component for air conditioning system
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 1
DLP High induction linear slot diffuser
The DLP series linear slot diffusers as been designed for the diffusion of air with installation in suspended ceiling. They are suitable for the diffusion of air in room with height between about 2,6 and 4 m or for more height in case of installation near wall or glass wall. They are available in lengths of 500 and 2000 mm with increment of 100 mm from 1 to 6 slot.
Ve r s i on i
Linear Slot Diffuser DLP
- DLPA... (hidden without frame)- DLPB... (with a 10 mm thick frame)- DLP...20 (20 mm width deflector and 10 mm width slot)- DLP...30 (30 mm width deflector and 15 mm width slot)- DLP...40 (40 mm width deflector and 20 mm width slot)- DLP...n... (n = 1,2,...,6 = n° of slot)- DLP.../PS (with standard plenum and sliding damper)- DLP.../PSI (with isolated plenum and sliding damper)
ES. DLPA30-2/PSI-1500 = Linear diffuser with 2 slot of 30 mm width, without frame, 1500 mm long, with isolated plenum.
Qu ick re fe rence se l ec t i on t ab le f o r DLP. . . 20
LegendQ [m3/hm] o [l/sm] supply air flow rate per linear metre
DLP...N the letter N indicates the number of diffuser’s slots
Δp [Pa] total pressure lost
NR noise rating (ISO standard, in relation to 10-12 W) taking no account of the attenuation of the room
20 30 40 50 60 70 80 90 100
200
300
400
50 60 70 80 90 100
200
300
400
500
600
700
800
900
1000
DLP20-1
DLP20-2
DLP20-3
DLP20-4
Q [m3/hm]
Q [l/sm]
∆p 10 20 50 Pa
NR 20 30 40
DLP20-5
DLP20-6
1500
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.2
DLP Linear slot diffuser
Qu ick re fe rence se l ec t i on t ab le f o r DLP. . . 30
Qu i ck re fe rence se l ec t i on t ab le f o r DLP. . . 40
Legend e no te s
Q [m3/hm] o [l/sm] supply air flow rate per linear metre
DLP...N the letter N indicates the number of diffuser’s slots
Δp [Pa] total pressur lost
NR noise rating (ISO standard, in relation to 10-12 W) taking no account of the attenuation of the room
- The value in the selection tables relate to linear metre
30 40 50 60 70 80 90 100
200
300
400
80 90 100
200
300
400
500
600
700
800
900
1000
DLP30-1
DLP30-2
DLP30-3
DLP30-4
Q [m3/hm]
Q [l/sm]
∆p 10 20 50 Pa
NR 20 30 40
DLP30-5
DLP30-6
1500
30 40 50 60 70 80 90 100
200
300
400
500
100
200
300
400
500
600
700
800
900
1000
2000
DLP40-1
DLP40-2
DLP40-3
DLP40-4
Q [m3/hm]
Q [l/sm]
∆p 10 20 50 Pa
NR 20 30 40
DLP40-5
DLP40-6
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 3
Linear slot diffuser DLP
DimensionPr i nc ipa l d imens i on i n a sec t i on v i ew
Pr i nc ipa l d imens i on i n a 3D v i ew
DLPA DLPB
Quant i t y and d imens i on o f t he p l enum’s connec t i on
DLP... slot number
L (mm) 1 2 3 4 5 6
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1 Connection
2 Connection
3 Connection
Legend Note
- DLP...20 Diffuser plenum dimension are: height H=20 mm and the connections diameter are Ø125 mm.
- DLP...30 e DLP...40 Diffuser plenum dimension are: height H=225 mm and the connections diameter are Ø150 mm.
L/6 L/6L/3 L/3
L/4L/2L/4
L/2L/2
L/4 L/2 L/4
L/6 L/3 L/3 L/6
L
H
4545
ØN
Slidingdumper
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.4
DLP Linear slot diffuser
AccessoriesAcces so r i e s
Angular for DLP...The angular for the DLP series diffuser are of three different model:
- 90° Angular (A-DLP...)
- T Angular (T-DLP...)
Head for DLPB...
Closing cap for DLP...
