clyde street bid set
DESCRIPTION
ÂTRANSCRIPT
-
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:1
5 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
COVER SHEET
G-001
BID SET
DRAWING LIST
GENERAL
G-001 COVER SHEET 11/16/2015
G-002 SYMBOLS & NOTES & CODE PLANS 11/16/2015
CIVIL
T1.1 TITLE SHEET 11/16/2015
GN1.1 GENERAL NOTES 11/16/2015
391-1 ALTA/ACSM TITLE SURVEY 11/16/2015
EX1.1 EXISTING CONDITIONS PLAN 11/16/2015
C2.1 SITE PLAN 11/16/2015
C2.2 SITE DETAILS 11/16/2015
ARCHITECTURAL
AS-101 ARCHITECTURAL SITE PLAN AND EXTERIORIMPROVEMENTS
11/16/2015
AD-101 DEMOLITION PLANS 11/16/2015
A-100 BASEMENT PLAN 11/16/2015
A-101 FIRST FLOOR PLAN 11/16/2015
A-102 SECOND FLOOR PLAN (3RD SIMILAR) 11/16/2015
AC-100 BASEMENT REFLECTED CEILING PLAN 11/16/2015
AC-101 FIRST FLOOR REFLECTED CEILING PLAN 11/16/2015
AC-102 SECOND FLOOR REFLECTED CEILING PLAN 11/16/2015
A-201 BUILDING ELEVATIONS 11/16/2015
A-202 BUILDING ELEVATIONS 11/16/2015
A-401 INTERIOR ELEVATIONS & DETAILS 11/16/2015
A-501 DETAILS 11/16/2015
A-601 SCHEDULE AND TYPES 11/16/2015
FIRE PROTECTION
FP-001 SYMBOLS, NOTES AND ABBREVIATIONS 11/16/2015
FP-100 BASEMENT PLAN 11/16/2015
FP-101 FIRST FLOOR PLAN 11/16/2015
FP-102 SECOND FLOOR PLAN 11/16/2015
FP-103 THIRD FLOOR PLAN 11/16/2015
FP-104 ATTIC PLAN 11/16/2015
PLUMBING
P-001 SYMBOLS, NOTES, ABBREVIATIONS AND SCHEDULES 11/16/2015
PD-101 DEMOLITION PLANS 11/16/2015
P-100 BASEMENT PLAN 11/16/2015
P-101 FIRST FLOOR PLAN 11/16/2015
P-102 SECOND FLOOR PLAN (3RD SIMILAR) 11/16/2015
MECHANCIAL
H-001 SYMBOLS, ABBREVIATIONS, LEGEND AND NOTES 11/16/2015
H-002 DIAGRAMS 11/16/2015
HD-101 DEMOLITION PLANS 11/16/2015
H-100 BASEMENT PLAN 11/16/2015
H-101 FIRST FLOOR PLAN 11/16/2015
H-102 SECOND FLOOR PLAN 11/16/2015
H-201 HEATING WATER RISER DIAGRAM 11/16/2015
ELECTRICAL
E-001 ELECTRICAL SYMBOLS, NOTES AND ABBREVIATIONS 11/16/2015
E-101 ELECTRICAL SITE PLAN 11/16/2015
E-200 BASEMENT PLAN - LIGHTING 11/16/2015
E-201 FIRST FLOOR PLAN - LIGHTING 11/16/2015
E-202 SECOND FLOOR PLAN - LIGHTING 11/16/2015
E-203 THIRD FLOOR PLAN - LIGHTING 11/16/2015
E-300 BASEMENT PLAN - POWER AND SYSTEMS 11/16/2015
E-301 FIRST FLOOR PLAN - POWER AND SYSTEMS 11/16/2015
E-302 SECOND FLOOR PLAN - POWER AND SYSTEMS 11/16/2015
E-303 THIRD FLOOR PLAN - POWER AND SYSTEMS 11/16/2015
E-600 ELECTRICAL RISER DIAGRAM 11/16/2015
E-601 RISER DIAGRAMS 11/16/2015
E-700 PANEL SCHEDULES 11/16/2015
E-701 PANEL SCHEDULES 11/16/2015
E-702 PANEL SCHEDULES 11/16/2015
Grand total: 54
CARNEGIE MELLON UNIVERSITY
CLYDE APARTMENTSBID SET - NOVEMBER 16, 2015
ARCHITECT
PERFIDO WEISKOPF WAGSTAFF + GOETTEL408 BOULEVARD OF THE ALLIESPITTSBURGH, PA 15219412 391 2884CONTACT: KEVIN WAGSTAFF, AIA
CLIENT
CARNEGIE MELLON UNIVERSITY5000 FORBES AVENUEPITTSBURGH PA, 15213412 268 2000CONTACT: UTKARSH GHILDYAL
STRUCTURAL ENGINEER
SCHNEIDER ENGINEERING, LLC
1196 BILLINGS DRIVEPITTSBURGH, PA 15241412 736 1298CONTACT: JOHN SCHNEIDER
MEPFP ENGINEER
CJL ENGINEERING
1555 CORAOPOLIS HEIHGTS ROAD, SUITE 4200MOON TOWNSHIP, PA 15108412 262 1220CONTACT: CHRIS CONROY
NO. DESCRIPTION DATE
-
RE
F
RE
F
RE
F
RE
F
UP
RE
F
RE
F
RE
F
RE
F
RE
FR
EF
UP
RE
F
ABBREVIATIONS
ACCACWADADAADJAFFALUMALTANODANSIAPCAPPROXAPTASFBDBHBLWBODBRBRGBRNZBTC TO CCAB CFSCIPCJ CLCLGCLOCMUCOCOLCONCCONTCORRCPTCSKCTCTRCU FTCU YDCWDBLDEMODEPTDHDIADIAGDIMDLDNEEAEFSEIFSEJEMEPSEQEOSESETREXISTFARFAYFBGFCFDFEFF ELFINFIN GRFLRFNDFRMGFRPFRRFSFTFTGFXGA GALVGCGRGYPGYP BDHCHDWDHPHTHOPIDINCLINSULKITLAULAVLFLINLLLLHLLVLSFMASMATLMAXMBRMDFMECHMEZZ MFRMOMSAMSNNNANICNRCNTSOAOCOPNGOSBPCCPLAMPLASTPOLYPTPTLPVCRRBRCPRDREFREQ'DREQ'SRMRORWCSSAMSCSCTSFSFRMSHSIMSPECSPFSQSSSSTSTOSTCSTLSTRUCTSYPTT/TCT>RNSPTRPLTSTYPUFASUNOUSAVARVBVATVIFVCTWw/WDw/OWHWWFXPS
AccessibleAluminum Clad WoodArea DrainAmericans with Disabilities ActAdjacentAbove Finished FloorAluminumAlternateAnodizeAmerican National Standards InstituteAcoustic Panel CeilingApproximateApartmentAbove Sub-FloorBoardBulkheadBelowBasis of DesignBedroomBearingBronzeBank TowerCenter to CenterCabinetClear Floor SpaceCast-in-PaceControl JointCenter LineCeilingClosetConcrete Masonry UnitClean-outColumnConcreteContinuousCorridorCarpetCountersunkCeramic TileCenterCubic FeetCubic YardCurtainwallDoubleDemolitionDepartmentDouble-Hung (Window)DiameterDiagonalDimensionDead LoadDownEastEachExterior Finish SystemExterior Insulation and Finish SystemExpansion JointEntrance MatExpanded Polystyrene Board (Insulation)EqualEdge of Structure/SlabEach SideExisting to RemainExistingFloor Area RatioFayette BuildingFiberglassFire CoreFloor DrainFire ExtinguisherFinished Floor ElevationFinishFinished GradeFloorFoundation DrainFramingFiber Reinforced PlasticFire Resistance RatingFlat SeamFoot, FeetFootingFixed (Window)GageGalvanizedGeneral ContractorGuest RoomGypsumGypsum BoardHollow CoreHardwoodHigh PointHeightHopper (Window)Inside DiameterInclude(s)(ing)InsulationKitchenLaundryLavatoryLinear FeetLinoleumLive LoadLong Leg HorizontalLong Leg VerticalLight Gauge Steel FramingMasonyMaterialMaximumMaster BedroomMedium Density FiberboardMechanicalMezzanineManufacturerMasonry OpeningMain Street AnnexMasoniteNorthNot ApplicableNot in ContractNoise Reduction CoefficientNot to ScaleOverallOn CenterOpeningOriented Strand BoardPrecast ConcretePlastic LaminatePlasterPolyethylene (Plast Sheet)Paint(ed)Pressure Treated LumberPolyvinyl ChlorideRadius, Riser, Thermal Resistance ValueRubber BaseReflected Ceiling PlanRoof DrainRefrigeratorRequiredRequirementsRoomRough OpeningRainwater ConductorSouthSelf-Adhered MembraneSolid CoreStructural Clay TileSquare FeetSpray-Applied Fire-Resistive MaterialsSingle HungSimilarSpecificationSpruce-Pine-FirSquareSimulated StoneStainless SteelStorageSound Transmission ClassSteelStructureSouthern Yellow PineTreadTop Of ___Traffic CoatingTongue and GrooveTransparentTripleTube SteelTypicalUniform Federal Accessibility StandardsUnless Noted OtherwiseUpper Street AnnexVariesVinyl Wall BaseVinyl Asbestos TileVerify in FieldVinyl Composition TileWestWithWoodWithoutWater HeaterWelded Wire FabricExtruded Polystyrene Board (Insulation)
CODE SUMMARY
BUILDING CODE SUMMARY:
APPLICABLE CODES: INTERNATIONAL EXISTING BUILDING CODE, 2009 (IEBC)(WITH PITTSBURGH INTERNATIONAL BUILDING CODE, 2009 AMENDMENTS) INTERNATIONAL ENERGY CONSERVATION CODE, 2009
INTERNATIONAL MECHANICAL CODE, 2009INTERNATIONAL FUEL GAS CODE, 2009NATIONAL ELECTRIC CODE, 2005ALLEGHENY COUNTY PLUMBING CODE
INTERNATIONAL EXISTING BUILDING CODE 2009 SUMMARY
CHAPTER 1 SCOPE AND ADMINISTRATION
101.4 GENERAL APPLICABILITY:
THIS CODE SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,ADDITION AND RELOCATION OF EXISTING BUILDINGS.
