Metra is the registered service mark for the Northeast Illinois Regional Commuter Railroad Corporation. May 23, 2018 Subject: Invitation for Bid No. 8521 Construction Services to Raise Piping from Underground to Aboveground at Metra’s Western Avenue Yard Addendum No. 2 Dear Sir/Madam: This Addendum No. 2 is being issued to correct, amend, add and/or delete certain words, phrases, sentences, or paragraphs in Invitation for Bid No. 8521. This Addendum No. 2 consists of: 1. Notice that Invitation for Bid Due Date has been changed: From: May 30, 2018 at 2:00 P.M. (LPT) To: June 5, 2018 at 2:00 P.M. (LPT) 2. Attached is a copy of the attachments submitted with Question 1, below. 3. Attached is a copy of the Site Assessment at Metra’s Western Avenue Facility 4. Attached is a copy of the first and second pre-bid meeting attendance sheets. 5. Metra’s response to vendorsquestions: No. Vendor Question Metra Response 1 I hereby respectfully request the name of Thermacor Preinsulated Piping Company be added by addendum to the above referenced project for the abovegrade prefabricated fuel system piping. Note that Thermacor is approved by Metra and currently under contract for similar piping with Protemp Contractors at the 47th street yard project. Specifications allow submitting products of manufacturers not named as long as they meet the salient characteristics that are indicated in the drawings and specifications.

Upload: others

Post on 14-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Metra is the registered service mark for the Northeast Illinois Regional Commuter Railroad Corporation.

May 23, 2018

Subject: Invitation for Bid No. 8521

Construction Services to Raise Piping from Underground to Aboveground at

Metra’s Western Avenue Yard

Addendum No. 2

Dear Sir/Madam:

This Addendum No. 2 is being issued to correct, amend, add and/or delete certain words, phrases,

sentences, or paragraphs in Invitation for Bid No. 8521.

This Addendum No. 2 consists of:

1. Notice that Invitation for Bid Due Date has been changed:

From: May 30, 2018 at 2:00 P.M. (LPT)

To: June 5, 2018 at 2:00 P.M. (LPT)

2. Attached is a copy of the attachments submitted with Question 1, below.

3. Attached is a copy of the Site Assessment at Metra’s Western Avenue Facility

4. Attached is a copy of the first and second pre-bid meeting attendance sheets.

5. Metra’s response to vendors’ questions:

No. Vendor Question Metra Response

1

I hereby respectfully request the name of

Thermacor Preinsulated Piping Company be

added by addendum to the above referenced

project for the abovegrade prefabricated fuel

system piping.

Note that Thermacor is approved by Metra and

currently under contract for similar piping with

Protemp Contractors at the 47th street yard

project.

Specifications allow submitting products of

manufacturers not named as long as they meet

the salient characteristics that are indicated in

the drawings and specifications.

Page 2: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

2

2

What is the invert elevation of the drain line we

are connecting to with manhole shown on S400 -

10? This must be field verified by the Contractor.

3 Is the soil removed from the site to be hauled off

as hazardous material?

Soil has been previously sampled and was

determined to not be hazardous. Soil sampling

will need to be conducted by the Contractor to

determine proper soil disposal procedures and

regulatory reporting requirements.

4 Is the ground water/perched water on site to be

hauled off site as hazardous material?

Unknown. Contractor will be responsible for

properly determining and managing per local

regulatory requirements.

5

Is there a current drawing of the existing water

line location at the new fuel boom area and end of

pipe bridge 1 to verify new footings will not

affect current location

This must be field verified by the Contractor.

6

Do you have a soil boring that has been

completed in the area that determine static soil

properties?

Yes. See attached Site Assessment report.

Contractor is responsible for determining soil

bearing capacities through testing prior to

beginning work.

7

Due to the complexity of material and subcontract

on this project I would like to request a Bid

Extension of two weeks to June 1, 2018.

The Invitation for Bid Due Date has been

changed:

From: May 30, 2018 at 2:00 P.M. (LPT)

To: June 5, 2018 at 2:00 P.M. (LPT)

8

The structural drawings do not specify any splices

in the pipe bridges. Are we able to utilize splices

to make shipping/handling/installing more

manageable? Or are the bridges to be constructed

as single pieces to the lengths specified, i.e. 70’,

108’ and 130’?

The structural drawings depict the end state.

Splices are not a design element; there is no

requirement for single pieces.

Page 3: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

3

9

In specification section 230529-8, Section 3.4.B,

it refers to a Painting Specification Section

099100. This specification section was not

provided in the bid documents. Can you please

provide it if painting it is required on this project.

Please advise.

Change to read: '3.4.B Touchup: Cleaning

and touchup painting of field welds, bolted

connections, and abraded areas of shop paint

on miscellaneous metal are specified in Section

055000 "Metal Fabrications".'

10

In specification section 230503-2 it states that the

contractors may have to work on the night shift

instead of the day shift. Please advise if all work

for this project must be done on the night shift.

Can the work inside the buildings be done on the

day shift?

Construction for the overhead piping shall be

Monday through Friday 6:00 a.m. -12:00 a.m.,

except for Tracks 7/8, for which work hours

shall be Monday through Friday 4:00 p.m. -

12:00 a.m.

Operations of the railroad facilities are to be

disrupted to a minimum extent. As stated in

Specification Section 230503, the contractors

should include in their bids any shift time,

weekend time, or overtime needed to minimize

disruptions.

11 If night shift is required, please advise on the

exact hours we can be on site Refer to the response for Question 10.

12

When the underground lines that are being

abandoned get the fluid pumped out, does Metra

intend to take possession of the fluids or are we to

dispose of them?

Contractor will be responsible for properly

removing and disposing of fluid being removed

from underground lines and disposing of

properly per local regulatory regulations. Any

recycling credits provided to the contractor by

fuel recycling companies will be credited back

to Metra.

13

Detail #9 on Sheet S202 shows walkway grates

that need to be provided. What is the total

quantity of these that are required? Are they

needed every so many feet?

Walkway grates are required at each lap joint,

as indicated in notes. The quantity of walkway

grates is determined by the number of joints

used. Match existing.

Page 4: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

4

14 Does the piping shown running inside the

building need to be insulated?

In accordance with specifications article

231113-3.16, indoor piping does not need to be

insulated.

15

Can you please provide a painting specification

with detail of exactly what needs to be painted on

the project?

All ferrous materials exposed outdoors and not

otherwise protected from corrosion are to be

painted. Specifications for painting of

products and materials are found in each

section for those items.

16

Drawing detail #1 on drawing S500 shows the

pipe supports for Coach House Building 4 with

the DFS pipe as external and the JOS, LOS and

LOR piping inside the building. The drawing

gives O.D. dimensions as if the JOS, LOS, and

LOR piping are insulated even though inside the

building. The question was posed during the bid

walk May 10th as to whether or not this needed to

be insulated piping. The answer given was that it

does not. Can we get a formal response as to

whether or not this piping inside Coach House 4

needs to be insulated?

In accordance with specifications article

231113-3.16, indoor piping does not need to be

insulated.

17

On Sheet S000, General Note #15 states “Any

Engineering design provided by others and

submitted for review or record shall bear the

stamp and signature of a PE.” Does this

statement mean that any structural items that are

submitted for review, whether already designed

by the Engineer of Record or not, has to have an

additional PE stamp?

Yes.

18

On Sheet S100 there is a note that states

“Contractor to engage and pay for a qualified

land surveyor or PE to survey adjacent existing

buildings, structures, and site improvements.”

Can you please advise to what extent we have to

survey the site? Do we only have to do the actual

areas where there will be new work, or does it

entail the entire facility?

Survey needs to be sufficient to document and

execute the work of this project only.

Page 5: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

19

20

21

22

23

On Sheet SOOO there is a note on the far righthand side of the page that states "Contractor to

engage and pay for a qualified geotechnicalengineering testing agency to perform tests andinspections and to provide geotechnical reports.

Can you please advise to what extent we need to

do these tests? Is it only for the immediate areasthat new work is being done?

Also, because we do not have an existinggeotechnical report we do not know where the

water table is on the site. Can you advise if

dewatering is going to be needed? And if so,what is to be done with any contaminated water?

On Sheet El 01 the drawn scale does not matchthe written scale of 1/32". Can you please advise

on the correct scale?

On Sheet M801, the pump schedule note #3,4 &5 refer to existing controls. Can you pleaseprovide the brand of controls that are existing?

We would like to formally request a timeextension so we will have enough time to have allthe subs review the addendum and be able to

make any adjustments that are needed.

Testing needs to be sufficient to establish thesoil properties required to document and

execute the work of this project.

Unknown. Contractor will be responsible for

properly determining and managing per local

regulatory requirements.

Scale is 1/32" = F-0" as written. Graphical

scale symbol is not correct size.

Existing control equipment is of variousbrands, including Square D and Artron

Products.

The Invitation for Bid Due Date has beenchanged:

From: May30,2018at2:OOP.M.(LPT)To: June 5,2018 at 2:00 P.M. (LPT)

Please acknowledge receipt of the Addendum in your bid submittal on paragraph 4.11 on page 7.

Failure to acknowledge this Addendum may result in your bid being determined non-responsive.

