CIM Users Group Meeting Gydnia, Poland 1-4 June 2015 CIM Users Group Gdynia, Poland 1-4, June 2015 Common Distribution Power System Model (towards 61968-13 Ed 2.0) Eric Lambert Didier Ilhat Mathieu Caujolle (EDF) Nejc Petrovic (EG) Gianluigi Proserpio (RSE)

Upload: lekhuong

Post on 21-May-2018

256 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

CIM Users Group Gdynia, Poland1-4, June 2015

Common Distribution Power System Model (towards 61968-13 Ed 2.0)

Eric Lambert – Didier Ilhat – Mathieu Caujolle (EDF)Nejc Petrovic (EG)

Gianluigi Proserpio (RSE)

Page 2: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Outline

• Why CDPSM ?, What is it ?• Notions from 61968-13 Ed 1, EPRI CIM Primer

• Time Line

• CDPSM Ed 2• What has been done

• Where are we heading to ?• Distribution Network Studies

• Feeder Task Force

• Conclusion

CDPSM 2

Page 3: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Why CDPSM ? What is it ?

• CIM was used at transmission level since 2000, and the profile was named “Common Power System Model”

• CDPSM was created to insure that Distribution needs were covered

• CDPSM will enable the information exchange between TSO and DSO

CDPSM 3

• Aims to Model Distribution Networks (MV, LV)

• Balanced, Unbalanced

• These Distribution Networkswill be exchanged in global, differential model

• The syntax used is RDF

• Load Flow calculation will be run upon these conforming data sets

• Node/Breaker & Bus/Branch

Page 4: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015CDPSM 4

Model Exchanges61968-13

61968-13 Edition 2 will berenamedCommon Distribution Power

System Model Profiles

Page 5: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Notions from CIM Primer Ed2

• PROFILE GROUP

CDPSM 5

Requirement:What are the Common Profilesfor T & D, What is specific to D ?

Page 6: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

CPSM Profile from CIM Primer Ed 2.

CDPSM 6

PROFILE A DATASET AValidated according to

PROFILE B DATASET B

Reference Reference

Page 7: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

CDPSM Profile from CIM Primer Ed 2

CDPSM 7

Requirement:Some electrical properties are mutualized and found in Asset related classes (Catalog)

Page 8: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

ENTSO-E Profile from CIM Primer Ed 2

CDPSM 8

CGMES (Common grid Model Exchange Standard)

Set of ENTSO-E Profiles Based on IEC 61970/61968 standards and related Profiles

EQ -TP - SSH – SV – DL – DY – GL

Page 9: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

CGMES UML Structure

CDPSM 9

What is relevant for Distribution ?

Keep it simple first, but preserve evolutivity

Page 10: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Time Line

• CDPSM was used by ADDRESS and DERri European Projects

• 61968-13 Edition 2 will be aligned on CIM 17CPSM : Common Power System Model CDPSM : Common Distribution Power System Model CGMES : Common Grid Model Exchange Standard

CDPSM 10

2001-2006 2008 2009 2011 2014 2015 2016

CPSM IOP testsfirst CDPSM trialsOrganiser : EPRI

First CDPSM IOP TestHost : Oncor (US)Organiser: UCACIM 14

Second CDPSM IOP TestHost : EDF (Fr)Organiser : UCACIM 15

IEC 61968-13 Ed 1 : IS

First CIM IOP test for UCTEHost : RTEOrganiser: UCA

CGMES IOP TestHost : ENTSO-EOrganizer : ENTSO-E

IEC 61968-13 Ed 2 IEC

CDPSMIOPtests

CGMESIOPtest

IEC 61970-452

IEC 61970-452IEC 61970-453IEC 61970-456IEC 61970-458

CGMES IOP TestHost : ENTSO-EOrganizer : ENTSO-E

ENTSO-EConformity Assessment

CDPSM Ed2 IOP ?

CIM 16

Page 11: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

CDPSM Ed 2 : What has been done?

• Use Cases

• Gap Analysis between CGMES and CDPSM needs

• CIM issues

• UML Profiling and Document Generation

• The CDPSM UML Tool chain

• Data Conversion from 2011 CDPSM 1.0 IOP test to CDPSM Ed 2.0

CDPSM 11

Page 12: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Use Cases (What has been done?) Use of 62559-2 IEC Use Case Template

Name of Use Case Short description Actors General

remarks

DSO provides its power system

models to TSO

In order to calculate the TSO grid power

flow, the DSO provides to TSO an aggregate

view of its power system model, including

the related states and measurements.

TSO

DSO

A customer provides its DER

plant power system models to

DSO

A DER connection to Distribution grid

request is supported by the description of an

aggregate view of the DER plant power

system model

DSO

DER

Could also be

applied for

“operational

planning” and

“network

operation” ?

