conception cm a4 - ingles rev 10 · 2018. 6. 11. · power of 50 kva ups 2 power of 100 kva ups 3...

6
UPS (Uninterruptible Power Supply) Digital Signal Processor CM COMANDOS LINEARES CM COMANDOS LINEARES Multi Active Three Phase CONCEPTION

Upload: others

Post on 11-Feb-2021

11 views

Category:

Documents


0 download

TRANSCRIPT

  • UPS (Uninterruptible Power Supply) Digital Signal Processor

    CM COMANDOS LINEARESCM COMANDOS LINEARES

    M ult i Ac t iveThree PhaseC O N C E P T I O N

  • A B O U T T H EC O M PA N Y

    With over 32 years in operation, CM Comandos is one of the

    largest UPS manufacturers in Latin America.

    Moreover, it is the sole leader in solutions for the corporate market. Certified by

    ISO-9001:2015 standards, CM Comandos stresses its commitment to excellence of

    its products and full clients satisfaction

    Innovation, quality, technology and reliability. Trademarks ofCM Comandos Lineares solutions

    U S A G E UPS of CM Comandos Lineares are suitable for critical-mission usage in all types of corporations,

    providing protection against power disturbances, such as cuts, micro cuts, noise, harmonic distortion,

    spikes, transients, under and over voltage and frequency variations.

    TECHNICAL SUPPORT

    B E N E F I T S CM Comandos equipment operates with greater precision, adds more features and are safer.

    CM COMANDOS LINEARES

    O SD LN IA NM EAO

    RC EM SC

    ISO9001

    2015

    Features that create high reliability and productivity in many types of applications, diminish flaws and

    hence maintenance costs. In short, being a CM Comandos client means having the return on capital

    invested and guarantees that only a company with wide technical support can offer.

    By choosing the brand CM Comandos Lineares you can count on the best

    technical support prior and post-sales from a company that has established

    itself over these 30 years as the market leader.

    State-of-the-art instrumentation, highly skilled workers, with national coverage and 24-hour service,

    seven days a week, call center and certified processes ensure the excellence of our support services.

    Q YUALIT

  • High Technology in Digital Signal Processing - DSP

    T H E M O S T M O D E R NC O R P O R AT E U P S

    We are living in an increasingly fast and practical world. A world connected by processors, chips, software and

    peripherals. But this is still not enough. That is why the world is moving forward to immediately processing data

    technologies. CM Comandos Lineares is one step ahead and offers its clients products with a revolutionary

    technology, called Digital Signal Processing - DSP.

    All the line of Multi Active UPS Conception has DSP

    technology. Feature that provides high performance and

    reliability

    for critical-mission applications, i.e. it protects the applications where continuous operation is of critical

    importance.

    can be upgraded adding new features

    in already installed units.

    Today, this technology is present in the most sophisticated electronic systems due to its high speed and reliability.

    Digital Signal Processors can process tens of millions of samples per second. This means real-time processing - the

    signal is processed at the same time it is received, without delays or slowdowns.

    Designed with heavy use of DSP technology resources, Multi Active UPS Conception adds new and advanced

    features that create a new development concept, in which equipment firmware

    If you are thinking about purchasing an

    UPS, count on CM Comandos solutions ,

    which ensures state-of-the-art

    technology, maximum protection,

    digital precision and real-time

    processing.

    200kVA Model

  • O N L I N E T E C H N O LO G Y W I T HS TAT I C M A I N T E N A N C E B Y PA S S

    M A I N F E AT U R E S

    Advanced TechnologyDSP (Digital Signal Processor)

    Internal Memory for 5 Thousand Records

    True RMS Measurements with Multimeters Accuracy

    Static Maintenance Bypass

    Real-Time Remote Management Software

    Multi Active Parallel System (Exclusive CM)

    Allows advanced and exclusive features in real time.

    They are ideal for non-linear load measurement.

    Add protection and increase of sensitive load reliability.

    Via TCP / IP with password protection for remote access, shutdown.

    t can be parallel as many units as needed, allowing system expansion, according to consumer demand.

    Allows tracking for analysis.

    I

    Display TFT 4,3" Touch Screen(Standard Item)

    Possibility of DSP Firmware Upgrade

    DSP-Monitored Actions

    Smart Control of the Cooler Speed

    Modern screen with touch commands, which allows UPS access via the Internet

    Ensures the use and preservation of investment.

    The actions are registered and recorded in the event log.

    They extend the life of equipment.

    OutputMains Input

    Input Alternating Current

    Direct Current

    Output Alternating Current

    Alternating Current Static Bypass

    Maintenance Alternating Current Static Bypass

    Static Maintenance Bypass

    It allows transfer and return of the UPS load to an alternate

    circuit of power supply for maintenance purposes. In any

    case, the power supply is continuous with no interruption.

    Rectifier Converts the energy

    from the mains of the utility provider or the generator into direct current, correcting or

    eliminating system input disturbances.

