Commercial VisionPRO™ 8000
210511
VisionPRO 8000 Features
• Commercial VisionPRO 8000 incorporates all the standard features of the VisionPRO family:- Sleek design
- Menu-driven programming
- Large touchscreen display
• But the Commercial VisionPRO 8000 goes even farther and is tailored with features specifically for commercial applications
OS Number Applications
TB8220U10032H/2C Conventional
3H/2C Heat Pump
310511
Commercial VisionPRO 8000
• Enhanced energy savings- Economizer output
- Holiday setback
• Commercialized control algorithm- Better and more consistent control in commercial applications
• Multiple keypad lockout levels• Configurable recovery ramps• Occupied/unoccupied scheduling • Title 24 energy/air quality compliance
The Commercial VisionPRO 8000 offers these distinguishable commercial features:
410511
Nomenclature
TB 8 22 0 U 1 003
Family Designation8 = VisionPRO touchscreen7 = VisionPRO conventional
Application0 = Standard
Specification DetailsLine DesignationTB = Buildings ThermostatTH = Homes Thermostat
System Stages22 = 2 Heat / 2 Cool
PowerU = Universal (dual powered, system flexibility, scheduling flexibility)
Commercial VisionPRO 8000
Installation Procedures
610511
Installation
• Steps to install Commercial VisionPRO 8000- Mounting
- Wiring
- Powering Thermostat
- Set Calendar
- Installer Setup Menus Main Settings Menu Regional Settings Menu Advanced Settings Menu
- System Test(s)
710511
Installation - Wallplate Mount
• Mounts directly on wall• 4” x 2” electrical box• Coverplate available
810511
Application Wiring
• Choose Conventional or Heat Pump terminal labels
• Insert wires in terminal block
• Jumper—factory installed
910511
Wiring 1 Heat/1Cool Conventional
1 = Power Supply2 = Factory Installed Jumper3 = Optional Sensor
1 Heat/1 Cool single transformer.
1010511
Wiring 2 Heat/2 Cool Conventional
1 = Power Supply2 = Factory Installed Jumper3 = Optional Sensor
2 Heat/2 Cool single transformer.
1110511
Wiring 1 Heat/1 Cool Heat Pump
1 = Power Supply2 = Factory Installed Jumper3 = Set to O or B in Setup4 = Optional Sensor
1 Heat/1 Cool Heat Pump with NO Auxiliary Heat.
1210511
Wiring 2 Heat/1 Cool Heat Pump
1 = Power Supply2 = Factory Installed Jumper3, 4 = Optional Sensor5 = Must Wire Common6 = Set to O or B in Setup
TOD/ECON
2 Heat/1 Cool Heat Pump with Auxiliary Heat.
1310511
Powering Thermostat
• Hardwired or
• Batteries (included)- 3 AAA Alkaline batteries
1410511
Mounting Thermostat on Wallplate
• Locks straight into position- Line up pins with the
terminals
- Push thermostat straight onto the wallplate until it snaps into place
1510511
Activate Real Time Clock
• To activate the Real Time Clock, simply pull on Tab to remove during installation
1610511
Set Calendar
• Real Time Clock – Set Calendar- Set Year
- Set Month
- Set Day
1710511
Set Time
• Real Time Clock – Set Time- Adjusts automatically for
daylight savings time
- Maintains time and day during power outage
• Press Done
Time
Can turn Daylight Savings Time feature off in Installer Setup
1810511
Initiate Installer Setup
1. Press the SYSTEM key2. PRESS and HOLD the
two unmarked keys as shown until the display changes- Approximately 5 seconds
1910511
Installer Setup Display
• Setup Number on Left- 4-digit number starting with
0
- Use the up arrow to advance to the next installer setup option
• Current Setting on Right- 2-digit number
- Use the up and down arrows to change the current setting
• Exit Installer Setup- Press the Done Key
CurrentSetting
SetupNumber
Commercial
2010511
Easy-to-Use Installer Setup Menus
1. Installer Setup is broken into 3 menus- Main Settings menu—numbers 0120 to 0290
Must Select the System Type
- Regional Settings menu—numbers 0300 to 0499- Advanced Settings menu—numbers 0500 to 0710
2. Smart Installer Setup- Setup numbers automatically change defaults based on
previous choices
- Setup number choices appear and disappear based on previous choices
