Application The 5050-2 is a combination fire & smoke damper with a 1 1/2 Hour UL 555 fire rating and a Class II UL555S Leakage rating. This damper utilizes a thermally responsive electric switch to allow for the return spring of the specified actuator to close the damper upon elevated temperature. The damper may be installed vertically or horizontally for use in barriers requiring both fire and leakage protection. This damper has been evaluated with bi-directional airflow, and is rated to 2000 FPM and 4" static pressure in compliance with UL555 6th edition and UL555S 4th edition. UL Listings File #R6189 UL555 1 1/2 Hour Fire standard UL555S Class II @ 250°F or 350°F <20 cfm / sq. ft. @ 4" w.g. Model 5050-2 meets or complies with the following as a smoke, fire or combination fire & smoke damper: CA State Fire Marshall Fire listing #3225-1518:100 Leakage listing #3230-1518:106 NFPA 90A & B, 92A & B All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code Options & Accessories Dual Blade Position Indicator Switches (Switch#1) Factory Supplied Sleeves – 18 or 14 Gauge, 18" or 24" deep (units with external mount actuators provided with 18 gauge side plate if no sleeve specified) Factory supplied ‘EZ Mount’ mounting angles Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems Standard Sizes See actuator section for internal mount minimums. Standard Construction Frame 4" Wrap around full channel frame – 16 GA Galvanized Steel Blades 22 GA Galvanized Steel , Modified Triple-V Design Bearings Integral Curl in Frame Design Linkage 14 GA Galvanized, on Blade Type (in airstream) Seals Compression type silicone seals Heat Responsive Device Electric-Thermal Disc, 165°F standard, 212°, 250° or 350°F optional Sealant UL Certified silicone caulk (sleeved units only) Fire Rating Leakage Rating Min. Vertical or Horizontal Max. Vertical Max Horizontal 1 1/2 Hour Fire Class II @ 250°F 6" x 6" 120" x 84" 144" x 90" ¹ 1 1/2 Hour Fire Class II @ 350°F 6" x 6" 120" x 84" 144" x 90" ¹ *Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified. Project: Location: Architect: Engineer: Contractor: PO Number: Date: Right hand external mount actuator standard Left hand external mount actuator shown. Internal mount actuator optional (see page 2). Combination Fire & Smoke Damper 1 1/2 Hour Fire / Class II Leakage For Use in Static or Dynamic Systems Model 5050-2 Submittal Filename: Prefco Submittal 5050-2 Rev. 27/12/14 A dim. is always width of blades Page 1 of 2 ¹ In Horizonal Applications, dampers exceeding 52”x42” must be mounted with the actuators above the rated floor

Upload: tranxuyen

Post on 30-Jan-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Combination Fire & Smoke Damper 1 1/2 Hour Fire / Class II ... Submittal PDFs 3-24-04/Prefco Submittal... · The 5050-2 is a combination fire & smoke damper with a 1 1/2 Hour UL 555

Application

The 5050-2 is a combination fire & smoke damper with a 1 1/2 Hour UL 555 firerating and a Class II UL555S Leakage rating. This damper utilizes a thermallyresponsive electric switch to allow for the return spring of the specified actuatorto close the damper upon elevated temperature. The damper may be installedvertically or horizontally for use in barriers requiring both fire and leakageprotection. This damper has been evaluated with bi-directional airflow, and israted to 2000 FPM and 4" static pressure in compliance with UL555 6th editionand UL555S 4th edition.

UL Listings – File #R6189

• UL555 1 1/2 Hour Fire standard• UL555S Class II @ 250°F or 350°F• <20 cfm / sq. ft. @ 4" w.g.

Model 5050-2 meets or complies with the following as a smoke, fire orcombination fire & smoke damper:

• CA State Fire Marshall Fire listing #3225-1518:100Leakage listing #3230-1518:106

• NFPA 90A & B, 92A & B

• All major building codes, including BOCA, ICBO/UBC, SBCCI & theICC International Code

Options & Accessories

❑ Dual Blade Position Indicator Switches (Switch#1)

❑ Factory Supplied Sleeves – 18 or 14 Gauge, 18" or 24" deep (units with external mount actuators provided with 18 gauge side plate if no sleeve specified)

❑ Factory supplied ‘EZ Mount’ mounting angles

❑ Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems

Standard Sizes

See actuator section for internal mount minimums.

