SAMSON AG · MESS- UND REGELTECHNIK · Weismüllerstraße 3 · 6031 4 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 · E-mail: [email protected] · Internet: www.samson.de Table of contents 9. Control valve actuators 9.1 General ............................................................................................................. .001 9.1.1. Actuator types .............................................................................................001 9. 1.2. Symbols and u nits for the calculation of Actuators ...................................... 002 9.2 Pneumatic actuator with a linear or rotational movement ............................ 005 9.2.1. Pneumatic diaphragm actuator ...................................................................005 9.2.1.1 Forces in valve and actu ator .......................................................... 007 9.2.2. Lay-out of a suitable valv e act uator ............................................................ 01 0 9.2.3. Requ ired a ctuator thrust f or globe valv es ................................................... 011 9.2.4. Dynamic forces need to be considered in case of flow to close tendencies ...................................................................................................................013 9.2.5. Calculation and sele ction o f an actuato r ..................................................... 01 9 9.2.5.1 General notes for the calculation and selection of a ctuators ......... 019 9.2.6. Fail-safe action .......................................................................................... 021 9.2.6.1 Major application cases .................................................................022 9.2.6.2 Flow force ...................................................................................... 022 9.2.6.3 Sealing , friction and other forces ................................................... 024 9.2.6.4 Actuato r force F a  in all cases of (a ) to ( f) Chapter 9.2.6. 1 .............. 025 9.2.6.5 Safety factors to actuator sizing .................................................. 028 9.2.6.6 Calculation examples (pressu re balance ): .................................... 029 9.2.6.7 Calculation of the Hysteresis: ........................................................032 9.2.6.8 Requ ired a ctuator torque for ro tary val ves .................................... 032 9.2.6.9 Actuato r torque for stan dard bu tterf ly va lves ................................. 033 9.2.7 . The main gro up of the pneumatic d iaphrag m linear act uators .................... 036 9.2.8. T echnical data fo r Packing and P lug s tem d iameter .................................. 038

Upload: jrfml

Post on 19-Oct-2015

540 views

Category:

Documents


32 download

DESCRIPTION

Samson HandBook

TRANSCRIPT

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9. Control valve actuators9.1 General ..............................................................................................................001

    9.1.1. Actuator types .............................................................................................001

    9.1.2. Symbols and units for the calculation of Actuators ......................................002

    9.2 Pneumatic actuator with a linear or rotational movement ............................005

    9.2.1. Pneumatic diaphragm actuator ...................................................................005

    9.2.1.1 Forces in valve and actuator ..........................................................007

    9.2.2. Lay-out of a suitable valve actuator ............................................................ 010

    9.2.3. Required actuator thrust for globe valves ................................................... 011

    9.2.4. Dynamic forces need to be considered in case of flow to close tendencies ................................................................................................................... 013

    9.2.5. Calculation and selection of an actuator ..................................................... 019

    9.2.5.1 General notes for the calculation and selection of actuators ......... 019

    9.2.6. Fail-safe action ..........................................................................................021

    9.2.6.1 Major application cases .................................................................022

    9.2.6.2 Flow force ......................................................................................022

    9.2.6.3 Sealing, friction and other forces ...................................................024

    9.2.6.4 Actuator force Fa in all cases of (a) to (f) Chapter 9.2.6.1 ..............025

    9.2.6.5 Safety factors to actuator sizing ..................................................028

    9.2.6.6 Calculation examples (pressure balance): ....................................029

    9.2.6.7 Calculation of the Hysteresis: ........................................................032

    9.2.6.8 Required actuator torque for rotary valves ....................................032

    9.2.6.9 Actuator torque for standard butterfly valves .................................033

    9.2.7. The main group of the pneumatic diaphragm linear actuators ....................036

    9.2.8. Technical data for Packing and Plug stem diameter ..................................038

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.2.9. Technical data for additional handwheel .....................................................038

    9.2.10. Mechanically adjustable bidirectional travel stop .......................................039

    9.2.11. Manual operation ......................................................................................040

    9.2.11.1 Pneumatic actuator Type 3277 with handwheel ............................ 041

    9.2.11.2 Hand-operated Actuator Type 3273 with side-mounted ...............043

    9.2.11.3 Hand-operated Actuator Type 3273 attached to Type 3241 Valve 044

    9.2.12. Actuator Selection with AC-Trim ................................................................045

    9.2.13. Control valves in case of fire .....................................................................046

    9.2.13.1 Safety cartridge ............................................................................047

    9.2.13.2 Fire-Safe / Fire lock .....................................................................049

    9.2.13.3 Simulation of a fire .......................................................................050

    9.2.13.4 Reversible operating direction ...................................................... 051

    9.2.13.5 Summary .....................................................................................052

    9.2.14. Overview of actuators Type 3271-52, 3271-5, and 3277-5 up to a diaphragm area 120 cm2. ............................................................................................053

    9.2.15. Overview of actuators Type 3271 up to a diaphragm area 1000 cm2. .......060

    9.2.16. Overview of the actuators of 1400 cm2 up to a diaphragm area 2 x 2800 cm2. ...........................................................................................................066

    9.2.17. Overview of actuators Type 3277 up to a diaphragm area 1000 cm2. ...... 070

    9.2.18. Overview of Actuators Type 3371, 3372, Type 2780-1, and Type 2780-2 ..077

    9.2.19. Actuators Type 2780-1, and Type 2780-2 .................................................078

    9.2.20. Pneumatic Actuators Type 3371 and Electropneumatic Actuators Type 3372 ...................................................................................................................081

    9.2.20.1 Technical data Pressures in psi and bar ....................................083

    9.2.21. The cost-efficient positioner Type 3725 ....................................................084

    9.2.22. Operating travels for fail-safe action .........................................................085

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.2.22.1 Operating travels for fail-safe action STEM EXTENDS ...............086

    9.2.22.2 Operating travels for fail-safe action STEM RETRACTS ............092

    9.2.23. Pneumatic piston actuator ........................................................................097

    9.2.24. Pneumatic Piston Actuator Type 3275 ......................................................097

    9.2.25. Principle of operation ................................................................................098

    9.2.26. Mounting Servovalve actuators on SAMSON Series 3240 and 3250 Valves ...................................................................................................................100

    9.2.26.1 PD Pneumatic linear actuator .....................................................100

    9.2.26.2 Double Acting .............................................................................. 101

    9.2.26.3 Double Acting with Handwheel .................................................... 101

    9.2.26.4 Double Acting with Manual Gear .................................................102

    9.2.26.5 Double Acting with Manual Hydraulic Pump ................................102

    9.2.27. Rack and pinion pneumatic actuator .........................................................108

    9.2.27.1 AIR TORQUE delivery program ...................................................109

    9.2.27.2 Design ..........................................................................................111

    9.2.27.3 Construction .................................................................................111

    9.2.27.4 Range of Options, ........................................................................ 113

    9.2.27.5 Quality Manufacturing .................................................................. 113

    9.2.27.6 Accessories available .................................................................. 113

    9.2.27.7 Multi-function indicator ................................................................. 114

    9.2.27.8 Operating conditions .................................................................... 116

    9.2.27.9 Operating function and direction of rotation ................................. 117

    9.2.27.10 Torque diagram Double Acting actuators ................................... 118

    9.2.27.11 Spring Return Actuator ............................................................... 118

    9.2.27.12 Air Torque Actuator Sizing ......................................................... 121

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.2.27.13 Sizing information .......................................................................122

    9.2.27.14 4th Generation pneumatic actuator ............................................ 124

    9.2.27.15 Pneumatic actuator Model AT 051 ............................................. 125

    9.2.27.16 Pneumatic actuator Model AT 101 ............................................. 126

    9.2.27.17 Pneumatic actuator Model AT 201 .............................................. 127

    9.2.27.18 Pneumatic actuator Model AT 251 .............................................. 128

    9.2.27.19 Pneumatic actuator Model AT 301 ............................................. 129

    9.2.27.20 Pneumatic actuator Model AT 351 .............................................130

    9.2.27.21 Pneumatic actuator Model AT 401 ............................................. 131

    9.2.27.22 Pneumatic actuator Model AT 451 ............................................. 132

    9.2.27.23 Pneumatic actuator Model AT 501 .............................................133

    9.2.27.24 Pneumatic actuator Model AT 551 .............................................134

    9.2.27.25 Pneumatic actuator Model AT 601 .............................................135

    9.2.27.26 Pneumatic actuator Model AT 651 .............................................136

    9.2.27.27 Pneumatic actuator Model AT 701 ............................................. 137

    9.2.27.28 Pneumatic actuator Model AT 801 .............................................138

    9.2.27.29 Protections Levels for 4th Generation Actuator ......................... 139

    9.2.27.30 Protections Levels for 4th Generation Actuator ......................... 140

    9.2.27.31 Full compliance with worldwide specifications ........................... 141

    9.2.27.32 Company Approvals .................................................................143

    9.2.28. Rotary Actuator Type 3278 ......................................................................144

    9.2.29. Pneumatic actuators of company Pfeiffer-Armaturen GmbH ....................146

    9.2.29.1 Multi - Turn Actuator - Pfeiffer Type BR 30a ............................... 147

    9.2.29.2 Additional equipment and add-on pieces: ...................................148

    9.2.29.3 Pfeiffer AT - Quarter-Turn Actuator Series BR31a ....................... 149

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.2.29.4 Additional equipment and add-on pieces: ...................................150

