clyde street bid set

21
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015 C PWWG PROJECT NUMBER REVISIONS 1 1 / 1 6 / 2 0 1 5 7 : 1 3 : 1 5 P M 618 CLYDE STREET, PITTSBURGH PA 21521.00 11/16/2015 CLYDE APARTMENTS CARNEGIE MELLON UNIVERSITY COVER SHEET G-001 BID SET DRAWING LIST GENERAL G-001 COVER SHEET 11/16/2015 G-002 SYMBOLS & NOTES & CODE PLANS 11/16/2015 CIVIL T1.1 TITLE SHEET 11/16/2015 GN1.1 GENERAL NOTES 11/16/2015 391-1 ALTA/ACSM TITLE SURVEY 11/16/2015 EX1.1 EXISTING CONDITIONS PLAN 11/16/2015 C2.1 SITE PLAN 11/16/2015 C2.2 SITE DETAILS 11/16/2015 ARCHITECTURAL AS-101 ARCHITECTURAL SITE PLAN AND EXTERIOR IMPROVEMENTS 11/16/2015 AD-101 DEMOLITION PLANS 11/16/2015 A-100 BASEMENT PLAN 11/16/2015 A-101 FIRST FLOOR PLAN 11/16/2015 A-102 SECOND FLOOR PLAN (3RD SIMILAR) 11/16/2015 AC-100 BASEMENT REFLECTED CEILING PLAN 11/16/2015 AC-101 FIRST FLOOR REFLECTED CEILING PLAN 11/16/2015 AC-102 SECOND FLOOR REFLECTED CEILING PLAN 11/16/2015 A-201 BUILDING ELEVATIONS 11/16/2015 A-202 BUILDING ELEVATIONS 11/16/2015 A-401 INTERIOR ELEVATIONS & DETAILS 11/16/2015 A-501 DETAILS 11/16/2015 A-601 SCHEDULE AND TYPES 11/16/2015 FIRE PROTECTION FP-001 SYMBOLS, NOTES AND ABBREVIATIONS 11/16/2015 FP-100 BASEMENT PLAN 11/16/2015 FP-101 FIRST FLOOR PLAN 11/16/2015 FP-102 SECOND FLOOR PLAN 11/16/2015 FP-103 THIRD FLOOR PLAN 11/16/2015 FP-104 ATTIC PLAN 11/16/2015 PLUMBING P-001 SYMBOLS, NOTES, ABBREVIATIONS AND SCHEDULES 11/16/2015 PD-101 DEMOLITION PLANS 11/16/2015 P-100 BASEMENT PLAN 11/16/2015 P-101 FIRST FLOOR PLAN 11/16/2015 P-102 SECOND FLOOR PLAN (3RD SIMILAR) 11/16/2015 MECHANCIAL H-001 SYMBOLS, ABBREVIATIONS, LEGEND AND NOTES 11/16/2015 H-002 DIAGRAMS 11/16/2015 HD-101 DEMOLITION PLANS 11/16/2015 H-100 BASEMENT PLAN 11/16/2015 H-101 FIRST FLOOR PLAN 11/16/2015 H-102 SECOND FLOOR PLAN 11/16/2015 H-201 HEATING WATER RISER DIAGRAM 11/16/2015 ELECTRICAL E-001 ELECTRICAL SYMBOLS, NOTES AND ABBREVIATIONS 11/16/2015 E-101 ELECTRICAL SITE PLAN 11/16/2015 E-200 BASEMENT PLAN - LIGHTING 11/16/2015 E-201 FIRST FLOOR PLAN - LIGHTING 11/16/2015 E-202 SECOND FLOOR PLAN - LIGHTING 11/16/2015 E-203 THIRD FLOOR PLAN - LIGHTING 11/16/2015 E-300 BASEMENT PLAN - POWER AND SYSTEMS 11/16/2015 E-301 FIRST FLOOR PLAN - POWER AND SYSTEMS 11/16/2015 E-302 SECOND FLOOR PLAN - POWER AND SYSTEMS 11/16/2015 E-303 THIRD FLOOR PLAN - POWER AND SYSTEMS 11/16/2015 E-600 ELECTRICAL RISER DIAGRAM 11/16/2015 E-601 RISER DIAGRAMS 11/16/2015 E-700 PANEL SCHEDULES 11/16/2015 E-701 PANEL SCHEDULES 11/16/2015 E-702 PANEL SCHEDULES 11/16/2015 Grand total: 54 CARNEGIE MELLON UNIVERSITY CLYDE APARTMENTS BID SET - NOVEMBER 16, 2015 ARCHITECT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 408 BOULEVARD OF THE ALLIES PITTSBURGH, PA 15219 412 391 2884 CONTACT: KEVIN WAGSTAFF, AIA CLIENT CARNEGIE MELLON UNIVERSITY 5000 FORBES AVENUE PITTSBURGH PA, 15213 412 268 2000 CONTACT: UTKARSH GHILDYAL STRUCTURAL ENGINEER SCHNEIDER ENGINEERING, LLC 1196 BILLINGS DRIVE PITTSBURGH, PA 15241 412 736 1298 CONTACT: JOHN SCHNEIDER MEPFP ENGINEER CJL ENGINEERING 1555 CORAOPOLIS HEIHGTS ROAD, SUITE 4200 MOON TOWNSHIP, PA 15108 412 262 1220 CONTACT: CHRIS CONROY NO. DESCRIPTION DATE

Upload: zachary-bauer

Post on 28-Jul-2016

242 views

Category:

Documents


1 download

DESCRIPTION

 

TRANSCRIPT

  • COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:1

    5 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    COVER SHEET

    G-001

    BID SET

    DRAWING LIST

    GENERAL

    G-001 COVER SHEET 11/16/2015

    G-002 SYMBOLS & NOTES & CODE PLANS 11/16/2015

    CIVIL

    T1.1 TITLE SHEET 11/16/2015

    GN1.1 GENERAL NOTES 11/16/2015

    391-1 ALTA/ACSM TITLE SURVEY 11/16/2015

    EX1.1 EXISTING CONDITIONS PLAN 11/16/2015

    C2.1 SITE PLAN 11/16/2015

    C2.2 SITE DETAILS 11/16/2015

    ARCHITECTURAL

    AS-101 ARCHITECTURAL SITE PLAN AND EXTERIORIMPROVEMENTS

    11/16/2015

    AD-101 DEMOLITION PLANS 11/16/2015

    A-100 BASEMENT PLAN 11/16/2015

    A-101 FIRST FLOOR PLAN 11/16/2015

    A-102 SECOND FLOOR PLAN (3RD SIMILAR) 11/16/2015

    AC-100 BASEMENT REFLECTED CEILING PLAN 11/16/2015

    AC-101 FIRST FLOOR REFLECTED CEILING PLAN 11/16/2015

    AC-102 SECOND FLOOR REFLECTED CEILING PLAN 11/16/2015

    A-201 BUILDING ELEVATIONS 11/16/2015

    A-202 BUILDING ELEVATIONS 11/16/2015

    A-401 INTERIOR ELEVATIONS & DETAILS 11/16/2015

    A-501 DETAILS 11/16/2015

    A-601 SCHEDULE AND TYPES 11/16/2015

    FIRE PROTECTION

    FP-001 SYMBOLS, NOTES AND ABBREVIATIONS 11/16/2015

    FP-100 BASEMENT PLAN 11/16/2015

    FP-101 FIRST FLOOR PLAN 11/16/2015

    FP-102 SECOND FLOOR PLAN 11/16/2015

    FP-103 THIRD FLOOR PLAN 11/16/2015

    FP-104 ATTIC PLAN 11/16/2015

    PLUMBING

    P-001 SYMBOLS, NOTES, ABBREVIATIONS AND SCHEDULES 11/16/2015

    PD-101 DEMOLITION PLANS 11/16/2015

    P-100 BASEMENT PLAN 11/16/2015

    P-101 FIRST FLOOR PLAN 11/16/2015

    P-102 SECOND FLOOR PLAN (3RD SIMILAR) 11/16/2015

    MECHANCIAL

    H-001 SYMBOLS, ABBREVIATIONS, LEGEND AND NOTES 11/16/2015

    H-002 DIAGRAMS 11/16/2015

    HD-101 DEMOLITION PLANS 11/16/2015

    H-100 BASEMENT PLAN 11/16/2015

    H-101 FIRST FLOOR PLAN 11/16/2015

    H-102 SECOND FLOOR PLAN 11/16/2015

    H-201 HEATING WATER RISER DIAGRAM 11/16/2015

    ELECTRICAL

    E-001 ELECTRICAL SYMBOLS, NOTES AND ABBREVIATIONS 11/16/2015

    E-101 ELECTRICAL SITE PLAN 11/16/2015

    E-200 BASEMENT PLAN - LIGHTING 11/16/2015

    E-201 FIRST FLOOR PLAN - LIGHTING 11/16/2015

    E-202 SECOND FLOOR PLAN - LIGHTING 11/16/2015

    E-203 THIRD FLOOR PLAN - LIGHTING 11/16/2015

    E-300 BASEMENT PLAN - POWER AND SYSTEMS 11/16/2015

    E-301 FIRST FLOOR PLAN - POWER AND SYSTEMS 11/16/2015

    E-302 SECOND FLOOR PLAN - POWER AND SYSTEMS 11/16/2015

    E-303 THIRD FLOOR PLAN - POWER AND SYSTEMS 11/16/2015

    E-600 ELECTRICAL RISER DIAGRAM 11/16/2015

    E-601 RISER DIAGRAMS 11/16/2015

    E-700 PANEL SCHEDULES 11/16/2015

    E-701 PANEL SCHEDULES 11/16/2015

    E-702 PANEL SCHEDULES 11/16/2015

    Grand total: 54

    CARNEGIE MELLON UNIVERSITY

    CLYDE APARTMENTSBID SET - NOVEMBER 16, 2015

    ARCHITECT

    PERFIDO WEISKOPF WAGSTAFF + GOETTEL408 BOULEVARD OF THE ALLIESPITTSBURGH, PA 15219412 391 2884CONTACT: KEVIN WAGSTAFF, AIA