The head are available only for the DLPB diffuser... For a better appearance and to give sense of continuity with the 10 mm frame two frame are installed on the short side of the diffuser, (H-DLP...).
The closing cup for the DLP diffuser must be used when the diffuser is installed without a plenum only with appearance purpose for avoid air passages between the room and the suspended ceiling (TC-DLP).
- Cross (X-DLP...)
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 5
Linear slot diffuser DLP
20 x n45
DLPA20 DLPA30
45
DLPA40
45
(n = num. of slot)30 x n
(n = num. of slot)40 x n
(n = num. of slot)
S l o t d imens i on f o r DLPA h idden mode l
S l o t d imens i on f o r DLPA h idden mode l
P lenum box d imens i on
(20 x n)+20
45
(20 x n)+10
DLPB20(n = num. of slot)
(30 x n)+20
45(30 x n)+10
DLPB30
(40 x n)+20
45
(40 x n)+10
DLPB40(n = num. of slot) (n = num. of slot)
90
DLP30-1 DLP30-2 DLP30-3 DLP30-4 DLP30-5 DLP30-6
80
DLP20-1 DLP20-2 DLP20-3 DLP20-4 DLP20-5 DLP20-6
120
DLP40-1 DLP40-2 DLP40-3 DLP40-4 DLP40-5 DLP40-6
80 80 80 100 120
90 90 120 150 180
120 160 200 240
15 15 15
15 15 15 15
120 15 15 15 15
200
225
225
Ø12
5Ø
150
Ø15
0
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.6
1 2 3 4 5 6 7 8 9
SX DX
1234...
(3)(1)
(2)
...
Various types of throw can be obtained by an appropriate orientation of the deflector (some example are showed in the next chapter). The available configurations are showed below.
Con f i gu raz i on i d i spon ib i l i
SX SX
Configuration A (Standard):Direction of the throw opposite respect the side of the plenum alimentation connection. Left deflector orientation SX (see deflector orientation legend)
Configuration B :
Direction of the throw toward the side of the plenum alimentation connection. Right deflector orientation DX (see deflector orientation legend)
DX DX
deflectororientation (1)
deflector n° (3)
1 2 3 ...
row
n°
(2)
1 sx sx sx sx
2 sx sx sx sx
3 sx sx sx sx
4 sx sx sx sx
5 sx sx sx sx
... sx sx sx sx
deflector orientation (1)
deflector n° (3)
1 2 3 ...
row
n°
(2)
1 dx dx dx dx
2 dx dx dx dx
3 dx dx dx dx
4 dx dx dx dx
5 dx dx dx dx
... dx dx dx dx
Ava i l ab le con f i gu ra t i on
deflector orientation (1)
deflector n° (3)
1 2 3 4 ...
row
n°
(2)
1 ... ... ... ... ...
2 ... ... ... ... ...
3 ... ... ... ... ...
4 ... ... ... ... ...
... ... ... ... ... ...
Deflector orientation legend
(1) DX = Toward the side of plenum alimentation SX = Opposite respect the side of plenum alimentation
(2) row number on the section starting from the side of the alimentation connection
(3) Deflector number like in the view from below
View from below
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 7
123456
1234
12
DXSX
DXSX
DXSX
DXSX
Configuration C :
Throw in two diverging opposite direction in case of even number of deflector.
deflector orientation (1)
deflector n° (3)
1 2 3 4 5 6 ...
row n°(2) 1 sx sx dx dx sx sx dx
deflector orientation (1)
deflector n° (3)
1 2 3 4 5 ...
row n° (2)1 dx dx dx dx dx dx2 sx sx sx sx sx sx
deflector orientation (1)
deflector n° (3)
1 2 3 ...
row
n°
(2) 1 dx dx dx dx
2 dx dx dx dx3 sx sx sx sx4 sx sx sx sx
deflector orientation (1)
deflector n° (3)
1 2 3 ...
row
n°
(2)
1 dx dx dx dx2 dx dx dx dx3 dx dx dx dx4 sx sx sx sx5 sx sx sx sx6 sx sx sx sx
Ava i l ab le con f i gu ra t i on
1 2 3 4 5 6 7 8 9
SX DX
1234...