101.5.2 COMPLIANCE METHOD:
WORK AREA COMPLIANCE METHOD.
WORK IN COMPLIANCE WITH CHAPTERS 4 THROUGH 12 SHALL BE CONSIDERED INCOMPLIANCE WITH THE PROVISIONS OF THIS CODE.
CHAPTERS 9-CHANGE OF OCCUPANCY, 10-ADDITIONS, 11-HISTORIC BUILDINGS, AND12-RELOCATED BUILDINGS ARE NOT APPLICABLE TO THIS PROJECT.
CHAPTER 4 CLASSIFICATION OF WORK
405.1 ALTERATION LEVEL 3
WORK AREA EXCEEDS 50% OF THE BUILDING AREA.
CHAPTER 6 ALTERATIONS LEVEL 1
603.1 FIRE PROTECTION:
ALTERATIONS SHALL BE DONE IN A MANNER THAT MAINTAINS THE LEVEL OF FIREPROTECTION PROVIDED.
EXISTING BUILDING ELEMENTS ARE NOT REQUIRED TO MEET CURRENT IBC FIRERATING REQUIREMENTS. THIS INCLUDES THE EXISTING FLOOR/CEILING ASSEMBLIES,THE EXISTING EXIT STAIRS AND DOORS, EXISTING CORRIDOR WALLS AND DOORS, ANDEXISTING UNIT SEPARATION WALLS.
605.1 ACCESSIBILITY:
ACCESSIBLE MEANS OF EGRESS ARE NOT REQUIRED IN EXISTING BUILDINGS.
TYPE B DWELLING UNITS ARE NOT REQUIRED IN EXISTING BUILDINGS.
TYPE A DWELLING UNIT REQUIREMENTS APPLY ONLY TO THE QUANTITY OF UNITSBEING ADDED. UNDER IBC, TYPE A UNITS ARE NOT REQUIRED FOR A QUANTITY OF 20UNITS AND UNDER.
CHAPTER 7 ALTERATIONS LEVEL 2
GENERAL:
701.3 COMPLIANCE
ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND SPACES SHALLCOMPLY WITH THE REQUIREMENTS OF IBC.
BUILDING ELEMENTS AND MATERIALS:
703.2.1 EXISTING VERTICAL OPENINGS:
EXCEPTION 11.2: EXISTING VERTICAL OPENINGS ARE NOT REQUIRED TO HAVE A FIRERATING PROVIDED THE BUILDING IS PROTECTED THROUGHOUT BY AN APPROVEDAUTOMATIC SPRINKLER SYSTEM.
703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE REQUIREMENTS:
EGRESS STAIRWAYS SHALL, AT A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHTCONSTRUCTION.
PROJECT SUMMARY
EXISTING BUILDING DATA
1940s BUILDING WITH SUBSEQUENT INTERIOR RENOVATIONSMASONRY BEARING WALLS WITH INTERIOR WOOD FLOOR AND ROOF STRUCTURE
IEBC ALTERATION LEVEL
LEVEL 3 ALTERATIONSWORK AREA EXCEEDING 50% OF BUILDING AREA
OCCUPANCY EXISTING TO REMAINR-2, MULTI-UNIT RESIDENTIAL, APARTMENT HOUSES-1, STORAGE (BASEMENT)
BUILDING AREA EXISTING TO REMAIN3 STORIES + BASEMENT @ 4,287 SF/FLOOR = 17,148 SF TOTAL
BUILDING HEIGHT EXISTING TO REMAIN3 STORIES
GRADE PLANE IS AVG 4.5' BELOW FLOOR 01GRADE PLANE TO TOP OF ROOF: 34.5'
PARKING SPACES EXISTING TO REMAIN15 SPACES (INCLUDING 1 HC VAN SPACE)
ZONING SUMMARY EXISTING TO REMAINDISTRICT : RM-H: MULTI-UNIT RESIDENTIAL - HIGH DENSITYPARCEL ID: 52-E-243LOT AREA: 17,669 SF
CONSTRUCTION TYPE EXISTING TO REMAINTYPE III-B; UN-PROTECTED COMBUSTIBLE
OCCUPANT LOADS EXISTING TO REMAINRESIDENTIAL: 200 GROSSSTORAGE: 300 GROSS
BASEMENT: 3,858 SF / 300 = 13FIRST FL: 4,287 / 200 = 22SECOND FL: 4,287 / 200 = 22THIRD FL: 4,287 / 200 = 22
TOTAL 79 OCCUPANTS (EXISTING TO REMAIN)
IECC CLIMATE ZONE
ALLEGHENY COUNTY, PA: CLIMATE ZONE 4-5 MARINE
703.4 INTERIOR FINISH:
NEW INTERIOR FINISHES SHALL COMPLY WITH IBC.
FIRE PROTECTION:
704.2.2 AUTOMATIC SPRINKLER PROTECTION:
REQUIRED FOR R-2 OCCUPANCY WHEN WORK AREA EXCEEDS 50% OF THE FLOORAREA.
704.4.1.6 FIRE ALARM SYSTEM:
A FIRE ALARM SYSTEM IS REQUIRED AS REQUIRED BY THE INTERNATIONAL FIRECODE FOR EXISTING R-2 OCCUPANCIES.
705 MEANS OF EGRESS:
704.4.3 SMOKE ALARMS:
INDIVIDUAL DWELLING UNITS REQUIRE SMOKE ALARMS IN ACCORDANCE WITH THEINTERNATIONAL FIRE CODE.
705.3.1 MINIMUM NUMBER OF EXITS:
THE MINIMUM NUMBER OF EXITS BASED ON THE OCCUPANCY AND THE OCCUPANTLOAD IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE.
705.4.2 DOOR SWINGS:
EGRESS DOORS SERVING AN OCCUPANT LOAD GREATER THAN 50 SHALL SWING INTHE DIRECTION OF TRAVEL.
705.5.1 CORRIDOR DOORS:
EXCEPTION 3: NEW CORRIDOR DOORS SHALL HAVE A 20 MINUTE FIRE RATING.
705.9 HANDRAILS:
A HANDRAIL IS REQUIRED ON AT LEAST ONE SIDE OF STAIRS. EXISTING HANDRAILSDO NOT HAVE TO MEET IBC PROVIDED THEY ARE NOT IN "DANGER OF COLLAPSING."NEW HANDRAILS SHALL COMPLY WITH IBC.
707 STRUCTURAL:
707.2 NEW STRUCTURAL MEMBERS:
NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING CONNECTIONS ANDANCHORAGE, SHALL COMPLY WITH IBC.
708 ELECTRICAL:
708.1 NEW INSTALLATIONS:
ALL NEWLY INSTALLED EQUIPMENTS AND WIRING RELATED TO WORK BEING DONE INTHE WORK AREA SHALL COMPLY WITH THE MATERIALS AND METHODSREQUIREMENTS OF CHAPTER 5.
709 MECHANICAL:
709.1 RECONFIGURED OR CONVERTED SPACES. ALL RECONFIGURED SPACESINTENDED FOR OCCUPANCY AND ALL SPACES CONVERTED TO HABITABLE OROCCUPIABLE SPACE IN ANY WORK AREA SHALL BE PROVIDED WITH NATURAL ORMECHANICAL VENTILATION IN ACCORDANCE WITH THE INTERNATIONAL MECHANICALCODE.
710 PLUMBING:
710.1 MINIMUM FIXTURES:
INCREASED FIXTURE COUNTS ARE NOT REQUIRED WHERE THE OCCUPANT LOAD ISNOT INCREASED BY MORE THAN 20%.
CHAPTER 8 ALTERATIONS LEVEL 3
805.2 MEANS OF EGRESS LIGHTING:
SHALL COMPLY WITH CURRENT IBC.
805.3 EXIT SIGNS:
SHALL COMPLY WITH CURRENT IBC.