    CLIENT

    CARNEGIE MELLON UNIVERSITY5000 FORBES AVENUEPITTSBURGH PA, 15213412 268 2000CONTACT: UTKARSH GHILDYAL

    STRUCTURAL ENGINEER

    SCHNEIDER ENGINEERING, LLC

    1196 BILLINGS DRIVEPITTSBURGH, PA 15241412 736 1298CONTACT: JOHN SCHNEIDER

    MEPFP ENGINEER

    CJL ENGINEERING

    1555 CORAOPOLIS HEIHGTS ROAD, SUITE 4200MOON TOWNSHIP, PA 15108412 262 1220CONTACT: CHRIS CONROY

    NO. DESCRIPTION DATE

  • RE

    F

    RE

    F

    RE

    F

    RE

    F

    UP

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    FR

    EF

    UP

    RE

    F

    ABBREVIATIONS

    ACCACWADADAADJAFFALUMALTANODANSIAPCAPPROXAPTASFBDBHBLWBODBRBRGBRNZBTC TO CCAB CFSCIPCJ CLCLGCLOCMUCOCOLCONCCONTCORRCPTCSKCTCTRCU FTCU YDCWDBLDEMODEPTDHDIADIAGDIMDLDNEEAEFSEIFSEJEMEPSEQEOSESETREXISTFARFAYFBGFCFDFEFF ELFINFIN GRFLRFNDFRMGFRPFRRFSFTFTGFXGA GALVGCGRGYPGYP BDHCHDWDHPHTHOPIDINCLINSULKITLAULAVLFLINLLLLHLLVLSFMASMATLMAXMBRMDFMECHMEZZ MFRMOMSAMSNNNANICNRCNTSOAOCOPNGOSBPCCPLAMPLASTPOLYPTPTLPVCRRBRCPRDREFREQ'DREQ'SRMRORWCSSAMSCSCTSFSFRMSHSIMSPECSPFSQSSSSTSTOSTCSTLSTRUCTSYPTT/TCT&GTRNSPTRPLTSTYPUFASUNOUSAVARVBVATVIFVCTWw/WDw/OWHWWFXPS

    AccessibleAluminum Clad WoodArea DrainAmericans with Disabilities ActAdjacentAbove Finished FloorAluminumAlternateAnodizeAmerican National Standards InstituteAcoustic Panel CeilingApproximateApartmentAbove Sub-FloorBoardBulkheadBelowBasis of DesignBedroomBearingBronzeBank TowerCenter to CenterCabinetClear Floor SpaceCast-in-PaceControl JointCenter LineCeilingClosetConcrete Masonry UnitClean-outColumnConcreteContinuousCorridorCarpetCountersunkCeramic TileCenterCubic FeetCubic YardCurtainwallDoubleDemolitionDepartmentDouble-Hung (Window)DiameterDiagonalDimensionDead LoadDownEastEachExterior Finish SystemExterior Insulation and Finish SystemExpansion JointEntrance MatExpanded Polystyrene Board (Insulation)EqualEdge of Structure/SlabEach SideExisting to RemainExistingFloor Area RatioFayette BuildingFiberglassFire CoreFloor DrainFire ExtinguisherFinished Floor ElevationFinishFinished GradeFloorFoundation DrainFramingFiber Reinforced PlasticFire Resistance RatingFlat SeamFoot, FeetFootingFixed (Window)GageGalvanizedGeneral ContractorGuest RoomGypsumGypsum BoardHollow CoreHardwoodHigh PointHeightHopper (Window)Inside DiameterInclude(s)(ing)InsulationKitchenLaundryLavatoryLinear FeetLinoleumLive LoadLong Leg HorizontalLong Leg VerticalLight Gauge Steel FramingMasonyMaterialMaximumMaster BedroomMedium Density FiberboardMechanicalMezzanineManufacturerMasonry OpeningMain Street AnnexMasoniteNorthNot ApplicableNot in ContractNoise Reduction CoefficientNot to ScaleOverallOn CenterOpeningOriented Strand BoardPrecast ConcretePlastic LaminatePlasterPolyethylene (Plast Sheet)Paint(ed)Pressure Treated LumberPolyvinyl ChlorideRadius, Riser, Thermal Resistance ValueRubber BaseReflected Ceiling PlanRoof DrainRefrigeratorRequiredRequirementsRoomRough OpeningRainwater ConductorSouthSelf-Adhered MembraneSolid CoreStructural Clay TileSquare FeetSpray-Applied Fire-Resistive MaterialsSingle HungSimilarSpecificationSpruce-Pine-FirSquareSimulated StoneStainless SteelStorageSound Transmission ClassSteelStructureSouthern Yellow PineTreadTop Of ___Traffic CoatingTongue and GrooveTransparentTripleTube SteelTypicalUniform Federal Accessibility StandardsUnless Noted OtherwiseUpper Street AnnexVariesVinyl Wall BaseVinyl Asbestos TileVerify in FieldVinyl Composition TileWestWithWoodWithoutWater HeaterWelded Wire FabricExtruded Polystyrene Board (Insulation)

    CODE SUMMARY

    BUILDING CODE SUMMARY:

    APPLICABLE CODES: INTERNATIONAL EXISTING BUILDING CODE, 2009 (IEBC)(WITH PITTSBURGH INTERNATIONAL BUILDING CODE, 2009 AMENDMENTS) INTERNATIONAL ENERGY CONSERVATION CODE, 2009

    INTERNATIONAL MECHANICAL CODE, 2009INTERNATIONAL FUEL GAS CODE, 2009NATIONAL ELECTRIC CODE, 2005ALLEGHENY COUNTY PLUMBING CODE

    INTERNATIONAL EXISTING BUILDING CODE 2009 SUMMARY

    CHAPTER 1 SCOPE AND ADMINISTRATION

    101.4 GENERAL APPLICABILITY:

    THIS CODE SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,ADDITION AND RELOCATION OF EXISTING BUILDINGS.

    101.5.2 COMPLIANCE METHOD:

    WORK AREA COMPLIANCE METHOD.

    WORK IN COMPLIANCE WITH CHAPTERS 4 THROUGH 12 SHALL BE CONSIDERED INCOMPLIANCE WITH THE PROVISIONS OF THIS CODE.

    CHAPTERS 9-CHANGE OF OCCUPANCY, 10-ADDITIONS, 11-HISTORIC BUILDINGS, AND12-RELOCATED BUILDINGS ARE NOT APPLICABLE TO THIS PROJECT.

    CHAPTER 4 CLASSIFICATION OF WORK

    405.1 ALTERATION LEVEL 3

    WORK AREA EXCEEDS 50% OF THE BUILDING AREA.

    CHAPTER 6 ALTERATIONS LEVEL 1

    603.1 FIRE PROTECTION:

    ALTERATIONS SHALL BE DONE IN A MANNER THAT MAINTAINS THE LEVEL OF FIREPROTECTION PROVIDED.

    EXISTING BUILDING ELEMENTS ARE NOT REQUIRED TO MEET CURRENT IBC FIRERATING REQUIREMENTS. THIS INCLUDES THE EXISTING FLOOR/CEILING ASSEMBLIES,THE EXISTING EXIT STAIRS AND DOORS, EXISTING CORRIDOR WALLS AND DOORS, ANDEXISTING UNIT SEPARATION WALLS.

    605.1 ACCESSIBILITY:

    ACCESSIBLE MEANS OF EGRESS ARE NOT REQUIRED IN EXISTING BUILDINGS.

    TYPE B DWELLING UNITS ARE NOT REQUIRED IN EXISTING BUILDINGS.

    TYPE A DWELLING UNIT REQUIREMENTS APPLY ONLY TO THE QUANTITY OF UNITSBEING ADDED. UNDER IBC, TYPE A UNITS ARE NOT REQUIRED FOR A QUANTITY OF 20UNITS AND UNDER.

    CHAPTER 7 ALTERATIONS LEVEL 2

    GENERAL:

    701.3 COMPLIANCE

    ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND SPACES SHALLCOMPLY WITH THE REQUIREMENTS OF IBC.

    BUILDING ELEMENTS AND MATERIALS:

    703.2.1 EXISTING VERTICAL OPENINGS:

    EXCEPTION 11.2: EXISTING VERTICAL OPENINGS ARE NOT REQUIRED TO HAVE A FIRERATING PROVIDED THE BUILDING IS PROTECTED THROUGHOUT BY AN APPROVEDAUTOMATIC SPRINKLER SYSTEM.

    703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE REQUIREMENTS:

    EGRESS STAIRWAYS SHALL, AT A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHTCONSTRUCTION.

    PROJECT SUMMARY

    EXISTING BUILDING DATA

    1940s BUILDING WITH SUBSEQUENT INTERIOR RENOVATIONSMASONRY BEARING WALLS WITH INTERIOR WOOD FLOOR AND ROOF STRUCTURE

    IEBC ALTERATION LEVEL

    LEVEL 3 ALTERATIONSWORK AREA EXCEEDING 50% OF BUILDING AREA

    OCCUPANCY EXISTING TO REMAINR-2, MULTI-UNIT RESIDENTIAL, APARTMENT HOUSES-1, STORAGE (BASEMENT)

    BUILDING AREA EXISTING TO REMAIN3 STORIES + BASEMENT @ 4,287 SF/FLOOR = 17,148 SF TOTAL

    BUILDING HEIGHT EXISTING TO REMAIN3 STORIES

    GRADE PLANE IS AVG 4.5' BELOW FLOOR 01GRADE PLANE TO TOP OF ROOF: 34.5'

    PARKING SPACES EXISTING TO REMAIN15 SPACES (INCLUDING 1 HC VAN SPACE)

    ZONING SUMMARY EXISTING TO REMAINDISTRICT : RM-H: MULTI-UNIT RESIDENTIAL - HIGH DENSITYPARCEL ID: 52-E-243LOT AREA: 17,669 SF

    CONSTRUCTION TYPE EXISTING TO REMAINTYPE III-B; UN-PROTECTED COMBUSTIBLE

    OCCUPANT LOADS EXISTING TO REMAINRESIDENTIAL: 200 GROSSSTORAGE: 300 GROSS

    BASEMENT: 3,858 SF / 300 = 13FIRST FL: 4,287 / 200 = 22SECOND FL: 4,287 / 200 = 22THIRD FL: 4,287 / 200 = 22

    TOTAL 79 OCCUPANTS (EXISTING TO REMAIN)

    IECC CLIMATE ZONE

    ALLEGHENY COUNTY, PA: CLIMATE ZONE 4-5 MARINE

    703.4 INTERIOR FINISH:

    NEW INTERIOR FINISHES SHALL COMPLY WITH IBC.

    FIRE PROTECTION:

    704.2.2 AUTOMATIC SPRINKLER PROTECTION:

    REQUIRED FOR R-2 OCCUPANCY WHEN WORK AREA EXCEEDS 50% OF THE FLOORAREA.

    704.4.1.6 FIRE ALARM SYSTEM:

    A FIRE ALARM SYSTEM IS REQUIRED AS REQUIRED BY THE INTERNATIONAL FIRECODE FOR EXISTING R-2 OCCUPANCIES.

