Kg

Operating Temperature -10ºC to 50ºC -10ºC to 50ºC -10ºC to 50ºC

Standards (Sounder only) EN54 Part 3 EN54 Part 3 N/A

Approvals LPCB Approved (CONV-IP-SN-R. CONV-SN-R. CONV-SN-ST-RR only)

See overleaf for Tone Table.* This product is not a visual alarm device and does not meet EN 54-23

l Very low power consumption means more sounders and strobes per circuit

l The strobe option is equivalent to a standard 3W xenon beacon and uses 1/20th of the power

l 4 Voice phrases and bell sound are available as standard

l 32 sounder tones are available

l Sounders are compatible with 12V and 24V systems

l A third wire option allows the selection of 2 alternative sounds. Ideal for class change applications

l Combined sounder strobe reduces installation costs

Page 23: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

23

The current data in the table is for Red strobe only.

Note also the nominal sound frequencies stated in the table are based on the resonance frequency of the transducer.

ELECTRONIC SOUNDER AND STROBE RANGE

TONE TABLE FOR SOUNDER ONLY AND SOUNDER / STROBE VARIANTS12V 24V

dB(A) @1m

Operating Current dB(A) @1m

Operating Current

Signal 1 Strobe Description SW1 Switch Graphical representation

With Strobe mA

Without Strobe mA

With Strobe mA

Without Strobe mA Signal 2 Strobe Signal 3 Strobe

Tone 1 1Hz Alternating tone 800/ 970Hz @ 2Hz - FP 1063.1 Telecoms BS 5839: Part 1 6 5 4 3 2 1

ON

101.8 16.5 7.4 101.8 9.5 3.4 Tone 3 0.5Hz Tone 6 1Hz

Tone 2 1Hz Alternating tone 800/ 970Hz @ 1Hz - BS 5839: Part 1 6 5 4 3 2 1

ON

101.7 16.5 7.3 101.7 9.5 3.4 Tone 3 0.5Hz Tone 6 1Hz

Tone 3 1Hz Intermittent tone 970Hz @ 1Hz LF back up alarm - BS 5839: Part 1 6 5 4 3 2 1

ON

101.6 15.5 4.5 101.6 8.2 2.0 Tone 5 0.8Hz Tone 6 1Hz

Tone 4 1Hz Intermittent tone 2850Hz @ 1Hz HF back up alarm - 2nd tone BS 5839: Part 1

6 5 4 3 2 1 ON

103.7 15.8 5.5 103.7 8.5 2.5 Tone 3 0.5Hz Tone 6 1Hz

Tone 5 0.8Hz Intermittent tone 970Hz 0.25s - on, 1s off - BS 5839: Part 1 6 5 4 3 2 1