808.1 MINIMUM ENERGY REQUIREMENTS:
LEVEL 3 ALTERATIONS TO EXISTING BUILDINGS OR STRUCTURES ARE PERMITTEDWITHOUT REQUIRING THE ENTIRE BUILDING OR STRUCTURE TO COMPLY WITH THEENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATIONCODE OR INTERNATIONAL RESIDENTIAL CODE. THE ALTERATIONS SHALL CONFORMTO THE ENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATIONCODE ORINTERNATIONAL RESIDENTIAL CODE AS THEY RELATE TO NEWCONSTRUCTION ONLY
INTERNATIONAL BUILDING CODE 2009 SUMMARY
CHAPTER 3 USE AND OCCUPANCY
EXISTING USE: R-2, S-1PROPOSED USE: NO CHANGE
CHAPTER 5 GENERAL HEIGHT AND AREA LIMITATIONS
CHAPTER 6 TYPE OF CONSTRUCTION
EXISTING TYPE: IIIB EXISTING TO REMAIN
FIRE RESISANCE RATING REQUIREMENTS:PRIMARY STRUCTURAL FRAME: 0 HR (EXISTING TO REMAIN)BEARING EXT WALLS: 2 HR (EXISTING TO REMAIN)BEARING INT WALLS: 0 HR (EXISTING TO REMAIN)NON-BEARING WALLS: 0 HRFLOOR CONSTRUCTION: 0 HR (EXISTING TO REMAIN & LIMITED WORK)ROOF CONSTRUCTION: 0 HR (EXISTING TO REMAIN)
CHAPTER 7 - FIRE AND SMOKE PROTECTION
NO PROPOSED FIRE PARTITIONS.
CHAPTER 10 MEANS OF EGRESS
1005.1 EGRESS WIDTH:
.3 FOR STAIRWAYS
.2 FOR OTHER COMPONENTS
1006.1 ILLUMINATION:
THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATEDAT ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF EGRESS ISOCCUPIED.
1009.1 STAIRWAY WIDTH:
EXCEPTION 1: STAIRS SERVING LESS THAN 50 OCCUPANTS SHALL BE 36" MIN
1011.1 EXIT SIGNS:
ACCESS TO EXITS SHALL BE MARKED BY READILY VISIBLE EXIT SIGNS IN CASESWHERE THE EXIT OR PATH OF EGRESS TRAVEL IS NOT IMMEDIATELY VISIBLE TOOCCUPANTS.
UNIT TABULATION:
THIRD FLOOR 6 2-BEDROOM UNITS
SECOND FLOOR 6 2-BEDROOM UNITS
FIRST FLOOR 4 2-BEDROOM UNITS1 1-BEDROOM ADA UNIT
TOTAL UNITS 17
TOTAL BEDS 34
PROJECT LINE SYMBOLS LEGEND
Existing Items to Remain.
New Construction
Hidden or Overhead Items
Existing Items to be Removed
Center Lines / Column Line
Limit of Work
PROJECT MATERIALS LEGEND
Undisturbed Earth
Compacted Fill
Topsoil
Gravel
Concrete
Sand, Grout,Parging, Stucco
Concrete Masonry(or EXIST Generic MAS / SCT)
Brick
GYP / Stud Wall(or Generic Existing Wall)
Existing Partitionto be Removed
Metal
Wood
Existing MASto be Removed
EXISTNEW
SECTION HATCH
EXISTNEW
SURFACE HATCH
Stone Cladding
Existing FLR / Areato be Removed.
Note: See Sheet Legends for sheet-specific line types not represented below.
Note: See Sheet Legends for sheet-specific material / hatch patterns not represented below.
10001.A
SYMBOLS
INTERIOR / EXTERIOR ELEVATION
BUILDING / WALL SECTION
DETAIL
DETAIL / ENLARGED PLAN
COLUMN LINE
FLOOR ELEVATION LINE
SPOT ELEVATION
WALL TYPE TAG
ROOM NAME AND NUMBER
DOOR TAG
KEYNOTE
SHEET KEYNOTE
SHEET FIXTURE NOTE
DRAWING REFERENCE
NEW DOOR
A-101
11
11 11
11
1
101
ROOM NAME
101
2A
1
1
/1 A101
100'-0"
A101
1SIM
183 SF
WATER & GAS
302 SF
ELECTRIC
522 SF
LAUNDRY
522 SF
GENERAL STORAGE
302 SF
MECHANICAL
425 SF
BICYCLES
123 SF
NOT USED
64 SF
DATA
210 SF
MECHANICAL
210 SF
MAINTENANCE
*EXISTING TO REMAINSTAIR WIDTH: 36"STAIR CAPACITY: 120
DOOR WIDTH: 36''DOOR CAPACITY: 160
BASEMENTOCCUPANTS: EXISTING TO REMAIN
WEST STAIR
215 SF
MECH STORAGE
520 SF
APARTMENT B
517 SF
APARTMENT A
511 SF
APARTMENT C - ADA
BEDROOM100 SF
BEDROOM137 SF
BEDROOM104 SF
BEDROOM104 SF
ADA DOUBLEBEDROOM
198 SF
414 SF
COMMON ROOM
517 SF
APARTMENT A
520 SF
APARTMENT B
347 SF
CORRIDORWEST STAIR
EAST STAIR
*EXISTING TO REMAINSTAIR WIDTH: 36"STAIR CAPACITY: 120
DOOR WIDTH: 36''DOOR CAPACITY: 160
* EXISTING TO REMAINSTAIR WIDTH: 38"+
STAIR CAPACITY: 126
DOOR WIDTH: 36''DOOR CAPACITY: 160
EAST EXIT STAIRDISCARGES DIRECTLYTO EXTERIOR AT GRADE
WEST EXIT STAIRDISCARGES DIRECTLYTO EXTERIOR AT GRADE
17 OCC
FLOOR 01OCCUPANTS: EXISING TO REMAIN
517 SF
APARTMENT A
517 SF
APARTMENT A
520 SF
APARTMENT B
520 SF
APARTMENT B516 SF
APARTMENT A
517 SF
APARTMENT A
NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.
*EXISTING TO REMAINSTAIR WIDTH: 36"STAIR CAPACITY: 120
DOOR WIDTH: 36''DOOR CAPACITY: 160
* EXISTING TO REMAINSTAIR WIDTH: 38"+
STAIR CAPACITY: 126
DOOR WIDTH: 36''DOOR CAPACITY: 160
FLOOR 02 & 03OCCUPANTS: EXISING TO REMAIN
WEST STAIR
EAST STAIR
GENERAL CODE PLAN NOTES
1. Fire Ratings are code minimum requirements forfire barriers & partitions. Penetrations throughrated construction and fire-rated joint systemsshall match or exceed these ratings.
2. See A-601 for wall types and assemblies.Specified partition types may exceed codeminimum ratings.
CODE PLAN LEGEND
30-MIN Rated Wallfor any new work
60-MIN Rated Wallfor any new work
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:1
8 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
SYMBOLS & NOTES &CODE PLANS
G-002
BID SET
KEYNOTE LEGEND - MASTER
92700.A Glass-Fiber-Reinforced PlasterFabrication
92900.G 5/8" Gypsum Wallboard
92900.H 5/8" Type X Gypsum Wallboard
92900.U V Control Joint
93010.A Ceramic Tile
93100.B Metal Edge Strip
95100.C APC-2
95300.B Tee
95300.F Suspension Wire
96516.D Rubber Sheet Floor Covering
96519.D Vinyl Composition Floor Tile
96800.A Carpet
102600.C Corner Guard
102800.S 24" Towel Bar
113100.E Range Hood
113100.F Refrigerator/Freezer
123200.A Manufactured Wood Casework
123600.C Plastic-Laminate Countertop
KEYNOTE LEGEND - MASTER
33000.A Cast-in-Place Concrete Footing
51200.E Structural Steel Channel
61000.A Blocking
61000.C Furring
61000.I 2x4
61000.J 2x6
61000.L 2x10
61600.G 3/4" Plywood Sub-Flooring
62023 Interior Finish Carpentry (basicpremanufactured trim
62023.A Wood Base
64300.D Wood Railing
64600.E Wood Casing
72500.E High Temperature Self-Adhering SheetUnderlayment
74600.C Fiber-Cement Soffit
81400.A Wood Door Frame
81400.B Flush Wood Door
92216.J 3 5/8" Steel Stud
92613.B 1/8" Veneer Plaster
3/32" = 1'-0" G-002
4BASEMENT CODE PLAN
3/32" = 1'-0" G-002
5FIRST FLOOR CODE PLAN
3/32" = 1'-0" G-002
6SECOND FLOOR CODE PLAN
NO. DESCRIPTION DATE
-
618 CLYDE STREETEXISTING 3 STORY PLUS BASEMENT APARMENT BUILDING
CLYDE HOUSE
CLY
DE
ST
RE
ET
50' R
OW
EXISTING ASPHALT DRIVEWAY
EXISTINGENTRYPORCH
AIR CONDENSER;SEE MECH
02
03
09
05
08
10
10
01
11
04
906.06'
PROPOSED CONCRETE SIDEWALK;SEE CIVIL. SLOPE NOT TO EXCEED 1:20
01
06
01
05
12
10
06
GENERAL FLOOR PLAN NOTES
A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &
coordination purposes.C. All windows, except at bathrooms, of apartments and
commom room to have window treatments (seespec).