Sincerely,

^f^t^//

James Barker

Department HeadConstruction & Facilities Maintenance Procurement

JB/pp

Page 6: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

TG-aE^mCO^ PGFWtS SYSTEMSPrefabricated/pre-insulated jacketed piping systems for above or

below grade use. Prefabricated manholes/ heat traced piping

containment pipe systems ana catnoaic protection.

r=fvei

.^S)FLEKEC^AFT 3^©VST^GE^Pipe expansion joints, rubber joints, pipe guides/ stainless steel flex

connectors/ special/small expansion loops, link type pipe seals/ wall

sleeves, puisation aampeners ana surge suppressors.

S»SOB¥i NEATT^ACEElectric heat trace cables for freeze protection or temperature

maintenance for piping.

Addendum 2Attachment RE: Question 1

1

Page 7: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Addendum 2Attachment RE: Question 1

2

Page 8: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

United States | Canada | Brazil | UK | Ireland | Netherlands | Australia Asia Pacific | Russia | Middle East | Africa

135 S. LaSalle Street, Suite 3500, Chicago, IL 60603 USA T +1-312-541-4200 F +1 312-541-0340 W www.rpsgroup.com | www.gaiatech.com

Confidential October 6, 2016 

Todd Cabonor Metra Department Head – Industrial Hygiene 547 West Jackson Boulevard, 7th Floor Chicago, Illinois 60661 

Re:  Site Assessment  Western Avenue Yard 2741 West Grand Ave Chicago, Illinois 

Dear Mr. Cabonor: 

GaiaTech  Incorporated dba as RPS GaiaTech has completed a Site Assessment at  the Western Avenue facility  located  at  2741 West  Grand  Avenue,  Chicago,  Illinois  (the  “Site”).  The  scope  of  work  was completed in accordance with the approved proposal, dated April 14, 2016.  

BACKGROUND 

Metra  operates  a  rail  yard  at  2741  West  Grand  Avenue  in  Chicago,  IL  which  includes  a  fuel  and petroleum product storage and dispensing area. Metra  is planning to replace approximately 850  linear feet of below grade piping with new above ground  lines. Approximately 750  linear  feet of  the piping runs  underneath  or  near  the  tracks  in  the  active  rail  yard,  therefore  the  below  grade  piping will  be abandoned in place.  

Removal and closure of UST  system components  (including piping)  is  regulated under 35IAC Part 175 (Technical Requirements  for USTs) and Part 176  (Administrative Requirements  for USTs). Part 175.840 outlines  the  requirements which must be met  in order  to  abandon UST  components  in place.  These requirements include a demonstration of eligibility for a waiver of the removal requirement for the UST and/or piping, which is typically only granted where it would be infeasible to remove the system due to loss of adjacent or  subjacent  support of nearby  structures,  such as  railroad  tracks,  streets, and other USTs. This determination may be made by a professional engineer, and  is subject to OSFM review  for approval. Part 175.840 also  requires preparation of a Certificate of Site Conditions with site drawings prior to abandoning the UST and/or piping. 

Part 176.330 outlines the requirements  for completing a Site Assessment prior to abandoning a UST  ‐ the  same  requirements  apply  to  a UST  system  or  portions  of  a UST  system,  including  underground piping.  The  procedures  for  selecting  sample  locations  for  a  Site Assessment  under  Part  176.330  are referenced  and  described  in  Part  734.210  (Pollution  Control  Board,  Early  Action  for  USTs).  These 

Addendum 2Site Assessment

Page 9: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Mr. Todd Cabonor October 6, 2016 Page 2 

requirements include two soil borings/samples (one on each side of the piping) for every 20 linear feet (or  fraction  thereof) of piping. Part 734.210 directs  the agency  to excuse  the drilling of one or more borings  if  drilling  is made  impractical  by  site‐specific  circumstances.  RPS  GaiaTech  understands  that active railroad tracks are recognized by the agency as making soil borings in those locations impractical.   SCOPE OF WORK  The subject site assessment consisted of 10 soil borings, one installed along each side of the piping run, spaced every 20 feet. Per Part 734.210, these borings were conducted to a maximum depth of 15 feet and  at  least  1  soil  sample was  collected  from  each  5  foot  section of  each boring,  at  a depth where contamination  is most  likely  to  be  present.  Samples were  analyzed  for  volatile  organic  compounds (VOCs) and polynuclear aromatic hydrocarbons (PAHs).  Prior to field work, utilities were cleared through the Illinois and City of Chicago one call utility locating services.  Ground  Penetrating  Radar  Systems,  Inc.  (GPRS),  under  the  direction  of  RPS  GaiaTech, performed a geophysical survey of the proposed sampling locations for evidence of unidentified buried utilities or underground structures.  On May 7, 2016 and  June 8, 2016 RPS GaiaTech mobilized  to  the site with a direct push  (Geoprobe®) contractor  to  conduct  the  soil borings. Due  to  the  possibility of buried utilities  in  the  vicinity of  the sample  locations,  an  “air  knife” was  to  be  used  to  prevent  damage.  An  air  knife  consists  of  an  air compressor which  provides  the  air movement  for  a  vacuum  unit.  This  vacuum,  combined with  the compressed air, allows for the safe excavation of soil and gravel without damaging the buried utilities. The air knife was used to excavate a 5‐inch diameter borehole to a depth of 5 feet below ground surface (bgs) at each boring. The Geoprobe® was then used to conduct the remainder of the boring.   A  total of eleven borings were conducted. Soil boring  locations are  illustrated on  the Boring Location Map (Figure 1). Individual sample locations were selected to be as close as possible to the underground piping trench while providing adequate clearance for the underground utilities and the rail tracks.   The  soil borings were  completed using direct push and air knife  technology, as described above. The borings were  advanced  to  a maximum depth of 15  feet bgs. The down‐hole non‐dedicated  sampling equipment  was  decontaminated  between  locations  using  an  Alconox®/water  wash  and  scrubbing, followed by a potable water  rinse. New and disposable  sampling materials were used when possible (e.g., plastic sample liners and gloves).    During use of  the Geoprobe®, continuous soil samples were collected using steel sampling  tubes with plastic  sample  liners.  The  soil  samples  collected  from  each  bore  hole  were  visually  described  and classified using  the Unified Soil Classification System as a guide. Observations were also made  for  the presence of  fill material and visual/olfactory evidence to suggest  impact  (e.g., unusual odors, staining, etc.)    Representative samples of  the soil  intervals were placed  in sealed plastic bags  for headspace analysis with a photoionization detector (PID). The PID readings are expressed in units of parts per million (ppm) by volume, relative to an isobutylene standard. The field screening was used to provide an indication of 

Page 10: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Mr. Todd Cabonor October 6, 2016 Page 3 

the  potential  presence  of  volatile  organic  constituents  and  to  aid  in  the  selection  of  samples  for laboratory analysis. The soil sample descriptions and the field screening results were recorded on boring logs (see Appendix A).   Based on field screening results and visual observations, one soil sample was selected from each 5‐foot sample liner for laboratory analysis. Soil samples for analysis were placed in laboratory supplied jars and stored  in  a  cooler  with  ice.  Appropriate  decontamination  procedures  were  followed  during  sample collection and proper chain of custody procedures were employed.   At  the  completion  of  sampling,  the  Geoprobe  section  of  each  boring  location  was  backfilled  with bentonite  chips  and  excess  cuttings.  The  railroad ballast material  (coarse  gravel)  encountered  in  the upper portion of each boring (see geology section below) removed by the air knife was returned to the upper portion of  the borehole. The surface was  then patched  (if necessary)  to match  the pre‐existing conditions (concrete).      Analytical Testing Program The soil samples were submitted to Stat Analysis following standard chain‐of‐custody procedures. The soil samples were analyzed in accordance with United States Environmental Protection Agency (USEPA) SW‐846 Methods  for  VOCs  using  USEPA Method  8260B  and  PAHs  using  USEPA Method  8270C,  as required under Part 734.210.   FINDINGS  Geology and Hydrogeology The  subsurface  conditions  at  the  Site  generally  consist  of  gravel  backfill  (primarily  railroad  ballast material)  to  a depth of  approximately 7  feet bgs underlain by  silty  clays. At  some  locations perched water was present in the backfill at 5.5 feet bgs. Soil boring logs are presented in Appendix A.   Field Screening Results Elevated PID readings were recorded from soil samples collected from borings WA‐8 and WA‐10.  Analytical Results RPS GaiaTech compared the analytical results to the screening levels established in IEPA’s TACO. The soil analytical  results  are  summarized  in  Table 1.  The  analytical  reports  and  chain‐of‐custody  records  are included in Appendix B.  Select  PAH  compounds  were  detected  in  soil  samples  in  excess  of  the  default  background concentrations developed by  IEPA  for  the City of Chicago. However,  the detected compounds did not exceed the default TACO standards.   CONCLUSIONS  RPS GaiaTech has completed the investigation at the Western Avenue Yard facility located at 2741 West Grand Avenue, Chicago, Illinois. The following conclusions are based on the observations and analytical results obtained during this investigation: 

Page 11: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Mr. Todd Cabonor October 6, 2016 Page 4 

 

Concentrations  of  PAH  compounds were  detected  in  soil  samples  above  the  default  City  of Chicago background levels, but below the TACO Soil Remediation Objectives. 

The  results of  this  investigation may be used  in  the application of a permit  from  the Chicago Department  of  Public Health  for  the  removal  and/or  abandonment  of  the  underground  pipe lines at the site. 