    9.2.29.5 Safety position: ............................................................................150

    9.2.29.6 Air drive torque ............................................................................ 151

    9.2.30. Pneumatic actuators of company VETEC Ventiltechnik GmbH ................ 152

    9.2.30.1 Diaphragm or rotary actuators .....................................................153

    9.2.30.2 Direction of flow, Actuator action, and Fail-safe position: ............155

    9.2.31. VETEC Actuator Type R (rolling diaphragm or rotary actuator) ................156

    9.2.31.1 Principle of operation: ..................................................................158

    9.2.32. VETEC Actuator Type AT (Rack and Piston actuator) ..............................160

    9.2.32.1 Principle of operation ...................................................................162

    9.2.33. New design features .................................................................................165

    9.2.33.1 Vetec Type 62.7 AT short pattern with flanges .............................165

    9.2.33.2 Vetec Type 82.7 R short pattern with flanges ..............................165

    9.2.34. VETEC Actuator Type MN (rotary or diaphragm actuator) ........................166

    9.2.34.1 Principle of operation ...................................................................167

    9.2.35. VETEC Actuator Type MD (rotary or diaphragm actuator) ........................168

    9.2.35.1 Principle of operation ...................................................................169

    9.2.36. VETEC Actuator Type MZ (rotary or diaphragm actuator) ........................ 171

    9.2.36.1 Principle of operation ................................................................... 172

    9.2.37. VETEC Actuator Type S (rotary or diaphragm actuator) ........................... 174

    9.2.37.1 Principle of operation ................................................................... 176

    9.3 Pneumatic single acting quarter turn scotch-yoke actuators ......................177

    9.3.1. Symmetrical scotch-yoke ............................................................................ 179

    9.3.2. Canted scotch-yoke .................................................................................... 179

    9.3.3. Scotch Yoke ................................................................................................180

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.3.4. Quarter-Turn Pneumatic Actuators ............................................................. 181

    9.3.5. Quarter-Turn Pneumatic Actuators .............................................................182

    9.3.5.1 Applications ...................................................................................183

    9.4 Electric with a linear or rotational movement ................................................184

    9.4.1. Electro-mechanical Actuators .....................................................................184

    9.4.2. Electro-mechanical and electro-hydraulic actuator .....................................186

    9.4.2.1 Electric Actuator Type 5857 ...........................................................188

    9.4.2.2 Accessories for version with digital positioner ...............................189

    9.4.2.3 Additional electrical equipment ......................................................190

    9.4.2.4 Electrical connection .....................................................................192

    9.4.3. Controller with Electric Actuator Type 5757 ................................................193

    9.4.3.1 Application .....................................................................................194

    9.4.4. Electric Actuator Type 5724 and Type 5725 ...............................................196

    9.4.4.1 Type 5724 ...................................................................................... 197

    9.4.4.2 Type 5725 ...................................................................................... 197

    9.4.4.3 Examples of electrical actuator Type 5824/5825 with various control valves .............................................................................................199

    9.4.5. Electro-hydraulic actuator ...........................................................................200

    9.4.6. Electrohydraulic Actuators Types 3274-11 to -23 ........................................203

    9.4.7. Electric Actuator Type 3374 .........................................................................209

    9.4.7.1 Principle of operation ...................................................................... 211

    9.4.7.2 Fail-safe action .............................................................................. 211

    9.4.8. Electric Actuator Type 3375 ........................................................................ 214

    9.4.9. Electro-mechanical Actuators - PSL Overview ........................................... 216

    9.4.9.1 PSL Electro-mechanical Actuators ................................................ 219

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.4.9.2 PS-AMS The All-In-One Actuators ................................................221

    9.4.9.3 Optional Accessories .....................................................................224

    9.4.9.4 Mounting the PSL Actuator onto the Valves SAMSON Series 3240, 3250, and 3280. .............................................................................225

    9.4.9.5 Type of limit cut-off ........................................................................225

    9.4.9.6 Force/stroke-dependent limit switch cut-off ...................................226

    9.4.9.7 Stroke-dependent limit switch cut-off .............................................227

    9.4.9.8 Electric Supply ...............................................................................228

    9.4.9.9 Wiring diagram ..............................................................................228

    9.4.9.10 Maximum thermal switch loading .................................................229

    9.4.10. Electric actuators outside source ..............................................................230

    9.4.10.1 Linear Actuator Type SAM ............................................................232

    9.4.10.2 Principle of operation ...................................................................233

    9.4.10.3 Electrical connection ....................................................................235

    9.4.11. Electronic actuators of Company AUMA Riester GmbH & Co. KG ............236

    9.4.11.1 Multi-turn actuators SAR 07.2 to SAR 30.2 ..................................237

    9.4.11.2 Linear thrust unit LE 12.1 to LE 200.1 for multi-turn actuators ......239

    9.4.11.3 Range of application .....................................................................240

    9.4.11.4 Mounting to valve .........................................................................242

    9.4.11.5 Actuators without integral controls (AUMA NORM) ......................245

    9.4.11.6 Actuators with integral controls .....................................................245

    9.4.11.7 AUMA MATIC AM .........................................................................245

    9.4.11.8 AUMATIC AC ...............................................................................246

    9.4.11.9 Electric rotary-type actuator for control service (AUMA RIESTER KG) ................................................................................................ 247

    9.4.11.10 Electric rotary-type actuator for control service ..........................249

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.4.11.11 Standard version .........................................................................250

    9.4.11.12 Accessories ................................................................................250

    9.4.11.13 Motor ........................................................................................... 251

    9.4.11.14 AUMA MATIC .............................................................................254

    9.4.11.15 Wiring diagram AM4R AUMA MATIC AM 01.1/AM 02.1 ..............258

    9.5 Explosion-protected actuator ..........................................................................259

    9.5.1. What is an explosion? .................................................................................259

    9.5.2. What is explosion protection? .....................................................................259

    9.5.3. ATEX Directive 94/9/EC .............................................................................259

    9.5.4. Classification of potentially explosive atmospheres ....................................260

    9.5.5. Zone/equipment category ...........................................................................260

    9.5.6. Explosion group/temperature class ............................................................261

    9.5.7. How to achieve explosion protection? .........................................................263

    9.5.7.1 Increased safety (EEx e) ................................................................263

    9.5.7.2 Flameproof enclosure (EEx d) .......................................................263

    9.5.7.3 Constructional safety (c) ................................................................264

    9.5.7.4 Who tests what? ............................................................................264

    9.5.7.5 Auma Marking ................................................................................265

    9.5.7.6 Electric actuators and non-electrical explosion protection .............266

    9.5.8. Explosion-protected actuator ......................................................................269

    9.5.8.1 Explosion-protected actuator from Company SCHISCHEK ...........270

    9.5.8.2 Accessories and special designs (additional price) .......................272

    9.5.8.3 Ex-d valve actuators without spring return, 24 to 240 V AC/DC Type ExRun ...................................................................................273

    9.5.8.4 Ex-n valve actuators without spring return, 24 to 240 V AC/DC Type RedRun ................................................................................. 274

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Table of contents

    9.5.8.5 Wiring diagram of Type ExRun ......................................................276

    9.5.9. Type 3510 Micro-flow Valve with explosion-proof electric actuator .............278

    9.6 Hydraulic with a linear movement ...................................................................279

    9.6.1. Hydraulic Scotch Yoke Valve Actuators .......................................................280

    9.6.1.1 Reliability by Design .......................................................................281

    9.6.1.2 Safety by Design ............................................................................281

    9.6.1.3 High Performance by Design .........................................................281

    9.6.1.4 Override Options ............................................................................281

    9.6.1.5 Key Design Features ......................................................................282

    9.6.1.6 VETEC Rotary valve with Pleiger hydraulic actuator ......................283

    9.6.2. Hydraulic- actuating systems of Welland & Tuxhorn AG .............................284

    9.6.2.1 Functions .......................................................................................285

    9.6.2.2 Design ...........................................................................................286

    9.6.2.3 Setup of an electro-hydraulic Control Loop ...................................286

    9.6.2.4 Hydraulic Servo-Systems - Establishment and Manufacturing ......288

    9.7 Data Sheet for Control Valves according to DIN EN 60 534-7 ......................289

    9.8 Data Sheet for Control Valves according to ISA Form S20.50. Rev. 1 .........290

  • SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

  • General Page 001 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9. Control valve actuators9.1 GeneralThe control effectiveness of a control loop is unquestionable determined by the weakest element of the chain. This is often the valve actuator. If one presupposes a continuity of the control valve characteristic i.e. an inherent characteristic curve without turning points, the quality of the actuator is, for an attainable control effectiveness, in most cases, more important than the quality of the valve characteristic curve.The following chapter illustrates the different actuator principles, explains the authoritative parameters for an actuator selection and focuses above all on the calculation of the required actuator thrust and the selection of a suitable actuator type. A purely static or quasi static consideration however is not sufficient to describe the complicated interactions between the control valve and the actuator. Rather dynamic forces must also be considered for critical applications. Unfortunately, there are no obligatory references available in the corresponding literature which will permit a generalization and a simple calculation method with regard to dynamic forces. Therefore the given recommendations are based on the calculation of the SAMSON group experts, their valve sizing software and the authors.

