Clearing the Air: The Impact and
Cause of Microbial Growth in
HVAC Systems
![Page 2: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/2.jpg)
2019 IAQA Annual Meeting
IntroductionSimple Truths about HVAC and Microbial Growth
• Microbial growth is a normal attribute of all
HVAC systems
• Only limited microbial taxa are suited to grow
inside an HVAC system
Oxygen
• Approximately 21%
Nutrients
• Fructose
• Glucose
• Sucrose
• Mannitol
• Arabitol
Moisture
• Water Activity Between 0.60-0.98 for Most Fungal Taxa
Viable Spores
• Requires Incubation
• Potato Dextrose Agar
• Corn Meal Agar
• Malt Extract Agar
Suitable Temperature
• Between 0-40°C (32-104°F)
![Page 3: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/3.jpg)
2019 IAQA Annual Meeting
Agenda
• Content
• Understanding HVAC Systems
• Characteristics of Microbial
Growth
• Relationship between HVAC
System and Microbial Growth
• Condensation inside HVAC Air
Handlers
• Test Procedures
• How to Mitigate Microbial Growth
• Can We Control the Microbial
Growth
![Page 4: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/4.jpg)
2019 IAQA Annual Meeting
Understanding HVAC Systems
1) Fundamental Operation and
Components
2) Conditions at Areas Where Microbial
Growth Occurs
3) How The Right Conditions are
Achieved on HVAC Surfaces
Vapor-Compression Refrigeration Cycle Commonly
known as HVAC (Heating, Ventilation and Air
Conditioning)
![Page 5: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/5.jpg)
2019 IAQA Annual Meeting
Understanding HVAC SystemsFundamental Operation and Components
• Compressor
• Condenser Coil
• Evaporator Coil
• Thermostatic Expansion Valve
• Blower
• Electrical (Motors, Capacitors,
Wires, Switches, etc.)
• Thermostat/Humidistat
• Duct Work
• Registers
![Page 6: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/6.jpg)
2019 IAQA Annual Meeting
Understanding HVAC Systems
• Content
Ideal Vapor-Compression Cycle
Common Residential Split System
![Page 7: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/7.jpg)
2019 IAQA Annual Meeting
Understanding HVAC SystemsDetermining the Conditions at Microbial Growth Locations
The Science of Psychrometrics
Growth Surfaces
• Ducting
• Metal Components
• Registers
• Wires
• Paper Labels
![Page 8: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/8.jpg)
2019 IAQA Annual Meeting
Understanding HVAC SystemsConditions for Microbial Growth in an HVAC System
• Standard Operation
• 100% Relative Humidity After
Evaporator Coils
• Dry Bulb Temp At or Below Dew
Point Temperature
• HVAC Inefficiencies Decrease
Moisture Removal
![Page 9: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/9.jpg)
2019 IAQA Annual Meeting
Characteristics of Microbial Growth
• Content
Microbial Growth on HVAC Components
• Cladosporium
• Yeasts
• Phoma
• Rhizopus
• Acremonium
• Penicillium
• Asp/Pen-like
Cladosporium sp. Yeasts Acremonium sp.
Penicillium sp.
![Page 10: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/10.jpg)
2019 IAQA Annual Meeting
Characteristics of Microbial GrowthMicrobial Growth on HVAC Components
Lab Results (n=37)
Asp/Pen-like Low
Penicillium Medium Low Low Low
Acremonium Low Low Medium Low
Rhizopus Low
Phoma Low Low Low
Yeasts Low Low Low
Cladosporium Low Low High High High Low Low Low
Microbial
GrowthFiberglass Duct
Evaporator
Coil
AHU Metal
InteriorSupply Vent
Duct Face
Interior/ExteriorAHU Wires AHU Paper Drain Pan
Low 1-3, Medium 4-6, High >7
![Page 11: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/11.jpg)
2019 IAQA Annual Meeting
Characteristics of Microbial GrowthWater Activity for Microbial Growth
![Page 12: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/12.jpg)
2019 IAQA Annual Meeting
Characteristics of Microbial GrowthWater Activity for Microbial Growth
![Page 13: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/13.jpg)
2019 IAQA Annual Meeting
Characteristics of Microbial GrowthNutrient Sources for Microbial Growth Indoors
• Cellulose Fibers
• Plants
• Decayed Organic
Matter
• Fruits
• Flowers
• Fabric (Organic)
![Page 14: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/14.jpg)
2019 IAQA Annual Meeting
Characteristics of Microbial Growth
• Skin Cells
• Hair
• Clothing
Fibers
• Bacteria
• Dust Mites
• Dead Bug
Fragments
• Soil Particles
• Pollen
• Plastic
Composition of Dust
Hess-Kosa, Kathleen (2002). Indoor Air Quality: sampling methodologies. CRC Press. p. 216Pelley, J., Tracing the chemistry of household dust, Chemical & Engineering News, American Chemical Society, 2018
![Page 15: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/15.jpg)
2019 IAQA Annual Meeting
Characteristics of Microbial GrowthIdeal Temperature Ranges
• Commonly Between 50-
100°F for Microbial Growth
• Ideal Temperatures Vary
