The City Multi
YHM-A Range
For more information on Mitsubishi Electric visit www.barbourproductsearch.info
The new City MultiYHM-A range providesthe per fect solution for more demandingapplications
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
the name Mitsubishi is synonymous with excellenceKnown the world over, Mitsubishi is a trusted global leaderassociated with a variety of products and services. Founded in1907, the company known today as Mitsubishi Electric, quicklyrose to the forefront of the air conditioning industry - a position we still enjoy today.
Unsurpassed air conditioning from Mitsubishi ElectricAir conditioning is an ideal way of controlling the air quality inside any building, large or small. Not only does it cool in the summer months but air conditioning can also heat, replacing traditionalheating systems. More and more people today are experiencing the benefits of comfortable working,living and leisure environments made possible with air conditioning. As market leaders, we prideourselves in providing high performance, competitive systems with low running costs.
Protecting the environmentMitsubishi Electric are the only air conditioning manufacturer recognised in the top 5 companies in the world for their sustainable environmental policy. Portfolio 21 only selects those companieswith an explicit commitment to sustainable business practices such as energy and resource efficiency, minimising ecological impacts of products and reducing greenhouse gas emissions. Our constant investment and product development enables Mitsubishi Electric to produce themost efficient equipment possible, whilst helping to protect the environment at the same time. For more information on Portfolio 21 please visit www.portfolio21.com.
The Forest Stewardship Council (FSC) is an international network promotingresponsible management of the world's forest. The paper this brochure isprinted on supports the development of responsible forest managementworldwide. The wood comes from FSC certified, well managed forests, company controlled sources and/or recycled material.
3
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
The New City Multi
YHM-A Range
The City Multi YHM-A range is Mitsubishi Electric’s answer to large scale VRF (Variable Refrigerant Flow) applications. The efficiencyof City Multi is second to none and offers a substantial increase in energy efficiency, with corresponding EER/COP ratings.
The City Multi Y Series range offers a simple and flexiblesolution where there is a demand for a changeover capability between heating and cooling, helping to ensurea constant, comfortable indoor climate. With a wide rangeof 76 indoor units, up to 50 (depending on the capacityavailable) can be connected to a single Y series outdoor unit.
Mitsubishi Electric also has the ability to provide simultaneousheating and cooling through its R2 systems. The differencehere being that this is achieved through only two pipesrather than the conventional three. By using MitsubishiElectric’s 2-pipe heat recovery technology, substantial savings can again be made on annual running costs. 50indoor units can now be connected to an R2 system.
Sophisticated technology, combined with a high levelof control and energy efficiency:
City Multi is perfectly positioned to meetthe demands of today’s market.
Highly eff icient& extremely flexible
4
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
� Increased Energy EfficiencyNew wrap around coil on 3 sides of the unit offers greater system efficiency. Highest ever COP’s compared to previous YGM-A models
� Increased Pipe LengthsTotal system pipe lengths of up to 1000m and furthest pipe lengths of 165m
� High Sensible Cooling FunctionRaised off coil temperatures offer a 10% increase in sensible cooling capacity over standard operation
� Low Starting Currents8 amp starting current for all models
� Reduced Noise LevelsDevelopments in fan blade shape and weight have produced an even higher performance and this alongsidethe compressor compartment now being sealed, have also managed to achieve lower noise levels. Acoustic Kits are also now available to reduce noise levels down to 47dB(A)
� Cooling Operation Set Temperature of 14ºC DBOffers benefits to environments such as gyms & laboratories (ducted & floor standing indoor units only)
� Effective Use of Space21% reduction in footprint size and a 10% reduction in height compared to previous YGM-A version
� Blue Fin TreatmentThe heat exchangers of all City Multi outdoor units have undergone this anti-corrosion treatment
� 100% Inverter ControlThe larger models now contain either 2 or 3 inverter driven compressors
� New High COP SystemAvailable in both Y Series and R2, alongside the standard systems
� Weight Reduction33kg reduction in weight (comparing size 250 unit against previous YGM-A model)
� Replace TechnologyEnables the reuse of existing R22 pipework, whilst allowing the upgradeto some of the most efficient systems available in the market
� Refrigerant Volume Checking FunctionEnabling customers to easily comply with the F-Gas regulation
5
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
The BasicsWhat is VRF?VRF stands for Variable Refrigerant Flow. A VRF air conditioning system modulates the flow of refrigerant depending upon the capacity requirements of the building. A VRF system comprises of a condensing unitsited externally and a series of multiple indoor units toprovide cooling and/or heating to the occupied space.
Our answer to VRFMitsubishi Electric sets the boundaries of VRF technologywith the City Multi range, which is available using R410Arefrigerant with zero ODP (Ozone Depletion Potential).The range has been specifically designed for today's building requirements and addresses key market issuessuch as energy efficiency, adaptability and reliability. Mitsubishi Electric manufactures the only 2-pipe heat recovery simultaneous heating and cooling system in theworld and equally unique, a water-cooled version. With user friendly control systems utilising Internet technology and integrated cooling and ventilation indoorunits, City Multi is the benchmark and market leader in VRF technology.
What is inverter driven technology?Mitsubishi Electric spends more than 5% of its turnoveron research and development, with our engineers alwayslooking at ways in which we can improve and lead in airconditioning efficiency. The use of inverter technology inour City Multi systems is paramount in this process, working by varying the compressor speed to match thecooling or heating load, thereby consuming only thepower necessary to match the exact requirement of the room.
When City Multi is operating at partial load, the energyefficiency of the system is significantly higher than at fullload. In a typical application partial load conditions prevailfor more than 90% of operation time. A fixed speed system can only operate at 100% capacity and cannot matchthe annual efficiencies of an inverter system.