    The majority of all industrial control valves installed worldwide is even today still driven by pneumatic diaphragm actuators. This actuator type is therefore of course in the center of interest and attention.

    9.1.1. Actuator typesA first criterion in the distinguishing of different actuator types is the style and the manner in which the actuator thrust is generated. Here the user can select from the following actuating principles:

    Actuator

    Pneumatic with a linear or rotational

    movement

    Diaphragm

    Piston

    Rack & Pinion

    Scotch Yoke

    Scotch Yoke

    Electric with a linear or rotational

    movement

    Hydraulic with a linear movement

    Electro-mechanical

    Electro-hydraulic

    Figure 9.1.1.-1: Actuator types

  • Chapter 9. Control valve actuatorsPage 002 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.1.2. Symbols and units for the calculation of Actuators

    Symbol Meaning Source Unit

    A Required (effective) diaphragm area SVS cm2

    c Actuator stem sealing force and other forces SVS -CS Spring stiffness = A(pst100 - pst0) H/Hnom. SVSDa Pressure balance cylinder diameter SVS mmdsd Shaft diameter of rotary valve - mmf FTC correction factor of fluid force Fp (open)f1 Friction coefficient dependent on stem seal SVS N/mmf2 Coefficient depended on required seat sealing Class SVS N/mmf3 Friction coefficient for pressure balanced plugs SVS N/mmFa Effective actuator force (thrust) SVS NFB Bellows elastic force SVS NFf Ff = pst0 = pre-load spring trust SVS N

    Fa/Fo Minimum safety value, Close safety factor SVS -FS/Fw Open safety factor (SAMSON sizing Ff = FS) SVS -

    FM Force due to weight, force due to acceleration) SVS NFm Required actuator force (thrust) pressure balanced. SVS N

    Fmax.Actuator trust: Max. allowed trust depends to max. temperature

    Fmreq.Required actuator thrust Fmrequ. = Fp1+FSF+FR+FRB+FM

    SVS N

    Foreq. Required actuator trust SVS NFo Required actuator force (thrust). SVS NFP Pressure force (Pst A) SVS N

    Fp1Flow (fluid) forces pressure balance f(p1) Fp1 = / 4 Sd2

    SVS N

    FRFriction force caused by stuffing box (packing) FR = f1 Sd

    SVS N

    FRa Friction force (negligible in diaphragm actuator) SVS N

    FRBFriction force (pressure balance sealing force) FRB = f3 Da

    SVS N

    FS Spring pre-load trust FS = pst0 A SVS N

    FSESpring force (elastic)Air to open: FSE = FS + CS HAir to close: FSE = FS + CS (Hnom. H)

    SVS N

    FSFSealing force (seat loading force) when valve closed; FSF = (f2 Sb)

    SVS N

  • General Page 003 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.1.2. Symbols and units for the calculation of Actuators

    Symbol Meaning Source Unit

    Fp Flow (fluid) forces SVS N

    FwTotal friction force of valve and actuator system Fw = FR+cFw = FR+FRB+c in case of pressure balance

    SVS N

    g Gravity acceleration g = 9.81 m/s2 m/s2

    Hnom. Rated (nominal) travel SVS mmH Actual travel SVS mm

    hRelative travel = H/Hnom. 60534-1 -Relative travel = H/Hnom. 100 60534-9 %

    M Mass of plug and actuator stem systemMA Actuator torque SVS Nm

    Mdyn Dynamic torque SVS NmML Bearing friction torque SVS NmMSt Shaft sealing torque SVS Nm

    pASpecified shut down pressure for actuator sizing: take care to the required seat leakage rate and valve strength parameter

    bar

    p Pressure differential p1 - p2 barp0 Pressure differential at 0 % flow or near to min. flow bar

    p100 Pressure differential at 100 % flow or near to max. flow

    p1max

    Allowed p depends to the chosen actuator and strength of the stem with pressure balance

    ( )a SF RB1max.

    2d

    F F F cp

    S10 4

    =

    SVS bar

    pmax

    Allowed p depends to the chosen actuator and strength of the stem pmax on plug calculation max. force see also pApmax > pA > p0 without pressure balance

    ( )a SF Rpmax.

    2b

    F F F c

    S10 4

    =

    SVS bar

    ps Min. required air supply pst100 for fail safe ATC SVS barpst Signal pressure SVS barg

  • Chapter 9. Control valve actuatorsPage 004 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.1.2. Symbols and units for the calculation of Actuators

    Symbol Meaning Source Unit

    psu Supply pressure SVS bargpst0 Lower value: spring range SVS barg

    pst100 Upper value: spring range SVS bargps0req. Min. required pre-load spring force pst0 for fail safe ATO SVS barg

    Sb Seat bore diameter SVS mmqvmax. Operation condition m3/hqvmin. Operation condition m3/h

    Sd Stem diameter SVS mm

    S0Spring trust / torque characteristic (assumed linear) N / Nm

    SB Actuator trust Fa = pst A to travel from 0 to 100 % NSz Fluid closing force {f (p characteristic)} N

    SB 1 Required torque MA = pst A (to open rotary valve) NSB 2 Required torque MA = pst A (to close rotary valve) NSF Safety factor SVS -

    S stat. Break-off and friction torque () f(p characteristic) N

    S dyn. Dynamic torque with closing tendency (-) f(p characteristic)

    Valve-Actuator opening and closing time (See Chapter 20)

    acc Index for actuator accessories -pa Atmospheric pressure SVS bar

    pNV Supply network pressure SVS bargt Stroking time of pneumatic actuator SVS s

    to1, to2, to3

    Opening times: for valve opening SVS s

    to1, to2, to3

    Closing times: for valve closing SVS s

    T1 Inlet temperature KTA Temperature in actuator internal volumes SVS K

    VAActuator internal volume, (diaphragm chamber, filled with air) SVS m

    3

    Actuator internal volume differential quotient SVS m3 d/dt

    V0 Dead volume f(A) SVS m3

    Table 9.1.2.-1: Symbols and units for the calculation of Actuators

    AVV

  • Pneumatic actuator with a linear or rotational movement Page 005 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2 Pneumatic actuator with a linear or rotational movementThe majority of final control elements in the classical process industries are still today controlled by pneumatic actuators. Either continuously regulated or activated according to a desired On-Off service, i.e. simply driven into one of the two possible end positions. Pneumatic actuators can be divided into two main categories:

    Pneumatic diaphragm actuators

    Pneumatic piston actuators

    9.2.1. Pneumatic diaphragm actuatorThe biggest percentage of all control valves installed worldwide in process industries are activated by pneumatic diaphragm actuators. This actuator type essentially consists of two metal shells (the diaphragm housing), the actuator stem and the diaphragm plate. The actuator thrust is transmitted via the high-strength, fabric-inserted diaphragm and the diaphragm plate onto the actuator stem (Figure 9.2.1.1.-1 and Figure 9.2.1.-2).

    Unlike a piston actuator, whose travel depends on the length of the cylinder and the piston-rod, the travel of the pneumatic diaphragm actuator is limited by the shape of the case and the diaphragm. Within a limited travel range, the diaphragm area remains almost constant.

    High flexibility of the diaphragm ensures a minimum friction and hysteresis. These qualities predestine the pneumatic diaphragm actuator particularly for control tasks where a high actuator thrust, a good sensitivity and low supply pressures (2.5 to 4.0 bar) are important.

    Pneumatic diaphragm actuators are usually designed for maximum supply pressures of approximately 6.0 bar.