    InverterIt converts the direct current from the rectifier or battery into alternating current output, shaped like a pure sine wave, disturbance-free.

    Battery bankStores backup power to power the UPS over a predetermined period, known as UPS runtime.

    Static BypassProtection system that,

    in case of problems,

    automatically transfers

    the load to an alternate

    circuit without breaking

    the power supply.

    Present Mains

    Mains Failure

    Static Bypass

    Maintenance Static Bypass

    Multi Active UPS ConceptionThree Phase

    REMOTE MANAGEMENTINTERFACE

    DISPL AY TFT 4 ,3” TOUCHSCREENTOUCH COMMAND

    They are made up of several tools. The

    NetMate SNMP Adapter allows you to

    remotely manage the UPS via the

    Internet through a web browser,

    monitor status and send alerts via

    email.IP Power software is a Windows

    Application management tool and the

    Client version is specific to automate

    the shutdown of servers, being able to

    automatically and simultaneously

    disconnect multiple servers and

    stations.The ArmModbus Adapter allows

    integration of the UPS via aRS485, to Building Automation

    Systems.

  • M U LT I A C T I V E PA R A L L E L S Y S T E M ( E X C L U S I V E O F C M C O M A N D O S )

    CM Comandos Lineares has developed an innovative and pioneering system in the world of parallelism between UPSs. Multi

    Active Parallel System allows system expansion, according to your consumption demand and may parallel as many units needed

    to meet your demand, increasing system capacity and its application reliability.

    P O S S I B I L I T Y O F P O W E R S U M M A T I O N

    It allows connection to power summation, using two or more UPSs to meet the demand of full load. When used for power summation, it allows the connection of UPSs with different powers. When the connection is made with UPS of different powers, the load will be distributed proportionately.

    It allows parallel redundant connection N + 1, N + 2, N + 3 ... N + X, allowing the disengagement of one or more units, keeping the active load.

    R E D U N D A N T P A R A L L E L C O N N E C T I O N

    Communication between UPS is the common communication bus, where information goes by, including charge level, timing and status of the bypass.

    C O M M U N I C A T I O N B E T W E E N U P S

    All UPSs are autonomous, operate independently in the system

    and have individual control.

    N O M A S T E R O R S L A V E U P S

    As many units can be parallel as needed, allowing system expansion, according to consumption demand.

    U N L I M I T E D P A R A L L E L I S M

    B AT T E R Y B A N K PA R A L L E L I S MAllows battery bank paralleling (when they are of the same nominal voltage).

    U P S M A I N T E N A N C E

    It allows insertion and removal of UPS from the system without the need to stop.

    S H U T D O W N I N T E R FA C E A N D R E M O T E M A N A G E M E N T

    Input Mains

    Output

    UPS 1 Power of 50 kVA

    UPS 2 Power of 100 kVA

    UPS 3Power of 20 kVA

    Load Provided by the System = 400 kVA

    UPS 4Power of

    30 kVA

    UPS 5Power of 80 kVA

    UPS 6 Power of 120 kVA

    Multi-Servers Multiplatform Multi-O.S.

    D UPSMON Remote Management Interface

    F

    Interface Shutdown

    H Software UPSMON Remote Station with internet connection

    Ethernet Local Network

    A UPSMON Management Interface

    PC withInternet

    C Interface Shutdown Client LAN

    DB9 Microprocessor PortRJ45 Ethernet Network

    B Interface Shutdown

    E SNMP Web Monitoring

    G

    Software integrating all UPS monitoring

  • CM

    .MKT

    103

    .1 R

    EV.1

    0 - S

    peci

    ficat

    ions

    are

    sub

    ject

    to c

    hang

    e w

    ithou

    t pre

    viou

    s no

    tice.

    We

    enco

    urag

    e re

    cycl

    ing

    T E C H N I C A L D ATA

    Input

    Voltage: • Three Phase: 208 / 220 / 380 / 400 / 440V

    Allowance variance: • ± 15% of nominal voltage

    Frequency: 50 or 60 Hz

    Variation of Allowable Frequency: ± 8%Settingon:

    • Three Phase: 3F + N + TPower Factor:

    • 0,8 • 0,99*

    Output

    Voltage: • 208 / 220 / 380 / 400 / 440V

    Available Power: • 5/10/15/20/30/40/60/80/100/120/160/200 kVA

    Static Regulation: ± 1% nominal

    Frequency: 50 or 60 Hz Frequency Variance:

    • ± 0,05% in battery modeSetting:

    • Three Phase: 3F +N + T

    Power Factor: 0,8

    Waveform: sine

    Harmonic Distortion THD: less than 1%, total

    Peak Factor: 3:1

    Overload Capacity: 125% for 25s

    Efficiency: 90%

    Batteries

    Line Voltage: • 288VDC (5 to 30 kVA • 384VDC (40 to 80 kVA) • 480 VDC (100 to 200 kVA)