 CLOSURE  We  appreciate  the  opportunity  to  be  of  service  on  this  project.  Please  do  not  hesitate  to  call  the undersigned at 312‐541‐4200, if you have any questions or comments.  Sincerely,    RPS GaiaTech   Technical Review and    Concurrence by:            Adam Page    Eric Leitz Senior Geologist    Senior Geologist  Attachments:  Figure 1 – Sample Location Map     Table 1 ‐ Soil Analytical Results Summary      Appendix A ‐ Soil Boring Logs      Appendix B ‐ Laboratory Analytical Report     Appendix C – OSFM Site Assessment Results Report Form 

Page 12: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Figure & Table

Page 13: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the
Page 14: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Table 1Soil Sample Analytical Results

Metra - Western AveChicago, IL

Boring ID WA-3 SA-1 WA-5 WA-6 WA-7Sample Depth 0-5 8-9 0-5 9-10 0-5 0-5 8-10 0-4 8-10 8-10 10-12.5 7-10 10-12.5 5-10 10-15 3 5-7 10-12.5Collection Date Ingestion Inhalation Ingestion Inhalation Ingestion Inhalation Class I Class II 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 05/07/2016 06/08/2016 06/08/2016 06/08/2016 06/08/2016 06/08/2016

BTEX‐USEPA Methods 

5035A/8260B

Benzene 12 0.8 100 1.6 2,300 2.2 0.03 0.17 NE < 0.0061 < 0.0049 < 0.0060 < 0.0059 < 0.0056 < 0.0056 < 0.0049 < 0.0050 < 0.0056 < 0.0050 < 0.0051 < 0.0090 < 0.0048 < 0.0052 < 0.0052 < 0.0045 < 0.0070 < 0.0048Ethylbenzene 7,800 400 200,000 400 20,000 58 13 19 NE < 0.0061 < 0.0049 < 0.0060 < 0.0059 < 0.0056 < 0.0056 < 0.0049 < 0.0050 < 0.0056 < 0.0050 < 0.0051 < 0.0090 < 0.0048 < 0.0052 < 0.0052 < 0.0045 < 0.0070 < 0.0048Toluene 16,000 650 410,000 650 410,000 42 12 29 NE < 0.0061 < 0.0049 < 0.0060 < 0.0059 < 0.0056 < 0.0056 < 0.0049 < 0.0050 < 0.0056 < 0.0050 < 0.0051 < 0.0090 < 0.0048 < 0.0052 < 0.0052 < 0.0045 < 0.0070 < 0.0048Xylenes, Total 16,000 320 410,000 320 41,000 5.6 150 150 NE < 0.019 < 0.015 < 0.018 < 0.018 < 0.017 < 0.016 0.03 < 0.016 < 0.017 < 0.016 < 0.016 < 0.026 < 0.015 < 0.016 < 0.016 < 0.014 < 0.021 < 0.014

PNAs‐ USEPA Method  

8310

Acenaphthene 4,700 --- 120,000 --- 120,000 --- 570 2,900 0.09 < 0.035 0.16 < 0.034 < 0.039 < 0.035 0.21 < 0.040 < 0.037 < 0.042 < 0.042 < 0.040 1.9 < 0.040 < 0.041 < 0.041 < 0.039 0.37 < 0.041Anthracene 23,000 --- 610,000 --- 610,000 --- 12,000 59,000 0.25 < 0.035 0.075 0.037 < 0.039 < 0.035 0.18 < 0.040 0.18 < 0.042 < 0.042 < 0.040 0.79 < 0.040 < 0.041 < 0.041 < 0.039 0.24 < 0.041Benz(a)anthracene 0.9 --- 8 --- 170 --- 2 8 1.1 < 0.035 < 0.040 0.094 < 0.039 < 0.035 0.25 < 0.040 0.3 < 0.042 < 0.042 < 0.040 0.073 < 0.040 < 0.041 < 0.041 < 0.039 0.081 < 0.041Benzo(a)pyrene 0.09 --- 0.8 --- 17 --- 8 82 1.3 < 0.035 < 0.040 0.1 < 0.039 0.036 0.21 < 0.040 0.3 < 0.042 < 0.042 < 0.040 < 0.050 < 0.040 < 0.041 < 0.041 < 0.039 0.065 < 0.041Benzo(b)fluoranthene 0.9 --- 8 --- 170 --- 5 25 1.5 < 0.035 < 0.040 0.14 < 0.039 0.045 0.21 < 0.040 0.4 < 0.042 < 0.042 < 0.040 0.055 < 0.040 < 0.041 < 0.041 < 0.039 0.097 < 0.041Benzo(g,h,i)perylene NE NE NE NE NE NE NE NE 0.68 < 0.035 < 0.040 0.1 < 0.039 < 0.035 0.13 < 0.040 0.27 < 0.042 < 0.042 < 0.040 < 0.050 < 0.040 < 0.041 < 0.041 < 0.039 0.057 < 0.041Benzo(k)fluoranthene 9 --- 78 --- 1,700 --- 49 250 0.99 < 0.035 < 0.040 0.088 < 0.039 < 0.035 0.21 < 0.040 0.24 < 0.042 < 0.042 < 0.040 < 0.050 < 0.040 < 0.041 < 0.041 < 0.039 0.073 < 0.041Chrysene 88 --- 780 --- 17,000 --- 160 800 1.2 < 0.035 < 0.040 0.12 < 0.039 0.046 0.26 < 0.040 0.39 < 0.042 < 0.042 < 0.040 0.1 < 0.040 < 0.041 < 0.041 < 0.039 0.13 < 0.041Dibenz(a,h)anthracene 0.09 --- 0.8 --- 17 --- 2 7.6 0.2 < 0.035 < 0.040 < 0.034 < 0.039 < 0.035 < 0.035 < 0.040 0.064 < 0.042 < 0.042 < 0.040 < 0.050 < 0.040 < 0.041 < 0.041 < 0.039 < 0.042 < 0.041Fluoranthene 3,100 --- 82,000 --- 82,000 --- 4,300 21,000 2.7 0.047 < 0.040 0.17 < 0.039 0.067 0.55 < 0.040 0.49 < 0.042 < 0.042 < 0.040 0.27 < 0.040 < 0.041 < 0.041 < 0.039 0.31 < 0.041Fluorene 3,100 --- 82,000 --- 82,000 --- 560 2,800 0.1 < 0.035 0.19 0.054 < 0.039 < 0.035 0.23 < 0.040 0.22 < 0.042 < 0.042 < 0.040 < 0.050 < 0.040 < 0.041 < 0.041 < 0.039 0.28 < 0.041Indeno(1,2,3-cd)pyrene 0.9 --- 8 --- 170 --- 14 69 0.86 < 0.035 < 0.040 0.077 < 0.039 < 0.035 0.12 < 0.040 0.21 < 0.042 < 0.042 < 0.040 < 0.050 < 0.040 < 0.041 < 0.041 < 0.039 < 0.042 < 0.041Naphthalene 1,600 170 41,000 270 4,100 1.8 12 18 0.04 < 0.035 < 0.040 < 0.034 < 0.039 < 0.035 0.055 < 0.040 < 0.037 < 0.042 < 0.042 < 0.040 < 0.050 < 0.040 < 0.041 < 0.041 < 0.039 < 0.042 < 0.041Phenanthrene NE NE NE NE NE NE NE NE 1.3 < 0.035 0.4 0.18 < 0.039 0.056 0.63 < 0.040 0.44 < 0.042 < 0.042 < 0.040 4.2 < 0.040 < 0.041 < 0.041 < 0.039 0.7 0.11Pyrene 2,300 --- 61,000 --- 61,000 --- 4,200 21,000 1.9 0.044 0.049 0.16 < 0.039 0.064 0.5 < 0.040 0.68 < 0.042 < 0.042 < 0.040 0.35 < 0.040 < 0.041 < 0.041 < 0.039 0.4 < 0.041

Notes:Samples analyzed at STAT Analysis Corporation, Chicago, IL; Only detected analytes are listed.Comparison Standards Adapted from IEPA TACO (Section 742 Appendix B)BTEX: Benzene, Toluene, Ethylbenzene and Xylenes PNAs: Polynuclear AromaticsNE: Not Estabilishedug/L is approximately equivalent to parts per billion (ppb)Bold values indicate levels that exceed Chicago Background PAH ConcentrationsUnderlinded values indicate levels that exceed Residential Soil Ingestion, or Inhalation Values

mg/Kg

WA-4 WA-8Default Background

Concentrations

mg/Kg

mg/Kg

ResidentialRoute Specific Values for Soil

Industrial/Commercial Route Specific Values for Soil

Construction Worker Route Specific Values for Soil

WA-9 WA-10

mg/Kg

Groundwater Ingestion Exposure Route Values

WA-1 WA-2

Page 1

Page 15: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Appendix A:

Soil Boring Logs

Page 16: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-1.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-1

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 15 ft bgs

Total Depth of Well : 15 ft bgs

Logged By : EL

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

12

14

16

Sam

ple

1

2

3

Blo

w C

ount

% R

ecov

ery

AK

80

100

PID

(pp

m)