What is a Heat Pump system?Mitsubishi Electric’s City Multi Y Series, is a heat pumpsystem, which provides either heating or cooling to abuilding at any given time.
What is a Heat Recovery system?Mitsubishi Electric’s City Multi R2 series has the ability toprovide heating and cooling at the same time in areasconnected to the same outdoor unit.
6
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
7
Why R410A?R410A is a more efficient refrigerant as it has a higherspecific heat capacity when compared to R407c or R22.This higher energy carrying capacity allows for smallerpipe sizes, longer pipe runs and reduces the volume of refrigerant within a system.
This is a major factor when complying with EN378, a European standard concerning safety and environmentalrequirements in the design, manufacture, installation, operation, maintenance and disposal of refrigerating systems.
Why Heat Recovery?Flexibility and efficiency are key factors when selecting aheat recovery system. For example, while a heat pumpsystem is adequate for a large open plan office, businessesthat have a more partitioned structure to an office will require the need to simultaneously heat or cool different sections of the office according to each usersindividual preferences.
The efficiency of this type of system comes from the ability to use the by-products of cooling and heating totransfer energy where it is required, thus acting as a balanced heat exchanger achieving up to 20% cost savings over a conventional heat pump system. The number of connection sites needed for an R2 systemare also significantly lower than those needed for a threepipe version. This helps to reduce installation costs, further increasing the savings associated with City Multi.
The BC Controller houses a liquid/gas separator, allowing the outdoor unit to deliver a mixture (2 phase)of hot gas for heating and liquid for cooling, all throughthe same pipe. Three pipe systems allocate a pipe toeach of these phases. When this mixture arrives at the BC Controller, it is separated and the correctphase delivered to each indoor unit depending on theindividual requirement of either heating or cooling.
How does the R2 Heat Recovery System operate on 2 Pipe’s?
The secret of City Multi heat recovery systems lies in the BC Controller
Comparison example of piping connection sites
= 3 sites= 2 sites
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
Energy efficiency has always been the driver for City Multi technological development. Technology that always delivers the quality and reliability needed for commercial air conditioning environments. Mitsubishi Electric spend more than 5% of their turnover on research and development, with our engineers always looking at ways in which we can improveand lead in Air Conditioning efficiency.
City Multi R410A YHM-A technology
Using the ver y latest in IPM (Intelligent Power Module) technology, precise control of energy input is achieved allowing City Multi to further improve COPs for R410A systems. IPM uses 1Hz steps of capacity control,matching building requirements through more accurate control of the occupied space with reduced power input. As in previous versions, IPM technology operates extremely effectively under par t load conditions (50-80% of operating capacity), a condition that most systems will be in for their normal working life. Therefore theconsideration of efficiency at part load is accounted for as well as when at peak load conditions, offering high system efficiency all year round.
Stable and smooth operation - 100% inverter control
All City Multi compressors are inverter-driven - Capable of precisely matching a building's cooling andheating demands.
The outdoor unit combinations comprise of one module for 8-18hp systems (for R2 up to 16hp), two modules for20-36hp systems (for R2, 18-32hp) and three modules for 38-50hp systems (Y series only). Each module carries one inverter compressor making simple and highly reliable control possible. Not only does it allow low starting currents,the inverter driven compressor also provides precise indoor comfort and adapts to the air conditioning load, achieving smooth transition across the range of compressor frequencies.
The technology to make
8
City Multi the
Y Series 8-18hp / R2 8-16hp Y Series 38-50hpY Series 20-36hp / R2 18-32hp
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
9
natural choiceHeat Interchange Unit
To further enhance the class leading efficiencyof City Multi, the unique Heat InterchangeCircuit provides extra sub cooling. This systemallows optimum refrigerant distribution tomultiple indoor units, by allowing more effective use of refrigerant flowing through theelectronic expansion valves. Because of theadded efficiency, volumes of refrigerantin systems are continuing to reduce.
The difference between YHM-A and previous Mitsubishi Electric models
Technology is key when increased efficiency is demanded. The City Multi YHM-A range is designed to deliver this.
A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerantcircuit (low pressure loss) including new accumulator design also adds a few more points to the efficiency scale. Enhancements to the heat interchange circuit, inverter driven fan motor and heat exchanger design, again add vitalincreases to overall system efficiency and COPs.
The importance of COP
COP stands for “Co-efficient of Performance”. It is a measure of the useful energy a system can deliver compared to the energy that it consumes. It is calculated by dividing the energy output by the energy input of a system. The higher the figure then the more efficient the system is deemed to be, with commensurate reduced running costs. For Heat Pumps to be included on the Energy Technology Product List under the Enhanced Capital Allowance scheme, they must achieve a heating COP of 3.4 and a cooling EER (energy efficiency ratio) of 3.0. Therefore every input of 1kW of energy must deliver an output of 3.4kW for heating and 3.0kW for cooling, achieving an energy label of B.
Total Energy Conservation
Comparison of COP (energy efficiency) of an 8hp YHM-A system.
CITY MULTI REFRIGERANT CIRCUIT
NORMAL REFRIGERANT CIRCUIT
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
10
A wide choice of models
The model line up
The new YHM-A outdoor models are modular in design and as such differingcombinations of them can be connected together to create the required outdoorunit size needed for a particular application.
Both the Y Series and R2 ranges come in standard (-P) and high COP (-EP) versions. In addition,the standard versions allow for space-saving by virtue of the combination of units having a smallerfoot print than the high COP versions.