2110511
Main Menu Installer Setup Menu Items
• Setting the Calendar- Year, Month, Date
• Schedule Options- 7 day
- Non-Programmable
• System Type- 12 choices
• Fan Operation• O/B terminal• Continuous backlight
• Cycles per hour- Compressor
- Heat (Emergency Heat)
• Recovery rates- Heat (1-20°F/hour)
- Cool (1-20°F/hour)
• Additional Menus- Go to Self Test
- Go to Regional Menu
- Go to both Regional and Advanced Menus
2210511
Main Setting Menu Items
Universal Application• Up to 2 Heat/2 Cool
(plus Aux Heat)- Forced Warm Air
Single stage Multistage
- Heat Pumps Single stage Multistage
Commercial
2310511
Main Setting Menu Items
Universal Scheduling• Multiple Programming Options
- 7 Day
- 5-1-1
- 5-2
- 1 Day
- Non-programmable
• Select Schedule Periods- OCC1, UNOCC1,
OCC2, UNOCC2
- OCC1, UNOCC2
Commercial
2410511
Main Setting Menu Items
Backlighting• On-Demand
- Whenever a key is pressed, the light will stay on for approximately 8 seconds
• Continuously- Must be hardwired with a
common and installer setup set to continuous
Commercial
2510511
Regional Settings Menu Item
• Auto or Manual Changeover• Deadband• Fahrenheit or Celsius• Daylight Savings• Remote Temperature Sensor
- Outdoor or Indoor Remote
• Compressor Lockout (Heat Pump Only)• Auxiliary Lockout (Heat Pump Only)
2610511
Regional Settings Menu Item
Changeover• Auto Changeover
- Default position
• Manual Changeover- Set in Regional Installer Setup menu
Commercial
2710511
Regional Settings Menu Item
Outdoor Temperature Sensor• C7089U
- 2-wire remote sensor
- Hook up to the S1 and S2 terminals at the thermostat
- 200 feet maximum
• View outside temperature on home screen or by pressing the More key
• Used for Heat Pump System Temperature Lockouts
2810511
Regional Settings Menu Item
Remote Indoor Temperature Sensor• T7770A (20K NTC) or C7189U (10K NTC)
- 2-wire remote sensor
- Selectable via ISU 340
• Sensors can be used as follows:- One sensor
- Multiple sensors
2910511
Installation
Series-Parallel Temperature Averaging Networks
S1 S2
Thermostat
T7770A T7770A
T7770A T7770A
S1 S2
Thermostat
T7770A T7770A T7770A
T7770A T7770A T7770A
T7770A T7770A T7770A
3010511
Advanced Settings Menu Items
• Number of Periods• Compressor Off Time• Temperature Range Stops
- Heat and Cool
• 12 or 24 hour clock• Extended Fan Operation
- Heat and Cool
• Keypad Lockout- Partial 1, Partial 2, or full
• Temperature Control(s)- Heat and cool recovery
• Display Offset• Reset Defaults
- Installer setup and schedule
3110511
Advanced Settings Recovery Ramps
• Recovery Ramps- Recovery scheme ramps the setpoint towards the desired
setpoint
- Ramped setpoint helps eliminate overshoot with oversized commercial equipment
Commercial VisionPRO 8000
Recovery Operation
3310511
7070ooFF
6060ooFF
Set Point Temperature
Actual Temperature
Heating
UNOCC OCC
Conventional Recovery
3410511
7070ooFF
6060ooFF
Set Point Temperature
Actual Temperature
UNOCC OCC
Heating
Commercial Recovery Ramps
Setpoint actually ramps up at a user-defined rate during recovery
3510511
Conventional Recovery
Cooling
8585ooFF
7878ooFF
Set Point Temperature
UNOCC OCC
Actual Temperature
3610511
Cooling
8585ooFF
7878ooFF
Set Point Temperature
UNOCC OCC
Actual Temperature
Commercial Recovery Ramps
3710511
Recovery
• “Recovery” is shown to alert occupant that the system is in recovery mode- Note: The setpoint
displayed during recovery is the final setpoint, not the ramping setpoint
Advanced Settings Menu Items
Commercial
3810511
Installation
Extended Fan Operation• Heat
- Fan runs 90 seconds after call for heat ends
- Available if thermostat has control of fan
• Cool- Fan runs 40 seconds after
call for cool ends
Advanced Settings Menu Items
Commercial
3910511
Installation
• Test HVAC equipment- Cool stages
- Fan
- Heat stages
• Overrides compressor delay
Installer System Test
Commercial
Part of Installer Setup.