    705 MEANS OF EGRESS:

    704.4.3 SMOKE ALARMS:

    INDIVIDUAL DWELLING UNITS REQUIRE SMOKE ALARMS IN ACCORDANCE WITH THEINTERNATIONAL FIRE CODE.

    705.3.1 MINIMUM NUMBER OF EXITS:

    THE MINIMUM NUMBER OF EXITS BASED ON THE OCCUPANCY AND THE OCCUPANTLOAD IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE.

    705.4.2 DOOR SWINGS:

    EGRESS DOORS SERVING AN OCCUPANT LOAD GREATER THAN 50 SHALL SWING INTHE DIRECTION OF TRAVEL.

    705.5.1 CORRIDOR DOORS:

    EXCEPTION 3: NEW CORRIDOR DOORS SHALL HAVE A 20 MINUTE FIRE RATING.

    705.9 HANDRAILS:

    A HANDRAIL IS REQUIRED ON AT LEAST ONE SIDE OF STAIRS. EXISTING HANDRAILSDO NOT HAVE TO MEET IBC PROVIDED THEY ARE NOT IN "DANGER OF COLLAPSING."NEW HANDRAILS SHALL COMPLY WITH IBC.

    707 STRUCTURAL:

    707.2 NEW STRUCTURAL MEMBERS:

    NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING CONNECTIONS ANDANCHORAGE, SHALL COMPLY WITH IBC.

    708 ELECTRICAL:

    708.1 NEW INSTALLATIONS:

    ALL NEWLY INSTALLED EQUIPMENTS AND WIRING RELATED TO WORK BEING DONE INTHE WORK AREA SHALL COMPLY WITH THE MATERIALS AND METHODSREQUIREMENTS OF CHAPTER 5.

    709 MECHANICAL:

    709.1 RECONFIGURED OR CONVERTED SPACES. ALL RECONFIGURED SPACESINTENDED FOR OCCUPANCY AND ALL SPACES CONVERTED TO HABITABLE OROCCUPIABLE SPACE IN ANY WORK AREA SHALL BE PROVIDED WITH NATURAL ORMECHANICAL VENTILATION IN ACCORDANCE WITH THE INTERNATIONAL MECHANICALCODE.

    710 PLUMBING:

    710.1 MINIMUM FIXTURES:

    INCREASED FIXTURE COUNTS ARE NOT REQUIRED WHERE THE OCCUPANT LOAD ISNOT INCREASED BY MORE THAN 20%.

    CHAPTER 8 ALTERATIONS LEVEL 3

    805.2 MEANS OF EGRESS LIGHTING:

    SHALL COMPLY WITH CURRENT IBC.

    805.3 EXIT SIGNS:

    SHALL COMPLY WITH CURRENT IBC.

    808.1 MINIMUM ENERGY REQUIREMENTS:

    LEVEL 3 ALTERATIONS TO EXISTING BUILDINGS OR STRUCTURES ARE PERMITTEDWITHOUT REQUIRING THE ENTIRE BUILDING OR STRUCTURE TO COMPLY WITH THEENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATIONCODE OR INTERNATIONAL RESIDENTIAL CODE. THE ALTERATIONS SHALL CONFORMTO THE ENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATIONCODE ORINTERNATIONAL RESIDENTIAL CODE AS THEY RELATE TO NEWCONSTRUCTION ONLY

    INTERNATIONAL BUILDING CODE 2009 SUMMARY

    CHAPTER 3 USE AND OCCUPANCY

    EXISTING USE: R-2, S-1PROPOSED USE: NO CHANGE

    CHAPTER 5 GENERAL HEIGHT AND AREA LIMITATIONS

    CHAPTER 6 TYPE OF CONSTRUCTION

    EXISTING TYPE: IIIB EXISTING TO REMAIN

    FIRE RESISANCE RATING REQUIREMENTS:PRIMARY STRUCTURAL FRAME: 0 HR (EXISTING TO REMAIN)BEARING EXT WALLS: 2 HR (EXISTING TO REMAIN)BEARING INT WALLS: 0 HR (EXISTING TO REMAIN)NON-BEARING WALLS: 0 HRFLOOR CONSTRUCTION: 0 HR (EXISTING TO REMAIN & LIMITED WORK)ROOF CONSTRUCTION: 0 HR (EXISTING TO REMAIN)

    CHAPTER 7 - FIRE AND SMOKE PROTECTION

    NO PROPOSED FIRE PARTITIONS.

    CHAPTER 10 MEANS OF EGRESS

    1005.1 EGRESS WIDTH:

    .3 FOR STAIRWAYS

    .2 FOR OTHER COMPONENTS

    1006.1 ILLUMINATION:

    THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATEDAT ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF EGRESS ISOCCUPIED.

    1009.1 STAIRWAY WIDTH:

    EXCEPTION 1: STAIRS SERVING LESS THAN 50 OCCUPANTS SHALL BE 36" MIN

    1011.1 EXIT SIGNS:

    ACCESS TO EXITS SHALL BE MARKED BY READILY VISIBLE EXIT SIGNS IN CASESWHERE THE EXIT OR PATH OF EGRESS TRAVEL IS NOT IMMEDIATELY VISIBLE TOOCCUPANTS.

    UNIT TABULATION:

    THIRD FLOOR 6 2-BEDROOM UNITS

    SECOND FLOOR 6 2-BEDROOM UNITS

    FIRST FLOOR 4 2-BEDROOM UNITS1 1-BEDROOM ADA UNIT

    TOTAL UNITS 17

    TOTAL BEDS 34

    PROJECT LINE SYMBOLS LEGEND

    Existing Items to Remain.

    New Construction

    Hidden or Overhead Items

    Existing Items to be Removed

    Center Lines / Column Line

    Limit of Work

    PROJECT MATERIALS LEGEND

    Undisturbed Earth

    Compacted Fill

    Topsoil

    Gravel

    Concrete

    Sand, Grout,Parging, Stucco

    Concrete Masonry(or EXIST Generic MAS / SCT)

    Brick

    GYP / Stud Wall(or Generic Existing Wall)

    Existing Partitionto be Removed

    Metal

    Wood

    Existing MASto be Removed

    EXISTNEW

    SECTION HATCH

    EXISTNEW

    SURFACE HATCH

    Stone Cladding

    Existing FLR / Areato be Removed.

    Note: See Sheet Legends for sheet-specific line types not represented below.

    Note: See Sheet Legends for sheet-specific material / hatch patterns not represented below.

    10001.A

    SYMBOLS

    INTERIOR / EXTERIOR ELEVATION

    BUILDING / WALL SECTION

    DETAIL

    DETAIL / ENLARGED PLAN

    COLUMN LINE

    FLOOR ELEVATION LINE

    SPOT ELEVATION

    WALL TYPE TAG

    ROOM NAME AND NUMBER

    DOOR TAG

    KEYNOTE

    SHEET KEYNOTE

    SHEET FIXTURE NOTE

    DRAWING REFERENCE

    NEW DOOR

    A-101

    11

    11 11

    11

    1

    101

    ROOM NAME

    101

    2A

    1

    1

    /1 A101

    100'-0"

    A101

    1SIM

    183 SF

    WATER & GAS

    302 SF

    ELECTRIC

    522 SF

    LAUNDRY

    522 SF

    GENERAL STORAGE

    302 SF

    MECHANICAL

    425 SF

    BICYCLES

    123 SF

    NOT USED

    64 SF

    DATA

    210 SF

    MECHANICAL

    210 SF

    MAINTENANCE

    *EXISTING TO REMAINSTAIR WIDTH: 36"STAIR CAPACITY: 120

    DOOR WIDTH: 36''DOOR CAPACITY: 160

    BASEMENTOCCUPANTS: EXISTING TO REMAIN

    WEST STAIR

    215 SF

    MECH STORAGE

    520 SF

    APARTMENT B

    517 SF

    APARTMENT A

    511 SF

    APARTMENT C - ADA

    BEDROOM100 SF

    BEDROOM137 SF

    BEDROOM104 SF

    BEDROOM104 SF

    ADA DOUBLEBEDROOM

    198 SF

    414 SF

    COMMON ROOM

    517 SF

    APARTMENT A

    520 SF

    APARTMENT B

    347 SF

    CORRIDORWEST STAIR

    EAST STAIR

    *EXISTING TO REMAINSTAIR WIDTH: 36"STAIR CAPACITY: 120

    DOOR WIDTH: 36''DOOR CAPACITY: 160

    * EXISTING TO REMAINSTAIR WIDTH: 38"+

    STAIR CAPACITY: 126

    DOOR WIDTH: 36''DOOR CAPACITY: 160

    EAST EXIT STAIRDISCARGES DIRECTLYTO EXTERIOR AT GRADE

    WEST EXIT STAIRDISCARGES DIRECTLYTO EXTERIOR AT GRADE

    17 OCC

    FLOOR 01OCCUPANTS: EXISING TO REMAIN

    517 SF

    APARTMENT A

    517 SF

    APARTMENT A

    520 SF

    APARTMENT B

    520 SF

    APARTMENT B516 SF

    APARTMENT A

    517 SF

    APARTMENT A

    NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.

    *EXISTING TO REMAINSTAIR WIDTH: 36"STAIR CAPACITY: 120

    DOOR WIDTH: 36''DOOR CAPACITY: 160

    * EXISTING TO REMAINSTAIR WIDTH: 38"+

    STAIR CAPACITY: 126

    DOOR WIDTH: 36''DOOR CAPACITY: 160

    FLOOR 02 & 03OCCUPANTS: EXISING TO REMAIN

    WEST STAIR

    EAST STAIR

    GENERAL CODE PLAN NOTES

    1. Fire Ratings are code minimum requirements forfire barriers & partitions. Penetrations throughrated construction and fire-rated joint systemsshall match or exceed these ratings.