ON

101.2 12.0 2.0 101.4 6.0 1.0 Tone 2 0.5Hz Tone 6 1Hz

Tone 6 1Hz Continuous @ 970Hz - BS 5839: Part 1 6 5 4 3 2 1 ON

102.0 16.5 8.0 102.1 9.8 3.7 Tone 3 0.5Hz Tone 1 1Hz

Tone 7 0.5Hz Slow sweep 300Hz- 1200Hz over 2s - Vds2300 Signal 6 5 4 3 2 1

ON

99.3 13.0 7.9 99.3 7.0 3.7 Tone 3 0.5Hz Tone 6 1Hz

Tone 8 1Hz Fast sweep 800Hz - 970Hz @ 7Hz - BS 5839: Part 1 6 5 4 3 2 1

ON

93.5 16.3 8.2 93.7 9.4 3.7 Tone 3 0.5Hz Tone 6 1Hz

Tone 9 1Hz Medium sweep 800Hz - 970Hz @ 1Hz - BS 5839: Part 1 6 5 4 3 2 1

ON

94.1 16.5 8.7 94.3 9.5 4.0 Tone 3 0.5Hz Tone 6 1Hz

Tone 10 1Hz Continuous @ 2850Hz 6 5 4 3 2 1 ON

104.4 16.5 9.7 104.7 10.2 4.4 Tone 3 0.5Hz Tone 6 1Hz

Tone 11 1Hz Sweep 2400 - 2850Hz @ 7Hz 6 5 4 3 2 1 ON

100.2 16.5 11.2 100.8 10.6 5.4 Tone 12 0.5Hz Tone 10 1Hz

Tone 12 1Hz Sweep 2400 - 2850Hz @ 1Hz 6 5 4 3 2 1 ON

101.9 16.5 12.0 102.7 11.5 5.8 Tone 3 0.5Hz Tone 10 1Hz

Tone 13 0.86Hz Slow whoop 500Hz - 1200Hz over 3s with 0.5s off 6 5 4 3 2 1

ON

98.8 15.5 7.5 99.2 8.7 3.5 Tone 3 0.5Hz Tone 6 1Hz

Tone 14 1Hz Sweep 1200Hz @ 1200Hz - 500Hz @ 1Hz with 10ms silence - German DIN tone evacuate

6 5 4 3 2 1 ON

96.6 16.2 7.3 98.1 9.5 3.5 Tone 3 0.5Hz Tone 6 1Hz

Tone 15 1Hz Alternating tone 2400/ 2850Hz @ 2Hz 6 5 4 3 2 1 ON

101.7 16.5 12.0 102.5 11.8 6.2 Tone 12 0.5Hz Tone 10 1Hz

Tone 16 1Hz Alternating tone 554Hz for 100mS then 440Hz for 400ms - French AFNOR tone 6 5 4 3 2 1

ON

89.3 15.8 5.2 89.6 8.7 2.5 Tone 3 0.5Hz Tone 6 1Hz

Tone 17 1Hz Alternating tone 440Hz / 554Hz @ 2Hz - Turn out Sweden 6 5 4 3 2 1

ON

90.1 15.8 5.7 90.3 8.9 2.8 Tone 19 0.5Hz Tone 18 1Hz

Tone 18 1Hz Continuous 700Hz - All clear Sweden 6 5 4 3 2 1 ON

95.9 16.2 7.0 96.3 9.8 3.3 Tone 1 0.5Hz Tone 3 1Hz

Tone 19 1Hz

6s - On 12s - Off

Intermittent tone 700Hz 6s On 12s Off - Pre- vital message Sweden 6 5 4 3 2 1

ON

95.9 6.1 4.0 96.3 5.0 2.3 Tone 17 0.5Hz Tone 18 1Hz

Tone 20 1Hz Intermittent tone 1000Hz @ 1Hz - Local warning Sweden 6 5 4 3 2 1

ON

100.6 15.5 5.8 101.0 8.5 2.7 Tone 17 0.5Hz Tone 25 1Hz

Tone 21 1Hz Rising 1s, constant 4s, fall 1s @ 1000Hz - Industrial alarm Germany 6 5 4 3 2 1

ON

100.9 16.0 10.0 101.2 10.0 4.0 Tone 3 0.5Hz Tone 6 1Hz

Tone 22 1Hz

4s - On 4s - Off

Intermittent tone 700Hz 4s On , 4s Off - Industrial alarm Germany 6 5 4 3 2 1

ON

101.4 8.7 5.7 101.9 6.4 3.0 Tone 19 0.5Hz 6s - On 12s - Off Tone 6 1Hz

Tone 23 Sync. pulses

Emergency evacuation to ISO 8201 - ISO 8201 Tone 6 5 4 3 2 1

ON

104.0 12.0 4.0 104.5 6.0 1.5 Tone 3 0.5Hz Tone 6 1Hz

Tone 24 1Hz Slow whoop 500Hz - 1000Hz over 4.5s - Evacuate Netherlands 6 5 4 3 2 1