4010511
Installer System Tests
Installation
Test 1- Turn cool stage(s) on and off
Test 2- Turn fan on and off
Test 3- Turn heat stage(s) on and off
Test 4- Turn emergency heat on and
off (heat pump only)
Test 8- Turn TOD/Econ on and off
Arrows TurnSystem On
or Off
Arrows MoveTo Next Test
PressDone
to Exit
Commercial
Commercial VisionPRO 8000
Scheduling Procedures
4210511
Scheduling Feature Review
• Default Schedule is Energy Star• Menu Driven Program Scheduling• Each day can be scheduled differently• Ability to Select Multiple Days• Armchair Programming
4310511
Scheduling
Set the Schedule• Press the Schedule Key
Commercial
4410511
View Schedule
View Schedule• The current schedule period
will flash to indicate whichperiod is being viewed
• Press the Day and Periodyou wish to view
• Press Cancel or Doneto return to Home Screen
Commercial
4510511
Edit Schedule
Edit the Schedule• Press the EDIT key• View mode
Commercial
4610511
Schedule Day Selection
Pick Days to Schedule• Press any number of
the seven days ofthe week to edit
Commercial
4710511
Schedule Day Display
OK to Pick Multiple Days• Check marks appear
on the days chosen
Commercial
4810511
Schedule OCC1 Selection
Press OCC1 Key• OCC1 will begin to
flash, indicating itis chosen
Commercial
4910511
Scheduling
Set OCC1 Time• Use arrows to set the
OCC1 time
Commercial
5010511
Set Temperature
• Use arrows to set the heat temperature
• Use arrows to set the cool temperature
Commercial
5110511
Scheduling
Press UNOCC1 Key• UNOCC1 will begin to
flash indicating it is chosen- Set Time
- Set Temperatures
• Press OCC2 andUNOCC2 and Repeat
Commercial
5210511
Scheduling
Press Done Key• When finished setting
the times and temperaturesfor the Days Selected,press Done
Commercial
5310511
Saving Schedule Changes
Saving Changes• The Days scheduled
are shown• Display shows
Confirmation thatthe schedulechanges were made
Commercial
5410511
Cancel Schedule Period
To Cancel a Scheduled Period• From the edit screen, choose the period to cancel• Press the key
CANCEL PERIOD
Commercial
Example: Cancel UNOCC1
5510511
Cancel Schedule Period
Once the Scheduled Period is Canceled• Time & Temperatures disappear• The bar above the UNOCC1 period is removed
Commercial
Reinstate schedule period by pressing arrow keys to set time and temperature.
5610511
Scheduling
Fan Schedule• Press Fan key while in the Edit mode
- Auto (default—fan runs with system
- On—fan runs continuously during the schedule period
Commercial
5710511
Override Fan Schedule
Fan Schedule• Override Fan Schedule
- Press the fan key to the desired setting
- Like a mechanical fan switch. The fan will stay in ON until user manually changes fan setting back to Auto
Commercial
5810511
Following Schedule Display
Following Schedule• Home Screen
gives confirmation that schedule is being used
Commercial
5910511
Schedule Overrides
Schedule Overrides1. Holiday
- Holds temperature for a designated number of days
2. Override- Holds temperature
until the time the user sets (can be limited via ISU 535)
Commercial
6010511
Scheduling
Override• Holds temperature
temporarily until the next scheduled period time- Press Override key or Up
and Down Arrows next to temperature
- Next schedule period time is shown—this is when the temporary hold will end
- Adjust end time by pressing Up or Down Arrows next to the time
Commercial
6110511
Scheduling
Holiday• Hold temperature for a
designated number of days- Press Up and Down
Arrows to set the temperature desired while away
- Press Arrows to set the number of Days
Commercial
Press Cancel or Sched key to cancel Holiday early
Commercial VisionPRO 8000
Operation
6310511
Operation
Feature Review• Precise Temperature Control• System Status• View Outside Temperature• Clean Screen• Low Battery• Screen Locked• Temperature Range Stops• Compressor Protection
6410511
Operation
• The human body can sense a 2º F temperature change
• To keep occupants comfortable, the thermostat must keep the temperature within +/- 1º F of the set-point
SetPoint
72O F
71O F
70O F
69O F
68O F
Comfortable Temperature Control
6510511
Operation
Thermostat qualities that lead to comfortable temperature control• Top quality components• Innovative design• Superior control algorithms (Digital Thermostats)
- Controlling to an ideal Cycle Rate using Proportional + Integral Control
6610511
Operation
• Proportional + Integral Control- Proportional Error (P): The difference between the set-point
temperature and the room temperature
- Integral Error (I): The length of time the room temperature has differed from the set-point temperature
6710511
SetpointTemperature
RoomTemperature
A
A = Proportional Error
70°
68°
Proportional Error: The difference between the room temperature and the setpoint temperature
Operation
6810511
B + C + D = Integral Error
B C D
SetpointTemperature
RoomTemperature
70°
68°
70°
Integral Error: The length of time the room temperature has differed from the setpoint temperature
Operation
6910511
B + C + D = Integral Error
B C D
SetpointTemperature
RoomTemperature
70°
68°
SetpointTemperature
RoomTemperature
A70°
P+I Control: The P+I error is the sum of the two errors. The cycle rate used to maintain the set-point temperature is calculated using the P+I Error
Operation
7010511
Operation
System Status Indication• Cool On
- Thermostat calling for Cool
• Heat On- Thermostat calling for Heat
- Aux shown when auxiliary heat is called in Heat Pump Systems
Aux
7110511
Operation
View Outside Temperature• Outside Temperature is
shown in lower right hand corner of Home screen
Commercial
7210511
Operation
View Outside Temperature• Press More key
- If thermostat is set to auto changeover, press the More key to view the outside temperature
• Press Done or Cancel to return to Home screen
Commercial
7310511
Operation
Clean Screen• Press Screen key
- Activates a 30-second timer
- Locks out the Touch screen function
Commercial
7410511
Operation
Clean Screen• OK To Clean Screen
- During 30-second countdown, the screen can be cleaned
• Use damp cloth slightly moistened with water or household glass cleaner
Commercial
Never spray liquid directly on the thermostat
7510511
Operation
Clean Screen• Press Screen to restart
the 30-second timer• Press Done to return to
the Home screen
Commercial
7610511
Operation
Low Battery Indication• Flashes on Home screen
for approximately 30 days• Batteries are optional if a
24Vac common is used
Recommended: Replace batteries once a year.