    If one were to increase the supply pressure at room temperature, up to the destruction of the actuator, it would work out that, in most cases, the diaphragm would prove to be by no means the weakest part of the actuator. Rather, the actuator housing and the supporting diaphragm plates would normally deform beyond the permissible range before we reached a rupture of the strong diaphragm.

    Temperature limits for Diaphragm actuator

    Diaphragm area Diaphragm material: NBRDiaphragm material:

    EPDM

    80 to 120 cm2 - 35** to + 90 C On request

    240 to 700 cm2 - 35** to + 90 C - 50 to + 120 C

    1400 to 2800 cm2 - 40** to + 90 C On request

    ** In on/off service, the lowest value for the NBR diaphragm increases to -20 C.

    Table 9.2.1.-1: Temperature limits for Diaphragm actuator

  • Chapter 9. Control valve actuatorsPage 006 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    There are some reasons to limit the air supply at values < 6 bar to avoid over-stressing of actuator parts and also the valve trim-stem system

    On-off operations at higher frequencies

    In case of travel stops or other accessories, not designed for 6 bar

    Larger actuators with fail safe ATC need to be handled with care regarding too high closing trust: Fa = A (psu - pst100).

    Supply pressure regulators (mass production) or supply service units are responsible to limit the max. actuator trust to avoid mechanical damage. If this relatively inexpensive devices are responsible for the safety function of high end special valves (like compressor anti surge valves to protect expensive flow machines) long term reliability must be guaranteed. If at some locations commissioning, proper maintenance and instrumentation air quality cannot be guaranteed such dirt and oil sensitive pressure reduction equipment should be avoided. In case of too high air supply the actuator can be sized with spring bench rates which reduce the closing trust of the ATC application, e.g. spring bench rate 0.8 to 2.4 bar or 1.6 to 3.2 bar.

    SAMSON AG developed worldwide the first actuator with parallel spring design which seems to be the state-of-the-art on long term.

    The SAMSON Types 3271 and 3277 Pneumatic Actuators contain a rolling diaphragm and internal springs. A maximum of 30 springs can be installed, partly fitted inside one another.

    Special features

    Low overall height Powerful thrust at high response speed

    Low friction Various bench ranges by varying the number of springs or their compression

    No special tools required to change the bench range and to reverse the actuator action (also version with handwheel)

    Permissible operating temperatures from 50 to +120 C

    Direct attachment of accessories on additional yoke for

    Figure 9.2.1.-2: SAMSON Type 3277 for integral positioner attachment

  • Pneumatic actuator with a linear or rotational movement Page 007 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2.1.1 Forces in valve and actuator

    Fp

    FRa

    FSE

    Fa

    FR

    Fp

    FSFFM

    Figure 9.2.1.1.-1: Valve Type 3241 with pneumatic actuator Type 3271

    The following forces act upon the throttle trim including the plug stem: Actuator force: Fa (or actuator torque Ma) Friction force: FR (stem seal, possibly pressure balance seal) Inertial force: FM (force due to weight of plug, force due to acceleration) Flow force: Fp (due to the shut-off pressure) Sealing force: FSF (seat loading force) when valve is closed)

    Residual forces are present on the actuator stem in the pneumatic actuator: Actuator force: Fa (or actuator torque Ma) Friction force: FRa (negligible (0) however) Inertial force: FM (force due to weight, force due to acceleration) Elastic force: FSE (due to the springs elasticity) Pressure force: FP (Fp = Pst A) (signal pressure pst, diaphragm area A)

  • Chapter 9. Control valve actuatorsPage 008 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    5 1.1 1 6 6.1 3

    8

    12

    12.1

    11

    10

    12.1

    13

    2

    15

    16

    4

    7

    a

    9

    1 Nut1.1 Nut2 Actuator stem3 Vent plug4 Loading pressure

    connection5 Top diaphragm

    case6 Springs7 Diaphragm plate8 Diaphragm9 Nuts and bolts10 Yoke with bottom

    diaphragm case11 Loading pressure

    connection12 Stem seal12.1Dry bearing13 Wiper15 Ring nut16 Stem connector

    Dimension a350 cm = 209 mm700 cm = 246 mm

    Spring pressureSignal pressure pst

    Travel

    Figure 9.2.1.-2: Sectional diagram of Type 3277 with 240, 350, and 700 cm2 effective diaphragm area

    The Type 3277 pneumatic actuators with an effective diaphragm area of 240, 350 or 700 cm2 are primarily mounted to control valves from the Series 3240, 3250 and 3280.

    The actuator is made up of two diaphragm cases, a rolling diaphragm and springs. The lower diaphragm case is permanently fixed to the yoke which allows the direct attachment of either a pneumatic or electropneumatic positioner or a limit switch.

    The signal pressure creates a force at the diaphragm surface which is balanced by the springs (6) arranged in the actuator. The number of springs and their compression determine the bench range (signal pressure range) while taking the rated travel into account which is directly proportional to the signal pressure.

    A maximum of 30 springs can be installed, partly fitted inside one another. The stem connector (16) connects the actuator stem (2) with the plug stem of the control valve.

  • Pneumatic actuator with a linear or rotational movement Page 009 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    The self contained, spring-opposed pressure governor which was introduced decades ago and initiated the beginning of automation in process industries was the real predecessor of the contemporary pneumatic diaphragm actuator. Modern pneumatic diaphragm actuators developed from them over the course of the years. An essential break through happened with the introduction of high-strength fabrics of polyamide or polyester and oil and wear & tear resistant synthetic rubber. Both materials make a firm bonding via a specific vulcanization process and this guarantees the long service life of the diaphragm.

    Pneumatic diaphragm actuators compare the input signal, which affects the diaphragm,with the compression force from one or several return springs. Through a linear relationship between actuator travel and trailing force this also results also in a proportionality between actuator input signal and actuator travel. If one presupposes a linear valve characteristic and a constant differential pressure a proportionality also exists between the controller output signal and the process variable, i.e. the flow rate. Because of this feature, the pneumatic diaphragm actuator soon found wide-spread distribution. Another advantage of this simple and robust principle is the possibility of avoiding the use of a valve positioner, if it cannot be justified for economic reasons or in cases of extremely harsh environmental conditions.

    Advantages: Compact, only few parts required, very reliable. High actuator thrusts at low air supply pressures (< 6 bar). Proportional behavior via one or several return springs. Simple reversal on site possible (direct or reverse). Automatic failure position in case of auxiliary power loss. Low hysteresis and excellent sensitivity. Very broad application range (-35 C to 90 C NBR; -50 C to +120 C EPDM),

    lower temperatures with special diaphragm material on request.

    Relatively immune to shock and vibrations. Mounting in any position possible. High internal tightness allows interlocking for several hours. Lowest thrust-weight ratio of all actuators. Best cost/thrust ratio of all actuator types.

    Disadvantages: Limited valve travel (to approx. 1/8 of the diaphragm diameter) Unsuitable for high supply pressures (> 6 bar).

  • Chapter 9. Control valve actuatorsPage 010 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2.2. Lay-out of a suitable valve actuatorThe lay-out of a suitable control valve actuator requires that we consider a great number of parameters. The actuator indeed works only in an optimal manner, if both the process and environmental conditions as well as the corresponding characteristics and requirement profiles are exactly known. Based on this information, a calculation of the required actuator thrust (or torque) can be made and a suitable actuator selected. This depends in the first place on the main criteria: required actuator thrust, stroking speed and failure position. In addition to these main parameters, there are a number of further actuating variables, which have additionally to be considered during the calculation and specification of a suitable actuator.

    The following parameters and conditions are noted without suggesting that the list is definitive:

    Type of movement (linear or rotational). Transient response (proportional or integral). Action of movement (direct or reverse). Failure position in case of auxiliary power loss: (Open, Closed, Hold). Actuator signal (electrical or pneumatic). Input signal range (e.g. 4 to 20 mA). Nominal travel or nominal angle of rotation. Mounting interface between valve and actuator. Required actuator thrust with closed valve. Required actuator thrust with open valve. Required travel rigidity (stiffness) for a stable control service. Permissible accuracy deviation from the characteristic curve. Hysteresis, reversal error and sensitivity. Regulating time for full stroke travel or angle of rotation. Switching frequency (on time in percent for of electric actuators). Actuator volume (in case of pneumatic actuator). Time constant and corner frequency (with positioner). Resistance against shock and vibration (fatigue strength of actuator). Permissible ambient temperatures. Required protection class (against dust, water, moisture, e.g. IP65). Requirements with regard to corrosion resistance. Actuator and all accessories like positioners, boosters, solenoid valves and air supply pressure reduction device need proper air quality acc. to ISO 8573-1 Class 4 regarding micro-parts ( 1.0 < d < 5 m; < 1000 parts/m3) and Class 3 ( 1 mg/m3) regarding oil contamination otherwise filter systems are needed to protect each device.