08
09
10
10
04
11
02
05
0505 12
12
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:1
5 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
ARCHITECTURAL SITEPLAN AND EXTERIORIMPROVEMENTS
AS-101
BID SET
3/32" = 1'-0" AS-101
1ARCHITECTURAL SITE PLAN
NN
TRUEPLAN
NTS AS-101
5BASEMENT LEVEL OPNG TYPE B
SHEET KEYNOTES - SITE IMPROVEMENTS
01 EXISTING LAWN TO REMAIN; FILL ANDSEED DISTURBED AREAS
02 REPAIR EXISTING CONDUCTOR HEAD
03 DEMO EXISTING ROOF TO STRUCTURE;REPAIR ANY DAMAGED STRUCTURALWOOD; NEW ROOF TO BE EPDM &PROVIDE NEW SCUPPER TO EXISTINGCONDUCTOR HEAD. RE-FINISH SOFFITAND ADD EXTERIOR LIGHT; SEE AC-101
04 REMOVE IVY AND CABLES FROM SOUTHELEVATION. INSPECT AND REPAIR BRICKAND MORTAR AS NEEDED.
05 REMOVE ALL EXISTING EQUIP, CABLES,CONDUIT AND RECEPTACLES
06 PROVIDE FREEZE PROOF HOSE BIB
08 REPAIR OPENING IN MAS WALL
09 REPLACE BROKEN GLASS BLOCK
10 REMOVE VENT(S); INFILL WITH GLASSBLOCK
11 REMOVE EXISTING BIKE RACKS
12 REPLACE GUTTER AT WEST STAIREXTERIOR DOOR AND RELOCATEDOWNSPOUT. RE-FINISH SOFFIT AND ADDEXTERIOR LIGHT; SEE AC-101
NTS AS-101
6BASEMENT LEVEL OPNG TYPE C
NTS AS-101
7BASEMENT LEVEL OPNG TYPE D
NTS AS-101
4BASEMENT LEVEL OPNG TYPE A
NTS AS-101
9IVY ON SOUTH ELEVATION
NTS AS-101
8BIKE RACKS
NTS AS-101
3FRONT PORCH CONDUCTOR
NTS AS-101
2EXTERIOR CABLES
NTS AS-101
12EAST/FRONT ENTRY
NTS AS-101
11WEST/BACK ENTRY
NTS AS-101
10WEST STAIR PORCH ROOF
NO. DESCRIPTION DATE
-
RE
F
RE
F
RE
F
RE
F
RE
F
RE
F
RE
F
RE
F
RE
F
RE
F
RE
F
2A
3
E2
2B
E1
E3
2B
5
6
1' -
10"
5' -
9 3
/8"
6' - 6" 5' - 6 1/8"
7
TYP
TYP
UP
DN UP
DN
8
8
11 TYP
E4 TYP
12
TYP
TYPTYP
TYP
1
2A
NOTES:1. REMOVE ALL CEILING MATERIAL TO THE STRUCTURE
1
7' - 9 3/8" 5' - 6 1/8"
TY
P
2' -
0"
1' -
10"
7' -
0 3
/4"4
2B
NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.2. REFER TO FIRST FLOOR PLAN FOR TYPICAL NOTES.
UP
DNUP
DN
8
9
10
AT 2ND FL ONLY
2B2B
GENERAL DEMOLITION NOTES
1. See details on A-401 for ADD'L info regardingdemo of structural elements.
2. GC to inspect all existing refridgerators. Salvageappx. 50%; clean and re-use.
3. GC to inspect all existing kitchen cabinets.Salvage appx. 70%; clean and re-use.
4. Remove all floor finishes throughout building.5. Remove all ACT ceiling finish throughout all
units.(Units that do not need ceiling demo arenoted on the plans. See notes below)
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:1
4 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
DEMOLITION PLANS
AD-101
BID SET
1/8" = 1'-0" AD-101
2FIRST FLOOR DEMOLITION PLAN
NN
TRUEPLAN
1/8" = 1'-0" AD-101
1BASEMENT DEMOLITION PLAN
1/8" = 1'-0" AD-101
3SECOND FLOOR DEMOLITION PLAN
SHEET KEYNOTES - DEMO
EXISTING MATERIALS
E1 Aluminum double-hung window ETR.Contractor shall inspect each window andrepair all damaged sash and/or hardware.
E2 Stair and guardrailing ETR.
E3 Concrete stair and gaurdrailing ETR.
E4 Stainless steel sink basin ETR; clean andre-use.
DEMOLITION NOTES
1 Remove existing utlilty sinks and laundryequipment. See plumbing DWG's.
2A Remove window and MAS below to grade;salvage brick for infill. See west demoelevation.
2B Remove existing glass block window
3 Remove first floor in this area for wheelchairlift; see structural details on A-401
4 Demo existing basement slab in this area
5 Remove EXIST stud closet walls, TYP.
6 Remove EXIST unit entry door and frame,TYP.
7 Remove wood stud partitions. Undamagedlumber may be salvaged and reused
8 No ceiling finish removal is needed in this unit.
9 Remove ACT ceiling finish in this room only.
10 Remove ACT ceiling finish at 3rd floor ceilingof west stair.
11 Remove EXIST unit range and countertop.
12 Remove EXIST bathroom fixtures. See plumb
NO. DESCRIPTION DATE
-
183 SF
WATER & GAS
003
302 SF
ELECTRIC
001
522 SF
LAUNDRY
010
522 SF
GENERAL STORAGE
006
302 SF
MECHANICAL
008
425 SF
BICYCLES
007
123 SF
NOT USED
002
64 SF
DATA
004
210 SF
MECHANICAL
009
210 SF
MAINTENANCE
011
UTILITY SINK, SEE PLUMBING
STACKED WASHER/DRYER UNITS. PROVIDED BY OWNER
33000.A
340 SF
CORRIDOR
000
105 SF
WEST STAIR
STW-0
005
STW-0.1
4
4
1A
4
7' - 0 3/4" 5' - 6 1/8"
2' -
4 3
/4"
ALIG
N
AIR CONDENSER;SEE MECH
UP
REINF. w/ 3 #5 CONT. BTM. x1'-6'' LONG TRANSVERSE
BARS @ 24'' O.C.
12
A-401
4
1' -
1 1
/4"
4' -
8 1
/8"
UTILITY SINK,SEE PLUMBING
17A-401
215 SF
MECH STORAGE
005004
003
1A
1A
8' -
0"
14A-401
8' - 0"
1A
1A
1"
2
BRICK-INFILL ;SEE A-201
BIKE STORAGE; PROVIDED BY OWNER
6' - 0"
FIRE EXTINGUISHER, ETR
GENERAL FLOOR PLAN NOTES
A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &
coordination purposes.C. All windows, except at bathrooms, of apartments and
commom room to have window treatments (seespec).
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:12:5
4 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
BASEMENT PLAN
A-100
BID SET
1/4" = 1'-0" A-100
1BASEMENT PLAN
NN
TRUEPLAN
KEYNOTE LEGEND
33000.A Cast-in-Place Concrete Footing
NO. DESCRIPTION DATE
-
RE
F
RE
F
RE
F
RE
F
RE
F
WHEELCHAIRLIFT
BATH
ENTRY
CLOSET
KITCHEN
CLOSET
LIVING/DINING
520 SF
APARTMENT B
104
CLOSET
BATH
ENTRY
KITCHEN
LIVINGALCOVE
517 SF
APARTMENT A
102
DINING
ADA BATH
AD
A K
ITC
HE
N
511 SF
APARTMENT C - ADA
105
BEDROOM100 SF
BEDROOM137 SF
BEDROOM104 SF
BEDROOM104 SF
ADA DOUBLEBEDROOM
198 SF
LIVING/DINING
414 SF
COMMON ROOM
106
517 SF
APARTMENT A
101
520 SF
APARTMENT B
103
347 SF
CORRIDOR
100
WEST STAIR
STW-1
EAST STAIR
STE-1 ENTRY PORCH
101.1
101.2b
101.2a
STE-1.1 ST
E-1
.2
104.1
102.2a
102.2b
103.2a103.3
104.3
104.2a
105.1
105.3ADA
105.2
AD
A
106.1
105.4
AD
A
STW-1.1
102.1
6' - 3"
6' - 3"
3' - 6"
2' -
5"
2' -
5"
3A
2
1A1A
103.1
A-4019
A-401
19
13
A-4011
A-4012
8
1A
6' - 6'' MIN
ALIG
N
1A1A
ALIGN
ALIGN
1A
68 SF
ADA ENTRY
ADA-1
UP
DNUP
DN
AD
A-1
.2
ST
W-1
.2
6
5
REMOVE EXISTING SURFACEMOUNTED MAILBOXES; INFILLEXISTING HOLES IN THE WALL;SEE PHOTO ABOVE
EQ
EQ
EQ
EQ
2
60" MIN
5' - 3"
2'' TYP
4
A-401
1' - 0"1' - 0"
2'' TYP
2'' TYP
2'' TYP
A-501
16
VERIFY DIM IN FIELDWITH LOCATION OFEXISTING STACK ANDRADIATOR LINES
A-50124TYP
19
A-501
17A-401
103.2b
104.2b
14A-401
FIRE DEPARTMENT HOOK-UP;SEE FP DWGS
3
906.08'
906.06'
(+1/4" FROMEXTERIORELEVATION)
3' - 4 1/2"
4AB4AB
4AB
3' -
1 5
/8"
2 2
2 2
2
TYP
A-501 24TYP
INSTALL BULLETIN BOARDON THIS SIDE ONLY
2
7"
A-101
2Sim
NOTE: ACCESSIBLE UNITS ARENOT REQUIRED BY CODE. SEECODE SUMMARY ON G-002
16
555
2
2
2
2
WIRE SHELF AND ROD@ ALL CLOSETS, TYP
VIF
3' -
7 1
/4"
PLATFORM
2' -
7 1
3/1
6"
1AB
ALIGN
102600.C
,TYPTYP @ OUTSIDECORNERS IN CORRIDOR
FIRE EXTINGUISHER, ETR
GENERAL FLOOR PLAN NOTES
A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &
coordination purposes.C. All windows, except at bathrooms, of apartments and
commom room to have window treatments (seespec).