7710511
Operation
Keypad Lockouts• Partial Lockout 1
- Only Override, Holiday and Temperature Up and Down Arrows are available
• Partial Lockout 2- Only Override and
Holiday buttons are available
• Fully Locked- All keys are locked and
non-functional
Screen Locked
Commercial
7810511
Operation
Temperature Range Stops• Heat Setting
- Set the highest Heat temperature the user can set
• Cool Setting- Set the lowest Cool
temperature the user can set
Commercial
7910511
Operation
Compressor Protection• “Wait” shows in the
screen for compressor delay
8010511
Operation
Heat Pump Operation• System Indication• LED• Compressor Lockout• Auxiliary Heat Lockout
8110511
Operation
System LED• LED Indication
- Requires 24 Vac Common connection
- Operates off the “L” terminal
- Only visible through the thermostat cover when lit
Commercial
8210511
Operation
System LED• L Terminal Input
- L terminal is wired to an equipment monitor
- LED lights to signal a check or fail signal from the system
- May occur in any system mode
8310511
Operation
Compressor Lockout• Electric Auxiliary heat
- Must set outdoor temperature sensor for control
- Choose compressor lockout temperature in installer setup number 0350 No lockout 15, 20, 25, 30, 35, 40 or 450
FO
UT
DO
OR
TE
MP
ER
AT
UR
E
35 CompressorLockoutTemperature
COMPRESSOR ONLY•Fan does energize
AUXILIARY HEAT ONLY•Fan does energize
8410511
Operation
OU
TD
OO
R T
EM
PE
RA
TU
RE
50 Auxiliary HeatLockoutTemperature
COMPRESSOR ONLY•Fan does energize
AUXILIARY HEAT ONLY•Fan does energize
Auxiliary Heat Lockout• Electric Auxiliary heat
- Must set outdoor temperature sensor for control
- Choose auxiliary lockout temperature in installer setup number 0360 No lockout 40, 45, 50, 55 or 60 0F
8510511
Operation
Compressor and Auxiliary Heat Lockouts
• Electric Auxiliary heat- Must set outdoor
temperature sensor for control
- Choose compressor lockout temperature
- Choose auxiliary lockout temperature
5º F deadband between Compressor and Auxiliary Heat Lockout Temperatures
8610511
Operation
Dual Fuel Heat Pumps• Thermostat controls
backup fossil fuel heat- Outdoor temperature
sensor for control
- Choose Balance Point lockout temperature in installer setup number 0350 No lockout 15, 20, 25, 30, 35, 40 or 45
0FO
UT
DO
OR
TE
MP
ER
AT
UR
E
30 BalancePoint
COMPRESSOR ONLY•Fan does energize
FOSSIL FUEL ONLY•Fan does not energize
Emergency Head mode: Balance Point Temperature ignored
8710511
AUXILIARY HEAT RECOVERY RAMP
COMPRESSORRECOVERY
RAMP
Wake
Room Temperature
Recovery
Heat Pump Systems
8810511
Mild Weather: 50oF
Wake
Compressor SetpointAux. Heat SetpointRoom Temperature
Compressor:ON
OFF
Auxiliary Heat:ON
OFF
Recovery
Heat Pump Systems
8910511
Moderate Weather: 30oF
Wake
Compressor SetpointAux. Heat SetpointRoom Temperature
Compressor:ON
OFF
Auxiliary Heat:ON
OFF
Recovery
Heat Pump Systems
9010511
Severe Weather: 0oF
Wake
Compressor SetpointAux. Heat SetpointRoom Temperature
Compressor:ON
OFF
Auxiliary Heat:ON
OFF
Recovery
Heat Pump Systems
www.honeywell.com