Standard Construction

• Frame4" Wrap around full channel frame – 16 GA Galvanized Steel

• Blades22 GA Galvanized Steel , Modified Triple-V Design

• BearingsIntegral Curl in Frame Design

• Linkage14 GA Galvanized, on Blade Type (in airstream)

• SealsCompression type silicone seals

• Heat Responsive DeviceElectric-Thermal Disc, 165°F standard, 212°, 250° or 350°F optional

• SealantUL Certified silicone caulk (sleeved units only)

Fire Rating Leakage RatingMin. Verticalor Horizontal

Max.Vertical

MaxHorizontal

1 1/2 Hour Fire Class II @ 250°F 6" x 6" 120" x 84" 144" x 90" ¹

1 1/2 Hour Fire Class II @ 350°F 6" x 6" 120" x 84" 144" x 90" ¹

*Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.

Project:

Location:

Architect:

Engineer:

Contractor:

PO Number:

Date:

Right hand external mount actuator standardLeft hand external mount actuator shown.

Internal mount actuator optional (see page 2).

Combination Fire & Smoke Damper1 1/2 Hour Fire / Class II LeakageFor Use in Static or Dynamic Systems

Model 5050-2 SubmittalFilename: Prefco Submittal 5050-2 Rev. 27/12/14

A dim. is always width of blades

Page 1 of 2

¹ In Horizonal Applications, dampers exceeding 52”x42” must be mounted with the actuators above the rated floor

Page 2: Combination Fire & Smoke Damper 1 1/2 Hour Fire / Class II ... Submittal PDFs 3-24-04/Prefco Submittal... · The 5050-2 is a combination fire & smoke damper with a 1 1/2 Hour UL 555

Page 2 of 2

Combination Fire & Smoke Damper1 1/2 Hour Fire / Class II LeakageFor Use in Static or Dynamic Systems

Model 5050-2 SubmittalFilename: Prefco Submittal 5050-2 Rev. 27/12/14

Specifications

Actuators will be mounted externally on the right side unless otherwise specified.Actuators available for internal or external mount (all must be factory mounted):

* Damper must be at least 13" in height for actuator to mount internally.* Unit must be 10" or greater in width for any internal actuator mounting orientation.* The factory will mount the actuator parallel to the damper, whenever height allows,

unless otherwise specified.

Actuator Model Voltage (AC)Power Consumption

Running Holding

Belimo FSNF120 120 0.23A, 18W 0.09A, 6W

Belimo FSNF24 24 24VA 24VA

Honeywell ML4115 120 0.18A, 18W 0.11A, 9W

Honeywell ML8115 24 16VA 8VA

Honeywell MS4209F, MS4309F 120 0.25A, 23W 0.13A, 7W

Honeywell MS8209F, MS8309F 24 23VA 7VA

Honeywell MS4120F 120 0.35A, 35W 0.15A, 10W

Honeywell MS8120F 24 45VA 10VA

Mounting Configurations

Actuator Mounted Parallel to the damper

Actuator Mounted perpendicular to the damper

*Available Down ToMin Height

Actuator Mounted Parallel to the dampe

Actuator Mounted perpendicular to the damper

*Available Down ToMin Height

Actuator Mounted Parallel to the damper

Actuator Mounted perpendicular to the damper

*Available Down ToMin Height

Typical Pressure Drop Per Duct Velocity

Pressure drop information is from a 24" x 24" damper. Pressure drop through a smaller damper will be higher.

Duct Velocity (FPM) 500 600 700 800 900 1000 1250 1500 1750 2000 3000 4000

Full Open .010 .013 .015 .021 .030 .035 .040 .067 .080 .100 .250 .480

Pressure Drop / Inches of Water

*Damper height must be at least 18"for actuator to mount internally.

*Damper height must be at least 18"for actuator to mount internally.

*Damper height must be at least 13"for actuator to mount internally.