clinical teaching facility: the prescription for energy savings

16
Clinical Teaching Facility: The Prescription for Energy Savings Tim Rielly, Facilities Manager Hillcrest & Tavis Werts PE, EnerNOC Project Manager UC San Diego

Upload: ima

Post on 04-Feb-2016

16 views

Category:

Documents


0 download

DESCRIPTION

Clinical Teaching Facility: The Prescription for Energy Savings. Tim Rielly , Facilities Manager Hillcrest & Tavis Werts PE, EnerNOC Project Manager UC San Diego. UCOP GOAL: Climate Neutrality by 2025. UC San Diego Investment in Energy Efficiency. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Clinical Teaching Facility: The Prescription for Energy Savings

Clinical Teaching Facility:

The Prescription for Energy Savings

Tim Rielly, Facilities Manager Hillcrest &Tavis Werts PE, EnerNOC Project Manager

UC San Diego

Page 2: Clinical Teaching Facility: The Prescription for Energy Savings

2004

2005

2006

2007

2008

2009

2010

2011

2012

-

2,000,000

4,000,000

6,000,000

8,000,000

10,000,000

12,000,000

14,000,000

16,000,000

18,000,000

-

0.0020

0.0040

0.0060

0.0080

0.0100

0.0120

0.0140

0.0160

0.0180 UC San Diego Greenhouse Gas Index

Total MGSF GHG tonnes / GSF-YR

Main

tain

ed

Gro

ss S

q F

eet T

on

nes/G

ross S

q F

t-Year

UCOP GOAL:Climate

Neutrality by 2025

Page 3: Clinical Teaching Facility: The Prescription for Energy Savings

UC San DiegoInvestment in Energy Efficiency

Funded by utility incentives and a low interest revenue bond

Program will yield $8.9M in avoided annual energy costs from 48M kw-hr/yr reduction

In seven years, UCSD will complete $85.5M of projects, with $13.3M in incentives

2010

2011

2012

2013

(pro

ject

ed)

2014

(pro

ject

ed)

Tota

l$0

$1,000,000

$2,000,000

$3,000,000

$4,000,000

$5,000,000

$6,000,000

$7,000,000

Annual 15-Year Debt Service

Annual Savings

Page 4: Clinical Teaching Facility: The Prescription for Energy Savings

Energy Efficiency Program Breakdown

Lab HVAC

Retrofits

42%

Non-Lab HVAC Retrofits

8%

MBCx25%

Data Center

3%

Lighting8%

Plug Loads &

Other3% Central Plant

Retrofits12%

Lab HVAC

Retrofits

60%Non-Lab

HVAC Retrofit

s5%

MBCx18%

Data Center

1%

Light-ing7%

Plug Loads

& Other

2%

Central Plant Retrofits

6%

by Savings by Cost

Page 5: Clinical Teaching Facility: The Prescription for Energy Savings

La Jolla Campus

Hillcrest Campus

Page 6: Clinical Teaching Facility: The Prescription for Energy Savings

UC San Diego’s Hillcrest Campus

Page 7: Clinical Teaching Facility: The Prescription for Energy Savings

Clinical Teaching Facility

• Built in 1978• 3 Buildings - 131,000 GSF• Medical Research Labs and Office Space• 14 Air Handlers• Annual Energy Bill: $670,000

Page 8: Clinical Teaching Facility: The Prescription for Energy Savings

Metering

Electricity Chilled Water Hot Water

Eight different energy feeds

required monitoring for M&V Option C:

Whole Building Analysis!

Page 9: Clinical Teaching Facility: The Prescription for Energy Savings

Existing HVAC Infrastructure

• 2 Air Handlers per building plus 2 dedicated vivarium units•1 100% outside air and 1 economizer unit per building

Page 10: Clinical Teaching Facility: The Prescription for Energy Savings

Implemented Improvements

•Pressure-Independent Chilled Water Valves•SAT Reset Sequence• Programming to Prevent

Simultaneous Heating and Cooling•Heating Hot Water Reset• Replace Leaking Reheat Valves• Replace and Optimize Economizers

Page 11: Clinical Teaching Facility: The Prescription for Energy Savings

CTF’s New Baseline

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec0

500

1,000

1,500

2,000

2,500

3,000

3,500

4,000

0

50,000

100,000

150,000

200,000

250,000

300,000

350,000

Monthly Energy Consumption for the Clinical Teaching Facility

Pre-Implementation Hot Water (MMBtu) Post-Implementation Hot Water (MMBtu)Pre-Implementation Chilled Water (MMBtu) Post-Implementation Chilled Water (MMBtu)Pre-Implementation Electricity (kWh) Post-Implementation Electricity (kWh)

MM

Btu

kWh

Page 12: Clinical Teaching Facility: The Prescription for Energy Savings

Energy Savings

Annual Energy Usage

Category

Pre-Baseline Usage

Post-Baseline Usage

Energy Savings Cost Savings

Electricity (kWh/yr) 3,514,130 3,342,003 172,127 $13,770

Chilled water (MMBtu/yr) 23,746 12,704 11,042 $91,980

Hot water (MMBtu/yr) 20,254 7,581 12,673 $115,324

Page 13: Clinical Teaching Facility: The Prescription for Energy Savings

Best Practices

•Meter Installation•Upgraded AHUs to Modern Controls•MBCx provider worked closely with CUP staff

• Buy-in from Technicians prevents overriding setpoints• Plant staff is taking the training provided and

lessons learned to repeat the process at the hospital

Page 14: Clinical Teaching Facility: The Prescription for Energy Savings

Lessons Learned

• Control Vendor Contracts• Operator Acceptance of New Sequences• Economizer design• Early leak-by detection

Page 15: Clinical Teaching Facility: The Prescription for Energy Savings

Ongoing Improvements

•VAV Retrofit• Continuous Commissioning• Reduction of Minimum Room Air Exchange Rates, with Air Content Monitoring• Exhaust Fan Energy Optimization Through Air Content Monitoring and/or Wind Speed Monitoring• Optimize outside air requirements

Page 16: Clinical Teaching Facility: The Prescription for Energy Savings

Tim [email protected]

619-543-8268

Tavis [email protected]

m949-930-1596