compact integrated distribution substation cids catalog

Upload: alexns84

Post on 03-Apr-2018

235 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    1/12

    Compact IntegratedDistribution Substation(CIDS)

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    2/12

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    3/12

    2

    SAVE SPACE

    2.5m2 footprint for CIDS up to 630kVA.

    SAVE THE ENVIRONMENT

    No SF6, No PCB.

    SAVE MONEY

    Save up to 50% from conventional package substation with housing.

    ENSURE SAFETY FOR PUBLIC

    No exposed live parts.

    ENSURE SAFETY FROM FIREIf filled with flame retardant fluid.

    1- INTRODUCTION

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    4/12

    3

    2- DESCRIPTION

    The CIDS is a compact fully integrated outdoor package substation with medium

    voltage equipment, transformer, and low voltage equipment. The package

    substation is completely manufactured and assembled ready for installation on site.

    It ensures a high level of protection against access to live parts with a protection

    degree of IP 54 according to IEC 60529.

    The operation and control is achieved from the front of the unit, with separate

    compartments for medium voltage and low voltage sections. Four lifting lugs

    located on the upper part enable the lifting of the complete unit easily.

    2.1. Major Benefits

    2.1.1. Compact design-Reduced footprint Reduction of space requirement. Reduction of footprint.

    2.1.2. Cost Savings Minimum installation and maintenance labor costs.

    Minimum civil work; no building or vault structure.

    No need for main low voltage circuit breaker.

    2.1.3. Operational Integrity Components are assembled and tested as an integral unit at the factory.

    Access to all elements of control and protection in one casing.

    2.1.4. Safety Live parts inside the secure enclosure are hidden from the public and

    environment. If filled with flame retardant fluid, risk of transformer fire is greatly reduced due to

    high fire and flash points.

    2.1.5. Environmental Integrity Low profile design requires minimum real estate.

    Dielectric fluid replaces ozone-depleting SF6 gas, currently used in RMU switching

    modules.

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    5/12

    4

    2.2. Main Components

    2.2.1. Enclosure

    Single compact enclosure housing the transformer, medium voltage and low voltage

    sections.

    The is designed to be installed outdoor, with a protection degree of IP 54 according

    to IEC 60529

    2.2.2. Low voltage sectionThis section can be designed and manufactured according to the needs of each

    customer. Basic equipment includes:

    Low voltage bushings

    Three current transformers

    Four outgoing circuits by fuse links

    Three ammeters

    One voltmeter + one selector switchOptional:

    Circuit breakers instead of fuse links

    Multifunction electronic meter

    2.2.3. Medium voltage sectionIt includes the following components:

    Plug-in bushings

    Two sectionalizing switches for incoming and outgoing lines with earthling facility

    Main interrupter for protection against overloads and secondary short circuits

    Backup fuses for protection against internal faults

    Tap changer for voltage control (off-load)

    Voltage presence indicators

    Hotstick for sectionalizing switch operationOptional:

    Earth fault and short circuit indicators

    2.2.4. Transformer sectionIt includes the core and the windings of the transformer.

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    6/12

    5

    Plug-in bushing (Fig 1)

    Built in capacitive point for voltage presence detection.

    Three phase loadbreak sectionalizing switch (Fig 2)Make-Before-Break operation.

    Silver plated copper contacts.

    Open/Close/Earth positions.

    Back-Up current limiting fuse(Fig 3)

    For transformer internal faults.

    Protects and isolates faulty equipment.

    Coordinated with main interrupter (4), gives full range of fault protection.

    Main interrupter (Fig 4)

    Current and temperature sensitive protective device.

    Protects from overloads and secondary faults.

    Three phase trip, externally resettable.

    Insulating fluidStandard mineral PCB free oil according to IEC 60296.

    Optional: fire resistant high fire point organic or synthetic fluid.

    Fig 1 Plug-in bushing Fig 4 Main interrupter Fig 2 Three phase load break

    sectionalizing switch

    Fig 3 Back-up current limiting

    fuse

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    7/12

    6

    2.3. CIDS Single Line Diagram

    Earth

    Earth

    B

    Source

    LV

    Panel

    Closed

    A

    Source

    2Closed

    1

    5Open

    LV

    Open

    3 4 TransformerCoil

    Fig 5 Lifting Lugs Fig 8 Three phase main

    interrupter

    Fig 6 Name Plate +

    single line diagramFig 7 Mimic and labels

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    8/12

    7

    Design ambient temperature 40C

    Frequency 50Hz or 60Hz

    2.4. Technical Data

    Rated voltages

    Primary highest voltage 12kV /17.5kV/24kV

    Rated secondary voltage From 231V up to 433V

    Vector group Dyn11

    Lightning impulse voltage (primary) 75kV/95kV/125kV

    Industrial frequency withstand during 1 min (primary) 28kV/38kV/50kV

    Off load tap changer (5 positions) 2x2.5%

    No load losses 445W 840W 920WLoad losses 2715W 3950W 6020W

    Short circuit impedance 4.00% 4.00% 4.00%

    ACCORDING TO IEC 60076 STANDARD

    Rated short duration admissible current 16kA

    Sectionalizing switch for input-output and ground

    Highest voltage level 12kV /17.5kV/24kV

    Rated direct current 630A for 12kV primary

    400A for 17.5kV and 24kV primary

    Fuses

    Highest voltage level 24kV

    Maximum interrupting current 50kA rms

    Plug-in bushings, 6 in loop

    Highest voltage level 24kV

    Rated direct current 630A

    ACCORDING TO IEC 60298 STANDARD

    Rated voltage From 231V up to 433V

    Rated current Up to 1000A (according to transformer rating)