0.9

42.7

8.4

US

CS

FL

CL

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose, slight diesel odor

4.5' - saturated, strong diesel odor, black staining, oily

SILTY CLAY, greenish gray, soft, plastic, moist

11' - Brown

End of Boring at 15 ft bgs

WA-1

Page 17: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-2.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-2

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 10 ft bgs

Total Depth of Well : 10 ft bgs

Logged By : EL

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

Sam

ple

1

2

Blo

w C

ount

% R

ecov

ery

AK

90

PID

(pp

m)

38.5

0.5

US

CS

FL

CL

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose, diesel odor

5' - saturated, strong diesel odor, sheen, oily

SILTY CLAY, greenish gray, soft, plastic, moist

End of Boring at 10 ft bgs

WA-2

Page 18: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-3.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-3

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 10 ft bgs

Total Depth of Well : 10 ft bgs

Logged By : EL

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

Sam

ple

1

2

Blo

w C

ount

% R

ecov

ery

AK

90

PID

(pp

m)

6.6

221.6

US

CS

FL

CL

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose, diesel odor

4.5' - saturated, strong diesel odor, sheen, oily

SILTY CLAY, greenish gray, soft, plastic, moist

End of Boring at 10 ft bgs

WA-3

Page 19: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-4.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-4

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 10 ft bgs

Total Depth of Well : 10 ft bgs

Logged By : EL

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

Sam

ple

1

2

Blo

w C

ount

% R

ecov

ery

AK

90

PID

(pp

m)

24.2

6.7

US

CS

FL

CL

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose, diesel odor

4.5' - saturated, strong diesel odor, sheen, oily

SILTY CLAY, greenish gray, soft, plastic, moist

End of Boring at 10 ft bgs

WA-4

Page 20: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-5.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-5

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 10 ft bgs

Total Depth of Well : 10 ft bgs

Logged By : AP

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

Sam

ple

1

2

3

Blo

w C

ount

% R

ecov

ery

AK

0

100

PID

(pp

m)

--

--

2.4

US

CS

FL

CL

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose, diesel odor

5' - saturated, strong diesel odor, sheen, oily

SILTY CLAY, greenish gray, low plasticicty, diesel/oil odor

End of Boring at 10 ft bgs

WA-5

Page 21: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-6.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-6

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 10 ft bgs

Total Depth of Well : 10 ft bgs

Logged By : AP

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

Sam

ple

1

2

3

Blo

w C

ount

% R

ecov

ery

AK

0

100

PID

(pp

m)

--

--

2.6

US

CS

FL

CL

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose, diesel odor

5' - Wet without diesel odor

SILTY CLAY, greenish gray, low plasticicty, diesel/oil odor

End of Boring at 10 ft bgs

WA-6

Page 22: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-7.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-7

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 15 ft bgs

Total Depth of Well : 15 ft bgs

Logged By : AP

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

12

14

16

Sam

ple

1

2

3

4

Blo

w C

ount

% R

ecov

ery

AK

5

100

100

PID

(pp

m)

--

0.4

0.2

0.1

US

CS

FL

CL

CL

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose, with wood debris

SILTY CLAY, greenish gray, dry, hard

SILTY CLAY, tan-brown dry, hard

End of Boring at 15 ft bgs

WA-7

Page 23: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-8.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-8

FUNCTION INFORMATION

Date/Time Started : 5/7/16

Date/Time Completed : 5/7/16

Total Depth of Boring : 15 ft bgs

Total Depth of Well : 15 ft bgs

Logged By : AP

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

12

14

16

Sam

ple

1

2

3

4

5

Blo

w C

ount

% R

ecov

ery

AK

0

5

90

90

PID

(pp

m)

--

--

150.5

9.0

1.5

US

CS

FL

SP-GR

GR

AP

HIC

DESCRIPTION

FILL - Course gravel (RR ballast) some fines, loose

5' - Black with diesel/oil odor

SAND and GRAVEL, black, diesel odor

End of Boring at 15 ft bgs

WA-8

Page 24: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-9.b

or

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-9

FUNCTION INFORMATION

Date/Time Started : 6/8/16

Date/Time Completed : 6/8/16

Total Depth of Boring : 15 ft bgs

Total Depth of Well : 15 ft bgs

Logged By : AP

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

12

14

16

Sam

ple

1

2

3

Blo

w C

ount

% R

ecov

ery

AK

5

25

PID

(pp

m)

0.1

17.9

3.9

US

CS

FL

CL

GR

AP

HIC

DESCRIPTION

Concrete

Pea GRAVEL, Loose Dry

8' - Black, wet, with oil odor

Gray SILTY CLAY, moist

End of Boring at 15 ft bgs

WA-9

Page 25: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

10-1

0-20

16 C

:\Use

rs\A

Pag

e\D

eskt

op\M

ET

RA

- W

este

rn A

ve\b

orel

ogs\

WA

-10.

bor

Metra Western AveChicago, IL

GaiaTech Project #161602

GAIATECH BORING LOG WA-10

FUNCTION INFORMATION

Date/Time Started : 6/8/16

Date/Time Completed : 6/8/16

Total Depth of Boring : 15 ft bgs

Total Depth of Well : 15 ft bgs

Logged By : AP

Drilling Method : Air Knife/Geoprobe

Hole Diameter : 6 inches/2 Inches

Drilling Company : Cabeno

Sampling Method : Macrocore

DepthIn

Feet

0

2

4

6

8

10

12

14

16

Sam

ple

1

2

3

4

5

6

7

Blo

w C

ount

% R

ecov

ery

AK

100

100

50

50

100

100

PID

(pp

m)

0.1

1.2

0.3

52.7

48.4

23

12.4

US

CS

FL

CL

CL

SW

CL

GR

AP

HIC

DESCRIPTION

Concrete

Pea GRAVEL, Loose Dry

Dark gray SILTY CLAY, dry, hard

Black SILTY CLAY, dry hard, diesel odor

Black SILTY SAND, trace gravel, moist, diesel odor

Olive gray SILTY CLAY, dry medium plasticity

End of Boring at 15 ft bgs

WA-10

Page 26: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Appendix B:

Laboratory Analytical Reports

Page 27: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Page 1 of 22

Page 28: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

May 16, 2016Date:STAT Analysis Corporation

Project: Western Metra, Chicago, ILClient: Gaiatech

Work Order: 16050373Work Order Sample Summary

Lab Sample ID Client Sample ID Collection DateTag Number Date Received

Revision 0

16050373-001A WA-1 0-5 5/7/2016 11:40:00 AM 5/9/201616050373-001B WA-1 0-5 5/7/2016 11:40:00 AM 5/9/201616050373-002A WA-2 0-5 5/7/2016 11:55:00 AM 5/9/201616050373-002B WA-2 0-5 5/7/2016 11:55:00 AM 5/9/201616050373-003A WA-3 0-5 5/7/2016 12:00:00 PM 5/9/201616050373-003B WA-3 0-5 5/7/2016 12:00:00 PM 5/9/201616050373-004A WA-4 0-5 5/7/2016 12:05:00 PM 5/9/201616050373-004B WA-4 0-5 5/7/2016 12:05:00 PM 5/9/201616050373-005A SA-1 5/7/2016 12:15:00 PM 5/9/201616050373-005B SA-1 5/7/2016 12:15:00 PM 5/9/201616050373-006A WA-5 8-10 5/7/2016 3:25:00 PM 5/9/201616050373-006B WA-5 8-10 5/7/2016 3:25:00 PM 5/9/201616050373-007A WA-6 8-10 5/7/2016 3:45:00 PM 5/9/201616050373-007B WA-6 8-10 5/7/2016 3:45:00 PM 5/9/201616050373-008A WA-7 10-12.5 5/7/2016 3:35:00 PM 5/9/201616050373-008B WA-7 10-12.5 5/7/2016 3:35:00 PM 5/9/201616050373-009A WA-8 7-10 5/7/2016 3:55:00 PM 5/9/201616050373-009B WA-8 7-10 5/7/2016 3:55:00 PM 5/9/201616050373-010A WA-8 10-12.5 5/7/2016 4:00:00 PM 5/9/201616050373-010B WA-8 10-12.5 5/7/2016 4:00:00 PM 5/9/201616050373-011A WA-1 5/7/2016 1:00:00 PM 5/9/201616050373-011B WA-1 5/7/2016 1:00:00 PM 5/9/201616050373-012A WA-2 5/7/2016 1:30:00 PM 5/9/201616050373-013A WA-3 5/7/2016 2:05:00 PM 5/9/201616050373-014A WA-4 5/7/2016 3:25:00 PM 5/9/201616050373-014B WA-4 5/7/2016 3:25:00 PM 5/9/201616050373-015A WA-1 8-9 5/7/2016 12:20:00 PM 5/9/201616050373-015B WA-1 8-9 5/7/2016 12:20:00 PM 5/9/201616050373-016A WA-2 9-10 5/7/2016 12:25:00 PM 5/9/201616050373-016B WA-2 9-10 5/7/2016 12:25:00 PM 5/9/201616050373-017A WA-4 8-10 5/7/2016 12:35:00 PM 5/9/201616050373-017B WA-4 8-10 5/7/2016 12:35:00 PM 5/9/2016

Page 2 of 22

Page 29: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

May 16, 2016Date:STAT Analysis Corporation

Project: Western Metra, Chicago, ILCLIENT: Gaiatech

Work Order: 16050373CASE NARRATIVE

Revision 0

Due to matrix interference, sample WA-8 7-10 (16050373-9A) has VOC surrogate Toluene-d8 outside of control limits (138% recovery, QC Limits 73-122%). All other surrogates are within control limits.