414 SF
COMMON ROOM
106
EXIST FLR JOISTS TO REMAIN
EXIST FLR JOISTS TO BE CUT
2X10 JOISTS @ 16'' O.C. w/3/4'' PLYWOOD FLR DECKING
COORDINATE IN FIELD
COORDINATE IN FIELD
15
A-401
11
A-401
REMOVE MAILBOX FRAMES ANDPATCH PLASTER WALL
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:12:5
6 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
FIRST FLOOR PLAN
A-101
BID SET
NN
TRUEPLAN
1/4" = 1'-0" A-101
1FIRST FLOOR PLAN
1/2" = 1'-0" A-101
2FIRST FLOOR ADA LIFT FRAMING PLAN
KEYNOTE LEGEND
102600.C
Corner Guard
NTS A-101
3MAILBOX WALL REPAIR-1
NO. DESCRIPTION DATE
-
RE
F
RE
F
RE
F
RE
FR
EF
RE
F
517 SF
APARTMENT A
201
517 SF
APARTMENT A
202
520 SF
APARTMENT B
204
520 SF
APARTMENT B
203
516 SF
APARTMENT A
205
517 SF
APARTMENT A
206
NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.2. REFER TO FIRST FLOOR PLAN FOR TYPICAL NOTES.
EAST STAIR
STE-2
347 SF
CORRIDOR
200WEST STAIR
STW-2
STE-2.1
201.2b
201.2a
202.2a
202.2b
203.1
203.2a
203.3
204.1
205.2b
205.2a
STW-2.1
206.2a
206.2b
202.1
201.1205.1
206.1
6' - 3"
2' -
5"
A-4012
3' - 8 3/4"
1A1A
ALIGN
5
UP
DN UP
6
EQ
EQ
EQ
EQ
EQ
EQ
EQ
EQ
DN
2'' TYP
2'' TYP
2'' TYP
2'' TYP
2'' TYP
17A-401
204.3204.2a
204.2b
203.2b
14A-401
NEW ROOFING; SEE NOTES ON AS101
REPAIR EXISTING CONDUCTOR HEAD;SEE NOTES ON AS101
REPLACE GUTTER ANDDOWNSPOUT ON
EXISTING CANOPY;SEE NOTES ON AS101
NEW SCUPPER; SEE NOTES ON AS101
5
2
2
2
2
2
6' - 3"
2' -
5"1A1A
ALIGN
2'' TYP 2
2
2 2
2
2
2
102600.CTYP @ OUTSIDECORNERS IN CORRIDOR
FIRE EXTINGUISHER, ETR
GENERAL FLOOR PLAN NOTES
A. All wall types are type 1 unless noted otherwise.B. Furniture is not in contract; shown for test fit &
coordination purposes.C. All windows, except at bathrooms, of apartments and
commom room to have window treatments (seespec).
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:12:5
8 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
SECOND FLOOR PLAN(3RD SIMILAR)
A-102
BID SET
NN
TRUEPLAN
1/4" = 1'-0" A-102
1SECOND FLOOR PLAN
NO. DESCRIPTION DATE
-
302 SF
ELECTRIC
001
210 SF
MAINTENANCE
011
522 SF
LAUNDRY
010
210 SF
MECHANICAL
009
302 SF
MECHANICAL
008
425 SF
BICYCLES
007
522 SF
GENERAL STORAGE
006
64 SF
DATA
004
183 SF
WATER & GAS
003
105 SF
WEST STAIR
STW-0
340 SF
CORRIDOR
000123 SF
NOT USED
002
7' - 1 3/4" , TYP THIS LEVEL
OPEN TO ABOVE
4' - 0" 9' - 0" 9' - 0" 9' - 0"
GENERAL NOTES:1. COORDINATE PLACEMENT OF LIGHT FIXTURES WITH EXISTING CONDITIONS; PIPING, ETC
215 SF
MECH STORAGE
005
COORDINATE FURNACE DUCT WORKWITH EXISTING AND NEW PIPING
4
A-601
TYP AT THIS LEVEL
GENERAL CLG PLAN NOTES
1. Light fixtures should be centered in CLG areas,rooms, or CLG tiles, UNO.
2. MEP fixtures are shown for coordination w/ CLGplans. Refer to FP, P, E, & H drawings for fixturetypes and other information.
3. All unit ceilings are furred directly on existingplaster (see detail ) UNO withelevation marker and detail callout.
Light Fixtures
Mechanical Grilles
Sprinkler Head
CLG PLAN LEGEND
APC-1PT
TYPE "X"GYP
/5 A-501
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:1
0 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
BASEMENT REFLECTEDCEILING PLAN
AC-100
BID SET
1/4" = 1'-0" AC-100
1BASEMENT REFLECTED CEILING PLAN
NO. DESCRIPTION DATE
-
GENERAL CLG PLAN NOTES
1. Light fixtures should be centered in CLG areas,rooms, or CLG tiles, UNO.
2. MEP fixtures are shown for coordination w/ CLGplans. Refer to FP, P, E, & H drawings for fixturetypes and other information.
3. All unit ceilings are furred directly on existingplaster (see detail ) UNO withelevation marker and detail callout.
Light Fixtures
Mechanical Grilles
Sprinkler Head
CLG PLAN LEGEND
APC-1PT
TYPE "X"GYP
/5 A-501
7' - 5"
517 SF
APARTMENT A
102
517 SF
APARTMENT A
101
120 SF
EAST STAIR
STE-1
108 SF
WEST STAIR
STW-1
511 SF
APARTMENT C - ADA
105
414 SF
COMMON ROOM
106
520 SF
APARTMENT B
104
520 SF
APARTMENT B
103
347 SF
CORRIDOR
100
EQ EQ
TY
P
1' -
2"
EQ EQEQ EQ EQ EQ EQ EQEQ EQEQ EQ
6' - 11"
6' - 11"E
QE
Q
5' -
0"
1' - 2"
4
A-601
10' - 0" 2' - 0"
2' -
0"
10' -
0"
2' - 0" 16' - 0"
4' -
0"
2' -
0"
3' - 3"
WINDOW
20' - 0" 20' - 0"
20
A-501
1' -
6"
1' -
6"
1' -
6"
1' -
6"
15
A-501
1
TYP FOR UNIT 105 EXCEPT AT BULKHEAD
10
A-501
EQ
EQ
20
A-501
EQ 4' - 0" EQ
EQ
4' -
6"
EQ
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:1
1 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
FIRST FLOORREFLECTED CEILINGPLAN
AC-101
BID SET
KEYNOTE LEGEND
1/4" = 1'-0" AC-101
1FIRST FLOOR REFLECTED CEILING PLAN
SHEET KEYNOTES - RCP
REFLECTED CEILING PLAN NOTES
1 Patch and plaster @ all demo-ed walls prior toinstalling new ceiling
NO. DESCRIPTION DATE
-
517 SF
APARTMENT A
206
520 SF
APARTMENT B
204
347 SF
CORRIDOR
200
520 SF
APARTMENT B
203
516 SF
APARTMENT A
205
517 SF
APARTMENT A
201
517 SF
APARTMENT A
202
120 SF
EAST STAIR
STE-2
108 SF
WEST STAIR
STW-2
EQ EQEQ EQEQ EQEQ EQ EQ EQ EQ EQ
1
20' - 0" 20' - 0"
NOTES:1. SECOND AND THIRD FLOOR PLANS HAVE IDENTICAL APARTMENT PLANS.2. REFER TO FIRST FLOOR PLAN FOR TYPICAL NOTES.
1' -
6"
1' -
6"
1' -
6"
1' -
6"
1' -
6"
,3RD FLOOR CEILING OFWEST STAIR, ONLY
/5 A-501
GENERAL CLG PLAN NOTES
1. Light fixtures should be centered in CLG areas,rooms, or CLG tiles, UNO.
2. MEP fixtures are shown for coordination w/ CLGplans. Refer to FP, P, E, & H drawings for fixturetypes and other information.
3. All unit ceilings are furred directly on existingplaster (see detail ) UNO withelevation marker and detail callout.
Light Fixtures
Mechanical Grilles
Sprinkler Head
CLG PLAN LEGEND
APC-1PT
TYPE "X"GYP
/5 A-501
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:1
2 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
SECOND FLOORREFLECTED CEILINGPLAN
AC-102
BID SET
1/4" = 1'-0" AC-102
1SECOND FLOOR REFLECTED CEILING PLAN
KEYNOTE LEGEND
SHEET KEYNOTES - RCP
REFLECTED CEILING PLAN NOTES
1 Patch and plaster @ all demo-ed walls prior toinstalling new ceiling
NO. DESCRIPTION DATE
-
FIRST FLOOR100' - 0"
ROOF JOIST BEARING126' - 6 1/2"
SECOND FLOOR109' - 1 3/4"
BASEMENT91' - 10"
THIRD FLOOR118' - 3 1/2"
8' -
3"
9' -
1 3
/4"
9' -
1 3
/4"
8' -
2"
REPLACE EXISTING GLASS BLOCKWINDOWS ON SOUTH FACADE WITHWITH DOUBLE HUNG WINDOW, TYP(APPX SIZE 3'-0"W x 3'-2"H; VIF)
FREEZE PROOF HOSE-BIB;SEE PLUMBING
EXTERIORSECURITY LIGHT,TYP; SEE ELEC
EQEQ
1' -
6"
FIRST FLOOR100' - 0"
ROOF JOIST BEARING126' - 6 1/2"
SECOND FLOOR109' - 1 3/4"
BASEMENT91' - 10"
THIRD FLOOR118' - 3 1/2"
8' -
3"
9' -
1 3
/4"
9' -
1 3
/4"
8' -
2"
NEW DOOR @ WEST STAIR ;SEE DETAILS ON A-501
NEW DOOR @ ADA ENTRY &TRANSOM WINDOW ABOVE;SEE DETAILS ON A-501
INFILL w/ SALVAGED BRICK
EXTERIORSECURITY LIGHT,TYP; SEE ELEC
NEW GUTTER ANDDOWNSPOUT ON EXISTINGCANOPY, SEE AS-101
NEW SOFFIT, SEE /20 A-501
18
A-501
1' - 6"
1' -
6"
1' -
6"
CL
1' - 6"
1' -
6"
FIRST FLOOR100' - 0"
ROOF JOIST BEARING126' - 6 1/2"
SECOND FLOOR109' - 1 3/4"
BASEMENT91' - 10"
THIRD FLOOR118' - 3 1/2"
8' -
3"
9' -
1 3
/4"
9' -
1 3
/4"
8' -
2"
REMOVE EXISTING WINDOW.