DSO1 and DSO2 mutual

exchange their power system

models

DSO1 and DSO2 mutual exchange their

power system models in order to manage

the grid in case of outages on a boundary

feeder

DSO1

DSO2

TSO and DSO provides their

power system models to a third

party

TSO and DSO provides their power system

models to a third party in order to perform an

ex-post analysis of a power quality issue (i.e

Voltage Dips)

TSO

DSO

Authority

DSO/DNO internal information

exchange

A DSO/DNO exchanges various information

or data between different systems within the

company

DSO or

DNO

DNOs provide their power system

models to DSO

In order to perform network planning,

various analyses, outage management, etc.,

of the whole distribution grid, the DSO needs

power system models of the subordinate

DNOs grids.

DSO

DNO

DNOs own and

operate a part

of the whole

distribution grid

for which the

DSO is

responsible of

(Slovenian

case).

CDPSM 12

Page 13: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Gap Analysis between CGMES and CDPSM needs(What has been done?)

CDSPM 13

Other Utility Distribution networkare welcometo feed this gap Analysis !

Page 14: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

CIM ISSUES

• 2 CIM Issues Solved with CIM 17

• 2 remaining CIM issues

14

Page 15: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

UML Profiling and Document Generation(What has been done?)

CSPM 15

Diagram Layout will be usedSSH will be usedDynamics not used

CGMES CDPSM

CIM

Page 16: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

The CDPSM UML tool chain

CDPSM 16

MODSARUS®

jCleanCim + = 61968-13 Ed 2

MODSARUS®

+

CDPSMUse Cases

CDPSMProfiles1

2

Page 17: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Data Conversion from 2011 CDPSM IOP test to CDPSM Ed 2.0(What is beeing done?)

CDPSM 17

EDF files from 2011 IOP tests : MV RURAL, MV URBAN, MV-LV network

CDPSMed 12011

CIM15

CDPSMed 22016

CIM 17

Data Converter RiseClipse

ValidationReport

Other validation

tools

3CDPSMDataSetValidation

Page 18: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Where are we heading to ?

• Distribution Network Studies

• Feeder Task Force report

• CDPSM IOP Test• Feedback to ENTSO-E CGMES, DSO associations

• Feedback to IEC Working Groups

• Publication of 61968-13 Ed 2

• List of additonal Use Cases, Requirements to prepare 61968-13 Ed 3

CDPSM 18

Page 19: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Distribution Network Studies

• EDF R&D DisNetSimpl Network Simulator

CDPSM 19

CDPSM Ed 2.0

Is based onIs based on

Is based on

CDPSMLOAD FLOW

54 Network“Settings”

Page 20: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Feeder task force status report

• Approx. 5 conference calls until now

• Approx. 10 people actively participating

• First objective is to gather as many use cases and requirements as possible from DNOs/DSOs

• Currently in the process of reviewing different requirements that havebeen expressed by different participants and also possible solutions

• Our aim is not to modify the UML model significantly

• We always have to have backward compatibility in mind

CDPSM 20

Page 21: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Feeder modelling – core problems

CDPSM 21

Page 22: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Feeder modelling

CDPSM 22

cla ss Cir cui ts

IdentifiedObject

Cir cui t

EquipmentContainer

Cor e::Substa t ion

EquipmentContainer

Cor e::Ba y

EquipmentContainer

W ir es::Line

EquipmentContainer

W ir es::P lant

+Circuit 0..1

+Plant 0..*

+Circuit

0..1

+Line 0..*

+Circuit

0..1

+Bay

0..1

+Circuit

0..*

+Substation

0..*

+Bays 0..*

+Substation 0..1

Page 23: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Feeder modelling – some open issues

• What is the start of the feeder (The breaker, the terminal) ?

• Where does the feeder end (with a substation, a sectionalizer) ?

• What are the rules in a meshed network vs a radial network?

• Does it contain equipment ?

• Does it associate with the Bay ?

• What are the rules in a LV network ?

• What are the rules when using the Line class vs the feeder class ?

• Where is the feeder class derived from?

• Does this solution support all our requirements?

CDPSM 23

Page 24: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Conclusion

This work will support DSO Network Modeling issues• Its goal is to clarify what are :

• DSO requirements• Common TSO/DSO requirements• TSO/DSO information exchange requirements

• Its goal is to get the most of Vendor Tools• Minimization of specificities

• A good standard can’t be defined without good requirements• DSO representatives are welcome to join IEC TC57

• Our aim is to walk the talk…

CDPSM 24

Page 25: Common Distribution Power System Model - UCAIugcimug.ucaiug.org/Meetings/Europe2015/Documents/UCACIMug_CDPSM_v1.4.pdfCommon Distribution Power System Model ... First CIM IOP test for

CIM Users Group Meeting – Gydnia, Poland – 1-4 June 2015

Thanks for your attention ! • Bibliography

• IEC 61968-13 IS 2008

• http://cimug.ucaiug.org/Groups/CIMInterop/CDPSM Interop/EDF CDPSM IOP REPORT/EDF Readme IOPReport CDPSM 2009.pdf -

• http://cimug.ucaiug.org/CIM Interop Documents/2011 UCAIug IOP Tests - Part 3, 4, 6, 9, 13/CDPSM 2011 IOPFinal Report.pdf

• http://www.addressfp7.org/ http://www.der-ri.net

CDPSM 25