Page 1: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

COMPATIBILITY REPORT

Balluff BIS014K Read/Write IO-Link Device

PLC

DCS/HMI/SCADA

IO-LINK SENSORS/ACTUATORS

Page 2: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Table of Contents

Table of Contents .................................................................................................................................................................... 2

Test Report Overview ............................................................................................................................................................. 3

IO-Link Master – IO-Link Diagnostics Page ............................................................................................................................ 3

Configuring IO-Link Settings Settings ..................................................................................................................................... 4

After Configuring Friendly Port Names ................................................................................................................................ 5

Setting Up Passwords ............................................................................................................................................................. 6

IO-Link Device Configuration .................................................................................................................................................. 7

Loading the IODD Files ....................................................................................................................................................... 7

Verifying that the Correct IODD Files Loaded ..................................................................................................................... 9

Changing Parameters - GUI .............................................................................................................................................. 10

Changing Parameters - ISDU Interface ............................................................................................................................. 12

Using the Data Storage Feature ........................................................................................................................................... 14

Manual Data Storage ......................................................................................................................................................... 20

Using the Device Validation Feature ..................................................................................................................................... 24

Incompatible Device Attached to Port ............................................................................................................................... 24

Compatible Device Attached to Port ................................................................................................................................. 25

Identical Device Validation ................................................................................................................................................ 25

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 2

Page 3: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Test Report Overview

The Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link device operates properly with the Comtrol IO-Link Master. This report contains the following topics:

• IO-Link Master – IO-Link Diagnostics page

• Configuring IO-Link settings

• Setting up passwords

• IO-Link device configuration

• Using the data storage feature

• Using the device validation feature

The Read/Write IO-Link device was tested using Application Base v1.3.17 on the IO-Link Master 4-EIP (machine mountable IP67). This report does not illustrate all Comtrol IO-Link Master features, such as: EtherNet/IP and Modbus/TCP configuration, uploading the latest software, or network configuration.

IO-Link Master – IO-Link Diagnostics Page

Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays the Read/Write IO-Link devices on Ports 1 and 2.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 3

Page 4: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Configuring IO-Link Settings Settings

During IO-Link configuration, the Minimum Cycle Time can be left to the default value, as the IO-Link Master negotiates the required Cycle Time with each IO-Link device.

This example shows configuring a port-friendly name. The Data Storage and Device Validation features are discussed later in this report after using the IO-Link Master to configure the BIS M-458-045-001-07-54 parameters.

1. Click Configuration | IO-Link and then the EDIT button on the corresponding port.

2. Enter the port friendly name and click SAVE.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 4

Page 5: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

After Configuring Friendly Port Names

You can use the IO-Link Configuration page to customize the Port Name. The IO-Link Diagnostics page now displays a friendly port name.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 5

Page 6: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Setting Up Passwords

The IO-Link Master ships from the factory without passwords and administrative permissions are granted. You can use the Advanced | Accounts page to set up passwords for the IO-Link Master. Admin, Operator, and User permissions are defined in the help system on the Accounts page.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 6

Page 7: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

IO-Link Device Configuration

You can use the Comtrol IO-Link Master to configure the IO-Link device.

• If an IODD file is loaded, you may want to use the GUI on the top of the IO-Link Device Description – Port page to change parameter settings.

• If an IODD file is not loaded, you can use the ISDU Interface on the bottom of the IO-Link Device Description – Port page

This section discusses the following topics:

• Loading IODD files

• Verifying that the correct IODD file is loaded

• Changing IO-Link device parameters using the GUI

• Resetting to the IO-Link device to factory defaults

• Changing IO-Link device parameters using the ISDU Interface

Loading the IODD Files

The IODD file was easy to locate and download from the Balluff web site.

1. Click Attached Devices | IODD Files.

2. Click the UPLOAD IODD FILE button.

3. Click Browse, select the file set to upload, and click the Open button.

4. Click the UPLOAD button.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 7

Page 8: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

5. The IO-Link Master loads only the files required and may issue a message like this:

6. Click the file name if you want to view the .xml file.

7. Optionally, review the xml file before device configuration.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 8

Page 9: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Verifying that the Correct IODD Files Loaded

You can use the IO-Link Master to verify that the correct IODD files for a product is loaded using the Summary page.