    2. See A-601 for wall types and assemblies.Specified partition types may exceed codeminimum ratings.

    CODE PLAN LEGEND

    30-MIN Rated Wallfor any new work

    60-MIN Rated Wallfor any new work

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:1

    8 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    SYMBOLS & NOTES &CODE PLANS

    G-002

    BID SET

    KEYNOTE LEGEND - MASTER

    92700.A Glass-Fiber-Reinforced PlasterFabrication

    92900.G 5/8" Gypsum Wallboard

    92900.H 5/8" Type X Gypsum Wallboard

    92900.U V Control Joint

    93010.A Ceramic Tile

    93100.B Metal Edge Strip

    95100.C APC-2

    95300.B Tee

    95300.F Suspension Wire

    96516.D Rubber Sheet Floor Covering

    96519.D Vinyl Composition Floor Tile

    96800.A Carpet

    102600.C Corner Guard

    102800.S 24" Towel Bar

    113100.E Range Hood

    113100.F Refrigerator/Freezer

    123200.A Manufactured Wood Casework

    123600.C Plastic-Laminate Countertop

    KEYNOTE LEGEND - MASTER

    33000.A Cast-in-Place Concrete Footing

    51200.E Structural Steel Channel

    61000.A Blocking

    61000.C Furring

    61000.I 2x4

    61000.J 2x6

    61000.L 2x10

    61600.G 3/4" Plywood Sub-Flooring

    62023 Interior Finish Carpentry (basicpremanufactured trim

    62023.A Wood Base

    64300.D Wood Railing

    64600.E Wood Casing

    72500.E High Temperature Self-Adhering SheetUnderlayment

    74600.C Fiber-Cement Soffit

    81400.A Wood Door Frame

    81400.B Flush Wood Door

    92216.J 3 5/8" Steel Stud

    92613.B 1/8" Veneer Plaster

    3/32" = 1'-0" G-002

    4BASEMENT CODE PLAN

    3/32" = 1'-0" G-002

    5FIRST FLOOR CODE PLAN

    3/32" = 1'-0" G-002

    6SECOND FLOOR CODE PLAN

    NO. DESCRIPTION DATE

  • 618 CLYDE STREETEXISTING 3 STORY PLUS BASEMENT APARMENT BUILDING

    CLYDE HOUSE

    CLY

    DE

    ST

    RE

    ET

    50' R

    OW

    EXISTING ASPHALT DRIVEWAY

    EXISTINGENTRYPORCH

    AIR CONDENSER;SEE MECH

    02

    03

    09

    05

    08

    10

    10

    01

    11

    04

    906.06'

    PROPOSED CONCRETE SIDEWALK;SEE CIVIL. SLOPE NOT TO EXCEED 1:20

    01

    06

    01

    05

    12

    10

    06

    GENERAL FLOOR PLAN NOTES

    A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &

    coordination purposes.C. All windows, except at bathrooms, of apartments and

    commom room to have window treatments (seespec).

    08

    09

    10

    10

    04

    11

    02

    05

    0505 12

    12

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:1

    5 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    ARCHITECTURAL SITEPLAN AND EXTERIORIMPROVEMENTS

    AS-101

    BID SET

    3/32" = 1'-0" AS-101

    1ARCHITECTURAL SITE PLAN

    NN

    TRUEPLAN

    NTS AS-101

    5BASEMENT LEVEL OPNG TYPE B

    SHEET KEYNOTES - SITE IMPROVEMENTS

    01 EXISTING LAWN TO REMAIN; FILL ANDSEED DISTURBED AREAS

    02 REPAIR EXISTING CONDUCTOR HEAD

    03 DEMO EXISTING ROOF TO STRUCTURE;REPAIR ANY DAMAGED STRUCTURALWOOD; NEW ROOF TO BE EPDM &PROVIDE NEW SCUPPER TO EXISTINGCONDUCTOR HEAD. RE-FINISH SOFFITAND ADD EXTERIOR LIGHT; SEE AC-101

    04 REMOVE IVY AND CABLES FROM SOUTHELEVATION. INSPECT AND REPAIR BRICKAND MORTAR AS NEEDED.

    05 REMOVE ALL EXISTING EQUIP, CABLES,CONDUIT AND RECEPTACLES

    06 PROVIDE FREEZE PROOF HOSE BIB

    08 REPAIR OPENING IN MAS WALL

    09 REPLACE BROKEN GLASS BLOCK

    10 REMOVE VENT(S); INFILL WITH GLASSBLOCK

    11 REMOVE EXISTING BIKE RACKS

    12 REPLACE GUTTER AT WEST STAIREXTERIOR DOOR AND RELOCATEDOWNSPOUT. RE-FINISH SOFFIT AND ADDEXTERIOR LIGHT; SEE AC-101

    NTS AS-101

    6BASEMENT LEVEL OPNG TYPE C

    NTS AS-101

    7BASEMENT LEVEL OPNG TYPE D

    NTS AS-101

    4BASEMENT LEVEL OPNG TYPE A

    NTS AS-101

    9IVY ON SOUTH ELEVATION

    NTS AS-101

    8BIKE RACKS

    NTS AS-101

    3FRONT PORCH CONDUCTOR

    NTS AS-101

    2EXTERIOR CABLES

    NTS AS-101

    12EAST/FRONT ENTRY

    NTS AS-101

    11WEST/BACK ENTRY

    NTS AS-101

    10WEST STAIR PORCH ROOF

    NO. DESCRIPTION DATE

  • RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    2A

    3

    E2

    2B

    E1

    E3

    2B

    5

    6

    1' -

    10"

    5' -

    9 3

    /8"

    6' - 6" 5' - 6 1/8"

    7

    TYP

    TYP

    UP

    DN UP

    DN

    8

    8

    11 TYP

    E4 TYP

    12

    TYP

    TYPTYP

    TYP

    1

    2A

    NOTES:1. REMOVE ALL CEILING MATERIAL TO THE STRUCTURE

    1

    7' - 9 3/8" 5' - 6 1/8"

    TY

    P

    2' -

    0"

    1' -

    10"

    7' -

    0 3

    /4"4

    2B

    NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.2. REFER TO FIRST FLOOR PLAN FOR TYPICAL NOTES.

    UP

    DNUP

    DN

    8

    9

    10

    AT 2ND FL ONLY

    2B2B

    GENERAL DEMOLITION NOTES

    1. See details on A-401 for ADD'L info regardingdemo of structural elements.

    2. GC to inspect all existing refridgerators. Salvageappx. 50%; clean and re-use.

    3. GC to inspect all existing kitchen cabinets.Salvage appx. 70%; clean and re-use.

    4. Remove all floor finishes throughout building.5. Remove all ACT ceiling finish throughout all

    units.(Units that do not need ceiling demo arenoted on the plans. See notes below)

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:1

    4 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    DEMOLITION PLANS

    AD-101

    BID SET

    1/8" = 1'-0" AD-101

    2FIRST FLOOR DEMOLITION PLAN

    NN

    TRUEPLAN

    1/8" = 1'-0" AD-101

    1BASEMENT DEMOLITION PLAN

    1/8" = 1'-0" AD-101

    3SECOND FLOOR DEMOLITION PLAN

    SHEET KEYNOTES - DEMO

    EXISTING MATERIALS

    E1 Aluminum double-hung window ETR.Contractor shall inspect each window andrepair all damaged sash and/or hardware.

    E2 Stair and guardrailing ETR.

    E3 Concrete stair and gaurdrailing ETR.

    E4 Stainless steel sink basin ETR; clean andre-use.

    DEMOLITION NOTES

    1 Remove existing utlilty sinks and laundryequipment. See plumbing DWG's.

    2A Remove window and MAS below to grade;salvage brick for infill. See west demoelevation.

    2B Remove existing glass block window

    3 Remove first floor in this area for wheelchairlift; see structural details on A-401

    4 Demo existing basement slab in this area

    5 Remove EXIST stud closet walls, TYP.

    6 Remove EXIST unit entry door and frame,TYP.

    7 Remove wood stud partitions. Undamagedlumber may be salvaged and reused

    8 No ceiling finish removal is needed in this unit.

    9 Remove ACT ceiling finish in this room only.

    10 Remove ACT ceiling finish at 3rd floor ceilingof west stair.

    11 Remove EXIST unit range and countertop.

    12 Remove EXIST bathroom fixtures. See plumb

    NO. DESCRIPTION DATE

  • 183 SF

    WATER & GAS

    003

    302 SF

    ELECTRIC

    001

    522 SF

    LAUNDRY

    010

    522 SF

    GENERAL STORAGE

    006

    302 SF

    MECHANICAL

    008

    425 SF

    BICYCLES

    007

    123 SF

    NOT USED

    002

    64 SF

    DATA

    004

    210 SF

    MECHANICAL

    009

    210 SF

    MAINTENANCE

    011

    UTILITY SINK, SEE PLUMBING

    STACKED WASHER/DRYER UNITS. PROVIDED BY OWNER

    33000.A

    340 SF

    CORRIDOR

    000

    105 SF

    WEST STAIR

    STW-0

    005

    STW-0.1

    4

    4

    1A

    4

    7' - 0 3/4" 5' - 6 1/8"

    2' -

    4 3

    /4"

    ALIG

    N

    AIR CONDENSER;SEE MECH

    UP

    REINF. w/ 3 #5 CONT. BTM. x1'-6'' LONG TRANSVERSE

    BARS @ 24'' O.C.

    12

    A-401

    4

    1' -

    1 1

    /4"

    4' -

    8 1

    /8"

    UTILITY SINK,SEE PLUMBING

    17A-401

    215 SF

    MECH STORAGE

    005004

    003

    1A

    1A

    8' -

    0"

    14A-401

    8' - 0"

    1A

    1A

    1"

    2

    BRICK-INFILL ;SEE A-201

    BIKE STORAGE; PROVIDED BY OWNER

    6' - 0"

    FIRE EXTINGUISHER, ETR

    GENERAL FLOOR PLAN NOTES

    A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &

    coordination purposes.C. All windows, except at bathrooms, of apartments and

    commom room to have window treatments (seespec).

