27 MARCH 2018Field Service Technician(s):
REGINALD RICHARD
2880 Bergey Road, Ste. KHatfield, PA 19440
Control ID #: 315-165018-7598
Date(s) Tested:
Cleanroom Certification Report
Prepared for:
SICBOY INDUSTRIES1218 COMMERCE CT, UNIT B
LAFAYETTE, CO 80026
Attention:
KEVIN KIRKPATRICK970-217-0035
Presents:
www.envservices.com800 - 345 - 6094
SUMMARY REPORT 3
OVERVIEW 4
HEPA LEAK HEPA FILTER LEAK TEST 5
ROOM PRESSURIZATION ROOM PRESSURIZATION 6
ANTE ROOM AIR SUPPLY VOLUMES & AIR CHANGES PER HOUR 7
ANTE ROOM PARTICLE COUNTS 8
CLEANROOM 1 AIR SUPPLY VOLUMES & AIR CHANGES PER HOUR 9
CLEANROOM 1 PARTICLE COUNTS 10
CLEANROOM 2 AIR SUPPLY VOLUMES & AIR CHANGES PER HOUR 11
CLEANROOM 2 PARTICLE COUNTS 12
SECONDARY TEST 13
TEST EQUIPMENT 14
TABLE OF CONTENTS
ANTE ROOMTest Test Result Specification Pass / Fail Comment
Total Air Changes / Hr. 49 N/A For Reference OnlyISO Class ISO 8 ISO 8 PASS
CLEANROOM 1Test Test Result Specification Pass / Fail Comment
Total Air Changes / Hr. 38 N/A For Reference OnlyISO Class ISO 7 ISO 7 PASS
CLEANROOM 2Test Test Result Specification Pass / Fail Comment
Total Air Changes / Hr. 39 N/A For Reference OnlyISO Class ISO 7 ISO 7 PASS
HEPA LEAKTest Test Result Specification Pass / Fail Comment
HEPA Leak ≤ 0.01% ≤ 0.01% PASSROOM PRESSURIZATION
Test Test Result Specification Pass / Fail CommentPressure Ref: Cleanroom
2 to ante room: Positive | 0.075 N/A For Reference OnlyPressure Ref: Cleanroom
1 to ante room: Negative | 0.079 N/A For Reference OnlyPressure Ref: Cleanroom 1 out the conveyer belt
window:Positive | 0.081 N/A For Reference Only
Pressure Ref: Ante room to outside: Positive | 0.056 N/A For Reference Only
All testing is performed by qualified personnel using instrumentation, procedures and methods which ensure measurements observed are reliable. When specified, testing is performed in accordance with current ISO-17025, ISO-14644, USP-<797> and ENV's Quality Manual. Specifications comply with applicable IEST recommended practices, CETA CAGS and/or customer determined specifications. Measurement instruments used are traceable to The National Institute of Standards and Technology (NIST). Results obtained apply to the specific room or equipment and are reflective of conditions at the time of this test.
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
3 of 14 Control ID #: 315-165018-7598
SUMMARY REPORTSICBOY INDUSTRIES
LONGMONT, CO 80503
CLEANROOM
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
4 of 14 Control ID #: 315-165018-7598
OVERVIEWSICBOY INDUSTRIES
LONGMONT, CO 80503
CLEANROOM
Aerosol challenge concentrations are ≥10ug/L.
PASS = No Leakage Detected
Test ResultPASS
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
5 of 14 Control ID #: 315-165018-7598
HEPA FILTER LEAK TESTOPERATIONAL / DYNAMIC
HEPA LEAK
Test ResultFor Reference Only
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
6 of 14 Control ID #: 315-165018-7598
ROOM PRESSURIZATION(UNITS IN INCHES WATER GAUGE) - OPERATIONAL / DYNAMIC
ROOM PRESSURIZATION
No. of Readings
Total Air Supply Volume
Room Air Changes/Hour
Room ACH Specification
Total ACH Specification
Total Air Changes/Hour
Room Volume
781
2
960
49
49
N/A
N/A
Test ResultFor Reference Only
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
7 of 14 Control ID #: 315-165018-7598
AIR SUPPLY VOLUMES & AIR CHANGES PER HOUR(UNITS IN CUBIC FEET PER MINUTE) - OPERATIONAL / DYNAMIC
ANTE ROOM
AT 0.5 MICRONS AND LARGER
* ISO Class 8 allows a maximun of 3520000 particles 0.5 microns per cubic meter as an average count at any location as long as the entire clean area meets the required statistical tests.