    Short time current (1s) 25kA

    Earthing Neutral solidly earthed

    Industrial frequency withstand during 1 min 2.5kV

    Lightning impulse withstand test 6kV

    ACCORDING TO IEC 60439 STANDARD

    GENERAL

    TRANSFORMER 250kVA 400kVA 630kVA

    MEDIUM VOLTAGE

    LOW VOLTAGE

    For 1000kVA please consult us

    For other requirements than the above table, please consult us

    Fig 9 Off load tap changer Fig 13 Dielectric

    level indicator

    Fig 10 LV porcelain

    bushings

    Fig 12 Pressure

    relief valve

    Fig 11 Medium voltage

    screened bushings

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    9/12

    8

    2.5. Dimensions and Weights

    D

    G

    L1

    H

    A

    C

    L2

    BF

    Ma d e in Lebanon

    MATELEC s.a.l

    B 2 C 1 C 2

    nc

    MagneX

    Fuse

    Sectional izingSw itch

    A

    BC

    ab

    c

    A 1 A 2 B 1

    ba

    Email:matelec@matelecgroup. comP. O . Box :12 J bei l -Lebanon

    Fax:+9619620934/35

    Manuf acturedby Matelec s.a. l

    Tel :+9619 620920

    E

    Rating

    kVA

    -C-

    mm

    -D-

    mm

    -E-

    mm

    -F-

    mm

    -G-

    mm

    -H-

    mm

    250

    400630

    1230

    12301230

    2080

    20802080

    1230

    12301230

    1975

    19751975

    715

    715715

    1117

    11171117

    813

    813813

    2550

    29003250

    Dimensions and weights are approximate and may change according to specifications.

    850

    850850

    Total

    Weight

    Kg

    -B-

    mm

    -A-

    mm

    Fig 14 Line Sectionalizing

    switch and earth controlsFig 16 Elbow ConnectorFig 15 Led ( voltage indicator) Fig 17 Grounding terminals

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    10/12

    9

    21

    18

    18

    19

    20

    15

    16

    17

    11

    12

    13

    14

    A2

    L1

    MadeinLebanonMATELECs.a.lABCabc

    A1

    a

    L2

    C2MagneXFuse

    Email:[email protected]: 12 Jbeil-LebanonManufactured byMatelecs.a.lB2C1

    nc

    B1

    b

    Fax:+961 9 620934/35Tel:+961 9 620 920S ectionalizingS witch

    25

    24

    23

    22

    1 2 3 4 5 6 7 8 109 26

    1. Lifting Lugs (Fig 5) 14. Line Sectionalizing switch and earth controls (Fig 14)

    2. Dielectric refill plug 15. Led ( voltage indicator) (Fig 15)

    3. Name Plate + single line diagram (Fig 6) 16. Medium voltage screened bushings (Fig 11)

    4. Mimic and labels (Fig 7) 17. Elbow Connector (Fig 16)

    5. Three phase main interrupter (Fig 8) 18. Grounding terminals (Fig 17)

    6. Off load tap changer (Fig 9) 19. Medium voltage cable support + clamps (Fig 18)

    7. LV porcelain bushings (Fig 10) 20. Medium voltage compartment (Fig 20)

    8. Power meter (Optional) 21. Rollers

    9. Current Transformers 22. Fuses

    10. Power Meter Protection Fuses (optional) 23. Low voltage compartment (Fig 21)

    11. Pressure relief valve (Fig 12) 24. Low voltage cable support + clamps

    12. Dielectric level indicator (Fig 13) 25. Drainage and sampling device

    13. Blocking device 26. Insulated device for drive (Hotstick) (Fig 19)

    Fig 18 Medium voltage cable

    support + clamps

    Fig 19 Insulated device for

    drive (Hotstick)

    Fig 20 Medium voltage

    compartment

    Fig 21 Low voltage

    compartment

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    11/12

    ELECTRICAL EQUIPMENT INDUSTRIES COMPANY LTD.

    P.O.Box 850175 Amman 11185

    Amman, Jordan

    Tel: (962) 6 5727861/2

    Fax: (962) 6 5727863

    E-mail: [email protected]

    INTERNATIONAL TRANSFORMERS MATELEC LTD.

    10th of Ramadan City, Egypt

    Tel: (20) 2 4149004 - 2901795

    Fax: (20) 2 4155614

    E-mail: [email protected]

    SAUDI MATELEC CO. FOR INDUSTRIES LTD.

    Dabab Street, Dabab Bldg, 3rd floor, Office N 10

    P.O.Box 52114, Riyadh 11563

    Riyadh, Kingdom of Saudi Arabia

    Tel: (966) 1 4029909

    Fax: (966) 1 4024280

    E-mail: [email protected]

    TRANSFO MATELEC S.A.

    ZI de Briangaud

    35600 Redon, France

    Tel: (33) 2 99711650

    Fax: (33) 2 99721700E-mail: [email protected]

    MATELEC S.A.L.

    Amchit - Ghorfine

    P.O.Box 12 Jbeil - Lebanon

    Tel: (961) 9 620920

    Fax: (961) 9 620934/5

    E-mail: [email protected]

  • 7/28/2019 Compact Integrated Distribution Substation CIDS Catalog

    12/12

    MATELEC GROUP

    Amchit - Ghorfine - P.O.Box: 12 Jbeil - Lebanon

    Tel: (961) 9 620 920 - Fax: (961) 9 620 934/5

    E-mail: [email protected]

    www.matelecgroup.com