    Required auxiliary energy for actuator (e.g. min. and max. pressure). Typical characteristics (e.g. effective diaphragm area). Actuator connections (e.g. G to G1 or to 1 NPT). Repeatability of positioning taking into account:

  • Pneumatic actuator with a linear or rotational movement Page 011 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Ambient temperature. Auxiliary energy. Process conditions.

    Other requirements, e.g. manual operation required for emergency situations?Therefore the user of valve actuators should prepare a check list, which contains all the important requirements and limiting conditions before he begins to specify the actuator. By this method it is ensured that all required functions have been considered, and an optimal actuator type for the respective task can be selected.

    9.2.3. Required actuator thrust for globe valvesThe fluid causes static and dynamic reaction forces which act on the plug and which must be absorbed, to a large extent, by the valve actuator. Static forces occur only with the valve closed i.e. if the flow is zero. In this case the internal pressure of the fluid attempts - in the normal flow direction - to open the valve and push the valve stem outwards. Dynamic forces result from heavy turbulence of the fluid. These forces cause vibrations and oscillations which often lead to early wear and tear in the valve or even failure of specific valve and/or actuator parts.

    Static forces of a globe valveA final control element, as represented schematically in Figure 9.2.3.-1, with a flow direction against the plug from below, tends to open, since the fluid pressure tries to push the plug upwards against the thrust of the actuator. This flow direction has been proven to be most effective and is used, in particular, with spring opposed pneumatic diaphragm actuators which have normally only limited travel rigidity. With a reversed flow, i.e. flow-to-close, instability might occur as will be demonstrated later. The total static thrust required in order to close a globe valve against the actual pressure differential, results from the sum of the individual force components which is briefly explained below. The necessary equations for a detailed calculation, the symbols and common units are shown.

    Flow force FpAssuming a normal flow direction from below against the plug (Figure 9.2.3.-1), the flow force can be computed if inlet pressure and outlet pressure as well as the characteristic values of the final control element are known. This is firstly the cross-sectional area of the valve seat and stem. For valves with bellows seal its mean diameter should be used. Since the cross-section of the seat ring is usually large compared to the stem cross-section, the flow force increases approx. proportionally with the differential pressure.

    Sealing force FSF (Closing force)Today one expects from a final control element not only a good rangeability, but often also tight shut-off capabilities are required. The permissible leakage is defined in accordance with IEC-60534-4, where different leakage classes apply (II to VI). A correct lay-out of a suitable actuator requires not only a compensation of the flow force which results from the differential pressure in the closed position, but beyond there this a considerable closing force with which the plug must be pressed into the valve seat required, in order to achieve

  • Chapter 9. Control valve actuatorsPage 012 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    the specified leakage rate or tight shut-off. As experience shows, a leakage-dependent specific seating force is required (per millimeter seat ring circumference) in order to enable satisfactory tightness. This means that the required closing force is approximately proportional to the seat ring diameter.

    Fa

    FR

    FSF

    Fp

    Sb

    Sd

    Figure 9.2.3.-1: Static forces acting on a globe valve (schematic)

    Friction force FRMost control valves still use a stuffing box which is required for the sealing of the valve stem (shaft), PTFE and graphite, which are often combined with special filling materials in order to improve hysteresis and sensitivity, are the most common package materials used today. Friction in the stuffing box can be roughly computed if the stem diameter d, the maximum pressure p and the package type are known. Generally, the frictional force increases proportionally with the stem diameter and the working pressure. A special packing coefficient is associated with the packing material.

  • Pneumatic actuator with a linear or rotational movement Page 013 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Friction force FRB in pressure balanced valvesThe principle of pressure balance is often applied on large valve sizes and high differential pressures. As a result, the actuator thrusts remains small in comparison with a non-pressure balanced control valve. The causes of friction are dynamic forces, which result mainly from the gap flow in the guide bushing and which press the plug firmly against the wall of the guide bushing. It is therefore erroneous to assume that pressure balanced valves require only very small actuator thrusts. These frictional forces in fact increase proportionally with the diameter of the guide bushing and with the differential pressure. Additional piston rings, which are often inserted in the plug to keep the leakage low, make things worse. Ignoring this frictional force is sometimes the reason why the final control element is unable to close, since the differential pressure normally increases with a decreasing flow, so that the friction force becomes highest near the closed position. The jamming effect is especially troublesome strongly with fluids which have no lubrication features e.g. like dry overheated steam or other dry gases.

    The pressure balance contoured plug seat configuration of SAMSON AG has not been changed to the non pressure balanced standard trim. The unique balanced design -see Chapter 6 Fig. 6.2.4.-3 is sealed in the valve bonnet and not in the seat area,

    Therefore the risk of jamming is minimized as well as the high dirt sensitiveness known from other cage retained pressure balanced systems.

    Weight force FMIn a case of a very heavy opturator (plug) with a considerable mass, emphasis must naturally give also to the weight of the plug (depending on the mounting position of the control valve), if the actuator has to be able to open or close the final control element against gravity forces.

    9.2.4. Dynamic forces need to be considered in case of flow to close tendenciesWhen considering static forces, the main factors apply to the valve in the closed position, i.e. the actuator must be able to close the valve against the highest differential pressure, On the other hand, an accurate and stable control service should be achieved for pressure balanced and/or double seated valves, in spite of low actuator forces and a relatively small travel stiffness when dynamic forces exist. Provided a comprehensive actuator calculation for a single seated control valve has been carried out, and that it considers all essential factors, the dynamic forces can usually be ignored because static forces normally predominate to a great extent.

    A different situation exists, however, in the case of a double seated or pressure balanced control valve. Here the dynamic forces can considerably exceed the static forces. This means that unstable regulating service and/or inadequate control characteristics might occur. The regulation service becomes particularly critical if with direct action, the installed characteristic of the pneumatic diaphragm actuator flattens so far that different travel positions can be assigned to the same actuator input signal (Figure 9.2.4.-1). This effect can be observed with control valves with a flow direction to close, i.e. the flow enters the valve from entry point on top of the plug. This misapplication often results in

  • Chapter 9. Control valve actuatorsPage 014 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    an uncertain correlation between the actuator input signal and the corresponding valve travel and should be avoided under all circumstances. While the signal range of the actuator becomes greater with the normal flow direction to open (approx. 160 % in Figure 9.2.4.-1), the signal range decreases in the case of re-verse flow direction (approx. 65 %) and this might cause instability.

    Considerable instability is often found near the closed position but rarely also instability can be found at opening position if here the total signal pressure characteristic SB turns negative (see Figure 9.2.4.-2 and Figure 9.2.4.-3). The plug usually flutters in this range and not only prevents a stable regulation, but also tends to self-destruction through hammer effects. The dynamic forces acting on the internals of the control valve can be greatly suppressed, if an actuator with sufficient rigidity (travel stiffness) is employed, Unlike self-locking electro actuators or very inflexible electro hydraulics actuators, pneumatic diaphragm actuators have only a limited stiffness, which is determined by the spring rate of the return spring(s). Empirically based findings prove that a satisfactory regulation can be expected even in the case of limited travel stiffness.

    Naturally, the requirements increase with an increasing differential pressure and with a larger diameter of plug. A re-calculation of the required minimum travel stiffness is recommended, if (1) high differential pressures occur, (2) the valve is pressure balanced, (3) the flow direction is reverse (flow-to-open). Since the user very seldom knows the precise physical dimensions in the case of an installed valve, the actual flow coefficient (Cv100 value) can also be used in a rough calculation. In addition, a valve specific stability factor may be utilized in order to observe the dynamic behavior of the valve depending on the trim. Cage and contoured plug valves, for instance, behave more favorably in this respect than do valves with parabolic plugs.

    %0 10 20

    0.2

    30 40

    0.4

    50 60

    0.6

    70 80

    0.8

    90 100

    1.0

    1.2

    1.4

    1.6

    1.8

    Signal range (bar)

    Valve openValve closed

    Flow direction FTOBench rangeFlow direction FTC

    instable

    Resulting force of fluid and spring for ATC

    Figure 9.2.4.-1: Characteristics of a pneumatic diaphragm actuator at different flow directions (schematic)

  • Pneumatic actuator with a linear or rotational movement Page 015 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    w

    FTC + ATO

    Yx

    p1

    p2

    SB

    SB

    SzSz

    Safe control rangepst

    Travel

    0.45

    p100fp0

    p100fp0

    pst0

    pst100

    DynamicJoukowsky peakWater hammer

    Spring force

    Fluid force

    S0

    Signal pressure - Travel diagram with non-stable signal pressure characteristic SB if the slope (gain) turns negative (-) to the positive (+) spring slope.