(3)(1)
(2)
...
deflector orientation (1)
deflector n° (3)
1 2 3 4 ...
row
n°
(2)
1 ... ... ... ... ...
2 ... ... ... ... ...
3 ... ... ... ... ...
4 ... ... ... ... ...
... ... ... ... ... ...
Deflector orientation legend
(1) DX = Toward the side of plenum alimentation SX = Opposite respect the side of plenum alimentation
(2) row number on the section starting from the side of the alimentation connection
(3) Deflector number like in the view from below
View from below
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.8
Configuration D :
Throw in two opposite converging direction. This type of configuration allows to obtain vertical throw, in case of ceiling installation, or horizontal, in case of wall installation.*NOTE: This kind of configuration is not possible with only one deflector row.
123456
1234
SXDX
SXDXSXDX
SXDXSXDXSXDX
Ava i l ab le con f i gu ra t i on
orientamentodeflettori (1)
n° deflettore (3)
1 2 3 4 5 ...
n°fila (2) 1 sx sx sx sx sx sx2 dx dx dx dx dx dx
orientamentodeflettori
n° deflettore
1 2 3 ...
n°fil
a
1 sx sx sx sx2 dx dx dx dx3 sx sx sx sx4 dx dx dx dx
orientamentodeflettori
n° deflettore
1 2 3 ...
n°fil
a
1 sx sx sx sx2 dx dx dx dx3 sx sx sx sx4 dx dx dx dx5 sx sx sx sx6 dx dx dx dx
1 2 3 4 5 6 7 8 9
SX DX
1234...
(3)(1)
(2)
...
deflector orientation (1)
deflector n° (3)
1 2 3 4 ...
row
n°
(2)
1 ... ... ... ... ...
2 ... ... ... ... ...
3 ... ... ... ... ...
4 ... ... ... ... ...
... ... ... ... ... ...
(1) DX = Toward the side of plenum alimentation SX = Opposite respect the side of plenum alimentation
(2) row number on the section starting from the side of the alimentation connection
(3) Deflector number like in the view from below
View from below
Deflector orientation legend
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 9
Configuration E :
This type of configuration allow the maximum customization of the diffuser. This configuration is designed to allow the costumer to orient the diffuser to obtain the desired air distribution. In this case the deflector orientation table result completely free, because is completely customizable:
Ava i l ab le con f i gu ra t i on
orientamentodeflettori (1)
n° Deflettore (3)
1 2 3 4 5 6 ...
n°fil
a (2
)
1 ... ... ... ... ... ... ...2 ... ... ... ... ... ... ...3 ... ... ... ... ... ... ...4 ... ... ... ... ... ... ...5 ... ... ... ... ... ... ...... ... ... ... ... ... ... ...
1 2 3 4 5 6 ...
123...
Here below an example of customized configuration to clarify the numbering system.
orientamentodeflettori
n° deflettore
1 2 3 4 5 6
n°fila1 dx dx dx dx dx dx2 dx dx dx dx dx dx3 sx sx sx sx sx sx
View from belowLateral view
(3) Deflector number
(2) Row number
SX DX
(1) Deflector Orientation
Deflector legend :
Example :
(1) DX = Toward the side of plenum alimentation SX = Opposite respect the side of plenum alimentation
(2) row number on the section starting from the side of the alimentation connection
(3) Deflector number like in the view from below
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.10
DLP Linear slot diffuser
Technical dataWork ing p r i nc ip l e
The inductive effect, generated by the high inlet air velocity, ensure a rapid decrease of the air velocity itself and at the same time an high temperature uniformities.The inlet angle, respect to the ceiling, ensure the ceiling effect moreover thanks to the stability of the air throw it is possible to reduce the air flow rate till about 40%.The geometry of the deflector is designed to reduce the pressure lost and the noise generated by the veloc-ity inlet.Normally the deflector are supplied with a single way length orientation independently of the number of the number of slot and of the deflector length, different configuration must be requested.The orientation can be easily modified, even when the deflector are installed, by extracting the plastic deflector and rotating them in the desiderate direction. Effective outlet area and noise generation do not change by changing deflector position.The number of the position of the standard connection of the plenum boxes , available with horizontal configuration (standard) or vertical configuration (on demand), provide a uniform distribution of air on all diffusers slot.Sliding dumper can be installed to precisely control the air flow across the diffuser. Depending by the deflec-tor position and orientation different type of throw can be obtained, here some example:
One way horizontal throw
Horizontal throw in opposite direction
Vertical throw near glass wall/wall
Vertical throw in the center of the room
Cons t ruc t i on
The DLP series linear diffusers has got black or white plastic deflector, with support, and frame if present, in natural anodized aluminium. The plenum box made of sendzimir zinc plated steel. In the insolated version the insulated material is certified in class 1 (D.M. 26-06-1984 art. 8). The plenum box connection is made by aluminium. The frame, if present, can be painted with all RAL colours.