REMOVE EXISTING GLASSBLOCK WINDOW
VIF
12' -
1"
3'-2".
REMOVE EXISTING DOORAND FRAME
REMOVE EXISTING WALL TO GRADE.(SALVAGE BRICK FOR INFILL)
REMOVE EXISTING GUTTERAND DOWNSPOUT
GENERAL ELEVATION NOTES
A. SEE AS-101 FOR EXTERIOR IMPROVEMENTSSCOPE.
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:12:5
9 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
BUILDING ELEVATIONS
A-201
BID SET
KEYNOTE LEGEND
3/16" = 1'-0" A-201
1SOUTH ELEVATION
3/16" = 1'-0" A-201
2WEST ELEVATION
3/16" = 1'-0" A-201
3WEST DEMOLITION ELEVATION
NO. DESCRIPTION DATE
-
FIRST FLOOR100' - 0"
ROOF JOIST BEARING126' - 6 1/2"
SECOND FLOOR109' - 1 3/4"
BASEMENT91' - 10"
THIRD FLOOR118' - 3 1/2"
1' -
0"
8' -
2"
9' -
1 3
/4"
9' -
1 3
/4"
8' -
3"
3' -
6"
T/FOOTING90' - 10"
T/PARAPET130' - 0 1/2"
EXTERIORSECURITY LIGHT,
TYP; SEE ELECEQEQ
1' -
6"
FIRST FLOOR100' - 0"
ROOF JOIST BEARING126' - 6 1/2"
SECOND FLOOR109' - 1 3/4"
BASEMENT91' - 10"
THIRD FLOOR118' - 3 1/2"
T/FOOTING90' - 10"
T/PARAPET130' - 0 1/2"
3' -
6"
8' -
3"
9' -
1 3
/4"
9' -
1 3
/4"
8' -
2"
1' -
0"
EXTERIORSECURITY LIGHT,TYP; SEE ELEC2
' - 6
"
CL
GENERAL ELEVATION NOTES
A. SEE AS-101 FOR EXTERIOR IMPROVEMENTSSCOPE.
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:0
1 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
BUILDING ELEVATIONS
A-202
BID SET
3/16" = 1'-0" A-202
1NORTH ELEVATION
3/16" = 1'-0" A-202
2EAST ELEVATION
NO. DESCRIPTION DATE
-
3' -
6"
MIR
RO
R
3' -
0"
2' - 0"
A-501
9ROBE HOOKON DOOR
SHELF102800
113100.E
113100.F
ELECTRICRANGE
2' -
6"
3' -
0"
40"
MA
X
1' - 6"
MIN
2' - 0"
MIN
1' - 0"
1' -
6"
4' -
0"
MIRROR
CL
34"
MA
X
2' - 0"ROBE HOOK
ADA SHOWERSEE PLUMB
ADA COMPLIANTP-TRAP COVER
SHELF102800
ADA SHOWER;SEE PLUMB
REMOVABLE BASE CABINETS; FLOORFINISH EXTENDS UNDER CABINETRY
2' - 6" 2' - 6" 2' - 3"
ADA WORK SURFACE; ADJACENT TO OVEN;30" CLEAR WHEN CABINET REMOVED
ADA SINK; 30" CLEAR WHEN CABINET REMOVED
1' -
6"
1' -
6"
1' -
1"
34"
MA
X C
OU
NT
ER
2' -
10"
48"
MA
X T
O B
OT
TO
M S
HE
LF
3' -
11"
OF
UP
PE
R C
AB
INE
T
123200.A
STAINLESS STEELBACKSPLASH
123600.C
,TYP
123600.C
113100.E
113100.F123200.A
MIN
3' - 6"
MAX
1' - 0"
7"-9"
OUTLET OF TOILETPAPER DISPENSER TOBE 15" - 48" A.F.F. ANDNOT BEHIND A GRAB BAR
2' -
0"
14
A-501
1' -
6"
1/2" FRAME EDGE TO WALL
61000.L
61000.J
92900.H
61000.L, 16'' O.C.
, BOTHSIDES
ADA ENTRY
COMMON ROOM
BIKE STORAGE
AT BASEMENT LEVEL
61000.J
33000.A
GRADE LEVEL
1/4
"
3"
61600.G
96519.D
EXISTING EXTERIORMASONRY WALL
FIRST FLOOR
V I F
ADA CHAIR LIFT
61600.G
PRESSURETREATED SILLPLATE
EXISTING SLAB
CUT SOLID SURFACEWALL @ WINDOW;PROVIDE SOLIDSURFACE SILL ANDSIDES @ WINDOW;SEAL ALL JOINTS, TYP
2' -
0"
2' -
0"
3' -
0"
102800.S
TOILET PAPER DISPENSER
102800.S
123600.C
FAUCET; SEE PLUMBING
CABINETS ETR @ 70%REPLACED @ 30%SEE NOTES ON AD-101
CABINETS ETR @ 70%REPLACED @ 30%SEE NOTES ON AD-101
2' - 0" 3' - 0"
2' -
6"
2' -
0"
3' -
0"
1' - 6" 3' - 6"
FIRST FLOOR100' - 0"
ROOF JOIST BEARING126' - 6 1/2"
SECOND FLOOR109' - 1 3/4"
THIRD FLOOR118' - 3 1/2"
DUCT FROM FURNACE
CORRIDORAPT
FIRE/SMOKE DAMPER ATREGISTER, TYP; SEE MECH
ACCESS PANELBEYOND, TYP
ACCESS PANELBEYOND, TYP
CORRIDOR AIR SUPPLYRISER DUCT; SEE MECH
EXIST CORRIDOR WALL(1HR)
DAMPER ACCESSIBLE FROMBASEMENT; SEE MECH
EXISTING CLOSETWALL
SHAFT WALL
SHAFT LINER ATFLOOR
PENETRATIONS, TYP
FIRST FLOOR100' - 0"
ROOF JOIST BEARING126' - 6 1/2"
SECOND FLOOR109' - 1 3/4"
THIRD FLOOR118' - 3 1/2"
SUPPLY DUCT TO CORRIDOR
REGISTER TOCORRIDOR BEYOND,
TYP; SEE MECH
ACCESS PANEL, TYP
CORRIDOR AIR SUPPLYRISER DUCT; SEE MECH
EXISTING 1HR STUD WALL
DAMPER ACCESSIBLEFROM BASEMENT; SEE
MECH
SHAFT WALL
PROPOSED WALL AT ADALAUNDRY CLOSET
SHAFT WALL ASSEMBLY TO RUNHORIZONTAL AT TOP OF SHAFT
TO ADA UNIT
SHAFT WALL SHAFT WALL
SHAFT LINER ATFLOOR
PENETRATIONS, TYP
4' -
0"
MA
X
6"
102800.S
ADA SHOWER;SEE PLUMB
A-501
14 6"
102800.S
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:0
6 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
INTERIOR ELEVATIONS& DETAILS
A-401
BID SET
KEYNOTE LEGEND
33000.A Cast-in-Place Concrete Footing
61000.J 2x6
61000.L 2x10
61600.G 3/4" Plywood Sub-Flooring
92900.H 5/8" Type X Gypsum Wallboard
96519.D Vinyl Composition Floor Tile
102800.S 24" Towel Bar
113100.E Range Hood
113100.F Refrigerator/Freezer
123200.A Manufactured Wood Casework
123600.C Plastic-Laminate Countertop
1/2" = 1'-0" A-401
1PR TYP Bathroom
1/2" = 1'-0" A-401
2PR TYP Kitchen
1/2" = 1'-0" A-401
13PR ADA Bathroom-2
1/2" = 1'-0" A-401
19PR ADA Bathroom-3
1/2" = 1'-0" A-401
9PR ADA Kitchen
1/2" = 1'-0" A-401
8PR ADA Bathroom-1
1 1/2" = 1'-0" A-401
4WHEELCHAIR LIFT DETAIL
1/2" = 1'-0" A-401
5PR TYP Bathroom-2
1/2" = 1'-0" A-401
6PR TYP Kitchen -2
1 1/2" = 1'-0" A-401
12ADA ENTRY STRUCTURAL DETAIL 1
1 1/2" = 1'-0" A-401
15ADA ENTRY STRUCTURAL DETAIL 2
1 1/2" = 1'-0" A-401
11ADA ENTRY STRUCTURAL DETAIL 3
1/2" = 1'-0" A-401
14SHAFT SECTION A
1/2" = 1'-0" A-401
17SHAFT SECTION B
1/2" = 1'-0" A-401
16PR ADA Bathroom-4
NO. DESCRIPTION DATE
-
FACE OF PERPENDICULAR WALL;WHERE APPLICABLE
64600.E
81400.A
81400.B
2" 3 1/2"
, SEE SCHED
PATCH PLASTER AS REQ'D,BOTH SIDES
V.I.F
.