ON

99.6 16.0 7.2 100.2 9.5 3.4 Tone 3 0.5Hz Tone 6 1Hz

Tone 25 1Hz Siren (ramp up from 500Hz - 1200Hz in 3s then ramp down 1200Hz - 500Hz in 3s)

6 5 4 3 2 1 ON

98.2 16.0 7.5 98.5 9.5 3.5 Tone 3 0.5Hz Tone 6 1Hz

Tone 26 1Hz Fast whoop 500Hz - 1000Hz @ 7Hz 6 5 4 3 2 1 ON

95.8 15.8 7.0 96.0 8.7 3.3 Tone 24 0.5Hz Tone 25 1Hz

Tone 27 Sync. pulses US temporal tone LF

6 5 4 3 2 1 ON

100.6 12.0 3.0 100.6 5.5 1.0 Tone 3 0.5Hz Tone 6 1Hz

Tone 28 Sync. pulses US temporal tone HF

6 5 4 3 2 1 ON

99.0 11.8 2.5 99.0 5.3 0.8 Tone 4 0.5Hz Tone 6 1Hz

Tone 29 1Hz LF buzz 800Hz- 970Hz @ 50Hz 6 5 4 3 2 1 ON

98.8 16.3 9.4 99.2 10.0 4.3 Tone 3 0.5Hz Tone 6 1Hz

Tone 30 1Hz Alternate 2500/ 3100 @ 2Hz - Security alarm 6 5 4 3 2 1

ON

101.6 16.5 13.0 102.2 10.8 6.4 Tone 3 0.5Hz Tone 31 1Hz

Tone 31 1Hz Alternate 2500 / 3100 @ 4Hz 6 5 4 3 2 1 ON

101.2 16.5 13.0 102.0 10.8 6.4 Tone 3 0.5Hz Tone 8 1Hz

Tone 32 1Hz Define during manufacture - default is a fast siren 6 5 4 3 2 1

ON

98.8 16.0 7.5 99.2 9.5 3.5 Tone 3 0.5Hz Tone 6 1Hz

Page 24: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

24

ELECTRONIC SOUNDER

TECHNICAL SPECIFICATION

Shallow Base

Deep Base BedheadSounder Base

IP Rating IP54 IP65 IP54

Approximate Weight 0.24kg 0.26kg 0.11kg 0.15kg

Operation Continuous

Operating Voltage Range 9-28V d.c.

Typical Sound Output @ 1m, 12V d.c. 93dBA 94dBA 87dBA

Typical Sound Output @ 1m, 24V d.c. 100dBA 97dBA 93dBA

Current Consumption 8mA @ 12V, 18mA @24V

Ambient Temperature -25ºC to +70ºC

ORDER CODES

Multitone Low Profile Sounder,

red with shallow base 74451-24NM

Multitone Low Profile Sounder,

red with deep base 74452-24NM

Sounder Base, white 3 tone 74456-24NM

Sounder Base Cover Plate 74456-61NM

Bedhead Sounder 74455-24NM

SPECIAL FEATURE

These sounders are useful for

small rooms such as Halls of

Residences. They may be used

with a detector which reduces

the number of fixing points or

as a standalone sounder with a

cover plate.

DIMENSIONS (mm)

30

42

10573

86

Bedhead Sounder

Shallow Base

Sounder Base

112

Deep Base93

A versatile 24V electronic

sounder for use in a wide range

of applications.

Sound signals may be set in

3 ways; continuous,

intermittent or warble.