Greatly Between Taxa
• Similar to Human Ideal
Temperatures
Rhizopus
Acremonium
Penicillium
Microbial
Cladosporium
Curvularia
Yeasts
Phoma
Temperature Ranges
0-28C (32-82F)
10-40C (50-104F)
27-38C (80-100F)
10-35C (50-95F)
No Data
>30C (>86F)
8-35C (46-95F)
![Page 16: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/16.jpg)
2019 IAQA Annual Meeting
Relationships Between HVAC
Systems and Microbial Growth
• Deposition (Fan Blade, Duct Work)
• Adsorption (Sticking of Particles on Surfaces)
• Electro Static Precipitation (All Interior
Surfaces)
• Absorption (Evaporator Coil, Paper Label)
• Gravity
• Increased Surface Area with Age
Simple Truth: An HVAC System is a Nutrient Sink
Nutrient Accumulation
![Page 17: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/17.jpg)
2019 IAQA Annual Meeting
Relationships Between HVAC Systems and
Microbial GrowthMoisture Sources
• HVAC Systems Create Conditions for Microbial
Growth
• Occupant Created Moisture (Cooking, Bathing,
Unconditioned Outside Air, Deferred
Maintenance, Irregular Thermostat Controls)
![Page 18: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/18.jpg)
2019 IAQA Annual Meeting
≈ 35°F≈100°F
≈50°F
≈ 60°FCladosporium
<35°F
Microbial Temperature Range
Temperature Range for AHU Interior
50-55°F Common Temperature of HVAC Supply Air
Relationships Between HVAC Systems
and Microbial GrowthTemperature Comparison between Air Handler Unit (AHU) Supply and
Microbial Growth
![Page 19: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/19.jpg)
2019 IAQA Annual Meeting
Psychrometrics Inside HVAC System
Condensation Inside HVAC Air Handlers
![Page 20: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/20.jpg)
2019 IAQA Annual Meeting
Condensation Inside HVAC Air HandlersHVAC Issues that Result In Excess Condensation
• Increased Latent Heat Load
• Refrigerant Low/High
• Introduction of Non-conditioned Air
• Clogged Filter
• Fan Always “on”
• Obstructed Evaporator Coils/Low
Fan Speed (Super Cooled Air)
• Series Wiring Configuration in a
Humid Environment
• Continuously Full Primary Drain
Pan
![Page 21: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/21.jpg)
2019 IAQA Annual Meeting
Test Procedures
• Content
Sample Surfaces &
Observations
![Page 22: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/22.jpg)
2019 IAQA Annual Meeting
Test ProceduresAnalyze Results
![Page 23: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/23.jpg)
2019 IAQA Annual Meeting
Test ProceduresDetermine Conditions at Sample Location
Supply Registers/Ducts
• Visible Condensation
• Temperatures
HVAC Air Handler
• Visible Condensation on
Interior/Exterior Surfaces
• Supply and Return
Temperature (ΔT)
• Relative Humidity (Return
Duct Only)
![Page 24: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/24.jpg)
2019 IAQA Annual Meeting
Test Procedures
Old System
• Historic Condensate Issues
• ΔT
• Examine Evaporator Coil
• Mold on Duct Work
• Dust Precipitation/Air Leaks
• Thermostat and Humidistat Settings
• Wiring Configuration
• Approximate Cooling Capacity per
Living Area (tons/sq ft)
• Effective Filter Fitting
Comparison of Old and New HVAC Systems
![Page 25: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/25.jpg)
2019 IAQA Annual Meeting
Test ProceduresComparison of Old and New HVAC Systems
New System
• Evidence of Condensate Issues
• ΔT
• Thermostat Settings
• Approximate Cooling Capacity per
Living Area (tons/sq ft)
• Excess Filtering
![Page 26: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/26.jpg)
2019 IAQA Annual Meeting
How to Mitigate Microbial Growth
• Content
Duct Cleaning
• Removes Bacterial and
Fungal Mass
• Temporary Solution
• Increases Air Flow/Reduces
Friction
• Reduces Nutrient Sources
![Page 27: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/27.jpg)
2019 IAQA Annual Meeting
How to Mitigate Microbial GrowthCoil Cleaning
• Removes Bacterial and
Fungal Mass
• Temporary Solution
• Increases Air Flow
• Reduces Nutrient Sources
• Increases HVAC Efficiency
![Page 28: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/28.jpg)
2019 IAQA Annual Meeting
How to Mitigate Microbial Growth
• Content
Register Cleaning
• Temporary Solution
• Indicator of Bigger Issue
(Elevated RH%, Excess Latent
Heat, Super-cooled Air)
![Page 29: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/29.jpg)
2019 IAQA Annual Meeting
How to Mitigate Microbial Growth
• Content
Application of Chemicals (i.e., biocides)
• Temporary Solution
• Toxic to Humans
• Remove Moisture to Avoid
Use
• Manual Removal of Visible
Growth is Recommended
![Page 30: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/30.jpg)
2019 IAQA Annual Meeting
Can We Control Microbial Growth?How Many Spores Pass Through an Air Handler?