1. Click Attached Devices | Summary.

2. Verify that the port that the device is connected to displays an xml file name in the IODD Name field, as illustrated in this image.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 9

Page 10: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Changing Parameters - GUI

Use the Edit button to easily configure the BIS M-458-045-001-07-54 using the table (GUI).

1. Click Attached Devices | Port 2 (in this example). The IO-Link device displays as expected in the PORT page.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 10

Page 11: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

2. Click the EDIT button and change several parameters and click SAVE.

A temporary limitation using the GUI has been reported.

Index 24 can be modified but changes to Index 64 resets all of the sub-indexes to 0. The IO-Link Device ISDU Interface works without any problems.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 11

Page 12: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Changing Parameters - ISDU Interface

This shows using the IO-Link ISDU Interface to change configuration parameters.

Please note:

• You must enter the decimal value for the ISDU Block Index and ISDU Sub-index.

• The following images do not display the complete web page.

• The following screenshots do not illustrate the system responses. The IO-Link Master responds with a command executed notification.

The following shows how to use the IO-Link ISDU Interface to change IO-Link device configuration parameters.

1. Verify that the BIS M-458-045-001-07-54 responds to queries.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 12

Page 13: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

2. Enter the hex equivalent of 254 for Index 64, Sub-index 6 and click SET.

3. Change ISDU Index 64, Sub-index 3 to 1.

4. Click REFRESH to view that the changes have been made.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 13

Page 14: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Using the Data Storage Feature

The following examples illustrate automatic and manual data storage.

This example automatically uploads data storage using the values from the previous subsection.

1. Access the Configuration | IO-Link Settings page.

2. Click the EDIT button on the corresponding port.

3. Click Automatic Upload Enable to On.

4. Click SAVE. The data storage (sensor configuration) uploads to the IO-Link Master as soon as the SAVE button is clicked.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 14

Page 15: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Notice that the IO-Link Diagnostics page displays that Automatic Data Storage Configuration for uploading and downloading is enabled.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 15

Page 16: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Notice that when you return to the IO-Link Diagnostics page that the Storage Contents field contains the Vendor ID and Device ID of the contents stored on the corresponding port.

5. Click EDIT, set Automatic Upload Enable to No.

6. Set Automatic Download Enable to Yes and click SAVE.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 16

Page 17: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

7. Notice the IO-Link Diagnostics page now displays Automatic Data Storage – Download.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 17

Page 18: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

8. Move the BIS0014K to another port and change several parameters, which are displayed below.

9. Replace the BIS0014K on Port 2.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 18

Page 19: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

10. Verify that the parameters are set to contents of the data storage.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 19

Page 20: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Manual Data Storage

The following illustrates how Manual Data Storage works.

1. Click Configuration | IO-Link Settings.

2. Click the EDIT button.

3. Click the UPLOAD button under Data Storage Manual Ops.

4. Click CONTINUE.

5. Click Ok to the DONE message and click SAVE to close the port.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 20

Page 21: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

6. Change BIS0014K parameters, as displayed in this illustration.

7. Click Configuration | IO-Link and then the EDIT button.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 21

Page 22: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

8. Click the DOWNLOAD button and then click the CONTINUE button.

9. Click Ok to the DONE message and click SAVE to close the port.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 22

Page 23: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

10. Observe that the parameters have been downloaded from the IO-Link Master to the BIS0014K.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 23

Page 24: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

Using the Device Validation Feature

The Read/Write IO-Link device supports Compatible Device Validation. IO-Link Master requires a device serial number for Identical Device Validation.

Incompatible Device Attached to Port

1. In the IO-Link Configuration page, click EDIT, set Device Validation mode to Compatible.

2. Click the GET ATTACHED button.

3. Click SAVE.

4. Remove the BIS0014K device from Port 2 and connect another IO-Link device (not a BIS M-458-045-001-07-54).

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 24

Page 25: COMPATIBILITY REPORT … · Two Balluff Read/Write IO-Link devices were connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displays

5. The IO-Link LED on the IO-Link Master is now flashing red to indicate that an incompatible device is connected to the port. In addition, the IO-Link Diagnostics page displays that an incompatible device is attached to the port.

Scroll down the page to view the error codes.

Compatible Device Attached to Port

Unable to test this feature with a single BIS0014K.

Identical Device Validation

Unable to test this feature with this device since a Device Serial Number is required for Identical Device Validation.

4/29/2015 Comtrol IO-Link Master | Balluff BIS014K (BIS M-458-045-001-07-54) Read/Write IO-Link Device 25