Page 3 of 22

Page 30: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-1 0-5Collection Date: 5/7/2016 11:40:00 AM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-001

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0061 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0061 mg/Kg-dry 1ND

Toluene 5/10/20160.0061 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.019 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.035 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.035 mg/Kg-dry 1ND

Anthracene 5/12/20160.035 mg/Kg-dry 1ND

Benz(a)anthracene 5/12/20160.035 mg/Kg-dry 1ND

Benzo(a)pyrene 5/12/20160.035 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/12/20160.035 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/12/20160.035 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/12/20160.035 mg/Kg-dry 1ND

Chrysene 5/12/20160.035 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/12/20160.035 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.035 mg/Kg-dry 10.047

Fluorene 5/12/20160.035 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/12/20160.035 mg/Kg-dry 1ND

Naphthalene 5/12/20160.035 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.035 mg/Kg-dry 1ND

Pyrene 5/12/20160.035 mg/Kg-dry 10.044

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 18.5

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 4 of 22

Page 31: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-2 0-5Collection Date: 5/7/2016 11:55:00 AM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-002

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0060 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0060 mg/Kg-dry 1ND

Toluene 5/10/20160.0060 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.018 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.034 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.034 mg/Kg-dry 1ND

Anthracene 5/12/20160.034 mg/Kg-dry 10.037

Benz(a)anthracene 5/12/20160.034 mg/Kg-dry 10.094

Benzo(a)pyrene 5/12/20160.034 mg/Kg-dry 10.10

Benzo(b)fluoranthene 5/12/20160.034 mg/Kg-dry 10.14

Benzo(g,h,i)perylene 5/12/20160.034 mg/Kg-dry 10.10

Benzo(k)fluoranthene 5/12/20160.034 mg/Kg-dry 10.088

Chrysene 5/12/20160.034 mg/Kg-dry 10.12

Dibenz(a,h)anthracene 5/12/20160.034 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.034 mg/Kg-dry 10.17

Fluorene 5/12/20160.034 mg/Kg-dry 10.054

Indeno(1,2,3-cd)pyrene 5/12/20160.034 mg/Kg-dry 10.077

Naphthalene 5/12/20160.034 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.034 mg/Kg-dry 10.18

Pyrene 5/12/20160.034 mg/Kg-dry 10.16

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 15.3

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 5 of 22

Page 32: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-3 0-5Collection Date: 5/7/2016 12:00:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-003

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0056 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0056 mg/Kg-dry 1ND

Toluene 5/10/20160.0056 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.017 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.035 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.035 mg/Kg-dry 1ND

Anthracene 5/12/20160.035 mg/Kg-dry 1ND

Benz(a)anthracene 5/12/20160.035 mg/Kg-dry 1ND

Benzo(a)pyrene 5/12/20160.035 mg/Kg-dry 10.036

Benzo(b)fluoranthene 5/12/20160.035 mg/Kg-dry 10.045

Benzo(g,h,i)perylene 5/12/20160.035 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/12/20160.035 mg/Kg-dry 1ND

Chrysene 5/12/20160.035 mg/Kg-dry 10.046

Dibenz(a,h)anthracene 5/12/20160.035 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.035 mg/Kg-dry 10.067

Fluorene 5/12/20160.035 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/12/20160.035 mg/Kg-dry 1ND

Naphthalene 5/12/20160.035 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.035 mg/Kg-dry 10.056

Pyrene 5/12/20160.035 mg/Kg-dry 10.064

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 17.0

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 6 of 22

Page 33: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-4 0-5Collection Date: 5/7/2016 12:05:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-004

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0056 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0056 mg/Kg-dry 1ND

Toluene 5/10/20160.0056 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.016 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.035 mg/Kg-dry 10.21

Acenaphthylene 5/12/20160.035 mg/Kg-dry 1ND

Anthracene 5/12/20160.035 mg/Kg-dry 10.18

Benz(a)anthracene 5/12/20160.035 mg/Kg-dry 10.25

Benzo(a)pyrene 5/12/20160.035 mg/Kg-dry 10.21

Benzo(b)fluoranthene 5/12/20160.035 mg/Kg-dry 10.21

Benzo(g,h,i)perylene 5/12/20160.035 mg/Kg-dry 10.13

Benzo(k)fluoranthene 5/12/20160.035 mg/Kg-dry 10.21

Chrysene 5/12/20160.035 mg/Kg-dry 10.26

Dibenz(a,h)anthracene 5/12/20160.035 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.035 mg/Kg-dry 10.55

Fluorene 5/12/20160.035 mg/Kg-dry 10.23

Indeno(1,2,3-cd)pyrene 5/12/20160.035 mg/Kg-dry 10.12

Naphthalene 5/12/20160.035 mg/Kg-dry 10.055

Phenanthrene 5/12/20160.035 mg/Kg-dry 10.63

Pyrene 5/12/20160.035 mg/Kg-dry 10.50

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 16.8

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 7 of 22

Page 34: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: SA-1Collection Date: 5/7/2016 12:15:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-005

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0050 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0050 mg/Kg-dry 1ND

Toluene 5/10/20160.0050 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.016 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.037 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.037 mg/Kg-dry 1ND

Anthracene 5/12/20160.037 mg/Kg-dry 10.18

Benz(a)anthracene 5/12/20160.037 mg/Kg-dry 10.30

Benzo(a)pyrene 5/12/20160.037 mg/Kg-dry 10.30

Benzo(b)fluoranthene 5/12/20160.037 mg/Kg-dry 10.40

Benzo(g,h,i)perylene 5/12/20160.037 mg/Kg-dry 10.27

Benzo(k)fluoranthene 5/12/20160.037 mg/Kg-dry 10.24

Chrysene 5/12/20160.037 mg/Kg-dry 10.39

Dibenz(a,h)anthracene 5/12/20160.037 mg/Kg-dry 10.064

Fluoranthene 5/12/20160.037 mg/Kg-dry 10.49

Fluorene 5/12/20160.037 mg/Kg-dry 10.22

Indeno(1,2,3-cd)pyrene 5/12/20160.037 mg/Kg-dry 10.21

Naphthalene 5/12/20160.037 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.037 mg/Kg-dry 10.44

Pyrene 5/12/20160.037 mg/Kg-dry 10.68

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 110.7

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 8 of 22

Page 35: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-5 8-10Collection Date: 5/7/2016 3:25:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-006

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0056 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0056 mg/Kg-dry 1ND

Toluene 5/10/20160.0056 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.017 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.042 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.042 mg/Kg-dry 1ND

Anthracene 5/12/20160.042 mg/Kg-dry 1ND

Benz(a)anthracene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(a)pyrene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/12/20160.042 mg/Kg-dry 1ND

Chrysene 5/12/20160.042 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/12/20160.042 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.042 mg/Kg-dry 1ND

Fluorene 5/12/20160.042 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/12/20160.042 mg/Kg-dry 1ND

Naphthalene 5/12/20160.042 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.042 mg/Kg-dry 1ND

Pyrene 5/12/20160.042 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 121.6

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 9 of 22

Page 36: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-6 8-10Collection Date: 5/7/2016 3:45:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-007

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0050 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0050 mg/Kg-dry 1ND

Toluene 5/10/20160.0050 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.016 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.042 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.042 mg/Kg-dry 1ND

Anthracene 5/12/20160.042 mg/Kg-dry 1ND

Benz(a)anthracene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(a)pyrene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/12/20160.042 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/12/20160.042 mg/Kg-dry 1ND

Chrysene 5/12/20160.042 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/12/20160.042 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.042 mg/Kg-dry 1ND

Fluorene 5/12/20160.042 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/12/20160.042 mg/Kg-dry 1ND

Naphthalene 5/12/20160.042 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.042 mg/Kg-dry 1ND

Pyrene 5/12/20160.042 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 122.6

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 10 of 22

Page 37: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-7 10-12.5Collection Date: 5/7/2016 3:35:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-008

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0051 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0051 mg/Kg-dry 1ND

Toluene 5/10/20160.0051 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.016 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.040 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.040 mg/Kg-dry 1ND

Anthracene 5/12/20160.040 mg/Kg-dry 1ND

Benz(a)anthracene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(a)pyrene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/12/20160.040 mg/Kg-dry 1ND

Chrysene 5/12/20160.040 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/12/20160.040 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.040 mg/Kg-dry 1ND

Fluorene 5/12/20160.040 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/12/20160.040 mg/Kg-dry 1ND

Naphthalene 5/12/20160.040 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.040 mg/Kg-dry 1ND

Pyrene 5/12/20160.040 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 118.1

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 11 of 22

Page 38: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-8 7-10Collection Date: 5/7/2016 3:55:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-009

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 5/9/2016Benzene 5/10/20160.0090 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0090 mg/Kg-dry 1ND

Toluene 5/10/20160.0090 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.026 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.050 mg/Kg-dry 11.9

Acenaphthylene 5/12/20160.050 mg/Kg-dry 1ND

Anthracene 5/12/20160.050 mg/Kg-dry 10.79

Benz(a)anthracene 5/12/20160.050 mg/Kg-dry 10.073

Benzo(a)pyrene 5/12/20160.050 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/12/20160.050 mg/Kg-dry 10.055