    Recharge System: controlled, automaticRecharge Time:

    • 8 to 10 hours for 90% of load

    Type: sealed, maintenance-free

    Static Bypass

    Action: automatic, DSP controlled

    Transfer Time: 0ms (null)

    Retransfer to Normal Mode: automatic

    Maintenance Static Bypass

    Allows UPS Maintenance without disconnecting the load

    Action: manual, through Circuit Breaker

    Change to Normal Mode: without interruption

    Electrical Protections

    Input and Output Undervoltage and Overvoltage

    DC Undervoltage and Overvoltage and Battery

    Overload and Short Circuit

    Minimum Battery Discharge

    Over temperature

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    Physical and Mechanical Features

    Compact dimensions TFT 4.3" Touch Screen Cabinet structure:

    • Rack: metal • Removable side and top covers • Finish: epoxy powder painting in graphite color

    with thermal and anticorrosive treatment Ventilation: forced, with digital speed control by

    DSPIsolation Transformer: electrostatics ShieldedCommunication port:

    • Serial RS232C Isolated Full Duplex -DB9 Female* • Dry Contact DB9 Female

    Management Interfaces

    Single and multi-user, client-server, multi-serverMultiple servers on a single UPSShutdown and Management ToolsProtocols:

    • Serial Rs232 • Serial Rs485* • SNMP / Telnet / http / TCP/IP*

    Management software * • UPSMAN / UPSMON / RCCMD • ASNMP CS121BL Adapter •

    Environments and operating systems • Windows 8 / 10 / 2010 • Linux

    (Brands of reuse manufacturers) * Optional

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    UNMS II

    *

    MeasurementTrue RMSOutput power in kVAOutput power in kWOutput Power FactorOutput VoltageOutput CurrentOutput FrequencyBattery voltageBattery current *Input Power Factor*Input voltageInput Current *Input Frequency

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    n

    AlarmsControlled by the DSP processorTypes of Alarms:

    • Sound: » Network Missing: 1 ring each 4 sec » Pre-alarm of Batteries: 1 ring per second » Internal UPS Failure: continuous alarm

    • Alert Messages: » LCD » Software UPSMON, local or remote » Message by e-mail, cell phone or pop-up: - Normal Operation - Network Failure - Pre-alarm of Batteries - Active Static Bypass - Active Manual Bypass - Output Overload - Fail

    n

    n

    Event LogStored Records:

    • Memory with 25,500 records (15 configuration logs and 495 event logs)

    • Indications of Date, time and occurrence • Measurements • Operation Status and Panel Alarms • Status of Internal Switches

    Autonomy of NVRAM: • 5 years (with UPS off )

    n

    n

    Operating FeaturesAudible Noise: 55 dBA to 60 dBA at 1 meterMTBF (Mean Time Between Failures): 200,000 hoursMTTR (Mean Time To Repair): 30 minutesAmbient Temperature:

    • UPS: 20ºC to 40ºC • Batteries: 0ºC to 30ºC • Recommended: 20ºC and 25ºC

    Relative Humidity: • 0% to 95% non-condensing • Recommended: 45% to 55%

    Altitude: up to 1,000mRecommended Environment Type:

    • Intern, indoor installation • Atmosphere: clean, free from conductive particles, toxic, flammable liquids and gases.

    Degree of Protection: IP-20

    n

    n

    n

    n

    n

    n

    n

    n

    5000 5,0 900 X 480 X 980 295

    10000 10,0 900 X 480 X 980 305

    15000 15,0 900 X 480 X 980 409

    20000 20,0 1180 X 550 X 980 560

    30000 30,0 1180 X 550 X 980 640

    4

    60000 60,0 1355 X 720 X 940 560

    80000 80,0 1900 X 780 X 920 730

    100000 100,0 1900 X 785 X 925 870

    120000 120,0 1900 X 785 X 925 1000

    160000 160,0 1900 X 1265 X 1000 1200

    200000 200,0 1900 X 1265 X 1000 1300

    300000 300,0 2010 X 2050 X 1000 2280

    0000 40,0 1355 X 720 X 940 490

    Model Power kVA

    Physical Dimensionh x w x d

    mm

    Weight (with

    batteries)

    Models with internal batteries

    Physical Dimensionh x w x d

    mm

    Power kVA

    Weight (with

    batteries)

    Model

    Models with no battery

    Sistema de Sustentabilidade Auditada

    CM COMANDOS LINEARES

    O SD N L IA NM EO A

    C R EM SC

    ISO9001

    2008

    O SD N L IA NM EO A

    C R EM SC

    ISO9001

    2015Q YUALIT

    Av. Eng. Alberto de Zagottis, 760 - 04675-085 - São Paulo - SP - BrazilPhone.: (+55 - 11) 5696-5000 www.cmcomandos.com.br