Page 25: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

25

ORDER CODES

Electronic Solenoid Bell 24V DC,

Red IP21 74430-88NM

Electronic Solenoid Bell 24V DC,

Red Weather Resistant IP44 74432-88NM

Electronic Solenoid Bell 230V AC,

Grey Weather Resistant IP44 74333-50NM

Electronic Solenoid Bell 12V DC,

Grey IP21 74431-66NM

TECHNICAL SPECIFICATION

Voltage 12 Vdc 24 Vdc 230 Vdc

Current12 Vdc 55 - 65mA24 Vdc 25 - 35mA

230 Vdc 20 - 30mA

Sound Output 93 - 95dB(A)

Monitoring Reverse polarity (dc only)

Protection IP44C ( Weather Resistant Option )

Construction Gong - steel, base - polycarbonate

Weight12 Volt 1.1KG24 Volt 1.1KG230 Volt 1.2KG

ColoursGong - Red or Grey

Base - Black

DIMENSIONS (mm)

155 85

155

130

BELLS

An electronic bell for a wide

range of uses. Metal casing

available in red or grey finish.

Suitable for semi flush or surface

mounting.

SMS offers an electronic bell for

a wide range of applications.

The combination of a miniature

solenoid with an integrated

control circuit allows excellent

sound coverage, minimum

current consumption and

increased reliability. The

improved aesthetics make the

bell suitable for all applications

including the most prestigious

locations.

FEATURES

l Modern design l Clip together assembly l Weatherproof kit option l High “ring” output

BENEFITS

l Suitable for all locations l Easy to fit l Provides protection up

to IP44C With Weather Resistant Option

l Easily identified signal

Page 26: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

26

DIMENSIONS (mm)

DOOR HOLDERS

Wall mountedFloor mounted Keeper plates

96

38.5

51

87

46

4 no. holes ø 5.0 on 54.0 PCD

Manual release button

51 95

45º

110

70

ø 20Cable Entry

80

TECHNICAL SPECIFICATION

Floor Mounted Wall Mounted

Voltage 24V dc 24V dc 230V ac

Approx Weight 700g 360g

Current Consumption 45mA 50mA 12mA

Ambient Temperature 0oC to 35oC 0oC to 40oC

Holding Force 200N

Residual Holding Force Zero

Finish White painted housing, zinc plated magnet White Fire Resistant ABS

Standards NA EN1155 :1997 (CPD Approved)

FEATURES

l Low profi le design l 200N holding force l Easy cable entry & exit l A.C. or D.C. options l Push button release/test l Floor mounting bracket

available l Anti-residual magnetism

feature l D.C. version polorised and

suppressed feature

ORDER CODES

Wall Mounted Door Holder

24V dc 04390-31

Wall Mounted Door Holder

230V ac 04390-55

Floor Mounted Door Holder

04390-41

Floor Bracket; fixing door holder

at right angle to floor 04390-92

Door Keeper Plate; metal keeper

plate in two pieces 04390-99

Door Holder Transformer Rectifier Power

Supply 2amp 24vdc HLS-PSU-TR20

Door Holder Transformer Rectifier Power

Supply 4amp 24vdc HLS-PSU-TR40

To close fire doors in an

emergency and prevent the

spread of fire and smoke.

Moulded ABS and steel

enclosure capable of floor or

wall mounting.

Complies with BS 5839-3.

Page 27: CONVENTIONAL FIRE SSTEMS CONTENTS - SMS Fire Detection …

C O N V E N T I O N A L F I R E S Y S T E M S

27

ORDER CODES

Duct Detector

Includes Venturi tube and

Duct Kit Mounting 17815-01

Remote Relay Module 17899-44

Optical Smoke Detector 72441-25

DUCT SMOKE DETECTOR

The Duct Detector kit is comprised of a conventional detector and duct detector housing. The

Duct Detector is mounted on the outside of the air duct. A venturi tube protrudes into the duct

and draws a sample of the air which passes over the sensor and returns back into the duct. When

the smoke density in the sampled air reaches the trigger level of the smoke detector an alarm will

be signalled on the fire alarm control panel.

TECHNICAL SPECIFICATION

Ingress Protection IP54

Operating Temperature -10oC to +60oC

Approx Weight 0.7Kg

Finish ABS plastic (Grey)

Air Velocity 1M/S to 20M/S

Quiescent Current 90μA

DIMENSIONS (mm)

300 120

110