11 1
/4"
EXISTING PLAST ONSCT WALL
81400.A
64600.E
5/8"3 1/2"
, (SEE SCHED)
61000.A
81400.B
THRESHOLD BELOW
EXTERIOR
PATCH PLASTER,AS REQ'D
SEAL AT BOTH SIDES
EXTERIOR DOOR; SEE SCHED
64600.E
81400.A
, (SEE SCHED)81400.B
V.I.F.
11 1/4"
PATCH PLASTER ASREQ'D, BOTH SIDES
EXISTING PLAST ONSCT WALL
81400.A
64600.E
5/8
"3 1
/2"
61000.A
, (SEE SCHED)81400.B
EXISTING STEEL LINTEL
PATCH PLASTER AS REQ'D
EXTERIOR
EXTERIOR DOOR; SEE SCHED
A-6
01
SE
E D
OO
R T
YP
ES
EXIST MASONRYWALL
EXIST FLOOR
EXIST EXTERIORSLAB
DOOR FRAME
PATCH PLASTERAS REQ'D
THRESHOLD
EXTERIOR DOOR;SEE SCHED
A-6
01
SE
E D
OO
R T
YP
ES
96516.D
96800.A93100.B
DOOR; WHEREAPPLICABLE
96519.DALIG
N
EXISTINGSUB-FLOOR
DOOR; WHEREAPPLICABLE
96519.D
EXISTING SUB-FLOOR
93010.A93010.A
93100.B
1 1/4"
EX
IST
ING
EXISTING PLASTERCEILING
92900.G
51200.E
ST
RU
CT
UR
E
EX
IST
ING
RO
OF
61000.C
74600.C
HOT DIPPEDGALVANIZEDSCREW
EXISTING PLAST ONSCT WALL
TAPE AND FEATHERFINISH TO EXISTINGCORNER
EX
IST
ING
FLO
OR
92216.J
92900.H
SE
E A
-601
1 H
R A
SS
EM
BLY
SE
E R
CP
95100.C
92900.H
95300.B
95300.F
92216.J
EX
IST
ING
FLO
OR
EXISTING PLASTERCEILING
92900.H
92700.A72500.E
PATCH ANDPLASTER EXISTINGCEILING WHEREAPPLICABLEBEFORE HANGINGNEW CEILING (TOKEEP FIRE RATINGOF EXISTINGFLOOR ASSEMBLY)
EXISTING EXTERIOR WALL
EXISTING WINDOW FRAME
EXISTING EDGE OF WINDOWOPENING
SOLID SURFACE @ SIDES OFWINDOW OPENING
ALIGN
SOLID SURFACE SHOWER WALL
SEAL AT ALL JOINTS/SEAMS, TYP
SHOWER
SOLID SURFACE SHOWERWALL; CUT FOR WINDOWOPENING
SOLID SURFACE @ WINDOW SILL
SE
E E
LE
VA
TIO
NS
4"
6 1
/4"1
1/2
"
25" TYP, UNO
SUPPORT, WHEREINDICATED IN ELEVATIONS
, PTD TO MATCHEXISTING
27"
MIN
RE
Q'D
KN
EE
SP
AC
E
FOR ADACOUNTER SPANUSE MTL PLATEIF NECESSARY
61000.A
62023.A
FLOOR FINISH EXTENDSUNDER CABINET AT ADA UNIT
6 1
/2"
EXISTING STAIRS
EXISTING HANDRAIL
WELD PIPE RAIL TO CONNECTEXISTING STAIR RAILS; ALIGNHEIGHT TO EXISTING @ TOPAND MIDDLESEE PHOTO: /29 A-501
WELD PIPE RAIL TOCONNECT EXISTINGSTAIR RAILS; ALIGNHEIGHT TO EXISTING@ TOP AND MIDDLESEE DETAIL: )/24 A-501
1 1/2" 1 1/2"
36".
EXISTING STAIR
64300.D
WALL MOUNT BRACKET@ 4'-0" OC MAX
EXISTING EXTERIOR WALL
EXISTING WINDOW FRAME
EXISTING WINDOW SILL61000.I
WRAP WITH SOLIDSURFACE AT ALLEXPOSED SIDES
GRAB BAR (SEE ELEV)
96519.D
EXISTINGMASONRY WALL
ADA ENTRYFLOOR; SEEDWGs ON A-4.01
EXTERIOR SLAB;SEE CIVIL
MASONRY ASREQ'D
ADA COMPLIANTTHRESHOLD
PATCH PLASTER,AS REQ'D
EXTERIOR DOOR;SEE SCHED
A-6
01
SE
E D
OO
R T
YP
ES
EXISTING STEEL LINTEL
PATCH PLASTER AS REQ'D
EXTERIOR
TRANSOM WINDOW
EXTERIOR DOOR; SEE SCHED
DOOR; WHEREAPPLICABLE
96519.D
EXISTINGSUB-FLOOR
96516.D, ON ADHESIVE
EQ EQ
93100.B
DOOR; WHEREAPPLICABLE
96519.D
EXISTINGSUB-FLOOR
EQ EQ
96519.D93100.B
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
6/2
015 7
:13:0
8 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
DETAILS
A-501
BID SET
KEYNOTE LEGEND
51200.E Structural Steel Channel
61000.A Blocking
61000.C Furring
61000.I 2x4
62023.A Wood Base
64300.D Wood Railing
64600.E Wood Casing
72500.E High Temperature Self-Adhering SheetUnderlayment
74600.C Fiber-Cement Soffit
81400.A Wood Door Frame
81400.B Flush Wood Door
92216.J 3 5/8" Steel Stud
92700.A Glass-Fiber-Reinforced PlasterFabrication
92900.G 5/8" Gypsum Wallboard
92900.H 5/8" Type X Gypsum Wallboard
93010.A Ceramic Tile
93100.B Metal Edge Strip
95100.C APC-2
95300.B Tee
95300.F Suspension Wire
96516.D Rubber Sheet Floor Covering
96519.D Vinyl Composition Floor Tile
96800.A Carpet
1 1/2" = 1'-0" A-501
1TYP DOOR JAMB
1 1/2" = 1'-0" A-501
6INTERIOR DOOR JAMB TO EXT SCT WALL
1 1/2" = 1'-0" A-501
11TYP EXTERIOR DR JAMB
1 1/2" = 1'-0" A-501
3TYP DOOR HEAD
1 1/2" = 1'-0" A-501
8INTERIOR DOOR HEAD TO EXT SCT WALL
1 1/2" = 1'-0" A-501
13TYP EXTERIOR DR HEAD
1 1/2" = 1'-0" A-501
12TYP EXTERIOR DR THRESHOLD
6" = 1'-0" A-501
2CARPET TO LVT TRANSITION DETAIL
6" = 1'-0" A-501
22LVT TO CERAMIC TILE TRANSITION DETAIL
1 1/2" = 1'-0" A-501
5TYP FLR/CLG @ EXISTING PLASTER
1 1/2" = 1'-0" A-501
20EXTERIOR SOFFIT
1 1/2" = 1'-0" A-501
16PLAN DETAIL CONNECTION TO EXISTING WALL
1 1/2" = 1'-0" A-501
10TYP FLR/CLG @ BULKHEAD
1 1/2" = 1'-0" A-501
15TYP DROPPED CLG
1 1/2" = 1'-0" A-501
9TYP SHOWER WINDOW SILL DETAIL
1 1/2" = 1'-0" A-501
4KITCHEN COUNTER DETAIL
1 1/2" = 1'-0" A-501
24TYP WEST STAIR HANDRAIL DETAIL
NTS A-501
29WEST STAIR RAIL EXISTING CONDITIONS
1 1/2" = 1'-0" A-501
19STAIR HANDRAIL DETAIL @ EAST STAIR ENTRY
1 1/2" = 1'-0" A-501
14GRAB BAR @ WINDOW BLOCKING DETAIL
1 1/2" = 1'-0" A-501
17EXTERIOR DR THRESHOLD AT ADA ENTRY
1 1/2" = 1'-0" A-501
18EXTERIOR DR HEAD AND TRANSOM
6" = 1'-0" A-501
27RUBBER TO LVT TRANSITION DETAIL
6" = 1'-0" A-501
7RUBBER TO LVT TRANSITION DETAIL
NO. DESCRIPTION DATE
-
1GYP BD PARTITION
92900.H
BRACING
92216.J
4 7/8"
2ONE-SIDED GYP BD PARTITION
92900.H
BRACING
92216.J
4 1/4"
, BOTH SIDES
92900.U
, @ 24" O.C.
, @ 24" O.C.
3GYP BD PARTITION W/ BLOCKING
BLOCKING FOR GRAB BARS
, @ 24" O.C.