Benzo(g,h,i)perylene 5/12/20160.050 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/12/20160.050 mg/Kg-dry 1ND

Chrysene 5/12/20160.050 mg/Kg-dry 10.10

Dibenz(a,h)anthracene 5/12/20160.050 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.050 mg/Kg-dry 10.27

Fluorene 5/12/20160.050 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/12/20160.050 mg/Kg-dry 1ND

Naphthalene 5/12/20160.050 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.050 mg/Kg-dry 14.2

Pyrene 5/12/20160.050 mg/Kg-dry 10.35

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 135.6

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 12 of 22

Page 39: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-8 10-12.5Collection Date: 5/7/2016 4:00:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-010

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: ADCPrep Date: 5/9/2016Benzene 5/10/20160.0048 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0048 mg/Kg-dry 1ND

Toluene 5/10/20160.0048 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.015 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/12/20160.040 mg/Kg-dry 1ND

Acenaphthylene 5/12/20160.040 mg/Kg-dry 1ND

Anthracene 5/12/20160.040 mg/Kg-dry 1ND

Benz(a)anthracene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(a)pyrene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/12/20160.040 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/12/20160.040 mg/Kg-dry 1ND

Chrysene 5/12/20160.040 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/12/20160.040 mg/Kg-dry 1ND

Fluoranthene 5/12/20160.040 mg/Kg-dry 1ND

Fluorene 5/12/20160.040 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/12/20160.040 mg/Kg-dry 1ND

Naphthalene 5/12/20160.040 mg/Kg-dry 1ND

Phenanthrene 5/12/20160.040 mg/Kg-dry 1ND

Pyrene 5/12/20160.040 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 119.4

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 13 of 22

Page 40: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-1Collection Date: 5/7/2016 1:00:00 PM

Matrix: Aqueous

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-011

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW8260B (SW5030B) Analyst: ADCPrep Date:

Benzene 5/10/20160.0050 mg/L 1ND

Ethylbenzene 5/10/20160.0050 mg/L 10.048

Toluene 5/10/20160.0050 mg/L 1ND

Xylenes, Total 5/10/20160.015 mg/L 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C-SIM (SW3510C) Analyst: DMPrep Date: 5/10/2016Acenaphthene 5/11/20160.0020 mg/L 1ND

Acenaphthylene 5/11/20160.0020 mg/L 1ND

Anthracene 5/11/20160.0020 mg/L 10.036

Benz(a)anthracene 5/11/20160.00020 mg/L 10.0039

Benzo(a)pyrene 5/11/20160.00020 mg/L 10.0026

Benzo(b)fluoranthene 5/11/20160.00020 mg/L 10.0018

Benzo(g,h,i)perylene 5/11/20160.0020 mg/L 1ND

Benzo(k)fluoranthene 5/11/20160.00020 mg/L 10.0013

Chrysene 5/11/20160.00020 mg/L 10.0055

Dibenz(a,h)anthracene 5/11/20160.00020 mg/L 1ND

Fluoranthene 5/11/20160.0020 mg/L 10.019

Fluorene 5/12/20160.020 mg/L 100.16

Indeno(1,2,3-cd)pyrene 5/11/20160.00020 mg/L 10.00068

Naphthalene 5/11/20160.0020 mg/L 1ND

Phenanthrene 5/12/20160.020 mg/L 100.24

Pyrene 5/12/20160.020 mg/L 100.059

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 14 of 22

Page 41: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-2Collection Date: 5/7/2016 1:30:00 PM

Matrix: Aqueous

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-012

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW8260B (SW5030B) Analyst: ADCPrep Date:

Benzene 5/11/20160.0050 mg/L 1ND

Ethylbenzene 5/11/20160.0050 mg/L 1ND

Toluene 5/11/20160.0050 mg/L 1ND

Xylenes, Total 5/11/20160.015 mg/L 1ND

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 15 of 22

Page 42: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-3Collection Date: 5/7/2016 2:05:00 PM

Matrix: Aqueous

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-013

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW8260B (SW5030B) Analyst: ADCPrep Date:

Benzene 5/10/20160.0050 mg/L 1ND

Ethylbenzene 5/10/20160.0050 mg/L 1ND

Toluene 5/10/20160.0050 mg/L 1ND

Xylenes, Total 5/10/20160.015 mg/L 1ND

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 16 of 22

Page 43: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-4Collection Date: 5/7/2016 3:25:00 PM

Matrix: Aqueous

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-014

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW8260B (SW5030B) Analyst: ADCPrep Date:

Benzene 5/10/20160.0050 mg/L 1ND

Ethylbenzene 5/10/20160.0050 mg/L 1ND

Toluene 5/10/20160.0050 mg/L 1ND

Xylenes, Total 5/10/20160.015 mg/L 10.019

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C-SIM (SW3510C) Analyst: DMPrep Date: 5/10/2016Acenaphthene 5/11/20160.0010 mg/L 1ND

Acenaphthylene 5/11/20160.0010 mg/L 1ND

Anthracene 5/11/20160.0010 mg/L 1ND

Benz(a)anthracene 5/11/20160.00010 mg/L 1ND

Benzo(a)pyrene 5/11/20160.00010 mg/L 1ND

Benzo(b)fluoranthene 5/11/20160.00010 mg/L 10.00011

Benzo(g,h,i)perylene 5/11/20160.0010 mg/L 1ND

Benzo(k)fluoranthene 5/11/20160.00010 mg/L 1ND

Chrysene 5/11/20160.00010 mg/L 10.00012

Dibenz(a,h)anthracene 5/11/20160.00010 mg/L 1ND

Fluoranthene 5/11/20160.0010 mg/L 1ND

Fluorene 5/11/20160.0010 mg/L 1ND

Indeno(1,2,3-cd)pyrene 5/11/20160.00010 mg/L 1ND

Naphthalene 5/11/20160.0010 mg/L 1ND

Phenanthrene 5/11/20160.0010 mg/L 1ND

Pyrene 5/11/20160.0010 mg/L 1ND

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 17 of 22

Page 44: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-1 8-9Collection Date: 5/7/2016 12:20:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-015

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: ADCPrep Date: 5/9/2016Benzene 5/10/20160.0049 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0049 mg/Kg-dry 1ND

Toluene 5/10/20160.0049 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.015 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/13/20160.040 mg/Kg-dry 10.16

Acenaphthylene 5/13/20160.040 mg/Kg-dry 1ND

Anthracene 5/13/20160.040 mg/Kg-dry 10.075

Benz(a)anthracene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(a)pyrene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/13/20160.040 mg/Kg-dry 1ND

Chrysene 5/13/20160.040 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/13/20160.040 mg/Kg-dry 1ND

Fluoranthene 5/13/20160.040 mg/Kg-dry 1ND

Fluorene 5/13/20160.040 mg/Kg-dry 10.19

Indeno(1,2,3-cd)pyrene 5/13/20160.040 mg/Kg-dry 1ND

Naphthalene 5/13/20160.040 mg/Kg-dry 1ND

Phenanthrene 5/13/20160.040 mg/Kg-dry 10.40

Pyrene 5/13/20160.040 mg/Kg-dry 10.049

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 119.0

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 18 of 22

Page 45: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-2 9-10Collection Date: 5/7/2016 12:25:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-016

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: ADCPrep Date: 5/9/2016Benzene 5/10/20160.0059 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0059 mg/Kg-dry 1ND

Toluene 5/10/20160.0059 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.018 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/13/20160.039 mg/Kg-dry 1ND

Acenaphthylene 5/13/20160.039 mg/Kg-dry 1ND

Anthracene 5/13/20160.039 mg/Kg-dry 1ND

Benz(a)anthracene 5/13/20160.039 mg/Kg-dry 1ND

Benzo(a)pyrene 5/13/20160.039 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/13/20160.039 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/13/20160.039 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/13/20160.039 mg/Kg-dry 1ND

Chrysene 5/13/20160.039 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/13/20160.039 mg/Kg-dry 1ND

Fluoranthene 5/13/20160.039 mg/Kg-dry 1ND

Fluorene 5/13/20160.039 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/13/20160.039 mg/Kg-dry 1ND

Naphthalene 5/13/20160.039 mg/Kg-dry 1ND

Phenanthrene 5/13/20160.039 mg/Kg-dry 1ND

Pyrene 5/13/20160.039 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 115.9

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 19 of 22

Page 46: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Western Metra, Chicago, IL

Client Sample ID: WA-4 8-10Collection Date: 5/7/2016 12:35:00 PM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16050373

DF

Lab ID: 16050373-017

Date Printed: May 16, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: May 16, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: ADCPrep Date: 5/9/2016Benzene 5/10/20160.0049 mg/Kg-dry 1ND

Ethylbenzene 5/10/20160.0049 mg/Kg-dry 1ND

Toluene 5/10/20160.0049 mg/Kg-dry 1ND

Xylenes, Total 5/10/20160.015 mg/Kg-dry 10.030

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: ERPPrep Date: 5/12/2016Acenaphthene 5/13/20160.040 mg/Kg-dry 1ND

Acenaphthylene 5/13/20160.040 mg/Kg-dry 1ND

Anthracene 5/13/20160.040 mg/Kg-dry 1ND

Benz(a)anthracene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(a)pyrene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(b)fluoranthene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 5/13/20160.040 mg/Kg-dry 1ND

