combustible gas controller

Upload: ace-winnie

Post on 14-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Combustible Gas Controller

    1/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-2100 Combustible Gas Ccontroller (BUS-Type)

    CA-2100

    11. Should use with our fixed probe (CA-217A-B)

    12. RS485 Industrial field BUS with lightning protection

    13. Printer output can print out alarm / fault information of system

    14. CA-2100 PLUS is the enhanced model of CA-2100

    SpecificationsWorking Method: Automatic Patrol

    Output Voltage: DC24V5A (Supply Power to The Probe #CA-217A-B)

    Communication Interface: RS485

    Working Voltage: AC220V/50Hz

    Transmission Distance:

  • 7/29/2019 Combustible Gas Controller

    2/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-217A-B Fixed Combustible Gas Detector/ Probe

    CA-217A-B

    Specifications

    Detection Principle: Catalytic Combustion

    Detection Method: Diffused

    Applicable Gas: Combustible Gases

    Working Method: Continuous WorkingDetection Scope: 0~100%LEL

    Respond Time:

  • 7/29/2019 Combustible Gas Controller

    3/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-2100D

    Specifications

    Working Method: Automatic PatrolOutput Voltage: DC24V@1A (Supply Power to The Probe #CA-217A-B)

    Communication Interface: RS485

    Working Voltage: AC220V/50HzTransmission Distance:

  • 7/29/2019 Combustible Gas Controller

    4/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-2100E

    Specifications

    Working Method: Automatic PatrolOutput Voltage: DC24V@3A (Supply Power to The Probe #CA-217A-B)

    Communication Interface: RS485Working Voltage: AC220V/50HzTransmission Distance:

  • 7/29/2019 Combustible Gas Controller

    5/16

    Features:1. Advanced MPU technology2. Max. capacity of system: 2 channels3. Work in patrol type4.Standard transmission signal of 4-20mA:

    PositiveTerminal,NegativeTerminal, Signal Line IO5. Three digitals display gas concentration ; four digitals

    display time.6. Alarm Function: 2 level output; Low Limit Alarm:

    10%-25%LEL (adjustable) ;High Limit Alarm: 26%-99%LEL (adjustable)

    7. Real-time clock, works continuously even out of power8. Zero adjustable function9. Should use with our fixed probe (CA-217A-D)

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-2100A

    Specifications

    Working Method: Automatic Patrol

    Output Voltage: DC24V@500mA (Supply Power to The Probe #CA-217A-B)Communication Interface: 4-20mA Standard Signal

    Working Voltage: AC220V/50HzTransmission Distance:

  • 7/29/2019 Combustible Gas Controller

    6/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-217A-D

    Specifications

    Detection Principle: Catalytic Combustion

    Detection Method: Diffused

    Applicable Gas: Combustible Gases

    Working Method: Continuous Working

    Detection Scope: 0~100%LEL

    Respond Time:

  • 7/29/2019 Combustible Gas Controller

    7/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-2100C

    6. Two levels alarming: The first level: 15%LEL (adjustable 10%-25%); the second level:

    50 %LEL ( adjustable 26%-99%

    7. Each level alarming output relay switch signal dependently

    8. Every alarming output DC24V pulse signal

    9. Able to return to zero,

    10. Should use with our fixed probe (CA-217A-D)

    Specifications

    Working Method: Automatic Patrol

    Output Voltage: DC12V@500mA (Supply Power to The Probe #CA-217A-B)Communication Interface: 4-20mA Standard Signal

    Working Voltage: AC220V/50HzTransmission Distance:

  • 7/29/2019 Combustible Gas Controller

    8/16

    Zhuhai Chuangan Electronic Co., Ltd.

    Specifications

    Detection Scope: 0%~100%LEL

    Protection Level:: IP54

    Display Mold: Digital

    Work Environment Tem:-20 ~+60 Hum

  • 7/29/2019 Combustible Gas Controller

    9/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-217A-K(DGW)

    Specifications

    Detection Principle: Catalytic Combustion

    Detection Method: Diffused

    Applicable Gas: Combustible Gases

    Working Method: Continuous Working

    Detection Scope: 0~100%LEL

    Respond Time:

  • 7/29/2019 Combustible Gas Controller

    10/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-386D-D2J

    Specifications

    Alarm Concentration: Hydrogen:125~750*10-6

    Natural Gas:1-25%LEL

    Liquefied Petroleum Gas:1~25%LEL

    Power Supply: AC220V/50Hz

    Power Monitoring: 5 W

    Operation Condition: Temperature:-100C~+500C

    Relative Humidity: 30%~95 %( Non-condensing)

    Respond Time: 20 S

    Recovery Time: 20 S

    Time of Shutoff the Valve :< =15S

    Torque: 30kg.cm

    Dimension: The Detector: 145X80X50 mm

    The Valve: 110X110X85 mm

    CA-386D-B Networking Wall Mounted Combustible Gas DetectorFeatures:1. Detection Gas: manufactured gas (hydrogen), natural

    gas, liquefied petroleum gas (LPG)2. Excellent sensor, stable and long-life, excellent oil

    smoke resistant performance

    3. Alarm Output: visual light and audio alarm, solenoidvalve signal, net-work signal output4. Material of Shell: ABS, electrostatic resistance surface