6 3/4"
61000.J
PARTITION TYPES NOTES
1. Refer to Code Floor Plans (G-002) for code required Fire-Resistance Ratings. In someinstances, specified UL assemblies may exceed the minimum rating required by code.Penetrations and joint systems for such assemblies should meet or exceed the coderequired fire-resistance ratings for such walls.
2. Provide blocking in walls behind all wall-mounted casework, equipment, handrailbrackets, grab bars, mirrors, and other wall mounted objects.
3. Provide Moisture Resistant gypsum board in all bathrooms, and kitchens.4. All gypsum board shall be 5/8" thick and all wall types are type 1 unless otherwise
noted.5. All gypsum board edges shall be located on a support.6. All metal stud partition framing shall extend to underside of CLG above, unless
otherwise noted.7. Extend all partition gypsum board to deflection track as applicable.8. Seal top of smoke and fire-rated partitions as applicable.9. Seal top of sound STC rated partitions.10. Contractor shall be responsible for FRR joints and FRR penetrations.
A. Delete sound blanket insulation.B. Partial Height Wall.
PARTITION TYPE MODIFIERS
4STRUCTURAL GYP BD PARTITION
UL NO. U-305; 1 HR FRR
, @ 24" O.C.
6 3/4"
61000.J
5SHAFT WALL
UL NO. U-469; 1 HR FFR
, @ 24" O.C.09 22
16.13.M5
92900.H
1" SHAFT WALL LINER
4 5/8"
SHAFT SIDE
92900.H, BOTH SIDES
FINISH SCHEDULE - APARTMENTS
ROOM:
BEDROOM
BEDROOM CLOSET
LIVING/DINING
KITCHEN
ADA CLOSET
BATHROOM
FLOOR:
Carpet
Carpet
LVT
LVT
LVT
Ceramic Tile
Existing WD base &new to match existing
WALL BASE & TRIM:
Ceramic Tile Base
WALL:
Patch & paint existingplaster / Paint GWB
CEILING:
Paint GWB
NOTES:
(1) PAINTED ACCENT WALL IN LIVING AREA / UNIT
AB
VA
RIE
S
VARIES
7' -
0"
3' - 0"
C
3' - 0"7' -
0" GL-02
1' -
6"
5"
5"5"
3' -
4"
2' -
9"
6" 3"
GL-01
AD
A
3' -
7"
MA
X
ST
AN
DA
RD
5' -
0"
ADDITIONAL DOORVIEWER (AT ADAUNIT ENTRY ONLY)
6"6"
1' -
0"
6"
6"
A
3 1
/2"
3 1/2" 3 1/2"
B
2"
2" 2"
C
2"
1" 1"
3' - 2"
TYPICAL ROOM SIGNAGEINSTALLED OUTSIDE OF ROOM S1
101ROOM NUMBER OR NAME1/32" RAISED ANDCONTRASTING ROMAN TEXT
1/32" RAISED BRAILE TEXTTO READ THE SAME ASROMAN TEXT ABOVE
EXIT DISCHARGE SIGNAGEINSTALLED INTERIOR SIDE OF EXIT STAIR DOOR S2
EXIT1/32" RAISED ANDCONTRASTING ROMAN TEXT
1/32" RAISED BRAILE TEXTTO READ THE SAME ASROMAN TEXT ABOVE
EXIT STAIR SIGNAGEINSTALLED OUTSIDE OF STAIR IN CORRIDOR S3
EXITSTAIR 1
1/32" RAISED ANDCONTRASTING ROMAN TEXT
1/32" RAISED BRAILE TEXTTO READ THE SAME ASROMAN TEXT ABOVE
SIGNAGE NOTES:
1. SIGNAGE DRAWINGS REPRESENT SIGNAGE TYPESONLY AND ARE DIAGRAMMATIC. ALL SIGNAGE IS TOBE FURNISHED AND INSTALLED BY THE OWNER.
2. ACCESSIBLE SIGNS SHALL COMPLY WITH MOUNTEDHEIGHT AND LOCATIONS IN ACCORDANCE WITH ANSIA117.1-2009.
3. SIGNAGE IS TO BE PROVIDED AT ALL LOCATIONSINDICATED ON DOOR SCHEDULE.
EX
IST
ING
FLO
OR
92900.H
EXISTING SUBFLOOR
EXISTING 2x10 WOOD JOIST
61000.I, IF NECESSARY1 H
R A
SS
EM
BLY
COPYRIGHT PERFIDO WEISKOPF WAGSTAFF + GOETTEL 2015C
PWWG PROJECT NUMBER
REVISIONS
11/1
8/2
015 4
:57:2
6 P
M
618 CLYDE STREET, PITTSBURGH PA
21521.00
11/16/2015
CLYDE APARTMENTS
CARNEGIE MELLON UNIVERSITY
SCHEDULE AND TYPES
A-601
BID SET
SCHEDULE - ROOMS/FINISHES - COMMON
ROOM FLOOR WALL
WALL FINISH
CEILING
NOTESNUMBER ROOM NAME FINISH BASE FINISH
BASEMENT
000 CORRIDOR Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
001 ELECTRIC Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
002 NOT USED Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
003 WATER & GAS Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
004 DATA Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
005 MECH STORAGE
006 GENERAL STORAGE Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
007 BICYCLES Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
008 MECHANICAL Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
009 MECHANICAL Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
010 LAUNDRY Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
011 MAINTENANCE Existing Concrete None Paint CMU 5/8'' Type X GWB, paint Patch CMU walls and remove existingceiling finishes prior to finishing.
STW-0 WEST STAIR Rubber Resilient Base Paint CMU Patch and paint existing plaster ceiling
FIRST FLOOR
100 CORRIDOR LVT Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
106 COMMON ROOM LVT Resilient Base Paint existing plaster 5/8'' Type X GWB, paint and APC
ADA-1 ADA ENTRY LVT Resilient Base 1/8" Plaster veneer onexisting walls / Painted GWB
(See common room)
STE-1 EAST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
STW-1 WEST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
SECOND FLOOR
200 CORRIDOR LVT Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
STE-2 EAST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
STW-2 WEST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
THIRD FLOOR
300 CORRIDOR LVT Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
STE-3 EAST STAIR Rubber Resilient Base Paint existing plaster Patch and paint existing plaster ceiling
STW-3 WEST STAIR Rubber Resilient Base Paint existing plaster 5/8'' Type X GWB, paint
KEYNOTE LEGEND
61000.I 2x4
61000.J 2x6
92216.J 3 5/8" Steel Stud
92900.H 5/8" Type X Gypsum Wallboard
92900.U V Control Joint
SCHEDULE - DOORS - TYPICAL
Description Type Mark Count
DOOR PANEL FRAME
HARDWARE FIRE RATINGWIDTH HEIGHT MATERIAL TYPE JAMB HEAD MATERIAL
EAST EGRESS STAIR STE-X.1 3 3' - 0" 7' - 0" SC WD B 7/A-501 8/A-501 WD-PT 03 60 MIN
WEST EGRESS STAIR STW-X.1 4 3' - 0" 7' - 0" SC WD B 7/A-501 8/A-501 WD-PT 03 60 MIN
MISC_UTILITY ROOM XXX 3 3' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT see notes below
EXTERIOR DOOR XXX-1.2 3 3' - 0" 7' - 0" ALUM / GL C 12/A-501 13/A-501 ALUM 04 20 MIN
TYPICAL ENTRY DOOR XXX.1 18 3' - 0" 7' - 0" SC WD A 7/A-501 8/A-501 WD-PT 06 20 MIN
TYP APT - BEDROOM XXX.2 32 2' - 6" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 08
ADA APT - BEDROOM XXX.2ADA 1 3' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 07
TYP APT - CLOSET XXX.3 6 4' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 09
ADA APT - CLOSET XXX.3ADA 1 5' - 8" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 09
ADA APT - BATH XXX.4ADA 1 3' - 0" 7' - 0" HC WD A 2/A-501 3/A-501 WD-PT 10
1/4" = 1'-0" A-601
2DOOR TYPES
1/4" = 1'-0" A-601
1DOOR FRAMES
1 1/2" = 1'-0" A-601
4UL FLOOR CEILING ASSEMBLY; UL Des L501
NOTES:1. VIF EXISTING OPENINGS AT REPLACEMENT DOOR LOCATIONS2. ALL DOORS AND FRAMES TO BE PAINTED3. MISC UTIL DOOR HARDWARE AS FOLLOWS:
DOOR 003 (WATER/GAS): 01DOOR 004 (DATA): 11DOOR 005 (MECH STORAGE): 02
ABBREVIATIONS:SC WD = SOLID CORE WOODHC WD = HOLLOW CORE WOODALUM / GL = ALUMINIM FRAME AND GLASS LITE
NO. DESCRIPTION DATE
SheetsG-001 - COVER SHEETG-002 - SYMBOLS & NOTES & CODE PLANSAS-101 - ARCHITECTURAL SITE PLAN AND EXTERIOR IMPROVEMENTSAD-101 - DEMOLITION PLANSA-100 - BASEMENT PLANA-101 - FIRST FLOOR PLANA-102 - SECOND FLOOR PLAN (3RD SIMILAR)AC-100 - BASEMENT REFLECTED CEILING PLANAC-101 - FIRST FLOOR REFLECTED CEILING PLANAC-102 - SECOND FLOOR REFLECTED CEILING PLANA-201 - BUILDING ELEVATIONSA-202 - BUILDING ELEVATIONSA-401 - INTERIOR ELEVATIONS & DETAILSA-501 - DETAILSA-601 - SCHEDULE AND TYPES