Benzo(k)fluoranthene 5/13/20160.040 mg/Kg-dry 1ND

Chrysene 5/13/20160.040 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 5/13/20160.040 mg/Kg-dry 1ND

Fluoranthene 5/13/20160.040 mg/Kg-dry 1ND

Fluorene 5/13/20160.040 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 5/13/20160.040 mg/Kg-dry 1ND

Naphthalene 5/13/20160.040 mg/Kg-dry 1ND

Phenanthrene 5/13/20160.040 mg/Kg-dry 1ND

Pyrene 5/13/20160.040 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 5/11/2016Percent Moisture * 5/12/20160.2 wt% 118.3

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 20 of 22

Page 47: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Page 21 of 22

Page 48: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Page 22 of 22

Page 49: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Page 1 of 9

Page 50: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

June 15, 2016Date:STAT Analysis Corporation

Project: Metra-Western, Chicago, ILClient: Gaiatech

Work Order: 16060313Work Order Sample Summary

Lab Sample ID Client Sample ID Collection DateTag Number Date Received

Revision 0

16060313-001A WA-9 5-10 6/8/2016 11:20:00 AM 6/8/201616060313-001B WA-9 5-10 6/8/2016 11:20:00 AM 6/8/201616060313-002A WA-9 10-15 6/8/2016 11:25:00 AM 6/8/201616060313-002B WA-9 10-15 6/8/2016 11:25:00 AM 6/8/201616060313-003A WA-10 3' 6/8/2016 11:30:00 AM 6/8/201616060313-003B WA-10 3' 6/8/2016 11:30:00 AM 6/8/201616060313-004A WA-10 5-7.5 6/8/2016 11:35:00 AM 6/8/201616060313-004B WA-10 5-7.5 6/8/2016 11:35:00 AM 6/8/201616060313-005A WA-10 10-12.5 6/8/2016 11:50:00 AM 6/8/201616060313-005B WA-10 10-12.5 6/8/2016 11:50:00 AM 6/8/2016

Page 2 of 9

Page 51: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Metra-Western, Chicago, IL

Client Sample ID: WA-9 5-10Collection Date: 6/8/2016 11:20:00 AM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16060313

DF

Lab ID: 16060313-001

Date Printed: June 15, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: June 15, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 6/8/2016Benzene 6/12/20160.0052 mg/Kg-dry 1ND

Ethylbenzene 6/12/20160.0052 mg/Kg-dry 1ND

Toluene 6/12/20160.0052 mg/Kg-dry 1ND

Xylenes, Total 6/12/20160.016 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: DMPrep Date: 6/13/2016Acenaphthene 6/14/20160.041 mg/Kg-dry 1ND

Acenaphthylene 6/14/20160.041 mg/Kg-dry 1ND

Anthracene 6/14/20160.041 mg/Kg-dry 1ND

Benz(a)anthracene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(a)pyrene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(b)fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(k)fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Chrysene 6/14/20160.041 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 6/14/20160.041 mg/Kg-dry 1ND

Fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Fluorene 6/14/20160.041 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 6/14/20160.041 mg/Kg-dry 1ND

Naphthalene 6/14/20160.041 mg/Kg-dry 1ND

Phenanthrene 6/14/20160.041 mg/Kg-dry 1ND

Pyrene 6/14/20160.041 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 6/8/2016Percent Moisture * 6/9/20160.2 wt% 119.5

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 3 of 9

Page 52: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Metra-Western, Chicago, IL

Client Sample ID: WA-9 10-15Collection Date: 6/8/2016 11:25:00 AM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16060313

DF

Lab ID: 16060313-002

Date Printed: June 15, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: June 15, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 6/8/2016Benzene 6/12/20160.0052 mg/Kg-dry 1ND

Ethylbenzene 6/12/20160.0052 mg/Kg-dry 1ND

Toluene 6/12/20160.0052 mg/Kg-dry 1ND

Xylenes, Total 6/12/20160.016 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: DMPrep Date: 6/13/2016Acenaphthene 6/14/20160.041 mg/Kg-dry 1ND

Acenaphthylene 6/14/20160.041 mg/Kg-dry 1ND

Anthracene 6/14/20160.041 mg/Kg-dry 1ND

Benz(a)anthracene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(a)pyrene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(b)fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(k)fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Chrysene 6/14/20160.041 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 6/14/20160.041 mg/Kg-dry 1ND

Fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Fluorene 6/14/20160.041 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 6/14/20160.041 mg/Kg-dry 1ND

Naphthalene 6/14/20160.041 mg/Kg-dry 1ND

Phenanthrene 6/14/20160.041 mg/Kg-dry 1ND

Pyrene 6/14/20160.041 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 6/8/2016Percent Moisture * 6/9/20160.2 wt% 120.0

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 4 of 9

Page 53: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Metra-Western, Chicago, IL

Client Sample ID: WA-10 3'Collection Date: 6/8/2016 11:30:00 AM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16060313

DF

Lab ID: 16060313-003

Date Printed: June 15, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: June 15, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 6/8/2016Benzene 6/12/20160.0045 mg/Kg-dry 1ND

Ethylbenzene 6/12/20160.0045 mg/Kg-dry 1ND

Toluene 6/12/20160.0045 mg/Kg-dry 1ND

Xylenes, Total 6/12/20160.014 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: DMPrep Date: 6/13/2016Acenaphthene 6/14/20160.039 mg/Kg-dry 1ND

Acenaphthylene 6/14/20160.039 mg/Kg-dry 1ND

Anthracene 6/14/20160.039 mg/Kg-dry 1ND

Benz(a)anthracene 6/14/20160.039 mg/Kg-dry 1ND

Benzo(a)pyrene 6/14/20160.039 mg/Kg-dry 1ND

Benzo(b)fluoranthene 6/14/20160.039 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 6/14/20160.039 mg/Kg-dry 1ND

Benzo(k)fluoranthene 6/14/20160.039 mg/Kg-dry 1ND

Chrysene 6/14/20160.039 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 6/14/20160.039 mg/Kg-dry 1ND

Fluoranthene 6/14/20160.039 mg/Kg-dry 1ND

Fluorene 6/14/20160.039 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 6/14/20160.039 mg/Kg-dry 1ND

Naphthalene 6/14/20160.039 mg/Kg-dry 1ND

Phenanthrene 6/14/20160.039 mg/Kg-dry 1ND

Pyrene 6/14/20160.039 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 6/8/2016Percent Moisture * 6/9/20160.2 wt% 115.9

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 5 of 9

Page 54: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Metra-Western, Chicago, IL

Client Sample ID: WA-10 5-7.5Collection Date: 6/8/2016 11:35:00 AM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16060313

DF

Lab ID: 16060313-004

Date Printed: June 15, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: June 15, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 6/8/2016Benzene 6/12/20160.0070 mg/Kg-dry 1ND

Ethylbenzene 6/12/20160.0070 mg/Kg-dry 1ND

Toluene 6/12/20160.0070 mg/Kg-dry 1ND

Xylenes, Total 6/12/20160.021 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: DMPrep Date: 6/13/2016Acenaphthene 6/14/20160.042 mg/Kg-dry 10.37

Acenaphthylene 6/14/20160.042 mg/Kg-dry 1ND

Anthracene 6/14/20160.042 mg/Kg-dry 10.24

Benz(a)anthracene 6/14/20160.042 mg/Kg-dry 10.081

Benzo(a)pyrene 6/14/20160.042 mg/Kg-dry 10.065

Benzo(b)fluoranthene 6/14/20160.042 mg/Kg-dry 10.097

Benzo(g,h,i)perylene 6/14/20160.042 mg/Kg-dry 10.057

Benzo(k)fluoranthene 6/14/20160.042 mg/Kg-dry 10.073

Chrysene 6/14/20160.042 mg/Kg-dry 10.13

Dibenz(a,h)anthracene 6/14/20160.042 mg/Kg-dry 1ND

Fluoranthene 6/14/20160.042 mg/Kg-dry 10.31

Fluorene 6/14/20160.042 mg/Kg-dry 10.28

Indeno(1,2,3-cd)pyrene 6/14/20160.042 mg/Kg-dry 1ND

Naphthalene 6/14/20160.042 mg/Kg-dry 1ND

Phenanthrene 6/14/20160.042 mg/Kg-dry 10.70

Pyrene 6/14/20160.042 mg/Kg-dry 10.40

Percent Moisture D2974 Analyst: GHPrep Date: 6/8/2016Percent Moisture * 6/9/20160.2 wt% 122.2

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 6 of 9

Page 55: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Project: Metra-Western, Chicago, IL

Client Sample ID: WA-10 10-12.5Collection Date: 6/8/2016 11:50:00 AM

Matrix: Soil

Analyses Result Qualifier Units Date AnalyzedRL

Client: GaiatechWork Order: 16060313

DF

Lab ID: 16060313-005

Date Printed: June 15, 2016

STAT Analysis Corporation2242 West Harrison St., Suite 200, Chicago, IL 60612-3766Tel: (312) 733-0551 Fax: (312) 733-2386 [email protected]

Date Reported: June 15, 2016

Accreditations:IEPA ELAP 100445;ORELAP IL300001;AIHA-LAP, LLC 101160;NVLAP LabCode 101202-0

