Minera Roof Trusses Limited Five Crosses Industrial Estate, Minera, Wrexham LL11 3RD Email: [email protected]Telephone: (01978) 758869 www.minera-rooftrusses.com Cold Water Storage Tank Platform Detail DETAIL ‘A’ DETAIL ‘B’ Water storage tank support detail in accordance with BS 5268 Part III for maximum span of truss 9.000m. Maximum tank size 300 litres supported on 4 trussed rafters (as Detailed A) OR 230 litres supported on 3 trussed rafters (as Detail B). MAXIMUM SPAN 9,000m. ALTERNATIVE SUPPORT BETWEEN MEMBERS Where space is limited this detail may be used between members A & B and B & C in order to gain head room. However, a minimum clearance of 25mm above the ceiling lining should be allowed, for possible deflection. Drawing Number: MRT-SD-10 Designer: BS5268 Last Revised: July 2016 Connect with us: Company Registration Number: 1325682 Tank placed central Span of truss S = Truss Spacing Galvanised steel joist hanger B 1/3 point 1/3 point C Bearer ‘A’ placed as close to 1/3 point as possible 1/3 point Wallplate Wallplate Tank Tank C C C C B B B A S S S S S S S S S A S S B A 1/2 1/2 1/2 1/2 1/3 2/3 2/3 1/3

Upload: others

Post on 07-Apr-2020

55 views

Category:

Documents


0 download

TRANSCRIPT

Minera Roof Trusses LimitedFive Crosses Industrial Estate, Minera, Wrexham LL11 3RD

Email: [email protected] • Telephone: (01978) 758869

www.minera-rooftrusses.com

Cold Water Storage Tank Platform Detail

DETAIL ‘A’

DETAIL ‘B’

Water storage tank support detail in accordance with BS 5268 Part III for maximum span of truss 9.000m. Maximum tank size 300 litres supported on 4 trussed rafters (as Detailed A) OR 230 litres supported on 3 trussed rafters (as Detail B).

MAXIMUM SPAN 9,000m.

ALTERNATIVE SUPPORT BETWEEN MEMBERSWhere space is limited this detail may be used between members A & B and B & C in order to gain head room. However, a minimum clearance of 25mm above the ceiling lining should be allowed, for possible deflection.

Drawing Number: MRT-SD-10Designer: BS5268Last Revised: July 2016

Connect with us:

Company Registration Number: 1325682

Tankplacedcentral

Span of truss

S = Truss Spacing

Galvanised steeljoist hanger

B

1⁄3 point

1⁄3 pointC Bearer ‘A’ placed as

close to 1⁄3 point as possible

1⁄3 point

Wallplate Wallplate

Tank

TankCC

C

C

BB

BA

SS

S

S

S

S

S

S

S

A

S

S

B

A

1⁄2

1⁄2

1⁄2

1⁄2

1⁄3

2⁄3

2⁄3

1⁄3