Horizontal throw with waal installation
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 11
Linear slot diffuser DLP
E f fec t i ve ou t l e t a rea S (m 2)The effective outlet area is a notional area that, once the velocity of the air is know, makes it possible to arrive at the rate of flow that actually passing through the diffuser. The measurement is carried out with an instrument that measures the air at various pint across the diffuser. The formula links the various parameter is as follow. Q = vk x S x 3600where
Q = supply air flow rate [m3/h]
vk = velocity relating to the effective outlet area S [m/s]
S = effective outlet area [m2] 5
punto di misura
S (m2)number of slot
1 2 3 4 5 6
DLP20-1000 0,0052 0,0104 0,0156 0,0208 0,0260 0,0312
DLP30-1000 0,0078 0,0156 0,0234 0,0312 0,0391 0,0469
DLP40-1000 0,0104 0,0208 0,0312 0,0417 0,0521 0,0625
Weight (Kg)number of slot
1 2 3 4 5 6
DLP20-1000 4,7 5,2 5,6 6,1 6,9 7,8
DLP30-1000 4,7 5,3 6,0 7,0 8,1 9,2
DLP40-1000 4,8 5,4 6,7 8,0 9,4 10,7
Pre s su re l o s t and no i se r a te DLP. . . 20
Q [m3/hm] supply rate per linear metre
vk [m/s] velocity relating to effective outlet area
Δp [Pa] total pressure loss
NR noise rating (ISO standard, in rela-tion to 10-12 W) taking no account of the attenuation of the room.
Legenda
3
4
5
6
7
8
9
10
v K [m
/s]
20 30 40 50 60 70 80 90 100
200
300
400
50 60 70 80 90 100
200
300
400
500
600
700
800
900
1000
5
6
7
89
10
20
30
40
50
60
70
8090
100
∆p
[Pa]
ρ = 1,2 kg/m3
NR
45
40
35
20
25
Q [m3/hm]
Q [l/sm]
Q [m3/hm]
Q [l/sm]
DLP2
0-1
DLP2
0-2
DLP2
0-3
DLP2
0-4
30
DLP2
0-5
DLP2
0-6
1500
In order to correctly use the chart in the following pages, one must correct them to fit the right installation configuration by using some coefficient depending to the installation configuration itself.
Using single slot linear diffusers, in order to obtain a two way throw is necessary alternate the direction of the deflector every 200 mm .
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.12
DLP Linear slot diffuser
Pre s su re l o s t and no i se l e ve l DLP. . . 30
Pre s su re l o s t and no i se l e ve l DLP. . . 40
Legend and no te s
Q [m3/hm] air flow rate per linear metre
vk [m/s] velocity relating to the effective outlet area S
Δp [Pa] total pressure lost
NR noise rating ( ISO standard, in relation to 10-12 W) taking no account of the attenuation of the room
• The Δp and NR values are relating to the configuration with sliding damper completely open
• The Δp and NR values do not change by changing the different configuration of orientation of the diffusers.