Y Series Heat Pump - Standard Version
Series
Y
R2
Size
Model Name
PUHY-P YHM-A
PUHY-EP YHM-A
PURY-P YHM-A
PURY-EP YHM-A
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250
8hp 10hp 12hp 14hp 16hp 18hp 20hp 22hp 24hp 26hp 28hp 30hp 32hp 34hp 36hp 38hp 40hp 42hp 44hp 46hp 48hp 50hp
� � � � � � � � � � � � � � � � � � � � �
� � � � � � � � � � � � �
� � � � � � � � � � �
� � � � � � �
10hp
PUHY-P250YHM-A
12hp
PUHY-P300YHM-A
Y Series (10-12hp) PUHY-P YHM-A
28hp
PUHY-P700YSHM-A
30hp
PUHY-P750YSHM-A
32hp
PUHY-P800YSHM-A
Y Series (28-36hp) PUHY-P YSHM-A
14hp
PUHY-P350YHM-A
16hp
PUHY-P400YHM-A
18hp
PUHY-P450YHM-A
Y Series (14 -18hp) PUHY-P YHM-A
38hp
PUHY-P950YSHM-A
40hp
PUHY-P1000YSHM-A
Y Series (38 -40hp) PUHY-P YSHM-A
20hp
PUHY-P500YSHM-A
22hp
PUHY-P550YSHM-A
24hp
PUHY-P600YSHM-A
26hp
PUHY-P650YSHM-A
Y Series (20 -26hp) PUHY-P YSHM-A
42hp
PUHY-P1050YSHM-A
Y Series (42hp) PUHY-P YSHM-A
44hp
PUHY-P1100YSHM-A
46hp
PUHY-P1150YSHM-A
48hp
PUHY-P1200YSHM-A
50hp
PUHY-P1250YSHM-A
Y Series (44-50hp) PUHY-P YSHM-A
34hp
PUHY-P850YSHM-A
36hp
PUHY-P900YSHM-A
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
11
Y Series Heat Pump - High COP Version
8hp
PUHY-EP200YHM-A
12hp
PUHY-EP300YHM-A
Y Series - High COP (8-12hp) PUHY-EP YHM-A
Y Series - High COP (28-30hp) PUHY-EP YSHM-A
16hp
PUHY-EP400YSHM-A
18hp
PUHY-EP450YSHM-A
20hp
PUHY-EP500YSHM-A
Y Series - High COP (16-20hp) PUHY-EP YSHM-A
32hp
PUHY-EP800YSHM-A
34hp
PUHY-EP850YSHM-A
28hp
PUHY-EP700YSHM-A
30hp
PUHY-EP750YSHM-A
Y Series - High COP (32-34hp) PUHY-EP YSHM-A
Y Series - High COP (22-26hp) PUHY-EP YSHM-A
36hp
PUHY-EP900YSHM-A
Y Series - High COP (36hp) PUHY-EP YSHM-A
22hp
PUHY-EP550YSHM-A
24hp
PUHY-EP600YSHM-A
26hp
PUHY-EP650YSHM-A
R2 Series Heat Recovery - Standard Version
10hp
PURY-P250YHM-A
12hp
PURY-P300YHM-A
R2 Series (10-12hp) PURY-P YHM-A
R2 Series (26-28hp) PURY-P YSHM-A
R2 Series (14-16hp) PURY-P YHM-A
30hp
PURY-P750YSHM-A
32hp
PURY-P800YSHM-A
26hp
PURY-P650YSHM-A
28hp
PURY-P700YSHM-A
R2 Series (30-32hp) PURY-P YSHM-A
R2 Series (18-24hp) PURY-P YSHM-A
14hp
PURY-P350YHM-A
16hp
PURY-P400YHM-A
20hp
PURY-P500YSHM-A
22hp
PURY-P550YSHM-A
24hp
PURY-P600YSHM-A
R2 Series Heat Recovery - High COP Version
8hp
PURY-EP200YHM-A
12hp
PURY-EP300YHM-A
R2 Series - High COP (8-12hp) PURY-EP YHM-A R2 Series - High COP (16-18hp) PURY-EP YSHM-A
24hp
PURY-EP600YSHM-A
R2 Series - High COP (24hp) PURY-EP YSHM-A
R2 Series - High COP (20-22hp) PURY-EP YSHM-A
16hp
PURY-EP400YSHM-A
18hp
PURY-EP450YSHM-A
20hp
PURY-EP500YSHM-A
22hp
PURY-EP550YSHM-A
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
High off coil / High sensible cooling
Poor design or application of air conditioning systems can sometimes lead to cold draughts and uneven room temperatures. Low off coil temperatures cause dehumidifying of the air which can create dry eyes and sore throats.
Mitsubishi Electric now provides a High Sensible Cooling Function specifically designed to deal with this. By raisingthe off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the resultbeing greater comfort for occupants. These high SHF’s are available throughout the range of indoor units, allowingoptimum selection of units tailored to more specific design criteria.
Reduced noise levels
New fan designCity Multi VRF systems led the introduction of larger single fan rotors some ten years ago, achieving substantially lower noise levels over multiple designs. Continuing the development in the areas of blade shape and weight, Mitsubishi Electric have managed to achieve even higher performance and lower noise levels.
To reduce noise levels further and comply with inner city residential noise regulations, all outdoor units include NightSet-back mode. This function works by lowering the fan speed and compressor frequency proportionally with reduction in demand (44dBA for PUHY-P250YHM-A). The compressor compartment is also now sealed, further reducing noise levels.
Features & benefits
12
LowNoise
New fan designReduction of operation noise
New heat exchanger designImprovement of COP
New inverter compressorImprovement of COP
New control box designImprovement of reliability and easy maintenance
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
13
Acoustic kits
A range of Acoustic Kits designed for noise reduction are also available. An industry first, the kits offer a 10dBA noise level reduction from standard.
