construction of new buildings for iit madras research park ... services - fire fighting... ·...

2
Construction of New Buildings for IIT Madras Research Park – Phase – II, SH: - Building external services – Fire fighting pipeline works SR. NO. DESCRIPTION OF ITEM QTY. UNIT Supply rate Installation rate Supply Amount Installation Amount 1 Supplying and laying testing & commissioning of MS C Class pipe conforming to IS 1239 up to 150 dia & IS3589 above 150 dia with 5.4mm thickness. Making leak proof welded joints including cutting the pipe to required length, preparation of pipe surface, etc.Testing the pipe line to a hydraulic pressure of 16kg / sq.cm for leak proof joints. providing and fixing Wrapping Pypkote 4mm thick (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards for corrosion protection of pipes that will be laid under the ground .] Note : The piping installation has to be put to hydraulic test 1.5 times Working pressure before applying paint 1 quote of anti corrosive paint and wrapping etc. complete including excavation, back filling, disposal of excess excavated earth, consolidation, including elbows, bends, couplings ,fabricating & fixing MS angle, flats, channels fabricated brackets, tees etc.etc complete Detail shown in Drawing Ref No. NAT- 557-IITM-FF-01, Rev - R4, Title - Site Plan External Fire Fighting Layout. a) 200mm dia 1999 Rmt b) 150mm dia 500 Rmt c) 100mm dia 10 Rmt d) 80mm dia 70 Rmt 2 Providing, laying, fixing and jointing in position M.S 'C' class pipes conforming to IS 1239 with welded joints and all necessary fittings like elbows, bends, couplings, tees, reducers as required including testing hydraulically to 1.5 times the working pressure painting with one coat of anticorrosive paint and two coats of red enamel paint etc complete. with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes laid above ground & suspended The quoted rate shall also include for chasing / chipping walls, making bore holes in walls / floor and making them good with filler material and finished in cementmorter etc. as per requirement. Detail shown in Drawing Ref No. NAT-557-IITM-FF-01, Rev - R4, Title - Site Plan External Fire Fighting Layout. a) 200mm dia 200 Rmt b) 80mm dia 70 Rmt 3 Providing, fabricating & fixing C.I. double flanged butterfly valve of approved make including with nuts,bolts,gaskets etc complete with valve chamber and cover for Fire Fighting movement a) 200mm dia 9 Nos b) 150mm dia RO Nos c) 100mm dia RO Nos 4 Constructing of following size brick masonry Valve chambers in 230mm thick brick walls in cement mortar 1:5 plastered inside and outside in C.M. 1:3 including 150 thick bed concrete in C.C. 1:3:6 and following size C.I. heavy frame and C.I. grating on 100 thick with heavy duty for fire movement cover. P.C.C. M-15 cap on top complete as directed depth up to 1500 mm a) 1000 mm X 1000 mm 4 Nos b) 750 mm X 750 mm 1 Nos 5 Providing, fabricating & fixing Heavy duty gun metal 63 dia outlet Single Hydrant valve to Courtyard stand posts including all nuts bolts gaskets etc complete 35 Nos 6 Providing, fabricating & fixing 2 lengths of 15 M long Flexible Canvass Rubber Pipe, branch pipe and nozzle and storing them in MS Hose Cabinet (Color as per TNFRS) with lockable glass shutters and fixing MS Hose Cabinet including vertical GI supports ( painting) at ground level in a location where it can be easily spotted. Detail shown in Drawing Ref No. NAT-557-IITM-FF-01, Rev - R4, T 35 Nos BILL OF QUANTITIES FOR EXTERNAL FIRE FIGHTING AND SPRINKLER RING MAIN AT IITMRP-CHENNAI Supply, Installation, Testing, Balancing and Commissioning of the following Fire Fighting & Sprinkler equipment and materials in accordance with Specifications and inclusive of all taxes, duties, loading, unloading, octroi, transportation, scaffolding, insurance and all other statutory payments. 1 of 2

Upload: lethuy

Post on 06-Mar-2018

217 views

Category:

Documents


2 download

TRANSCRIPT

Construction of New Buildings for IIT Madras Research Park

– Phase – II, SH: - Building external services

– Fire fighting pipeline works

SR.