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :12:5

    4 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    BASEMENT PLAN

    A-100

    BID SET

    1/4" = 1'-0" A-100

    1BASEMENT PLAN

    NN

    TRUEPLAN

    KEYNOTE LEGEND

    33000.A Cast-in-Place Concrete Footing

    NO. DESCRIPTION DATE

  • RE

    F

    RE

    F

    RE

    F

    RE

    F

    RE

    F

    WHEELCHAIRLIFT

    BATH

    ENTRY

    CLOSET

    KITCHEN

    CLOSET

    LIVING/DINING

    520 SF

    APARTMENT B

    104

    CLOSET

    BATH

    ENTRY

    KITCHEN

    LIVINGALCOVE

    517 SF

    APARTMENT A

    102

    DINING

    ADA BATH

    AD

    A K

    ITC

    HE

    N

    511 SF

    APARTMENT C - ADA

    105

    BEDROOM100 SF

    BEDROOM137 SF

    BEDROOM104 SF

    BEDROOM104 SF

    ADA DOUBLEBEDROOM

    198 SF

    LIVING/DINING

    414 SF

    COMMON ROOM

    106

    517 SF

    APARTMENT A

    101

    520 SF

    APARTMENT B

    103

    347 SF

    CORRIDOR

    100

    WEST STAIR

    STW-1

    EAST STAIR

    STE-1 ENTRY PORCH

    101.1

    101.2b

    101.2a

    STE-1.1 ST

    E-1

    .2

    104.1

    102.2a

    102.2b

    103.2a103.3

    104.3

    104.2a

    105.1

    105.3ADA

    105.2

    AD

    A

    106.1

    105.4

    AD

    A

    STW-1.1

    102.1

    6' - 3"

    6' - 3"

    3' - 6"

    2' -

    5"

    2' -

    5"

    3A

    2

    1A1A

    103.1

    A-4019

    A-401

    19

    13

    A-4011

    A-4012

    8

    1A

    6' - 6'' MIN

    ALIG

    N

    1A1A

    ALIGN

    ALIGN

    1A

    68 SF

    ADA ENTRY

    ADA-1

    UP

    DNUP

    DN

    AD

    A-1

    .2

    ST

    W-1

    .2

    6

    5

    REMOVE EXISTING SURFACEMOUNTED MAILBOXES; INFILLEXISTING HOLES IN THE WALL;SEE PHOTO ABOVE

    EQ

    EQ

    EQ

    EQ

    2

    60" MIN

    5' - 3"

    2'' TYP

    4

    A-401

    1' - 0"1' - 0"

    2'' TYP

    2'' TYP

    2'' TYP

    A-501

    16

    VERIFY DIM IN FIELDWITH LOCATION OFEXISTING STACK ANDRADIATOR LINES

    A-50124TYP

    19

    A-501

    17A-401

    103.2b

    104.2b

    14A-401

    FIRE DEPARTMENT HOOK-UP;SEE FP DWGS

    3

    906.08'

    906.06'

    (+1/4" FROMEXTERIORELEVATION)

    3' - 4 1/2"

    4AB4AB

    4AB

    3' -

    1 5

    /8"

    2 2

    2 2

    2

    TYP

    A-501 24TYP

    INSTALL BULLETIN BOARDON THIS SIDE ONLY

    2

    7"

    A-101

    2Sim

    NOTE: ACCESSIBLE UNITS ARENOT REQUIRED BY CODE. SEECODE SUMMARY ON G-002

    16

    555

    2

    2

    2

    2

    WIRE SHELF AND ROD@ ALL CLOSETS, TYP

    VIF

    3' -

    7 1

    /4"

    PLATFORM

    2' -

    7 1

    3/1

    6"

    1AB

    ALIGN

    102600.C

    ,TYPTYP @ OUTSIDECORNERS IN CORRIDOR

    FIRE EXTINGUISHER, ETR

    GENERAL FLOOR PLAN NOTES

    A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &

    coordination purposes.C. All windows, except at bathrooms, of apartments and

    commom room to have window treatments (seespec).

    414 SF

    COMMON ROOM

    106

    EXIST FLR JOISTS TO REMAIN

    EXIST FLR JOISTS TO BE CUT

    2X10 JOISTS @ 16'' O.C. w/3/4'' PLYWOOD FLR DECKING

    COORDINATE IN FIELD

    COORDINATE IN FIELD

    15

    A-401

    11

    A-401

    REMOVE MAILBOX FRAMES ANDPATCH PLASTER WALL

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :12:5

    6 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    FIRST FLOOR PLAN

    A-101

    BID SET

    NN

    TRUEPLAN

    1/4" = 1'-0" A-101

    1FIRST FLOOR PLAN

    1/2" = 1'-0" A-101

    2FIRST FLOOR ADA LIFT FRAMING PLAN

    KEYNOTE LEGEND

    102600.C

    Corner Guard

    NTS A-101

    3MAILBOX WALL REPAIR-1

    NO. DESCRIPTION DATE

  • RE

    F

    RE

    F

    RE

    F

    RE

    FR

    EF

    RE

    F

    517 SF

    APARTMENT A

    201

    517 SF

    APARTMENT A

    202

    520 SF

    APARTMENT B

    204

    520 SF

    APARTMENT B

    203

    516 SF

    APARTMENT A

    205

    517 SF

    APARTMENT A

    206

    NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.2. REFER TO FIRST FLOOR PLAN FOR TYPICAL NOTES.

    EAST STAIR

    STE-2

    347 SF

    CORRIDOR

    200WEST STAIR

    STW-2

    STE-2.1

    201.2b

    201.2a

    202.2a

    202.2b

    203.1

    203.2a

    203.3

    204.1

    205.2b

    205.2a

    STW-2.1

    206.2a

    206.2b

    202.1

    201.1205.1

    206.1

    6' - 3"

    2' -

    5"

    A-4012

    3' - 8 3/4"

    1A1A

    ALIGN

    5

    UP

    DN UP

    6

    EQ

    EQ

    EQ

    EQ

    EQ

    EQ

    EQ

    EQ

    DN

    2'' TYP

    2'' TYP

    2'' TYP

    2'' TYP

    2'' TYP

    17A-401

    204.3204.2a

    204.2b

    203.2b

    14A-401

    NEW ROOFING; SEE NOTES ON AS101

    REPAIR EXISTING CONDUCTOR HEAD;SEE NOTES ON AS101

    REPLACE GUTTER ANDDOWNSPOUT ON

    EXISTING CANOPY;SEE NOTES ON AS101

    NEW SCUPPER; SEE NOTES ON AS101

    5

    2

    2

    2

    2

    2

    6' - 3"

    2' -

    5"1A1A

    ALIGN

    2'' TYP 2

    2

    2 2

    2

    2

    2

    102600.CTYP @ OUTSIDECORNERS IN CORRIDOR

    FIRE EXTINGUISHER, ETR

    GENERAL FLOOR PLAN NOTES

    A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &

    coordination purposes.C. All windows, except at bathrooms, of apartments and

    commom room to have window treatments (seespec).

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :12:5

    8 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    SECOND FLOOR PLAN(3RD SIMILAR)

    A-102

    BID SET

    NN

    TRUEPLAN

    1/4" = 1'-0" A-102

    1SECOND FLOOR PLAN

    NO. DESCRIPTION DATE

  • 302 SF

    ELECTRIC

    001

    210 SF

    MAINTENANCE

    011

    522 SF

    LAUNDRY

    010

    210 SF

    MECHANICAL

    009

    302 SF

    MECHANICAL

    008

    425 SF

    BICYCLES

    007

    522 SF

    GENERAL STORAGE

    006

    64 SF

    DATA

    004

    183 SF

    WATER & GAS

    003

    105 SF

    WEST STAIR

    STW-0

    340 SF

    CORRIDOR

    000123 SF

    NOT USED

    002

    7' - 1 3/4" , TYP THIS LEVEL

    OPEN TO ABOVE

    4' - 0" 9' - 0" 9' - 0" 9' - 0"

    GENERAL NOTES:1. COORDINATE PLACEMENT OF LIGHT FIXTURES WITH EXISTING CONDITIONS; PIPING, ETC

    215 SF

    MECH STORAGE

    005

    COORDINATE FURNACE DUCT WORKWITH EXISTING AND NEW PIPING

    4

    A-601

    TYP AT THIS LEVEL

    GENERAL CLG PLAN NOTES

    1. Light fixtures should be centered in CLG areas,rooms, or CLG tiles, UNO.

    2. MEP fixtures are shown for coordination w/ CLGplans. Refer to FP, P, E, & H drawings for fixturetypes and other information.

    3. All unit ceilings are furred directly on existingplaster (see detail ) UNO withelevation marker and detail callout.

    Light Fixtures

    Mechanical Grilles

    Sprinkler Head

    CLG PLAN LEGEND

    APC-1PT

    TYPE "X"GYP

    /5 A-501

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:1

    0 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    BASEMENT REFLECTEDCEILING PLAN

    AC-100

    BID SET

    1/4" = 1'-0" AC-100

    1BASEMENT REFLECTED CEILING PLAN

    NO. DESCRIPTION DATE

  • GENERAL CLG PLAN NOTES

    1. Light fixtures should be centered in CLG areas,rooms, or CLG tiles, UNO.

    2. MEP fixtures are shown for coordination w/ CLGplans. Refer to FP, P, E, & H drawings for fixturetypes and other information.

    3. All unit ceilings are furred directly on existingplaster (see detail ) UNO withelevation marker and detail callout.

    Light Fixtures

    Mechanical Grilles

    Sprinkler Head

    CLG PLAN LEGEND

    APC-1PT

    TYPE "X"GYP

    /5 A-501

    7' - 5"

    517 SF

    APARTMENT A

    102

    517 SF

    APARTMENT A

    101

    120 SF

    EAST STAIR

    STE-1

    108 SF

    WEST STAIR

    STW-1

    511 SF

    APARTMENT C - ADA

    105

    414 SF

    COMMON ROOM

    106

    520 SF

    APARTMENT B

    104

    520 SF

    APARTMENT B

    103

    347 SF

    CORRIDOR

    100

    EQ EQ

    TY

    P

    1' -

    2"

    EQ EQEQ EQ EQ EQ EQ EQEQ EQEQ EQ

    6' - 11"

    6' - 11"E

    QE

    Q

    5' -

    0"

    1' - 2"

    4

    A-601

    10' - 0" 2' - 0"

    2' -

    0"

    10' -

    0"

    2' - 0" 16' - 0"

    4' -

    0"

    2' -

    0"

    3' - 3"

    WINDOW

    20' - 0" 20' - 0"

    20

    A-501

    1' -

    6"

    1' -

    6"

    1' -

    6"

    1' -

    6"

    15

    A-501

    1

    TYP FOR UNIT 105 EXCEPT AT BULKHEAD

    10

    A-501

    EQ

    EQ

    20

    A-501

    EQ 4' - 0" EQ

    EQ

    4' -

    6"

    EQ

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:1

    1 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    FIRST FLOORREFLECTED CEILINGPLAN

    AC-101

    BID SET

    KEYNOTE LEGEND

    1/4" = 1'-0" AC-101

    1FIRST FLOOR REFLECTED CEILING PLAN

    SHEET KEYNOTES - RCP

    REFLECTED CEILING PLAN NOTES

    1 Patch and plaster @ all demo-ed walls prior toinstalling new ceiling

    NO. DESCRIPTION DATE

  • 517 SF

    APARTMENT A

    206

    520 SF

    APARTMENT B

    204

    347 SF

    CORRIDOR

    200

    520 SF

    APARTMENT B

    203

    516 SF

    APARTMENT A

    205

    517 SF

    APARTMENT A

    201

    517 SF

    APARTMENT A

    202

    120 SF

    EAST STAIR

    STE-2

    108 SF

    WEST STAIR

    STW-2

    EQ EQEQ EQEQ EQEQ EQ EQ EQ EQ EQ

    1

    20' - 0" 20' - 0"

    NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.2. REFER TO FIRST FLOOR PLAN FOR TYPICAL NOTES.