For supply and / or installation please contact Ambient Acoustics on 01934 712802
Cooling operation set temperature of 14ºC
Environments such as gyms, laboratories etc often require the ability to cool lower than the standard comfort cooling setpoint. By selecting a dip switch on the unit, a cooling operation set temperature of 14ºC DB is possible on the floorstanding and ducted models only. The indoor unit fan will be fixed at high speed during this operation.
Refrigerant volume checking function
This function runs the system, measuring various temperatures and pressures throughout the system, comparing these to the values stored in the units memory from the previous service. If a leakage has occurred the system will indicate so, enabling customers to easily comply with the F-Gas regulation.
Replace technology
This unique function allows the re-use of refrigerant piping, controllers, power and control wiring for all previously installed Mitsubishi Electric R22 and R407c Heat Recovery and Cooling only systems and partial replace of HeatPumps (pressure regulations require one pipe from the outdoor to the first branch to be replaced).
This function offers unprecedented savings on installation costs, disruption to business and down time, not to mention the considerable running cost and CO2 emission savings - more than halving the running costs compared toa 10 year old unit.
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
Features & benefits
14
Effective use of space
The new models have a smaller foot print requirement than previous models. The width and depth have been reduced by 7% and 13% respectively, with the height being reduced by 130mm. (PUHY-P250YHM-A compared toprevious YGM-A versions).
Weight reduction
Weight has been reduced by approximately 33kg
(PUHY-P250YHM-A compared to previous YGM-A versions).
YGM-A YHM-A
YGM-A YHM-A
8-12hp systems (Y / R2 Series) 1.43m2
14-18hp systems (Y Series)14-16hp systems (R2 Series)
1.89m2
mm
33kg
Approximately 21% reduction in foot print(PUHY-P250)
The unit can easily be transported, even into inaccessible buildings
The downsized outdoor unit can be transported through an 800mm wide lift door
The narrow space between buildings makes it difficult to use a crane 8-12hp outdoor units Example of lift
mm
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
Blue Fin treatment
The anti-corrosion Blue Fin treatment of the heat exchanger is especially effective in urban environments where the traffic pollutions can damage the aluminium fins reducing the capacity and life expectancy of the unit.
All City Multi R410A outdoor units have been treated with Blue Fin.
Heating operation range
At low ambient temperatures the guaranteed operating range in heating is minus 20ºC
Operating range in cooling is from anoutdoor temperature of -5ºC, while that in heating is from an outdoor temperature of -20ºC.
R410A pipe sizing
As R410A has a higher specific heat capacity than R22, the pipework is smaller. This means the pipe itself is cheaper, easier to install and less riser space is required within the building.
10hp model
15
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
� Reduced noiseReduced noise thanks to the use of a newly designed centrifugal fan and coil. The PEFY-P-VMS1-E is the quietest unit of its type in the market (22dBA - size 15).
� Ultra thin body Height of only 200mm and narrow width of 700mm (P15-32), 900mm (P40-50) and 1100mm (P63). This model can be easily installed into tight spaces such as ceiling cavities or drop ceilings.
� Low cooling operation set temperatureCooling operation set temperature can be set down to 14ºC DB when used with YHM-A.
� Static pressure5-50Pa
New indoor units for 2008
PEFY-P-VMS1-E Ceiling Concealed Ducted Unit
The ultra thin unit offers increased flexibility, and is particularly suitable for places where low noise operation is desired from a slim line body. This unit now comes in a size 15, ideal for hotel rooms!
P15Capacity
NoiseLevel
P20 P25 P32 P40 P50 P63
28 29 30 32 33 35 36
24 25 26 27 30 32 33
22 23 24 24 28 30 30
HighFan
Speed Med
Low
Noise level table (Standard static pressure) at 15Pa
Mor
e th
an 1
0mm
Mor
e th
an 2
0mm
Ceiling surface Access door
700mm
16
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
PFFY-P- VLRMM-E Floor Standing Concealed Unit
A compact concealed unit providing simple, effective air conditioning in perimeter zones. The unit is easy to install and at only 220mm deep offers an unobtrusive method of delivering highly efficient air-conditioningperformance.
� Reduced noiseNoise levels have been reduced compared to the previous PFFY-P-VLRM-E version.
� Low cooling operation set temperatureCooling operation set temperature can be set down to 14ºC dB when used with YHM-A.
� Static pressureThe new unit has 3 static pressure settings - 20/40/60Pa ideal for ducting in the perimeter zone.
� Concealed unit for hidden installation The unit can be hidden behind a wardrobe in a hotel, then ducted above and below the wardrobe doors. This offers lower noise, less disruption and a low visual impact.