ANALYTICAL RESULTS

Revision 0

BTEX by GC/MS SW5035/8260B Analyst: JNMPrep Date: 6/8/2016Benzene 6/12/20160.0048 mg/Kg-dry 1ND

Ethylbenzene 6/12/20160.0048 mg/Kg-dry 1ND

Toluene 6/12/20160.0048 mg/Kg-dry 1ND

Xylenes, Total 6/12/20160.014 mg/Kg-dry 1ND

Polynuclear Aromatic Hydrocarbons by GC/MS SW8270C (SW3550B) Analyst: DMPrep Date: 6/13/2016Acenaphthene 6/14/20160.041 mg/Kg-dry 1ND

Acenaphthylene 6/14/20160.041 mg/Kg-dry 1ND

Anthracene 6/14/20160.041 mg/Kg-dry 1ND

Benz(a)anthracene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(a)pyrene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(b)fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(g,h,i)perylene 6/14/20160.041 mg/Kg-dry 1ND

Benzo(k)fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Chrysene 6/14/20160.041 mg/Kg-dry 1ND

Dibenz(a,h)anthracene 6/14/20160.041 mg/Kg-dry 1ND

Fluoranthene 6/14/20160.041 mg/Kg-dry 1ND

Fluorene 6/14/20160.041 mg/Kg-dry 1ND

Indeno(1,2,3-cd)pyrene 6/14/20160.041 mg/Kg-dry 1ND

Naphthalene 6/14/20160.041 mg/Kg-dry 1ND

Phenanthrene 6/14/20160.041 mg/Kg-dry 10.11

Pyrene 6/14/20160.041 mg/Kg-dry 1ND

Percent Moisture D2974 Analyst: GHPrep Date: 6/8/2016Percent Moisture * 6/9/20160.2 wt% 119.2

Qualifiers: J - Analyte detected below quanititation limitsB - Analyte detected in the associated Method Blank

S - Spike Recovery outside accepted recovery limitsR - RPD outside accepted recovery limits

ND - Not Detected at the Reporting Limit

E - Value above quantitation range* - Non-accredited parameterHT - Sample received past holding time

H - Holding time exceeded

RL - Reporting / Quantitation Limit for the analysis

Page 7 of 9

Page 56: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Page 8 of 9

Page 57: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Page 9 of 9

Page 58: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Appendix C:

OSFM Site Assessment Results Report Form

Page 59: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

Results: No Contamination

IEMA #:

Title: Professional Engineer

Expiration Date: 11/30/2017

Phone Number: (312) 541-4200

OFFICE OF THE ILLINOIS STATE FIRE MARSHAL

Site Assessment Results Report

Owner Name Commuter Rail Divisionof the RegionalTransportation Authority

Address 547 West Jackson Blvd.

Chicago, IL 60661-5717Contact Person Todd CabonorPhone Number

Owner - U0037941Facility Name Metra Western Avenue

Address 2871 W. Grand AvenueChicago, IL 60612Cook

Contact Person Todd CabonorPhone Number

Facility - 2031066

Tank # Capacity in Gallons Product Date Last Used Status Date Removed/Abandoned

1 48000 Diesel Fuel 01/01/0001 Currently in use 01/01/0001

2 48000 Diesel Fuel 01/01/0001 Currently in use 01/01/0001

3 48000 Diesel Fuel 01/01/0001 Currently in use 01/01/0001

4 48000 Diesel Fuel 01/01/0001 Currently in use 01/01/0001

5 10000 Diesel Fuel 01/01/0001 Currently in use 01/01/0001

17 1000 Diesel Fuel 12/01/1985 Exempt from registration 12/01/1985

Purpose of the Site Assessment: Voluntary

Date Release Reported:

Remarks: Site assessment conducted to facilitate future abandonment/removal of underground piping. Detected impacts areattributed to open release incident 20150182.

Under the penalties as provided by law pursuant to Section 1-109 of the Code of Civil Procedure, the undersigned certifiesthat the statements set forth in this instrument are true and correct, except as to matters stated to be on information andbelief and as to such matters the undersigned certifies as aforesaid that he/she verily believes the same to be true.

By checking this box, I certify that the site assessment was completed in accordance with all applicable rules andregulations of the Office of the State Fire Marshal as requred by 176.330(a)&(b).

Name: Steven Kline

License #: 062-051730

Company: RPS GaiaTech

Attached Documents

16050373(GaiaTech)Rev0.pdf

16060313(GaiaTech)Rev0.pdf

Submitted Date & Time: 10/11/2016 9:55:29 AM

Page 60: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

MetraThe way to really fly.

?<??

CONTRACTORS

Meeting Attendance

Subject Raise Piping from Underground to Aboveground at Metra's Western Avenue Yard Meeting OwnerPeter Papanikolau

Date April 24, 2018 Time 10:30 a.m. Location Metro's Western Avenue Yard

Name Affiliation/Position Phone # E-mail

1. -'/. / '^/.•/,- /-'/

2. ^C^ ^^r ^l^^^^t^f „ ^< ^>?-ZZ97' WH ^r^f^ €\[(^^^^^^l;^^wt^A"

\3. (^^^r ^^jrr^ C^/JT^/W^C 7^-^y^^ ^ ^y>i+(^ ji^cou^^ s, <^^

4- ^^- /^/^}y l./^ fh^L^. ^-J^J-^/ ^ff/^-. 7^0€^//A^^A^/>^/^^^

5. M^ (i^4nf ^/7i?/t/^n/ /^UW^ ^^i^fT <?1^^0/ ^</<} ^ ^WDf̂^?y^^/u . ^on-^

6- 1\^W P^A ^r/liKfUC^ T/v^ ^ W dill-^n ^6\CO<.<\jS) *\^f\L^o^ .

7- C^i/J^ ^_S€:^ P'f4. p^qr^JLn ^3-4-f-t-i44'z r ^•y.-^- ^-'^ [PW..^D^ • <- o^

8-^.^T^ ^^ \U[0 ? i^ejA^c^ ^ -ff^w -1/^J rj^f^f ^ jc^&. ^/^

9-^^^ ^^r^/ L^{/^^^ ^/^CT'^/C^ ^JoS €^-^>1 1^-^/TW ^^^>//^^f2^^^^^^10. ~'/.\ A/ •,'r- •-/- - "/"^ 7 .^

11. .'\-' '• -' ^ •; 1^1 0 /-////'••-

.:.^~'^ /€'^ -1/iif •/// ^ '.

A12. (H/Kti/ /^/W ^^ VtW^ ^/^'s/. /^ 414^° €~7^? .Sy/KH/, (^h ^f^^c^.^13.

£. ,—^ ^ ^^^-.^ '^.^^

14.

15.

16.

17.

18.

19.

20.

21.

22.

NOTE: Meeting owner should retain the original form in his/her files.

Addendum 2Pre-Bid Meeting Attendance Sheets

1

Page 61: Construction Services to Raise Piping from Underground to ... · pipe supports for Coach House Building 4 with the DFS pipe as external and the JOS, LOS and LOR piping inside the

MetraThe way to really fly.

Contractors

Meeting Attendance

Raise Piping from Underground to Aboveground at Metro's Western Avenue Yard Subject Meetina Owner Peter Papanikolau

Date May 10.2018 Time 10:30 a.m. Location Metra's Western Avenue Yard

Name Affiliation/Position Phone# E-mail

1. (b'fcol (^V^C^&T Ivicl^tOdevA; Vl^eclAmri/1^ lH^^\r^tr-r Tl^'?^-?^ ^e^dp^^c^^2>^ '^A^\ iTVl^tUK tjj^«t5-<^ &4T. <2/^:7^

hn) no /7/rft\-M^AM?_^ ^ix^'UitcTfflUJc. < 1̂^\

p^

^^^'> M^i^^L^3

4.^,^ ^r-y^r-^1/ML*1 C^^hS . Wt^a^} ^ ^^-^Cc^.^fvs.

•-B^LM^^ t^<-&A^ C-frlt C<LL^c.7Gy-^7-<SS><?y u <90L(^ tft^t- ct^^Sc^ft^tC.c.

5- ^^ ^^y ^//^/ ft^^nr^r^/ -^. /?^?-^J-^^/ <%/^A 7^ ^/^/ /»t^//^^s/^6. ~5.^ v^^ t^-fl^gr" YlfAj-f^

W./^.Jr-">c

T^73^ S^so / I t f ) S^l

&^^r V^i/^ (^ S^c^h&tJ.^^'

T^ujr^fffZ. ^AfX-^,7. ^/?(/^ /<{?^2/^/? 3/2* ^?? ^^^^

JA^rm^»

tj^fsJL., 3,7^^-hWO /^^?/^~3<<?^lon ^^9- a^ \-\KA^e. 0'^t-tAS (?r^r?Jc.r/o/0 77^<73^^ ^yA^ZltE.e.A^EtJ^cL^T^^o.? Cfl^\

,ji/^T

10. ,o^ -^ ^so^ 3-^)^ ^5-6o\-^ ^fet/^TJcCCT ^[^.So^i. ^-*^?IfeWjf ^^ ^^A\^A^}u)11. 4^w ^

12.

13.

14.

15.

16.

17.

18.

19.

20.

21,

22.

NOTE: Meeting owner should retain the original form in his/her files.

Addendum 2Pre-Bid Meeting Attendance Sheets

2