3
4
5
6
7
8
9
10
v K [m
/s]
30 40 50 60 70 80 90 100
200
300
400
500
80 90 100
200
300
400
500
600
700
800
900
1000
2000
5
6
7
89
10
20
30
40
50
60
70
8090
100
∆p
[Pa]
ρ = 1,2 kg/m3
NR
45
40
30
20
25
Q [m3/hm]
Q [l/sm]
Q [m3/hm]
Q [l/sm]
DLP3
0-1
DLP3
0-2
DLP3
0-3
DLP3
0-4
35
DLP3
0-5
DLP3
0-6
50
3
4
5
6
7
8
9
10
v K [m
/s]
30 40 50 60 70 80 90 100
200
300
400
500
600
100
200
300
400
500
600
700
800
900
1000
2000
5
6
7
89
10
20
30
40
50
60
70
8090
100
∆p
[Pa]
ρ = 1,2 kg/m3
NR
45
40
35
30
20
25
Q [m3/hm]
Q [l/sm]
Q [m3/hm]
Q [l/sm]
DLP4
0-1
DLP4
0-2
DLP4
0-3
DLP4
0-4
DLP4
0-5
DLP
40-6
50
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 13
Linear slot diffuser DLP
F lu sh w i th the ce i l i n g ho r i zon ta l t h row
Q [m3/h] o [l/s] air flow rate
vm [m/s] average velocity of the throw at distance L
L [m] throw (= x + y)
x [m] horizontal dimension of the throw
y [m] vertical dimension of the throw
L0,2 [m] throw with terminal velocity 0,2 m/s
D [m] distance between two diffusers
ΔT [°C] difference between supply air temperature and ambient temperature
Legend
• The throw are related to the one way DLP slot, 1 m long and with a single way configuration.
• For the throw of multiple slot diffuser and for the two way throw the values of L0,2 must be multiply for the corrector factor of the table in page 9.
• The chart of the horizontal throw for the flush with the ceiling installation can be utilized for wall installa-tion at a distance less then 300 mm from the ceiling
• The throw average velocity at distance x, different form that indicated in the chart, can be obtained using the equation:
20 30 40 50 60 70 80 90 100
50 60 70 80 90 100
200
300
400
500
0,5
0,6
0,70,80,9
1
2
3
4
5
6
78
L 0,2
[m]
00,511,522,53
y [m]
123
4
x o
D/2
[m]
00,511,522,533,54
00,511,522,533,544,55
∆T
-10 °C
0 °C
+10 °C� = 1,2 kg/m3
Q [m3/hm]
Q [l/sm]
5 DLP20
...1
DLP30
...1DLP
40...1
DL
H
y
1,80
L=x+y
OCCUPIED ZONE
x
vmvm
vm
y
L=D/2+y
vm
L
<300
mm
0,20,2 ( / ) ^ 0,8xv L x= ×
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.14
DLP Linear slot diffuser
Cor rec t i ve f ac to r
No. of slot Throw direction
CORRECTIVE FACTORHORIZONTAL THROW
CORRECTIVE FACTOR TEMPERATURE RATIO (RT)
CORRECTIVE FACTORINDUCTION RATIO (i)
DLP...20 DLP...30 DLP...40 DLP...20 DLP...30 DLP...40 DLP...20 DLP...30 DLP...40
1 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0
2 0,7 0,7 0,7 0,7 0,7 0,7 1,6 1,6 1,6
1 1,3 1,4 1,5 1,2 1,3 1,4 1,2 1,2 1,3
2 0,9 1,0 1,1 0,9 0,9 1,0 1,8 1,9 2,0
1 1,6 1,7 1,9 1,5 1,7 1,8 1,3 1,4 1,5
2 1,1 1,2 1,4 1,0 1,1 1,2 2,1 2,3 2,4
1 1,7 2,0 2,3 1,7 2,0 2,2 1,4 1,6 1,8
2 1,2 1,4 1,6 1,2 1,4 1,5 2,3 2,6 2,8
1 1,9 2,2 2,6 2,0 2,3 2,5 1,6 1,8 2,0
2 1,3 1,6 1,8 1,4 1,6 1,8 2,5 2,9 3,2
1 2,0 2,4 2,9 2,2 2,6 2,9 1,7 2,0 2,3
2 1,4 1,7 2,1 1,5 1,8 2,0 2,8 3,2 3,7
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 15
Linear slot diffuser DLP
Ver t i ca l t h row i n hea t i ng DLP. . . 20
30 40 50 60 70 80 90 100
100
200
300
400
0,5
0,60,70,80,9
1
2
3
4
5
y MA
X [m
]
Q [m3/hm]
Q [l/sm]
Q [m3/hm]
Q [l/sm]+1
0∆T0 [°C] +5
+15
+8
� = 1,2 kg/m3
For DLP20-4 multiply the flow rate by 2 and ymax by 1,3
For DLP20-6 multiply the flow rate by 3 e ymax per 1,6