17
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
18
Outdoor unit Y Series specifications
PUHY-P250YHM-A PUHY-P300YHM-A PUHY-P350YHM-A PUHY-P400YHM-A PUHY-P450YHM-A PUHY-P500YSHM-A PUHY-P550YSHM-A
Y Series Standard Outdoor Units 10-22hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
31.528.028.726.6
7.837.737.754.79
4.02 / 3.62
21
185
57
200
9207601710
380-415v, 50Hz
3
8
12.111.9
32
4 + earth
37.533.533.031.5
9.399.079.116.71
3.99 / 3.69
26
185
59
215
9207601710
380-415v, 50Hz
3
8
14.514.0
32
4 + earth
45.040.039.637.6
12.0911.2011.738.29
3.72 / 3.57
30
225
60
245
12207601710
380-415v, 50Hz
3
8
18.617.3
32
4 + earth
50.045.044.042.3
13.4713.2313.079.79
3.71 / 3.40
34
225
61
245
12207601710
380-415v, 50Hz
3
8
20.820.4
40
4 + earth
56.050.048.746.0
15.3816.2814.0011.40
3.64 / 3.07
39
225
62
245
12207601710
380-415v, 50Hz
3
8
23.725.1
50
4 + earth
63.056.054.851.5
16.4016.4714.9211.53
3.84 / 3.40
43
185 / 185
60
200 + 200
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
25.325.4
32 / 32
4 + earth
69.063.060.058.0
18.0618.3616.4312.85
3.82 / 3.43
47
185 / 185
60.5
200 + 215
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
27.928.3
32 / 32
4 + earth
PUHY-P600YSHM-A PUHY-P650YSHM-A PUHY-P700YSHM-A PUHY-P750YSHM-A PUHY-P800YSHM-A PUHY-P850YSHM-A PUHY-P900YSHM-A
Y Series Standard Outdoor Units 24-36hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
76.569.066.663.5
19.9218.7518.1313.13
3.84 / 3.68
50
185 / 225
60.5
200 + 245
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
30.728.9
32 / 32
4 + earth
81.573.070.967.2
21.9020.7919.9314.55
3.72 / 3.51
50
185 / 225
61
215 + 245
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
33.832.1
32 / 32
4 + earth
88.080.075.773.6
23.7122.4722.0516.18
3.71 / 3.56
50
225 / 225
61
245 + 245
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
36,634.7
32 / 32
4 + earth
95.085.081.778.2
25.4625.0723.6818.05
3.73 / 3.39
50
225 / 225
63
245 + 245
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
39.338.7
40 / 32
4 + earth
100.090.086.082.8
25.7027.6923.9019.94
3.89 / 3.25
50
225 / 225
64
245 + 245
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
39.742.8
50 / 32
4 + earth
108.096.095.088.3
28.4230.1826.1519.92
3.80 / 3.18
50
225 / 225
64.5
245 + 245
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
43.946.6
50 / 40
4 + earth
113.0101.099.492.9
30.2933.3327.8722.00
3.73 / 3.03
50
225 / 225
64.5
245 + 245
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
46.851.5
50 / 50
4 + earth
PUHY-P950YSHM-A PUHY-P1000YSHM-A PUHY-P1050YSHM-A PUHY-P1100YSHM-A PUHY-P1150YSHM-A PUHY-P1200YSHM-A PUHY-P1250YSHM-A
Y Series Standard Outdoor Units 38-50hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
119.5108.0105.299.4
30.0230.6827.6220.25
3.98 / 3.52
50
185 / 185 / 185
64
200 + 215 + 245
920 + 920 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
46.447.4
40 / 32 / 32
4 + earth
127.0113.0111.8104.0
33.1532.4730.5021.43
3.83 / 3.48
50
185 / 185 / 225
64
215 + 215 + 245
920 + 920 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
51.250.1
40 / 32 / 32
4 + earth
132.0118.0116.2108.6
35.0133.9032.2122.37
3.77 / 3.48
50
185 / 225 / 225
64
200 + 245 + 245
920 + 1220 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
54.152.4
40 / 32 / 32
4 + earth
140.0124.0123.2114.1
36.9335.8333.9823.65
3.79 / 3.46
50
225 / 225 / 225
64
245 + 245 + 245
1220 + 1220 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
57.055.3
40 / 32 / 32
4 + earth
145.0130.0127.6119.6
39.0839.3935.9526.00
3.71 / 3.30
50
225 / 225 / 225
64.5
245 + 245 + 245
1220 + 1220 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
60.460.8
50 / 32 / 32
4 + earth
150.0136.0132.0125.1
40.1041.7136.8927.53
3.74 / 3.26
50
225 / 225 / 225
65
245 + 245 + 245
1220 + 1220 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
61.964.4
50 / 40 / 32
4 + earth
156.5140.0137.7128.8
42.0645.0138.7029.71
3.72 / 3.11
50
225 / 225 / 225
65.5
245 + 245 + 245
1220 + 1220 + 1220760 + 760 + 7601710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
65.069.5
50 / 50 / 32
4 + earth
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
19
PUHY-EP200YHM-A PUHY-EP300YHM-A PUHY-EP400YSHM-A PUHY-EP450YSHM-A PUHY-EP500YSHM-A PUHY-EP550YSHM-A PUHY-EP600YSHM-A
Y Series High COP Outdoor Unit 8-24hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
25.022.423.021.3
5.775.185.713.21
4.33 / 4.32
17
185
57
200
9207601710
380-415v, 50Hz
3
8
8.98.0
20
4 + earth
37.533.533.031.5
9.288.259.006.11
4.04 / 4.06
26
225
60
245
12207601710
380-415v, 50Hz
3
8
14.312.7
32
4 + earth
50.045.044.042.3
11.5410.4111.197.70
4.33 / 4.32
34
185 / 185
60
200 + 200
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