    Risk of hunting (hammering) at small opening < 20 % travel and also possible oscillation (hunting) at > 35 % travel if pmax

  • Chapter 9. Control valve actuatorsPage 016 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Typical trim configurations with flow to close tendencies:

    Without going to details some graphics of the total force characteristic, which may turn from flow to open (stable) to flow to close (non stable tendencies) are sometimes causing trouble in liquid applications, if actuator sizing with know how not taken account stability in all travel positions.

    Angle type valves:(FTC in case of safety reasons; abrasive fluids; severe service)

    Perforated plugs need for liquids FTC for effective sound reduction

    Double seated valves: If flow goes from outside (above the plugs) to inside

    Three way valves: For dividing service with compact plug design or mixing service with two plugs above the seats.

    This trim selection must be avoided in case of after sale trim replacements. SAMSON AG avoid FTC tendencies with a compact trim for mixed service and a splitted two plug trim for dividing service.

    Rotary control valves:For butterfly and most of other rotary control valves the actuator sizing should take care of all static- and dynamic forces for all travel positions and need a special look to the actuator stiffness, if the dynamic force, which general has a FTC tendency is not negligible.

    Only a larger stiffness - which is (pst100 - pst0) A - can minimize the break off torque and carefully looking to travel start and travel end and the necessarily spring force or air supply can avoid bad surprises.

    Figure 9.2.4.-4: Leusch Butterfly Type LTR 43

  • Pneumatic actuator with a linear or rotational movement Page 017 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    SB 1

    S 0 li

    near

    SB 2

    (-) S d

    yn

    . S stat.

    10 20 30 40 50 60 70 80 90Opening angle

    Break off

    Fail safe: ATO (closed by spring force)Min. air supply psu

    pst open

    pst close

    Instable openingfor control > 70

    psu 2pst0

    pst

    (psu - pst100)MA S dyn

    pst0 MA

    psu MA S stat.

    MA Torque

    Signal pressure - opening diagram ATO (Closed with spring force) S0 Spring characteristic () ML= friction (break off) torque (against direction of travel) () MSt = Shaft sealing torque (against direction of travel)(-) Mdyn = dynamic torque f(size, p) (closing direction)SB1, SB2 Signal pressure characteristic to open and to close the rotary valve.Take care of the necessarily min. air supply and min. pre-load of the spring

    To check: pst0 MA > ML +MSt (psu pst100) MA > Mdyn. + MSt

    Figure 9.2.4.-5: Signal pressureopening diagram ATO

  • Chapter 9. Control valve actuatorsPage 018 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    6 linear(-)

    S dyn

    .s6VWDW10 20 30 40 50 60 70 80 90

    Opening angle

    Break off torque

    Fail safe: ATC (open by spring force)

    pst openpst100 pst0

    psu - pst100psu = 2pst100 SVWFORVH

    Instable openingfor control > 70

    SB 2

    SB 1

    Min. spring pre-load torque

    Min. air supply psupst

    MA TorqueSignal pressure - opening diagram ATC (Closed with air pressure). The dynamic torque (-) Mdyn. in some applications like flow machines anti-surge control with high performance low noise butterfly valves can get much higher values than shown here in case of high p at max. load. This closing torque need to be balanced safety with a necessarily spring pre-load torque. See sizing exampleTo check: (psu pst100) MA > ML + MSt pst00 MA > ML + MSt pst0 MA > Mdyn. + MSt

    Figure 9.2.4.-6: Signal pressureopening diagram ATC

  • Pneumatic actuator with a linear or rotational movement Page 019 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2.5. Calculation and selection of an actuatorFor the selection of a suitable pneumatic diaphragm actuator, it is vital to work through the previously mentioned check list. The following questions, which have a decisive influence on the actuator selection procedure, are to be answered without fail in this respect:

    Failure position: valve either closed or open? Nominal valve travel: actuator travel must be valve travel. Prescribed flow direction: flow to open or flow to close? Important physical dimensions: seat and stem diameter? Packing type: PTFE or graphite? Flow coefficient (Cv100 value)? Required actuator thrust in closed valve position? Required minimum full stroke regulating time for nominal valve travel? Is a positioner required? If not: required signal range? Does the interface match the actuator and the control valve? Minimum air supply pressure of the plant? Supply air quality can have a major impact to safety functions. Filter systems are recommended for each devise to keep air quality acc. to ISO 8573-1 in locations with lower standards.

    Minimum and maximum ambient temperatures? Required shock and/or vibration resistance? Special requirements with respect to corrosion resistance? Other demands of the customer?

    When all these items have been considered, a corresponding calculation and selection of a suitable valve actuator can be made.

    9.2.5.1 General notes for the calculation and selection of actuators A sufficient additional safety factor should always be planned, since an exact calculation of the required actuator thrust is quite complex and there could be a difference in the force balance from final inspection to after commissioning under process conditions as well as after long term operations.

    For DIN/DVGW valves and other quick closing and safety control valves (TV certificated) the actuator safety factor must be about 2.

    SAMSON Valve Sizing (SVS and SVSS) creates a general warning, if the safety factor become < 1.1. This min. safety factor expects ideal environmental condition like an in-house installation- and equates to the competitive conduct.

    Environmental conditions at delivery and plant location are often unknown as well how long valves are stored before commissioning. Valves may be delivered in hazardous areas and stored less protected. Then sealing material will be attacked from rain, sand and petrochemical dust and sometimes it can take month before the plant is ready for start up. Any packing-stem system will suffering more under static not pressurized conditions.

  • Chapter 9. Control valve actuatorsPage 020 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    The valve system friction may increase also from lack in commissioning (pipe installation without force compensation due to temperature elongation). Long term age-hardening of packing and sealing material occurs in case of no proper frequently maintenance. It is recommended to use a higher than 1.1 safety factor in case of those unknown (not ideal) random conditions. Therefore the required actuator force (trust): Fo = 1.25 Fa

    Large effective areas reduce the negative influence of friction forces on control valve performance by minimizing hysteresis and dead band. At request of the highest control controllability for expensive products like insulin also a low price actuator of smallest size may close against a moderate low shut down pressure. The valve performance and controllability interacting to the production quality and quantity, which significantly can improved with a larger actuator size selected in the first priority for lowest hysteresis and not for the shut down pressure.

    Diaphragm actuators have a considerably smaller hysteresis than piston actuators (up to 40 % hysteresis due to piston seals), which the positioned is likely to be unable to compensate on long term.

    Several spring assemblies with smaller springs distributed over the circumference offer a greater accuracy and mechanical stability than fewer large springs arranged in the center. In addition, the variability of the spring range and the stiffness of the actuator are increased

    The actuator characteristic should, ideally, be linear and the hysteresis small. Linearity errors stem mostly from a changing diaphragm area which might possibly result in an inadequate actuator thrust in the closed position.

    The actuator selection should also consider durability and maintenance. An application in the following climatic conditions should be guaranteed:

    Moderate Cold Dry warm Humid and warm

    Constructional arrangement of the valve interface and general firmness of the actuator should meet all requirements considering at the same time ambient influences. Demands regarding earthquake safety and/or radiation resistance in nuclear power plants are examples of this point.

    The selection of a suitable actuator should always consider possible future enhancements. Subsequent mounting of a hand wheel or positioner might be taken as examples. Mounting possibilities of further accessories should also be considered.

    Fatigue strength and impact resistance ought to be considered e.g. as they occur on ships.

    Corrosion-resistant paint coatings should be applied, in order to protect the actuator and guarantee the specified service life.

    All aspects of accident safety must be considered, in order to protect users against injuries.

  • Pneumatic actuator with a linear or rotational movement Page 021 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    An adequate quality assurance system (ISO 9001) and attention paid to valid standards and regulations is necessary, to guarantee correct state of the art products.

    9.2.6. Fail-safe action When the signal pressure fails, the fail-safe action of the actuator depends on whether the springs are installed in the top or bottom diaphragm chamber.

    Actuator stem extends (ATO)When the signal pressure is reduced or the air supply fails, the springs move the actuator stem downwards and close the valve.

    The valve opens when the signal pressure is increased enough to overcome the force exerted by the springs.

    Actuator stem retracts (ATC)When the signal pressure is reduced or the air supply fails, the springs move the actuator stem upwards and open the valve.

    The valve closes when the signal pressure is increased enough to overcome the force exerted by the springs.