NO.DESCRIPTION OF ITEM QTY. UNIT Supply rate Installation rate

Supply

Amount

Installation

Amount

1

Supplying and laying testing & commissioning of MS C Class pipe conforming to IS

1239 up to 150 dia & IS3589 above 150 dia with 5.4mm thickness. Making leak

proof welded joints including cutting the pipe to required length, preparation of pipe

surface, etc.Testing the pipe line to a hydraulic pressure of 16kg / sq.cm for leak

proof joints. providing and fixing Wrapping Pypkote 4mm thick (corrosion protection

tape) including supply and application of pipe coating and spiral Wrapping

(wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM

standards for corrosion protection of pipes that will be laid under the ground .] Note

: The piping installation has to be put to hydraulic test 1.5 times Working pressure

before applying paint 1 quote of anti corrosive paint and wrapping etc. complete

including excavation, back filling, disposal of excess excavated earth, consolidation,

including elbows, bends, couplings ,fabricating & fixing MS angle, flats, channels

fabricated brackets, tees etc.etc complete Detail shown in Drawing Ref No. NAT-

557-IITM-FF-01, Rev - R4, Title - Site Plan External Fire Fighting Layout.

a) 200mm dia 1999 Rmt

b) 150mm dia 500 Rmt

c) 100mm dia 10 Rmt

d) 80mm dia 70 Rmt

2

Providing, laying, fixing and jointing in position M.S 'C' class pipes conforming to IS

1239 with welded joints and all necessary fittings like elbows, bends, couplings,

tees, reducers as required including testing hydraulically to 1.5 times the working

pressure painting with one coat of anticorrosive paint and two coats of red enamel

paint etc complete. with fabricating & fixing MS angle, flats, channels fabricated

brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type

brackets for pipes laid above ground & suspended The quoted rate shall also

include for chasing / chipping walls, making bore holes in walls / floor and making

them good with filler material and finished in cementmorter etc. as per requirement.

Detail shown in Drawing Ref No. NAT-557-IITM-FF-01, Rev - R4, Title - Site Plan

External Fire Fighting Layout.

a) 200mm dia 200 Rmt

b) 80mm dia 70 Rmt

3

Providing, fabricating & fixing C.I. double flanged butterfly valve of approved make

including with nuts,bolts,gaskets etc complete with valve chamber and cover for

Fire Fighting movement

a) 200mm dia 9 Nos

b) 150mm dia RO Nos

c) 100mm dia RO Nos

4

Constructing of following size brick masonry Valve chambers in 230mm thick brick

walls in cement mortar 1:5 plastered inside and outside in C.M. 1:3 including 150

thick bed concrete in C.C. 1:3:6 and following size C.I. heavy frame and C.I. grating

on 100 thick with heavy duty for fire movement cover. P.C.C. M-15 cap on top

complete as directed depth up to 1500 mm

a) 1000 mm X 1000 mm 4 Nos

b) 750 mm X 750 mm 1 Nos

5Providing, fabricating & fixing Heavy duty gun metal 63 dia outlet Single Hydrant

valve to Courtyard stand posts including all nuts bolts gaskets etc complete35 Nos

6

Providing, fabricating & fixing 2 lengths of 15 M long Flexible Canvass Rubber

Pipe, branch pipe and nozzle and storing them in MS Hose Cabinet (Color as per

TNFRS) with lockable glass shutters and fixing MS Hose Cabinet including vertical

GI supports ( painting) at ground level in a location where it can be easily spotted.

Detail shown in Drawing Ref No. NAT-557-IITM-FF-01, Rev - R4, T

35 Nos

BILL OF QUANTITIES FOR EXTERNAL FIRE FIGHTING AND SPRINKLER RING MAIN AT IITMRP-CHENNAI

Supply, Installation, Testing, Balancing and Commissioning of the following Fire Fighting & Sprinkler equipment and materials in accordance with Specifications and

inclusive of all taxes, duties, loading, unloading, octroi, transportation, scaffolding, insurance and all other statutory payments.

1 of 2

Construction of New Buildings for IIT Madras Research Park

– Phase – II, SH: - Building external services

– Fire fighting pipeline works

SR.

NO.DESCRIPTION OF ITEM QTY. UNIT Supply rate Installation rate

Supply

Amount

Installation

Amount

BILL OF QUANTITIES FOR EXTERNAL FIRE FIGHTING AND SPRINKLER RING MAIN AT IITMRP-CHENNAI

Supply, Installation, Testing, Balancing and Commissioning of the following Fire Fighting & Sprinkler equipment and materials in accordance with Specifications and

inclusive of all taxes, duties, loading, unloading, octroi, transportation, scaffolding, insurance and all other statutory payments.

7

Providing, fabricating & fixing 4 way Siamese connection with 4 Nos. 63 mm

outlets, 200mm connecting pipe to fire hydrant ring with 150mm non- return valve

and 150mm gate valve etc. complete as shown on drg. (Fire connection to Hydrant

Ring)

1 No

8Fire statutory approval from Tamil Nadu Fire and Rescue Services. External fire

fighting system & pump room if applicable 1 Lot

9

Supply and Laying in position the RCC Hume pipes( Np3) of approved quality

including necessary collors,earth excavation up to required line slope level, PCC

1;2;4 Line supports, quary dust cushion of 150mm all sides, refilling with excavated

earth compaction 150mm suit compaction in layer etc.

a) 450 mmdia Mtrs 50

b) 300 mmdia Mtrs 60

Sub Total

Total