    1' -

    6"

    1' -

    6"

    1' -

    6"

    1' -

    6"

    1' -

    6"

    ,3RD FLOOR CEILING OFWEST STAIR, ONLY

    /5 A-501

    GENERAL CLG PLAN NOTES

    1. Light fixtures should be centered in CLG areas,rooms, or CLG tiles, UNO.

    2. MEP fixtures are shown for coordination w/ CLGplans. Refer to FP, P, E, & H drawings for fixturetypes and other information.

    3. All unit ceilings are furred directly on existingplaster (see detail ) UNO withelevation marker and detail callout.

    Light Fixtures

    Mechanical Grilles

    Sprinkler Head

    CLG PLAN LEGEND

    APC-1PT

    TYPE "X"GYP

    /5 A-501

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:1

    2 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    SECOND FLOORREFLECTED CEILINGPLAN

    AC-102

    BID SET

    1/4" = 1'-0" AC-102

    1SECOND FLOOR REFLECTED CEILING PLAN

    KEYNOTE LEGEND

    SHEET KEYNOTES - RCP

    REFLECTED CEILING PLAN NOTES

    1 Patch and plaster @ all demo-ed walls prior toinstalling new ceiling

    NO. DESCRIPTION DATE

  • FIRST FLOOR100' - 0"

    ROOF JOIST BEARING126' - 6 1/2"

    SECOND FLOOR109' - 1 3/4"

    BASEMENT91' - 10"

    THIRD FLOOR118' - 3 1/2"

    8' -

    3"

    9' -

    1 3

    /4"

    9' -

    1 3

    /4"

    8' -

    2"

    REPLACE EXISTING GLASS BLOCKWINDOWS ON SOUTH FACADE WITHWITH DOUBLE HUNG WINDOW, TYP(APPX SIZE 3'-0"W x 3'-2"H; VIF)

    FREEZE PROOF HOSE-BIB;SEE PLUMBING

    EXTERIORSECURITY LIGHT,TYP; SEE ELEC

    EQEQ

    1' -

    6"

    FIRST FLOOR100' - 0"

    ROOF JOIST BEARING126' - 6 1/2"

    SECOND FLOOR109' - 1 3/4"

    BASEMENT91' - 10"

    THIRD FLOOR118' - 3 1/2"

    8' -

    3"

    9' -

    1 3

    /4"

    9' -

    1 3

    /4"

    8' -

    2"

    NEW DOOR @ WEST STAIR ;SEE DETAILS ON A-501

    NEW DOOR @ ADA ENTRY &TRANSOM WINDOW ABOVE;SEE DETAILS ON A-501

    INFILL w/ SALVAGED BRICK

    EXTERIORSECURITY LIGHT,TYP; SEE ELEC

    NEW GUTTER ANDDOWNSPOUT ON EXISTINGCANOPY, SEE AS-101

    NEW SOFFIT, SEE /20 A-501

    18

    A-501

    1' - 6"

    1' -

    6"

    1' -

    6"

    CL

    1' - 6"

    1' -

    6"

    FIRST FLOOR100' - 0"

    ROOF JOIST BEARING126' - 6 1/2"

    SECOND FLOOR109' - 1 3/4"

    BASEMENT91' - 10"

    THIRD FLOOR118' - 3 1/2"

    8' -

    3"

    9' -

    1 3

    /4"

    9' -

    1 3

    /4"

    8' -

    2"

    REMOVE EXISTING WINDOW.

    REMOVE EXISTING GLASSBLOCK WINDOW

    VIF

    12' -

    1"

    3'-2".

    REMOVE EXISTING DOORAND FRAME

    REMOVE EXISTING WALL TO GRADE.(SALVAGE BRICK FOR INFILL)

    REMOVE EXISTING GUTTERAND DOWNSPOUT

    GENERAL ELEVATION NOTES

    A. SEE AS-101 FOR EXTERIOR IMPROVEMENTSSCOPE.

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :12:5

    9 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    BUILDING ELEVATIONS

    A-201

    BID SET

    KEYNOTE LEGEND

    3/16" = 1'-0" A-201

    1SOUTH ELEVATION

    3/16" = 1'-0" A-201

    2WEST ELEVATION

    3/16" = 1'-0" A-201

    3WEST DEMOLITION ELEVATION

    NO. DESCRIPTION DATE

  • FIRST FLOOR100' - 0"

    ROOF JOIST BEARING126' - 6 1/2"

    SECOND FLOOR109' - 1 3/4"

    BASEMENT91' - 10"

    THIRD FLOOR118' - 3 1/2"

    1' -

    0"

    8' -

    2"

    9' -

    1 3

    /4"

    9' -

    1 3

    /4"

    8' -

    3"

    3' -

    6"

    T/FOOTING90' - 10"

    T/PARAPET130' - 0 1/2"

    EXTERIORSECURITY LIGHT,

    TYP; SEE ELECEQEQ

    1' -

    6"

    FIRST FLOOR100' - 0"

    ROOF JOIST BEARING126' - 6 1/2"

    SECOND FLOOR109' - 1 3/4"

    BASEMENT91' - 10"

    THIRD FLOOR118' - 3 1/2"

    T/FOOTING90' - 10"

    T/PARAPET130' - 0 1/2"

    3' -

    6"

    8' -

    3"

    9' -

    1 3

    /4"

    9' -

    1 3

    /4"

    8' -

    2"

    1' -

    0"

    EXTERIORSECURITY LIGHT,TYP; SEE ELEC2

    ' - 6

    "

    CL

    GENERAL ELEVATION NOTES

    A. SEE AS-101 FOR EXTERIOR IMPROVEMENTSSCOPE.

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:0

    1 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    BUILDING ELEVATIONS

    A-202

    BID SET

    3/16" = 1'-0" A-202

    1NORTH ELEVATION

    3/16" = 1'-0" A-202

    2EAST ELEVATION

    NO. DESCRIPTION DATE

  • 3' -

    6"

    MIR

    RO

    R

    3' -

    0"

    2' - 0"

    A-501

    9ROBE HOOKON DOOR

    SHELF102800

    113100.E

    113100.F

    ELECTRICRANGE

    2' -

    6"

    3' -

    0"

    40"

    MA

    X

    1' - 6"

    MIN

    2' - 0"

    MIN

    1' - 0"

    1' -

    6"

    4' -

    0"

    MIRROR

    CL

    34"

    MA

    X

    2' - 0"ROBE HOOK

    ADA SHOWERSEE PLUMB

    ADA COMPLIANTP-TRAP COVER

    SHELF102800

    ADA SHOWER;SEE PLUMB

    REMOVABLE BASE CABINETS; FLOORFINISH EXTENDS UNDER CABINETRY

    2' - 6" 2' - 6" 2' - 3"

    ADA WORK SURFACE; ADJACENT TO OVEN;30" CLEAR WHEN CABINET REMOVED

    ADA SINK; 30" CLEAR WHEN CABINET REMOVED

    1' -

    6"

    1' -

    6"

    1' -

    1"

    34"

    MA

    X C

    OU

    NT

    ER

    2' -

    10"

    48"

    MA

    X T

    O B

    OT

    TO

    M S

    HE

    LF

    3' -

    11"

    OF

    UP

    PE

    R C

    AB

    INE

    T

    123200.A

    STAINLESS STEELBACKSPLASH

    123600.C

    ,TYP

    123600.C

    113100.E

    113100.F123200.A

    MIN

    3' - 6"

    MAX

    1' - 0"

    7"-9"

    OUTLET OF TOILETPAPER DISPENSER TOBE 15" - 48" A.F.F. ANDNOT BEHIND A GRAB BAR

    2' -

    0"

    14

    A-501

    1' -

    6"

    1/2" FRAME EDGE TO WALL

    61000.L

    61000.J

    92900.H

    61000.L, 16'' O.C.

    , BOTHSIDES

    ADA ENTRY

    COMMON ROOM

    BIKE STORAGE

    AT BASEMENT LEVEL

    61000.J

    33000.A

    GRADE LEVEL

    1/4

    "

    3"

    61600.G

    96519.D

    EXISTING EXTERIORMASONRY WALL

    FIRST FLOOR

    V I F

    ADA CHAIR LIFT

    61600.G

    PRESSURETREATED SILLPLATE

    EXISTING SLAB

    CUT SOLID SURFACEWALL @ WINDOW;PROVIDE SOLIDSURFACE SILL ANDSIDES @ WINDOW;SEAL ALL JOINTS, TYP

    2' -

    0"

    2' -

    0"

    3' -

    0"

    102800.S

    TOILET PAPER DISPENSER

    102800.S

    123600.C

    FAUCET; SEE PLUMBING

    CABINETS ETR @ 70%REPLACED @ 30%SEE NOTES ON AD-101

    CABINETS ETR @ 70%REPLACED @ 30%SEE NOTES ON AD-101

    2' - 0" 3' - 0"

    2' -

    6"

    2' -

    0"

    3' -

    0"

    1' - 6" 3' - 6"

    FIRST FLOOR100' - 0"

    ROOF JOIST BEARING126' - 6 1/2"

    SECOND FLOOR109' - 1 3/4"

    THIRD FLOOR118' - 3 1/2"

    DUCT FROM FURNACE

    CORRIDORAPT

    FIRE/SMOKE DAMPER ATREGISTER, TYP; SEE MECH

    ACCESS PANELBEYOND, TYP

    ACCESS PANELBEYOND, TYP

    CORRIDOR AIR SUPPLYRISER DUCT; SEE MECH

    EXIST CORRIDOR WALL(1HR)

    DAMPER ACCESSIBLE FROMBASEMENT; SEE MECH

    EXISTING CLOSETWALL

    SHAFT WALL

    SHAFT LINER ATFLOOR

    PENETRATIONS, TYP

    FIRST FLOOR100' - 0"

    ROOF JOIST BEARING126' - 6 1/2"

    SECOND FLOOR109' - 1 3/4"

    THIRD FLOOR118' - 3 1/2"

    SUPPLY DUCT TO CORRIDOR

    REGISTER TOCORRIDOR BEYOND,

    TYP; SEE MECH

    ACCESS PANEL, TYP

    CORRIDOR AIR SUPPLYRISER DUCT; SEE MECH

    EXISTING 1HR STUD WALL

    DAMPER ACCESSIBLEFROM BASEMENT; SEE

    MECH

    SHAFT WALL

    PROPOSED WALL AT ADALAUNDRY CLOSET

    SHAFT WALL ASSEMBLY TO RUNHORIZONTAL AT TOP OF SHAFT

    TO ADA UNIT

    SHAFT WALL SHAFT WALL

    SHAFT LINER ATFLOOR

    PENETRATIONS, TYP

    4' -

    0"