17.816.0
20 / 20
4 + earth
56.050.048.746.0
13.0513.1511.889.21
4.29 / 3.80
39
185 / 185
60
200 + 200
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
20.120.3
32 / 20
4 + earth
63.056.054.851.5
15.1413.4613.789.42
4.16 / 4.16
43
185 / 225
62
200 + 245
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
23.420.8
32 / 20
4 + earth
69.063.060.058.0
17.1216.3215.5811.42
4.03 / 3.86
47
185 / 225
62
200 + 245
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
26.425.2
32 / 32
4 + earth
76.569.066.663.5
18.9316.9917.2311.89
4.04 / 4.06
50
225 / 225
63
245 + 245
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
29.226.2
32 / 32
4 + earth
PUHY-EP650YSHM-A PUHY-EP700YSHM-A PUHY-EP750YSHM-A PUHY-EP800YSHM-A PUHY-EP850YSHM-A PUHY-EP900YSHM-A
Y Series High COP Outdoor Unit 26-36hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
81.573.070.967.2
19.1318.3417.4112.84
4.26 / 3.98
50
225 / 225
63
245 + 245
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
29.528.3
32 / 32
4 + earth
88.080.075.773.6
20.0020.9918.6015.11
4.40 / 3.81
50
185 / 185 / 225
63
200 + 200 + 245
920 + 920 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
30.932.4
32 / 20 / 20
4 + earth
95.085.081.778.2
22.1921.7920.6415.69
4.28 / 3.90
50
185 / 185 / 225
63
200 + 200 + 245
920 + 920 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
34.333.6
32 / 32 / 20
4 + earth
100.090.086.082.8
23.4122.0021.7715.84
4.27 / 4.09
50
185 / 225 / 225
64
200 + 245 + 245
920 +1220 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
36.134.0
32 / 32 / 20
4 + earth
108.096.095.088.3
25.5924.6723.5416.28
4.22 / 3.89
50
185 / 225 / 225
64
200 + 245 + 245
920 +1220 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
39.538.1
32 / 32 / 32
4 + earth
113.0101.099.492.9
27.9024.8725.6716.41
4.05 / 4.06
50
225 / 225 / 225
65
245 + 245 + 245
1220 +1220 + 1220760 + 760 + 760
1710 + 1710 + 1710
380-415v, 50Hz
3
8 / 8 / 8
43.138.4
32 / 32 / 32
4 + earth
Y Series Piping Restrictions
Total Piping LengthFurthest Piping LengthFurthest Piping Length After 1st BranchBetween Indoor and Outdoor Units - HeightBetween Indoor and Indoor Units - Height
1000m max165m max40m max50m max (40m max if outdoor installed below)15m max
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
20
Outdoor unit R2 Series specifications
PURY-P250YHM-A PURY-P300YHM-A PURY-P350YHM-A PURY-P400YHM-A PURY-P500YSHM-A PURY-P550YSHM-A
R2 Series Standard Outdoor Unit 10-22hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
31.528.028.726.6
7.837.737.754.79
4.02 / 3.62
25
185
57
235
9207601710
380-415v, 50Hz
3
8
12.111.9
32
4 + earth
37.533.533.031.5
9.589.259.296.85
3.91 / 3.62
30
185
59
240
9207601710
380-415v, 50Hz
3
8
14.814.2
32
4 + earth
45.040.039.637.6
12.4712.4712.109.23
3.60 / 3.20
35
225
60
265
12207601710
380-415v, 50Hz
3
8
19.219.2
32
4 + earth
50.045.044.042.3
13.7113.7413.3010.17
3.64 / 3.27
40
225
61
265
12207601710
380-415v, 50Hz
3
8
21.121.2
40
4 + earth
63.056.054.851.5
16.7916.7515.2811.73
3.75 / 3.34
48
185 / 185
60
235 + 235
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
25.925.8
32 / 32
4 + earth
69.063.060.058.0
18.8118.6817.1213.08
3.66 / 3.37
48
185 / 185
61
235 + 240
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
29.028.8
32 / 32
4 + earth
PURY-P600YSHM-A PURY-P650YSHM-A PURY-P700YSHM-A PURY-P750YSHM-A PURY-P800YSHM-A
R2 Series Standard Outdoor Unit 24-32hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
76.569.066.663.5
20.8319.6418.9613.75
3.67 / 3.51
48
185 / 185
62
240 + 240
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
32.130.3
32 / 32
4 + earth
81.573.070.967.2
22.5522.8020.5215.96
3.61 / 3.20
48
185 / 225
62.5
240 + 265
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
34.835.2
32 / 32
4 + earth
88.080.075.773.6
24.3024.7222.6017.80
3.62 / 3.23
48
185 / 225
63
240 + 265
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
37.538.2
40 / 32
4 + earth
95.085.081.778.2
26.3627.8624.5120.06
3.60 / 3.05
48
225 / 225
63.5
265 + 265
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
40.743.0
40 / 32
4 + earth
100.090.086.082.8
27.6429.7525.7121.42
3.61 / 3.02
48
225 / 225
64
265 + 265
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
42.745.9
40 / 40
4 + earth
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
21
PURY-EP200YHM-A PURY-EP300YHM-A PURY-EP400YSHM-A PURY-EP450YSHM-A PURY-EP500YSHM-A PURY-EP550YSHM-A PURY-EP600YSHM-A
R2 Series High COP Outdoor Unit 8-24hp
Model ReferenceCapacity (kW) Heating (nominal)
Cooling (nominal)Heating (UK)Cooling (UK)
Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)
COP/EER (nominal)
Max No. of Connectable Indoor Units
Airflow (m3/min) High
Noise (dBA)