    ATC

    pst

    pst

    ATO

    pst = Signalpressure

    Black arrow = Spring force

    Blue arrow = Air pressure

    pst

    FTC + ATC

    pst

    FTC + ATO

    pst

    FTO + ATC

    pst

    FTO + ATOFigure 9.2.6.-1: Fail-safe action

  • Chapter 9. Control valve actuatorsPage 022 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2.6.1 Major application casesOne must distinguish between the following application cases before beginning the relevant calculation procedure:

    (a) Valve without pressure balance, FTO flow direction to open, ATO (air failurespring CLOSED).

    (b) Valve without pressure balance, FTO flow direction to open, ATC (air failurespring OPEN).

    (c) Valve with pressure balance, FTO flow direction to open, ATO (air failurespring CLOSED).

    (d) Valve with pressure balance, FTO flow direction to open, ATC (air failure spring OPEN).

    (e) Valve without pressure balance, FTC flow direction to close, ATO (air failurespring CLOSED.

    (f) Valve with pressure balance, FTC flow direction to close, ATO (air failurespring CLOSED.

    (g) Valve with - or without pressure balance, FTC flow direction to close, ATC (air failurespring OPEN.

    The application mentioned under (g), i.e. valve with - or without pressure balance, flow direction to close and valve on air failure OPEN, must be avoided, because full stability can hardly be expected under these conditions (see Figure 9.2.4.-1).

    The required effective area of the actuator diaphragm and therefore the required actuator size is derived from the previously calculated actuator thrust. It is always recommended to add an additional safety factor of approx. 1.25 in order to ensure that the actuator is able to close the final control element, under all conditions, against the max. upstream pressure p1 or against the specified max. differential pressure pA. The following equations consider the relationships between actuator and valve in the different application examples.

    9.2.6.2 Flow forceDepending to the customer specification p is declared as pA; p0 or p1 max. For actuator sizing this value has the highest cost influence and must be clarified before starting the offer.

    Without pressure balance trim:FTO flow to open

    Flow force Fp = trust is opening (+) and need Fa trust to close (-)

    ( ) ( )2 2b d 2F S p S pp 4 10 = + (9-1)

  • Pneumatic actuator with a linear or rotational movement Page 023 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    If in the majority of trim variations the seat diameter Sb is essential larger than the stem or bellows seal diameter Sd the influence of Sd is negligible.

    ( )2bF S pp 4 10

    = (9-1.2.1)

    FTC flow to closeFp trust is closing (-) and need Fa trust to open (+)

    ( ) ( )2 2 2b d d 2F S S p S pp 4 10 =

    (9-1.2.2)

    The term for the closing force Fp = (Sb2 Sd2) p /(4 10) need to have a force correction for the open position with factor f: f = 0 if p100/p0 tends to zero; f = 0.4 if p100/p0 tends to 1f = 0.4 based on measurements with parabolic plugs (mentioned in VDI/VDE 3844)

    Remark: Fp at open position = Fp f

    With Pressure balance trim: FTO flow to open: (Standard flow direction)Fp and Fp1 trust result to open (+) and need Fa trust to close (-)In case of Da > Sb

    ( ) ( )2 2 2a b d 1F D S p S pp 4 10 = +

    (9-1.3.1)

    In case of Da = Sb (Standard for SAMSON pressure balance)

    2p1 d 1F S p 4 10

    =

    (9-1.3.2)

    FTC flow to close (on request for an angle type valve)Fp and Fp1 trust result to close (-) and need Fa trust to open (+)

    In case of Da > Sb

    ( ) ( )2 2 2a b d 1F D S p S pp 4 10 =

    (9-1.4.1)

    In case of Da = Sb (Standard for SAMSON pressure balance)

    2p1 d 1F S p 4 10

    =

    (9-1.4.2)

    b dS S>>

  • Chapter 9. Control valve actuatorsPage 024 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2.6.3 Sealing, friction and other forcesSealing force FSF if valve closed H = 0

    (9-2)= SF 2 bF f S

    f2 = for required leakage class N/mm

    Metallic 2 Class IVLapped in 20 Class VSoft sealing 0.3 Class VI

    Packing/Sealing friction FR without pressure balance

    R 1 dF f S= (9-3)

    Stem seal Friction coefficient f1 N/mm

    Series3240 3250

    DN up to 150 DN > 150Packing number 1 2 2PTFE- packing 1.6 3.2 3.2

    Graphite-packing 5 10 10Bellows 1.6 1.6

    Insulated section 1.6 1.6Univerdit Alchem 3.2 3.2

    Figure 9.2.6.3.-1: Stem seal Friction coefficient f1

    Friction in pressure balanced valves

    RB 3 aF f D= (9-4)

    Stem seal Friction coefficient f3 N/mmWith PTFE seal 3.0

    With Graphite seal 10

    Weight force of plug and actuator stem system

    MF M g= (9-5)

    Remark: - M normal installation; + M reverse hanging installationM = Mass of plug and actuator stem systemg = Gravity acceleration g = 9.81 m/s2

    Of interest only at larger sizes: DN 200 approximately 200 N DN 300 approximately 450 NWeight forces (FM) for small sizes are negligible. In this way, the following basic equations will apply for the calculation of the required actuator thrust considering the valve type, the flow direction and the respective failure position of the final control element:

  • Pneumatic actuator with a linear or rotational movement Page 025 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2.6.4 Actuator force Fa in all cases of (a) to (f) Chapter 9.2.6.1Actuator force FaCase (a) and case (b): No pressure balance, flow to open, failure position: ATC - OPEN or ATO - CLOSED,

    ( )a p SF RF F F F FM= + + + (9-6)

    From the variables of equation (9-1) equation (9-2) equation (9-3) we get:

    ( ) ( )2 2a b d 2 2 B 1 dF S p S p f S f S M g4 10

    = + + + + (9-6.1)

    Case (c) and case (d): With pressure balance, flow to open, failure position OPEN or CLOSED

    (9-7)a p1 SF R RBF F F F F (FM)= + + + +

    (9-7.1)( )2a d 1 2 B 1 d 3 aF S p (f S f S f D ) M g4 10

    = + + + +

    Case (e): No pressure balance, flow to close, failure position CLOSED

    ( )= + +a p R MF F F F (9-8)

    ( ) ( )2 2 2a b d d 2 1 dF S S p S p f S M g4 10

    = + + (9-8.1)

    If Sb >> Sd equation (9-8.1) could be simplified:

    ( )2 2a b dF S S p M g4 10

    = +

    (9-8.2)

    Fa trust here is needed to open the valve from 0 to 100 % travel. Important to check the actuator stiffness for control stability with equation (9-10) and check the closing position if the closing pressure differential is too small.

    st0 SF R 2 b 1 d10 p A F F f S f S > + = +

  • Chapter 9. Control valve actuatorsPage 026 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Case (f): With pressure balance, flow to close, failure position CLOSED

    ( )a p1 R RBF F F F FM= + + + (9-9)in case of Sb = Da

    ( )2a d 1 1 d 3 aF S p f S f D M g4 10

    = + + + (9-9.1)

    Fa trust here is needed to open the valve from 0 to 100% travel. Important to check the actuator stiffness for control stability with equation (9-10) and check the closing position if the closing pressure differential is too small.

    ( )st0 SF RB 2 b 1 d 3 a10 p A F F f S f S f D > + = + +

    With a reverse flow direction (fluid tends to close the valve), the plug is pressed into the seat by the differential pressure. This application should be limited to special cases only, in order to avoid instability with fine control requirements. A few exceptions are applications where it is either favorable

    To exploit the reaction force of the differential pressure for secure closing of the valve and/or to achieve tight shut-off, or

    To limit wear and tear inside the valve body caused - in the case of angle type valves - by erosion or/and abrasion.

    One main criterion for achieving adequate actuator stability is the difference of force gradients, when a reverse flow direction is chosen. Generally there exists in every travel position of the actuator, a balance between the actuator thrust which is determined by the effective diaphragm area multiplied by the actuator input signal and the trailing force of the return spring(s).

    Under dynamic conditions high fluid forces can occur, which act on the plug and considerably disturb this balance. From Figure 9.2.4.-1 it becomes clear, that the effective signal range in the case of direct action and a flow direction to close is considerably decreased which leads, unavoidably, to instability, since the force gradient resulting from fluid forces is higher that of the return spring(s). This makes, in such a case, a satisfactory regulation impossible. For this reason, the combination (direct action and flow to close service) should be excluded under all circumstances.

    However, the flow direction to close is even with reverse action (valve closed in case of air failure) not without problems. Near the closed position the reaction forces of the control valve normally increase greatly and may be superposed by a so called Joukowsky peak at larger sizes, long upstream pipe and high pipe velocity, so that the force balance is suddenly disturbed considerably. This imbalance can be slightly improved by the application of a positioner. The response time is, however, not fast enough by far, so that a continuous hammering of the plug might occur near the closed position.