    MA

    X

    6"

    102800.S

    ADA SHOWER;SEE PLUMB

    A-501

    14 6"

    102800.S

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:0

    6 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    INTERIOR ELEVATIONS& DETAILS

    A-401

    BID SET

    KEYNOTE LEGEND

    33000.A Cast-in-Place Concrete Footing

    61000.J 2x6

    61000.L 2x10

    61600.G 3/4" Plywood Sub-Flooring

    92900.H 5/8" Type X Gypsum Wallboard

    96519.D Vinyl Composition Floor Tile

    102800.S 24" Towel Bar

    113100.E Range Hood

    113100.F Refrigerator/Freezer

    123200.A Manufactured Wood Casework

    123600.C Plastic-Laminate Countertop

    1/2" = 1'-0" A-401

    1PR TYP Bathroom

    1/2" = 1'-0" A-401

    2PR TYP Kitchen

    1/2" = 1'-0" A-401

    13PR ADA Bathroom-2

    1/2" = 1'-0" A-401

    19PR ADA Bathroom-3

    1/2" = 1'-0" A-401

    9PR ADA Kitchen

    1/2" = 1'-0" A-401

    8PR ADA Bathroom-1

    1 1/2" = 1'-0" A-401

    4WHEELCHAIR LIFT DETAIL

    1/2" = 1'-0" A-401

    5PR TYP Bathroom-2

    1/2" = 1'-0" A-401

    6PR TYP Kitchen -2

    1 1/2" = 1'-0" A-401

    12ADA ENTRY STRUCTURAL DETAIL 1

    1 1/2" = 1'-0" A-401

    15ADA ENTRY STRUCTURAL DETAIL 2

    1 1/2" = 1'-0" A-401

    11ADA ENTRY STRUCTURAL DETAIL 3

    1/2" = 1'-0" A-401

    14SHAFT SECTION A

    1/2" = 1'-0" A-401

    17SHAFT SECTION B

    1/2" = 1'-0" A-401

    16PR ADA Bathroom-4

    NO. DESCRIPTION DATE

  • FACE OF PERPENDICULAR WALL;WHERE APPLICABLE

    64600.E

    81400.A

    81400.B

    2" 3 1/2"

    , SEE SCHED

    PATCH PLASTER AS REQ'D,BOTH SIDES

    V.I.F

    .

    11 1

    /4"

    EXISTING PLAST ONSCT WALL

    81400.A

    64600.E

    5/8"3 1/2"

    , (SEE SCHED)

    61000.A

    81400.B

    THRESHOLD BELOW

    EXTERIOR

    PATCH PLASTER,AS REQ'D

    SEAL AT BOTH SIDES

    EXTERIOR DOOR; SEE SCHED

    64600.E

    81400.A

    , (SEE SCHED)81400.B

    V.I.F.

    11 1/4"

    PATCH PLASTER ASREQ'D, BOTH SIDES

    EXISTING PLAST ONSCT WALL

    81400.A

    64600.E

    5/8

    "3 1

    /2"

    61000.A

    , (SEE SCHED)81400.B

    EXISTING STEEL LINTEL

    PATCH PLASTER AS REQ'D

    EXTERIOR

    EXTERIOR DOOR; SEE SCHED

    A-6

    01

    SE

    E D

    OO

    R T

    YP

    ES

    EXIST MASONRYWALL

    EXIST FLOOR

    EXIST EXTERIORSLAB

    DOOR FRAME

    PATCH PLASTERAS REQ'D

    THRESHOLD

    EXTERIOR DOOR;SEE SCHED

    A-6

    01

    SE

    E D

    OO

    R T

    YP

    ES

    96516.D

    96800.A93100.B

    DOOR; WHEREAPPLICABLE

    96519.DALIG

    N

    EXISTINGSUB-FLOOR

    DOOR; WHEREAPPLICABLE

    96519.D

    EXISTING SUB-FLOOR

    93010.A93010.A

    93100.B

    1 1/4"

    EX

    IST

    ING

    EXISTING PLASTERCEILING

    92900.G

    51200.E

    ST

    RU

    CT

    UR

    E

    EX

    IST

    ING

    RO

    OF

    61000.C

    74600.C

    HOT DIPPEDGALVANIZEDSCREW

    EXISTING PLAST ONSCT WALL

    TAPE AND FEATHERFINISH TO EXISTINGCORNER

    EX

    IST

    ING

    FLO

    OR

    92216.J

    92900.H

    SE

    E A

    -601

    1 H

    R A

    SS

    EM

    BLY

    SE

    E R

    CP

    95100.C

    92900.H

    95300.B

    95300.F

    92216.J

    EX

    IST

    ING

    FLO

    OR

    EXISTING PLASTERCEILING

    92900.H

    92700.A72500.E

    PATCH ANDPLASTER EXISTINGCEILING WHEREAPPLICABLEBEFORE HANGINGNEW CEILING (TOKEEP FIRE RATINGOF EXISTINGFLOOR ASSEMBLY)

    EXISTING EXTERIOR WALL

    EXISTING WINDOW FRAME

    EXISTING EDGE OF WINDOWOPENING

    SOLID SURFACE @ SIDES OFWINDOW OPENING

    ALIGN

    SOLID SURFACE SHOWER WALL

    SEAL AT ALL JOINTS/SEAMS, TYP

    SHOWER

    SOLID SURFACE SHOWERWALL; CUT FOR WINDOWOPENING

    SOLID SURFACE @ WINDOW SILL

    SE

    E E

    LE

    VA

    TIO

    NS

    4"

    6 1

    /4"1

    1/2

    "

    25" TYP, UNO

    SUPPORT, WHEREINDICATED IN ELEVATIONS

    , PTD TO MATCHEXISTING

    27"

    MIN

    RE

    Q'D

    KN

    EE

    SP

    AC

    E

    FOR ADACOUNTER SPANUSE MTL PLATEIF NECESSARY

    61000.A

    62023.A

    FLOOR FINISH EXTENDSUNDER CABINET AT ADA UNIT

    6 1

    /2"

    EXISTING STAIRS

    EXISTING HANDRAIL

    WELD PIPE RAIL TO CONNECTEXISTING STAIR RAILS; ALIGNHEIGHT TO EXISTING @ TOPAND MIDDLESEE PHOTO: /29 A-501

    WELD PIPE RAIL TOCONNECT EXISTINGSTAIR RAILS; ALIGNHEIGHT TO EXISTING@ TOP AND MIDDLESEE DETAIL: )/24 A-501

    1 1/2" 1 1/2"

    36".

    EXISTING STAIR

    64300.D

    WALL MOUNT BRACKET@ 4'-0" OC MAX

    EXISTING EXTERIOR WALL

    EXISTING WINDOW FRAME

    EXISTING WINDOW SILL61000.I

    WRAP WITH SOLIDSURFACE AT ALLEXPOSED SIDES

    GRAB BAR (SEE ELEV)

    96519.D

    EXISTINGMASONRY WALL

    ADA ENTRYFLOOR; SEEDWGs ON A-4.01

    EXTERIOR SLAB;SEE CIVIL

    MASONRY ASREQ'D

    ADA COMPLIANTTHRESHOLD

    PATCH PLASTER,AS REQ'D

    EXTERIOR DOOR;SEE SCHED

    A-6

    01

    SE

    E D

    OO

    R T

    YP

    ES

    EXISTING STEEL LINTEL

    PATCH PLASTER AS REQ'D

    EXTERIOR

    TRANSOM WINDOW

    EXTERIOR DOOR; SEE SCHED

    DOOR; WHEREAPPLICABLE

    96519.D

    EXISTINGSUB-FLOOR

    96516.D, ON ADHESIVE

    EQ EQ

    93100.B

    DOOR; WHEREAPPLICABLE

    96519.D

    EXISTINGSUB-FLOOR

    EQ EQ

    96519.D93100.B

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    6/2

    015 7

    :13:0

    8 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    DETAILS

    A-501

    BID SET

    KEYNOTE LEGEND

    51200.E Structural Steel Channel

    61000.A Blocking

    61000.C Furring

    61000.I 2x4

    62023.A Wood Base

    64300.D Wood Railing

    64600.E Wood Casing

    72500.E High Temperature Self-Adhering SheetUnderlayment

    74600.C Fiber-Cement Soffit

    81400.A Wood Door Frame

    81400.B Flush Wood Door

    92216.J 3 5/8" Steel Stud

    92700.A Glass-Fiber-Reinforced PlasterFabrication

    92900.G 5/8" Gypsum Wallboard

    92900.H 5/8" Type X Gypsum Wallboard

    93010.A Ceramic Tile

    93100.B Metal Edge Strip

    95100.C APC-2

    95300.B Tee

    95300.F Suspension Wire

    96516.D Rubber Sheet Floor Covering

    96519.D Vinyl Composition Floor Tile

    96800.A Carpet

    1 1/2" = 1'-0" A-501

    1TYP DOOR JAMB

    1 1/2" = 1'-0" A-501

    6INTERIOR DOOR JAMB TO EXT SCT WALL

    1 1/2" = 1'-0" A-501

    11TYP EXTERIOR DR JAMB

    1 1/2" = 1'-0" A-501

    3TYP DOOR HEAD

    1 1/2" = 1'-0" A-501

    8INTERIOR DOOR HEAD TO EXT SCT WALL

    1 1/2" = 1'-0" A-501

    13TYP EXTERIOR DR HEAD

    1 1/2" = 1'-0" A-501

    12TYP EXTERIOR DR THRESHOLD

    6" = 1'-0" A-501

    2CARPET TO LVT TRANSITION DETAIL

    6" = 1'-0" A-501

    22LVT TO CERAMIC TILE TRANSITION DETAIL

    1 1/2" = 1'-0" A-501

    5TYP FLR/CLG @ EXISTING PLASTER

    1 1/2" = 1'-0" A-501

    20EXTERIOR SOFFIT

    1 1/2" = 1'-0" A-501

    16PLAN DETAIL CONNECTION TO EXISTING WALL

    1 1/2" = 1'-0" A-501

    10TYP FLR/CLG @ BULKHEAD

    1 1/2" = 1'-0" A-501

    15TYP DROPPED CLG

    1 1/2" = 1'-0" A-501

    9TYP SHOWER WINDOW SILL DETAIL

    1 1/2" = 1'-0" A-501

    4KITCHEN COUNTER DETAIL

    1 1/2" = 1'-0" A-501

    24TYP WEST STAIR HANDRAIL DETAIL

    NTS A-501

    29WEST STAIR RAIL EXISTING CONDITIONS

    1 1/2" = 1'-0" A-501

    19STAIR HANDRAIL DETAIL @ EAST STAIR ENTRY

    1 1/2" = 1'-0" A-501

    14GRAB BAR @ WINDOW BLOCKING DETAIL

    1 1/2" = 1'-0" A-501

    17EXTERIOR DR THRESHOLD AT ADA ENTRY

    1 1/2" = 1'-0" A-501

    18EXTERIOR DR HEAD AND TRANSOM

    6" = 1'-0" A-501

    27RUBBER TO LVT TRANSITION DETAIL

    6" = 1'-0" A-501

    7RUBBER TO LVT TRANSITION DETAIL

    NO. DESCRIPTION DATE

  • 1GYP BD PARTITION

    92900.H

    BRACING

    92216.J

    4 7/8"

    2ONE-SIDED GYP BD PARTITION

    92900.H

    BRACING

    92216.J

    4 1/4"

    , BOTH SIDES

    92900.U

    , @ 24" O.C.