Weight (kg)
Dimensions (mm) WidthDepth
(1650mm without legs) Height
Electrical Supply
Phase
Starting Current (A)
Running Current (A) HeatingCooling
Fuse Rating (MCB sizes BS EN 60947-2) - (A)
Mains Cable No. Cores
25.022.423.021.3
5.815.235.753.24
4.30 / 4.28
20
185
57
235
9207601710
380-415v, 50Hz
3
8
8.98.0
20
4 + earth
37.533.533.031.5
9.378.339.096.16
4.00 / 4.02
30
225
60
265
12207601710
380-415v, 50Hz
3
8
14.412.8
32
4 + earth
50.045.044.042.3
11.7310.5711.387.82
4.26 / 4.25
40
185 / 185
60
235 + 235
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
18.116.3
20 / 20
4 + earth
56.050.048.746.0
13.7713.0912.539.16
4.06 / 3.81
45
185 / 185
60
235 + 235
920 + 920760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
21.220.2
32 / 20
4 + earth
63.056.054.851.5
15.3313.7013.959.59
4.10 / 4.08
48
185 / 225
62
235 + 265
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
23.621.1
32 / 20
4 + earth
69.063.060.058.0
17.3716.3815.8111.47
3.97 / 3.84
48
185 / 225
62
235 + 265
920 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
26.825.3
32 / 32
4 + earth
76.569.066.663.5
19.1217.0017.4011.90
4.00 / 4.05
48
225 / 225
63
265 + 265
1220 + 1220760 + 760
1710 + 1710
380-415v, 50Hz
3
8 / 8
29.526.2
32 / 32
4 + earth
Outdoor Model Max LengthTable 1: Total Piping LengthR2 Series Piping Restrictions
Graph 1: Total Piping Length Restrictions
P250, P300P350, P400, EP200, EP300P500, P550, EP400, EP450, EP500, EP550P600, P650, EP600P700, P750, P800
550m*1
600m*1
750m*1
800m*1
950m*1
*1 Please refer to Graph 1
1000
PURY-P700,750,800 YSHM-A
PURY-P600,650,800 YSHM-A, PURY-EP600YSHM-A
PURY-P500,550 YSHM-A, PURY-EP400,450,500,550 YSHM-A
PURY-P350,400 YHM-A, PURY-EP200,300 YHM-A
PURY-P250,300YHM-A
900
800
700
600
500
400
300
200
100
0
10 20 30 40 50 60 70 80 90 100 110
Tota
l Ext
ende
d Pi
pe L
engt
h (m
)
Distance Between Outdoor Unit and BC Controller (m)
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
22
R2 Series Piping Restrictions
Item Pipe Section Max Length
R2 Series Piping Restrictions
Piping Length (1 BC Controller, No Sub BC Controller)
Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IU
A+B+a+b+c+dA+B+d
AB+dHH1
h1h2
(See Table 1)165m
110m*1
60m*2 (40m)50m40m15m15m
*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
Item Pipe Section Max Length
R2 Series Piping Restrictions
Piping Length (>1 BC Controller for 1 Outdoor Unit)
Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IUHeight Between BC (Main or Sub) and BC (Sub)
A+B+C+D+E+a+b+c+d+e+fA+C+E+f
AB+d or C+D+e or C+E+f
HH1
h1h2h3
(See Table 1)165m
110m*1
60m*2 (40m)50m40m15m15m15m
*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
2323
Item Pipe Section Max Length
R2 Series Piping Restrictions
Piping Length (>1 BC Controller for 2 Outdoor Units)
Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IUHeight Between BC (Main or Sub) and BC (Sub)Length Between Main OU and Sub OUHeight Between Main OU and Sub OU
F+G+A+B+C+D+E+a+b+c+d+e+fF(G)+A+C+E+f
F(G)+AB+d or C+D+e or C+E+f
HH1
h1h2h3
F+G or Hh4
(See Table 1)165m
110m*1
60m*2 (40m)50m40m15m15m15m5m
0.1m
*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
BC Controllers
CMB-P104V-G CMB-P105V-G CMB-P106V-G
BC Controllers
Model ReferenceNumber of Connections
Weight (kg)
Dimensions (mm) WidthDepthHeight
Electrical Supply
Phase
Power Input (kW)
Running Current (A)
Fuse Rating (BS88) - HRC (A)
Mains Cable No. Cores
4
24
648362 + 70
284
220-240v, 50Hz
Single
0.085
0.36
6
3
5
27
648362 + 70
284
220-240v, 50Hz
Single
0.104
0.44
6
3
6
29
648362 + 70
284
220-240v, 50Hz
Single
0.123
0.52
6
3
CMB-P104V-GB
Slave BC ControllersModel ReferenceNumber of Connections
Weight (kg)
Dimensions (mm) WidthDepthHeight
Electrical Supply
Phase
Power Input (kW)
Running Current (A)
Fuse Rating (BS88) - HRC (A)
Mains Cable No. Cores
4
22
648362 + 70
284
220-240v, 50Hz
Single
0.076
0.32
6
3
CMB-P108V-GB
8
32
648362 + 70
284
220-240v, 50Hz
Single
0.151
0.63
6
3
CMB-P108V-GA
Master BC Controllers
Model ReferenceNumber of Connections
Weight (kg)
Dimensions (mm) WidthDepthHeight
Electrical Supply
Phase
Power Input (kW)
Running Current (A)
Fuse Rating (BS88) - HRC (A)
Mains Cable No. Cores
8
44
1110450 + 70
289
220-240v, 50Hz
Single
0.161
0.68
6
3
CMB-P1010V-GA
10
49
1110450 + 70
289
220-240v, 50Hz
Single
0.198
0.83
6
3
CMB-P1013V-GA
13
57
1110450 + 70
289
220-240v, 50Hz
Single
0.255
1.07
6
3
CMB-P1016V-GA
16
64
1110450 + 70
289
220-240v, 50Hz
Single
0.312
1.30
6
3
CMB-P1016V-HA
16
73
1110450 + 70
289
220-240v, 50Hz
Single
0.312
1.30
6
3
CMB-P1016V-HB
16
57
1098362 + 70
284
220-240v, 50Hz
Single
0.301
1.26
6
3
Note: CMB-P-V-G units are for use with PURY-(E)P200-350 YHM-A outdoor unit only.