• Assuming a 1 air change per
hour (ACH) rate
• ≈63% mix of outside air after
1 hour at 1 ACH
• 1,200 spores per cubic meter
• Over 15 years
• Assuming 3,400 cubic
meters per hour through air
handler
𝟑𝟒𝟎𝟎 ൗ𝒎𝟑
𝒉𝒓 × 𝟏𝟐𝟎𝟎 ൗ𝒔𝒑𝒐𝒓𝒆𝒔
𝒎𝟑 = 𝟒 × 𝟏𝟎𝟔 ൗ𝒔𝒑𝒐𝒓𝒆𝒔
𝒉𝒓
𝟒 × 𝟏𝟎𝟔 ൗ𝒔𝒑𝒐𝒓𝒆𝒔
𝒉𝒓 × ൗ𝟖𝟕𝟔𝟎 𝒉𝒓𝟏 𝒚𝒓 = 𝟑. 𝟓 × 𝟏𝟎𝟏𝟎 ൗ
𝒔𝒑𝒐𝒓𝒆𝒔𝒚𝒓
![Page 31: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/31.jpg)
2019 IAQA Annual Meeting
Can We Control Microbial Growth?UV Light
• Minimizes Bacteria and
Fungal Growth
• Closed Circuit Most Efficient
• Diminished Effectiveness
with Increased Distance from
Source
• Certain Taxa Affected
• Debris on UV Light
Levetin, E., et al., Effectiveness of Germicidal UV Radiation for Reducing Fungal Contamination within Air-Handling Units, Applied and Environmental Microbiology, 2001
![Page 32: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/32.jpg)
2019 IAQA Annual Meeting
Can We Control Microbial Growth?AHU HEPA Filter
• Normally Independent System
• Minimum Efficiency Reporting Value
(MERV) Rating
• True HEPA is >14
• Reduces Air Flow Through AHU
![Page 33: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/33.jpg)
2019 IAQA Annual Meeting
Can We Control Microbial Growth?
• Content
Air Scrubbers w/ HEPA Filters
• Three Stage Filters Used
• True HEPA Filters are Costly
• Bulky Equipment
• Excess Power Requirements
• Very Efficient (Particle
Removal)
![Page 34: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/34.jpg)
2019 IAQA Annual Meeting
Can We Control Microbial Growth?
• Content
Moisture Control
• Indication of HVAC Issues
• Reduced Moisture=Reduced
Microbial Growth
• Bulky Equipment in Some
Cases
• Excess Power Requirements
• Odor Reduction
![Page 35: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/35.jpg)
2019 IAQA Annual Meeting
Can We Control Microbial Growth?Remove Nutrient Sources
• Reduces Microbial Growth
• Most Effective on Non-porous
Surfaces
• Replace Carpet with Non-porous
Flooring
• Temporary Solution
• Complete Nutrient Removal is
Impossible
![Page 36: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/36.jpg)
2019 IAQA Annual Meeting
Conclusions
Simple Truths
HVAC Systems . . .
• produce moisture
• are intrinsically dirty
• encourage growth of a selected
group of microbial taxa
Maintenance and Proper Operation
are Critical for Peak Efficiency
![Page 37: Clearing the Air: The Impact and Cause of Microbial …...2019 IAQA Annual Meeting Nolan Wells, BSME, EI, MRSA Ralph Moon, Ph. D. CHMM, CIAQP GHD Services, Inc. Nolan.wells@ghd.com](https://reader030.vdocuments.mx/reader030/viewer/2022040606/5eaeb02fdcd6880bce2dca9a/html5/thumbnails/37.jpg)
2019 IAQA Annual Meeting
BibliographyKrause, M., Geer, W., Swenson, L., Fallah, P., and Robbins, C. (2006). Controlled study of mold growth and cleaning procedure on treated and untreated wet gypsum wallboard in an indoor environment. J Occup.Environ Hyg.
Simmons, R. B., Noble, J. A., Rose, L., Price, D. L., Crow, S. A., and Ahearn, D. G. (1997). Fungal colonization of automobile air conditioning systems. Journal of Industrial Microbiology & Biotechnology 19, 150-153.
Almaguer, M., Amador, V., Batista, A. Effect of temperature on growth and germination of conidia in Curvularia and Bipolaris species isolated from the air, Aerobiologia, 2012
Aldred, D., Magan, N., Lane, B., Influence of water activity and nutrients on growth and production of squalestatin S1 by a Phoma sp., Journal of Applied Microbiology