Ve r t i ca l t h row i n hea t i ng DLP. . . 30
30 40 50 60 70 80 90 100
100
200
300
400
500
600
0,50,60,70,80,9
1
2
3
4
56
y MA
X [m
]
Q [m3/hm]
Q [l/sm]
Q [m3/hm]
Q [l/sm]
+10∆T0 [°C] +5
+15
+8
� = 1,2 kg/m3
For DLP30-4 multiply the flow rate by 2 and ymax by 1,4
For DLP30-6 multiply the flow rate by 3 and ymax by 1,7
Ve r t i ca l t h row i n hea t i ng DLP. . . 40
60 70 80 90 100
200
200
300
400
500
600
700
0,50,60,70,80,9
1
2
3
4
56
y MA
X [m
]
Q [m3/hm]
Q [l/sm]
Q [m3/hm]
Q [l/sm]
+10∆T0 [°C] +5
+15
+8
� = 1,2 kg/m3
For DLP40-4 multiply the flow rate by 2 and ymax by 1,5
For DLP40-6 multiply the flow rate by 3 and ymax by 1,9
Legend and no te s
Q [m3/hm] o [l/s] flow rate for linear metre
ymax [m] maximum depth in heating
ΔT0 [°C] temperature difference between inlet air and envi-roment air
yMAX
www. t e c n o v e n t i l . comVER. 07/01/13We reserve the right to make any modification without prior notice.16
DLP Linear slot diffuser
Tempera tu re r a t i o
Legend e notesΔTL [°C] Temperature difference between the air stream and the environment at the distance
L (=x+y)
ΔT0 [°C] Temperature difference between air inlet and environment
RT=ΔTL/ΔT0 Temperature Ratio
The value in the chart are related to the one metre long DLP.
0,5
0,6
0,7
0,8
0,9 1 2 3 4 5 6 7 8 9 10
0,04
0,05
0,06
0,07
0,08
0,09
0,1
0,2
0,3
L =x+y [m]
RT
= ∆
T L/∆
T 0
DLP40-1
DLP20-1
ρ = 1,2 kg/m3
DLP30-1
I nduc t i on r a t i o
Legend e notesQL [m
3/hm] induced air flow rate at distance L (= x+y) per linear metre
QO [m3/hm] diffuser inlet air flow rate per metre
i=QL/QO induction rate
The values in the chart relates to throw by one metre long DLP.
The induction rate must be multiplied for some coefficient depending by the slot number. See pag. 10
0,5
0,6
0,7
0,8
0,9 1 2 3 4 5 6 7 8 9 10
5
6
7
8
9
10
20
30
40
50
L = x+y [m]
i (=Q
L/Q0)
DLP40-1
DLP30-1
DLP20-1
ρ = 1,2 kg/m3
www. t e c n o v e n t i l . comVER. 07/01/13
We reserve the right to make any modification without prior notice 17
Linear slot diffuser DLP
Fixing sistem
I n s t a l l a t i on
Sospension to becarried out by the client
M6 female threaded inserts
The installation of the DLP must be carried out as shown in figure, on all our plenum boxes we install four M6 female threaded insert to hang up to the ceiling using threaded bar.
I n s t a l l a t i on acce s so r i e s
Connection Plate
The connection plate is supplied to allow mounting two or more diffuser in line. It must be placed in the right position as show in the figure above. In the center of the connection plate there is a protrusion that allow to fix it in the diffuser external profile (C-DLP).
Fixing brackets for without plenum installation
The fixing bracket is supplied when one want to install the DLP diffuser without plenum, on it there are al-ready one, two, three or four holes depending on the number of slot, to fix the suspension threaded bar. The fixing brackets are always supplied for the without ple-num installation.
component for air conditioning sistem
tecno-vent i l s .p.a . V ia Parma, 226016 Sp ino d ’Adda (CR) Te l . +39 0373.980456Fax +39 0373.980681www.tecnovent i l . comin fo@tecnovent i l . com