57 26 N/A
Number of Locations
Highest concentration
Average concentration 95% UCL ISO Class
Resultingft³ m³ ft³ m³ ft³ m³
2013 906 N/A6 8
AT 0.5 MICRONS AND LARGER
Particulate Sampled
Sample Volume
1.00 ft³
8
11.15
120.00
ISO Target Class
Area(m²)
Area(ft²)
The above referenced clean zone has successfully passed the minimum requirements to meet the ISO class listed below per ISO Standard 14644-1:2015 for particle count testing of
cleanrooms and associated controlled enviroments.
Test ResultPASS
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
8 of 14 Control ID #: 315-165018-7598
PARTICLE COUNTSOPERATIONAL / DYNAMIC
ANTE ROOM
No. of Readings
Total Air Supply Volume
Room Air Changes/Hour
Room ACH Specification
Total ACH Specification
Total Air Changes/Hour
Room Volume
1025
3
1600
38
38
N/A
N/A
Test ResultFor Reference Only
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
9 of 14 Control ID #: 315-165018-7598
AIR SUPPLY VOLUMES & AIR CHANGES PER HOUR(UNITS IN CUBIC FEET PER MINUTE) - OPERATIONAL / DYNAMIC
CLEANROOM 1
AT 0.5 MICRONS AND LARGER
* ISO Class 7 allows a maximun of 352000 particles 0.5 microns per cubic meter as an average count at any location as long as the entire clean area meets the required statistical tests.
8 5 N/A
Number of Locations
Highest concentration
Average concentration 95% UCL ISO Class
Resultingft³ m³ ft³ m³ ft³ m³
283 159 N/A6 7
AT 0.5 MICRONS AND LARGER
Particulate Sampled
Sample Volume
1.00 ft³
7
18.58
200.00
ISO Target Class
Area(m²)
Area(ft²)
The above referenced clean zone has successfully passed the minimum requirements to meet the ISO class listed below per ISO Standard 14644-1:2015 for particle count testing of
cleanrooms and associated controlled enviroments.
Test ResultPASS
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
10 of 14 Control ID #: 315-165018-7598
PARTICLE COUNTSOPERATIONAL / DYNAMIC
CLEANROOM 1
No. of Readings
Total Air Supply Volume
Room Air Changes/Hour
Room ACH Specification
Total ACH Specification
Total Air Changes/Hour
Room Volume
1030
3
1600
39
39
N/A
N/A
Test ResultFor Reference Only
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
11 of 14 Control ID #: 315-165018-7598
AIR SUPPLY VOLUMES & AIR CHANGES PER HOUR(UNITS IN CUBIC FEET PER MINUTE) - OPERATIONAL / DYNAMIC
CLEANROOM 2
AT 0.5 MICRONS AND LARGER
* ISO Class 7 allows a maximun of 352000 particles 0.5 microns per cubic meter as an average count at any location as long as the entire clean area meets the required statistical tests.
31 14 N/A
Number of Locations
Highest concentration
Average concentration 95% UCL ISO Class
Resultingft³ m³ ft³ m³ ft³ m³
1095 500 N/A6 7
AT 0.5 MICRONS AND LARGER
Particulate Sampled
Sample Volume
1.00 ft³
7
18.58
200.00
ISO Target Class
Area(m²)
Area(ft²)
The above referenced clean zone has successfully passed the minimum requirements to meet the ISO class listed below per ISO Standard 14644-1:2015 for particle count testing of
cleanrooms and associated controlled enviroments.
Test ResultPASS
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
12 of 14 Control ID #: 315-165018-7598
PARTICLE COUNTSOPERATIONAL / DYNAMIC
CLEANROOM 2
*Temperature Unit: °F
Test ResultFor Reference Only
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
13 of 14 Control ID #: 315-165018-7598
SECONDARY TESTOPERATIONAL / DYNAMIC
Equipment Name Manufacturer Model Serial Calibration Due DatePHOTOMETER AIR TECHNIQUES TDA-2H 20753 29 SEP 18
PARTICLE COUNTER LIGHTHOUSE 3100E 180101066 31 JAN 19
MULTIMETER FLUKE 77/AN 45319012 09 OCT 18
TEMP & HUMID INDICATOR
VAISALA HM40 M1720265/M1610011
05 JUN 18
Test equipment calibration certificates available upon request.Company ID: CO0837-001 Unique ID: 603768
ENV SERVICES, Inc.PROVIDING NATIONWIDE SOLUTIONS, CERTIFICATION, CALIBRATION, VALIDATION, CLEANROOMS
Project: SICBOY INDUSTRIES1218 COMMERCE CT, UNIT BLAFAYETTE, CO 80026
14 of 14 Control ID #: 315-165018-7598
TEST EQUIPMENTSICBOY INDUSTRIES
LONGMONT, CO 80503
CLEANROOM