  • Pneumatic actuator with a linear or rotational movement Page 027 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    This must be in all circumstances avoided for wear and tear reasons. Essential for stable actuator operation is a sufficiently high spring rate whose force gradient must be higher at any travel position than the force gradient resulting from dynamic valve reaction forces. Furthermore, it should be noted that the actuator force direction of flow to close applications is reverse, i.e. the actuator force hat to pull the plug out of the seat. One should further differentiate between control service and ON-OFF service. In the latter case, a continuous hammering effect cannot occur, since the critical range is usually passed through very quickly. Important with reverse flow conditions is an examination of the required actuator rigidity or travel stiffness, in order to assure a stable control service.

    This stiffness depends on the spring rate and the diaphragm area of the pneumatic actuator: A (pst100 - pst0).

    Adequate control stability can be expected if the required maximum actuator thrust is in a certain relationship to the signal range of the actuator. The required signal range which, in turn, determines the travel stiffness can be roughly checked by means of the following equations. The disadvantageous case that the valve authority p100/p0 tends to zero, (means pqmax (9-10)

    ( )2 2b d 0F S S pp 4 10

    = (9-10.1)

    for cases Sd (9-10.2)

    With pressure balance:

    ( )st100 st0 p1A p p 10 2 F > (9-10.3)

    2p1 d 1F S p 4 10

    =

    (9-10.4)

    In case of Da = Sb (Standard for SAMSON pressure balance.

    The factor 2 in equation (9-10) tends to factor 1 if the valve authority p100/p0 also tends from 0 to 1. p0 roughly can be substitute with the max. p at qmin. but not with the specified pA for actuator closing, which could be much higher than p0. Control actions are not recommended below 20 % travel.1 Lean on VDI 3844 draft 2010-05

  • Chapter 9. Control valve actuatorsPage 028 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    For ON-OFF service the following rule applies for FTC

    ( )st100 st0 pA p p 10 1.33 F > (9-11)

    Based on long term experience with perforated plugs (FTC) a proven rule-of-thumb for the maximum permissible differential pressure p0 has been derived from equation 9-10 and 9-11 for applications with a flow direction to close.

    p0 roughly can be substitute with the max. p at qmin. but not with the specified pA for actuator closing, which could be much higher than p0.

    For control service:

    ( ) ( )0 st100 st0 2 2b d100p 0.5 A p p 4

    S S =

    (9-12)

    The factor 0.5 tends to factor 1 if the valve authority p100/p0 also tends from 0 to 1.

    For ON-OFF service:

    ( ) ( )0 st100 st0 2 2b d100p 0.75 A p p 4

    S S =

    (9-13)

    9.2.6.5 Safety factors to actuator sizing Important requirements and safety factors to actuator sizing published in SAMSON VALVE SIZING SVS and SVSS.

    Figure 9.2.6.5.-1: SAMSON Actuator sizing Fa : delivered actuator trust kN Foreq. : Required actuator trust kN Fmreq. : Required actuator trust (Pressure balanced) kN Fmax. : Actuator trust: Max. allowed trust depends to max. temperature kN pmax. : Allowed p depends to the chosen actuator and strength of the stem bar ps0req. : Min. required pre-load spring force pst0 for fail safe ATO bar pS : min. required air supply pst100 for fail safe ATC bar

    To check in case of pressure balance trim:pS: min. req. Air supply pst100 for full opening ATO bar

  • Pneumatic actuator with a linear or rotational movement Page 029 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Handling safety factors SF:Safety factor SF delivered actuator trust / required actuator trust. The factor SF is the result of selecting the actuator type (e.g. actuator data sheet information from Chapter 9.2.22 to Chapter 9.2.22.2 with higher trust than calculated. The responsible engineer should have information about environment, installation, local maintenance and warrantee conditions as well as special customer requirements. See also Chapter 9.2.5.1. If this random conditions are critical it is recommended to size SF higher than 1.1 (SVSS software warning value).

    If 1.1 < SF < 1.25 select an actuator type with SF equal or near to 1.25. (Is the SVSS software warning 2.0 than select near to 2.0)

    Fa/Fo or Fa/Fm without or with pressure balance warning in SAMSON Valve Sizing Specialist SVS / SVSS if SF < 1.1 recommended in hazardous areas = 1.25

    Open safety factor: only for fail safe ATCFf /Fw warning in SAMSON Valve Sizing Specialist SVS / SVSS if SF < 2.0 Ff = pst0 = pre-load spring trust, Fw = system friction

    9.2.6.6 Calculation examples (pressure balance): Fp1 forces can support to open (FTO) or to close (FTC) the valve. In case of pressure balance this forces are small in comparison to the total system friction forces

    w R RBF F F c= + +

    Flow to open FTOFail safe ATO Closing safety factor:

    ( )a st0

    2md 1 2 b 1 d 3 a

    F A p 10F S p f S f S f D

    4 10

    =

    + + +

    Opening safety factor:

    ( )( )

    su st100a

    m 1 d 3 a

    A p p 10FF f S f D

    =

    +

    Warning in SAMSON Valve Sizing Specialist SVS / SVSS if SF < 1.1 recommended in hazardous areas = 1.25

  • Chapter 9. Control valve actuatorsPage 030 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Flow to open FTOFail safe ATC

    Closing safety factor:

    ( )

    ( )su st100a

    2md 1 2 b 1 d 3 a

    A p p 10FF S p f S f S f D

    4 10

    =

    + + +

    Open safety factor:

    ( )a st0

    m 1 d 3 a

    F A p 10F f S f D

    =

    +

    Flow to close FTC: From safety point of view a specified high shut down pressure pA should only be used to check the valve and trim-stem system material strength values. In many applications pA could decrease to smaller values at least to atmosphere after the valve is closed. The required seat tightness quality (e.g. Class V) should stay under all p conditions.

    Flow to close FTCFail safe ATOClosing safety factor:

    ( )a st0

    m 2 b 1 d 3 a

    F A p 10F f S f S f D

    =

    + +

    Opening safety factor:

    ( )( )

    su st100a

    m p1 1 d 3 a

    A p p 10FF F f S f D

    =

    + +

    The term

    2p1 d 1F S p f 4 10

    =

    in case of pressure balance is nearly negligible

    f = 0 if p100/p0 tends to zero; f = 0.4 if p100/p0 tends to 1

    Warning in SAMSON Valve Sizing Specialist SVS / SVSS if SF < 1.1 recommended in hazardous areas = 1.25

  • Pneumatic actuator with a linear or rotational movement Page 031 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    Flow to close FTCFail safe ATCClosing safety factor:

    ( )( )

    su st100a

    m 2 b 1 d 3 a

    A p p 10FF f S f S f D

    =

    + +

    Open safety factor:

    ( )a st0

    m p1 1 d 3 a

    F A p 10F F f S f D

    =

    + +

    The term2

    p1 d 1F S p f 4 10

    =

    in case of pressure balance is nearly negligible f = 0 if p100/p0 tends to zero; f = 0.4 if p100/p0 tends to 1.

    Warning in SAMSON Valve Sizing Specialist SVS / SVSS if SF < 1.1 recommended in hazardous areas = 1.25

    Calculation example without pressure balance:Same method than above but delete f3 Da and replace Fp1 trust with Fp trust equations without pressure balance.

    Flow direction FTC Fail safe ATO

    Closing safety factor: a st0

    m 2 b 1 d

    F A p 10F f S f S

    =

    +

    Opening safety factor:

    ( )su st100am p 1 d

    A p p 10FF F f f S

    =

    +

    Warning in SAMSON Valve Sizing Specialist SVSS if SF < 1.1 recommended in hazardous areas = 1.25

    The term for the closing force

    ( )2 2b dF S S pp 4 10

    = Need to have a force correction for the open position with factor f: f = 0 if p100/p0 tends to zero; f = 0.4 if p100/p0 tends to 1f = 0.4 based on measurements with parabolic plugs (mentioned in VDI/VDE 3844)

  • Chapter 9. Control valve actuatorsPage 032 of 292

    SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main GermanyPhone: +49 69 4009-0 Fax: +49 69 4009-1507 E-mail: [email protected] Internet: www.samson.de

    9.2.6.7 Calculation of the Hysteresis:SAMSON VALVE SIZING SVSS specialist can check the hysteresis of the valve actuator system. A value which plays an important role for the total controllability.

    As a rule of thumb the hysteresis of a valve system without positioned should be < 5 % and with a positioner type of medium quality < 15%.

    For modern high quality positioners in the process industry SVSS the software generates a warning if the value is > 30%.

    ( )

    w

    st100 st0

    2 FHysteresis % 100 30 %

    10 A p p

    = <

    (9-14)

    If Hysteresis > 30% increase actuator stiffness: A (pst100 - pst0)

    More calculation examples are shown in Ch