    , @ 24" O.C.

    3GYP BD PARTITION W/ BLOCKING

    BLOCKING FOR GRAB BARS

    , @ 24" O.C.

    6 3/4"

    61000.J

    PARTITION TYPES NOTES

    1. Refer to Code Floor Plans (G-002) for code required Fire-Resistance Ratings. In someinstances, specified UL assemblies may exceed the minimum rating required by code.Penetrations and joint systems for such assemblies should meet or exceed the coderequired fire-resistance ratings for such walls.

    2. Provide blocking in walls behind all wall-mounted casework, equipment, handrailbrackets, grab bars, mirrors, and other wall mounted objects.

    3. Provide Moisture Resistant gypsum board in all bathrooms, and kitchens.4. All gypsum board shall be 5/8" thick and all wall types are type 1 unless otherwise

    noted.5. All gypsum board edges shall be located on a support.6. All metal stud partition framing shall extend to underside of CLG above, unless

    otherwise noted.7. Extend all partition gypsum board to deflection track as applicable.8. Seal top of smoke and fire-rated partitions as applicable.9. Seal top of sound STC rated partitions.10. Contractor shall be responsible for FRR joints and FRR penetrations.

    A. Delete sound blanket insulation.B. Partial Height Wall.

    PARTITION TYPE MODIFIERS

    4STRUCTURAL GYP BD PARTITION

    UL NO. U-305; 1 HR FRR

    , @ 24" O.C.

    6 3/4"

    61000.J

    5SHAFT WALL

    UL NO. U-469; 1 HR FFR

    , @ 24" O.C.09 22

    16.13.M5

    92900.H

    1" SHAFT WALL LINER

    4 5/8"

    SHAFT SIDE

    92900.H, BOTH SIDES

    FINISH SCHEDULE - APARTMENTS

    ROOM:

    BEDROOM

    BEDROOM CLOSET

    LIVING/DINING

    KITCHEN

    ADA CLOSET

    BATHROOM

    FLOOR:

    Carpet

    Carpet

    LVT

    LVT

    LVT

    Ceramic Tile

    Existing WD base &new to match existing

    WALL BASE & TRIM:

    Ceramic Tile Base

    WALL:

    Patch & paint existingplaster / Paint GWB

    CEILING:

    Paint GWB

    NOTES:

    (1) PAINTED ACCENT WALL IN LIVING AREA / UNIT

    AB

    VA

    RIE

    S

    VARIES

    7' -

    0"

    3' - 0"

    C

    3' - 0"7' -

    0" GL-02

    1' -

    6"

    5"

    5"5"

    3' -

    4"

    2' -

    9"

    6" 3"

    GL-01

    AD

    A

    3' -

    7"

    MA

    X

    ST

    AN

    DA

    RD

    5' -

    0"

    ADDITIONAL DOORVIEWER (AT ADAUNIT ENTRY ONLY)

    6"6"

    1' -

    0"

    6"

    6"

    A

    3 1

    /2"

    3 1/2" 3 1/2"

    B

    2"

    2" 2"

    C

    2"

    1" 1"

    3' - 2"

    TYPICAL ROOM SIGNAGEINSTALLED OUTSIDE OF ROOM S1

    101ROOM NUMBER OR NAME1/32" RAISED ANDCONTRASTING ROMAN TEXT

    1/32" RAISED BRAILE TEXTTO READ THE SAME ASROMAN TEXT ABOVE

    EXIT DISCHARGE SIGNAGEINSTALLED INTERIOR SIDE OF EXIT STAIR DOOR S2

    EXIT1/32" RAISED ANDCONTRASTING ROMAN TEXT

    1/32" RAISED BRAILE TEXTTO READ THE SAME ASROMAN TEXT ABOVE

    EXIT STAIR SIGNAGEINSTALLED OUTSIDE OF STAIR IN CORRIDOR S3

    EXITSTAIR 1

    1/32" RAISED ANDCONTRASTING ROMAN TEXT

    1/32" RAISED BRAILE TEXTTO READ THE SAME ASROMAN TEXT ABOVE

    SIGNAGE NOTES:

    1. SIGNAGE DRAWINGS REPRESENT SIGNAGE TYPESONLY AND ARE DIAGRAMMATIC. ALL SIGNAGE IS TOBE FURNISHED AND INSTALLED BY THE OWNER.

    2. ACCESSIBLE SIGNS SHALL COMPLY WITH MOUNTEDHEIGHT AND LOCATIONS IN ACCORDANCE WITH ANSIA117.1-2009.

    3. SIGNAGE IS TO BE PROVIDED AT ALL LOCATIONSINDICATED ON DOOR SCHEDULE.

    EX

    IST

    ING

    FLO

    OR

    92900.H

    EXISTING SUBFLOOR

    EXISTING 2x10 WOOD JOIST

    61000.I, IF NECESSARY1 H

    R A

    SS

    EM

    BLY

    COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C

    PWWG PROJECT NUMBER

    REVISIONS

    11/1

    8/2

    015 4

    :57:2

    6 P

    M

    618 CLYDE STREET, PITTSBURGH PA

    21521.00

    11/16/2015

    CLYDE APARTMENTS

    CARNEGIE MELLON UNIVERSITY

    SCHEDULE AND TYPES

    A-601

    BID SET

    SCHEDULE - ROOMS/FINISHES - COMMON

    ROOM FLOOR WALL

    WALL FINISH

    CEILING

    NOTESNUMBER ROOM NAME FINISH BASE FINISH

    BASEMENT

    000 CORRIDOR Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    001 ELECTRIC Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    002 NOT USED Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    003 WATER & GAS Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    004 DATA Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    005 MECH STORAGE

    006 GENERAL STORAGE Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    007 BICYCLES Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    008 MECHANICAL Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    009 MECHANICAL Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    010 LAUNDRY Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    011 MAINTENANCE Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.

    STW-0 WEST STAIR Rubber Resilient Base Paint CMU Patch and paint existing plaster ceiling

    FIRST FLOOR

    100 CORRIDOR LVT Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    106 COMMON ROOM LVT Resilient Base Paint existing plaster 5/8'' Type X GWB, paint and APC

    ADA-1 ADA ENTRY LVT Resilient Base 1/8" Plaster veneer onexisting walls / Painted GWB

    (See common room)

    STE-1 EAST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    STW-1 WEST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    SECOND FLOOR

    200 CORRIDOR LVT Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    STE-2 EAST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    STW-2 WEST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    THIRD FLOOR

    300 CORRIDOR LVT Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    STE-3 EAST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling

    STW-3 WEST STAIR Rubber Resilient Base Paint existing plaster 5/8'' Type X GWB, paint

    KEYNOTE LEGEND

    61000.I 2x4

    61000.J 2x6

    92216.J 3 5/8" Steel Stud

    92900.H 5/8" Type X Gypsum Wallboard

    92900.U V Control Joint

    SCHEDULE - DOORS - TYPICAL

    Description Type Mark Count

    DOOR PANEL FRAME

    HARDWARE FIRE RATINGWIDTH HEIGHT MATERIAL TYPE JAMB HEAD MATERIAL

    EAST EGRESS STAIR STE-X.1 3 3' - 0" 7' - 0" SC WD B 7/A-501 8/A-501 WD-PT 03 60 MIN

    WEST EGRESS STAIR STW-X.1 4 3' - 0" 7' - 0" SC WD B 7/A-501 8/A-501 WD-PT 03 60 MIN

    MISC_UTILITY ROOM XXX 3 3' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT see notes below

    EXTERIOR DOOR XXX-1.2 3 3' - 0" 7' - 0" ALUM / GL C 12/A-501 13/A-501 ALUM 04 20 MIN

    TYPICAL ENTRY DOOR XXX.1 18 3' - 0" 7' - 0" SC WD A 7/A-501 8/A-501 WD-PT 06 20 MIN

    TYP APT - BEDROOM XXX.2 32 2' - 6" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 08

    ADA APT - BEDROOM XXX.2ADA 1 3' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 07

    TYP APT - CLOSET XXX.3 6 4' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 09

    ADA APT - CLOSET XXX.3ADA 1 5' - 8" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 09

    ADA APT - BATH XXX.4ADA 1 3' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 10

    1/4" = 1'-0" A-601

    2DOOR TYPES

    1/4" = 1'-0" A-601

    1DOOR FRAMES

    1 1/2" = 1'-0" A-601

    4UL FLOOR CEILING ASSEMBLY; UL Des L501

    NOTES:1. VIF EXISTING OPENINGS AT REPLACEMENT DOOR LOCATIONS2. ALL DOORS AND FRAMES TO BE PAINTED3. MISC UTIL DOOR HARDWARE AS FOLLOWS:

    DOOR 003 (WATER/GAS): 01DOOR 004 (DATA): 11DOOR 005 (MECH STORAGE): 02

    ABBREVIATIONS:SC WD = SOLID CORE WOODHC WD = HOLLOW CORE WOODALUM / GL = ALUMINIM FRAME AND GLASS LITE

    NO. DESCRIPTION DATE

    SheetsG-001 - COVER SHEETG-002 - SYMBOLS & NOTES & CODE PLANSAS-101 - ARCHITECTURAL SITE PLAN AND EXTERIOR IMPROVEMENTSAD-101 - DEMOLITION PLANSA-100 - BASEMENT PLANA-101 - FIRST FLOOR PLANA-102 - SECOND FLOOR PLAN (3RD SIMILAR)AC-100 - BASEMENT REFLECTED CEILING PLANAC-101 - FIRST FLOOR REFLECTED CEILING PLANAC-102 - SECOND FLOOR REFLECTED CEILING PLANA-201 - BUILDING ELEVATIONSA-202 - BUILDING ELEVATIONSA-401 - INTERIOR ELEVATIONS & DETAILSA-501 - DETAILSA-601 - SCHEDULE AND TYPES