  • 7/29/2019 Combustible Gas Controller

    11/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-386D-B

    CA-386D-C Networking Ceiling Combustible Gas Detector

    CA-386D-C

    Specifications

    Model: CA-386D-B CA-386D-C

    AlarmConcentration:

    Hydrogen:125~750*10-6Natural Gas:1-25%LEL

    Liquefied Petroleum Gas:1~25%LEL

    Power Supply: DC12V-DC24V DC12V-DC24V

    PowerMonitoring:

    1 W 1 W

    OperationCondition: Temperature:-10

    0

    C~+50

    0

    CRelative Humidity: 30%~95 %

    Respond Time: 20 S

    Recovery Time: 20 S

    Detector Size 90*56*18mm 100*50mm

    Features:1.Detection Gas: manufactured gas (hydrogen), natural

    gas

    2.Excellent sensor, stable and long-life, excellent oil smokeresistant performance

    3. Alarm Output: visual light and audio alarm, solenoidvalve signal, net-work signal output

    4. Material of Shell: ABS, electrostatic resistance surface

  • 7/29/2019 Combustible Gas Controller

    12/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-386D-D2/CA-386D Independent Combustible Gas Detector

    Specifications

    Model: CA-386D

    Alarm Concentration: Hydrogen:125~750*10-6Natural Gas:1-25%LEL

    Liquefied Petroleum Gas:1~25%LEL

    Power Supply: AC220V/50Hz

    Power Monitoring: 4 W

    Operation Condition: Temperature:-100C~+500C

    Relative Humidity: 30%~95 %( Non-condensing)

    Respond Time: 20 S

    Recovery Time: 20 S

    Detector Size 130X80X50 (mm)

    Features:1. Detection Gas: manufactured gas (hydrogen),

    natural gas, liquefied petroleum gas (LPG)2. Excellent sensor, stable and long-life, excellent oil

    smoke resistant performance3. Alarm Output: visual light and audio alarm, solenoid

    valve signal, net-work signal output4. Material of Shell: ABS, electrostatic resistance

    surface

  • 7/29/2019 Combustible Gas Controller

    13/16

    Zhuhai Chuangan Electronic Co., Ltd.

    CA-389A Independent Gas Detector with LED Display

    Specifications

    Model: CA-389A

    Alarm Concentration: Hydrogen:125~750*10-6Natural Gas:1-25%LEL

    Liquefied Petroleum Gas:1~25%LEL

    Power Supply: AC220V/50Hz(Adjustable)

    Power Monitoring: 4 W

    Operation Condition: Temperature:-100C~+500C

    Relative Humidity: 30%~95 %( Non-condensing)Display Range 1%LEL---100%LEL

    Features:1. Detection Gas: manufactured gas (hydrogen),

    natural gas, liquefied petroleum gas (LPG)2. Excellent Imported sensor, stable and long-life, excellentoil smoke resistant performance3. Alarm Output: Led Display visual light and audio alarm,

    solenoid valve signal, net-work signal output4. Material of Shell: ABS, electrostatic resistance

    surface

  • 7/29/2019 Combustible Gas Controller

    14/16

    Zhuhai Chuangan Electronic Co., Ltd.

    Respond Time: 20 S

    Recovery Time: 20 S

    Detector Size 130X80X50 (mm)

    CA-CH1000 Carbon Monoxide Detector

    Specification1.Detection Principle: Electrochemical cell

    2.Display: Superbright LED Display

    3.Power light: Green LED flashes once every 30 seconds

    3.Low-battery warning

    4. Alarm Density:

    Under65ppm, Alarms Not Activate

    70ppm-150ppm, Alarms Within 60~189 minutes

    150-400ppm, Alarms Within 10~50 minutes

    400ppm-700ppm,Alarms Within 4~15 minutes700ppm-800ppm,Alarms Within 2~6 minutes

    Features:1.Use imported, reliable,sensitive and long performance

    life electrochemical sensor.2.Superbright LED Display3.Four level sub-alarm.4.Audible and Visual alarm5.Portability,Safety,Reliable

    6.Easy installation and maintenancel(Wall mounted)7.Low-battery warning

  • 7/29/2019 Combustible Gas Controller

    15/16

    Zhuhai Chuangan Electronic Co., Ltd.

    800ppm,Alarms Immediately

    5.Operating Voltage: 9V Battery

    6.Buzzer output: >85 DB at 3m

    7.Operation Condition:

    Temperature:-10 ~+50

    Relative Humidity: 30%~95 %8.Response Ttime: 30s

    9.Standby Current:

  • 7/29/2019 Combustible Gas Controller

    16/16

    Zhuhai Chuangan Electronic Co., Ltd.

    Temperature

    Max

    Working Pressure

    50 kPa Explosion-Proof

    Mark:

    Exm II T6

    Connection G 1/2 1/2G

    Pipe Thread Connection

    in line with ISO7 / 1Standard

    Way of Switch on Manual

    Address: No.1-4,2 2nd Floor No. 93 ZiJin Road, Xiangzhou District, Zhuhai, Guangdong Province,

    China

    Tel: 0756-2172385 0756-2172385 Fax :0756-2172386

    Web Site: http://caatm.en.alibaba.com http://www.caatm.com.cn

    E-mail: [email protected] [email protected]

    mailto:[email protected]:[email protected]