Note: CMB-P-V-GA units are for use with PURY-(E)P200-650Y(S)HM-A outdoor units only. CMB-P1016V-HA unit is for use with PURY-P700-800YSHM-A outdoor units only.
Note: CMB-P1016V-HB can be connected to a CMB-P1016V-HA.
24
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
25
Indoor unit specifications
PEFY-P15VMS1-E
PEFY-P-VMS1-E
Model Reference
Capacity (kW) Heating (nominal)
Cooling (nominal)
R410A Heating (UK)
R410A Cooling (UK)
R410A High Sensible Cooling (UK)
SHF R410A (UK)
High Sensible R410A (UK
Power Input (kW) Heating (nominal)
Cooling (nominal)
Airflow (m3/min) Lo-Mi-Hi
External Static Pressure (Pa) Lo-Mi1-Mi2-Hi
Noise (dBA) (5Pa) Lo-Mi-Hi
Weight (kg)
Dimensions (mm) Width
Depth
Height
Electrical Supply
Phase
Running Current (A) Heating
Cooling
Fuse Rating (BS88) - HRC (A)
Mains Cable No. Cores
1.9
1.7
1.8
1.5
1.2
0.93
1.00
0.03
0.05
5.0-6.0-7.0
5-15-35-50
22-24-28
19
700
700
200
220-240v, 50Hz
Single
0.31
0.42
6
3
PEFY-P20VMS1-E
2.5
2.2
2.3
2.0
1.6
0.85
1.00
0.03
0.05
5.5-6.5-8.0
5-15-35-50
23-25-29
19
700
700
200
220-240v, 50Hz
Single
0.36
0.47
6
3
PEFY-P25VMS1-E
3.2
2.8
3.0
2.5
2.0
0.84
0.90
0.04
0.06
5.5-7.0-9.0
5-15-35-50
24-26-30
19
700
700
200
220-240v, 50Hz
Single
0.39
0.50
6
3
PEFY-P32VMS1-E
4.0
3.6
3.7
3.2
2.6
0.78
0.85
0.05
0.07
6.0-8.0-10.0
5-15-35-50
24-27-32
20
700
700
200
220-240v, 50Hz
Single
0.39
0.50
6
3
PEFY-P40VMS1-E
5.0
4.5
4.6
4.0
3.3
0.75
0.82
0.05
0.07
8.0-9.5-11.0
5-15-35-50
28-30-33
24
900
700
200
220-240v, 50Hz
Single
0.45
0.56
6
3
6.3
5.6
5.8
5.0
4.1
0.74
0.78
0.07
0.09
9.5-11.0-13.0
5-15-35-50
30-32-35
24
900
700
200
220-240v, 50Hz
Single
0.56
0.67
6
3
PEFY-P63VMS1-E
8.0
7.1
7.4
6.3
5.2
0.75
0.79
0.07
0.09
12.0-14.0-16.5
5-15-35-50
30-33-36
28
1100
700
200
220-240v, 50Hz
Single
0.61
0.72
6
3
PEFY-P50VMS1-E
PFFY-P20VLRMM-E
PFFY-P-VLRMM-E
Model Reference
Capacity (kW) Heating (nominal)
Cooling (nominal)
R410A Heating (UK)
R410A Cooling (UK)
R410A High Sensible Cooling (UK)
SHF R410A (UK)
High Sensible R410A (UK)
Power Input (kW) Heating (nominal)
Cooling (nominal)
Airflow (m3/min) Lo-Mi-Hi
External Static Pressure (Pa) Lo-Mi-Hi
Noise (dBA) (20Pa) Lo-Mi-Hi
Weight (kg)
Dimensions (mm) Width
Depth
Height
Electrical Supply
Phase
Running Current (A) Heating
Cooling
Fuse Rating (BS88) - HRC (A)
Mains Cable No. Cores
2.5
2.2
2.3
2.0
1.6
0.80
0.88
0.04
0.04
4.5-5.5-6.5
20-40-60
31-36-40
18.5
886
220
639
220-240v, 50Hz
Single
0.34
0.34
6
3
PFFY-P25VLRMM-E
3.2
2.8
3.0
2.5
2.0
0.76
0.80
0.04
0.04
4.5-5.5-6.5
20-40-60
31-36-40
18.5
886
220
639
220-240v, 50Hz
Single
0.34
0.34
6
3
PFFY-P32VLRMM-E
4.0
3.6
3.7
3.2
2.6
0.75
0.81
0.04
0.04
6.5-7.5-9
20-40-60
27-32-37
20
1006
220
639
220-240v, 50Hz
Single
0.38
0.38
6
3
PFFY-P40VLRMM-E
5.0
4.5
4.6
4.0
3.3
0.75
0.79
0.05
0.05
8-9.5-11
20-40-60
30-36-40
21
1006
220
639
220-240v, 50Hz
Single
0.43
0.43
6
3
PFFY-P50VLRMM-E
6.3
5.6
5.8
5.0
4.1
0.76
0.80
0.05
0.05
10-12-14
20-40-60
32-37-41
25
1246
220
639
220-240v, 50Hz
Single
0.48
0.48
6
3
8.0
7.1
7.4
6.3
5.2
0.73
0.79
0.07
0.07
11-13-15.5
20-40-60
35-40-44
27
1246
220
639
220-240v, 50Hz
Single
0.59
0.59
6
3
PFFY-P63VLRMM-E
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
26
Accessories / Optional Extras
CMY-Y102S-G2CMY-Y102L-G2CMY-Y202-G2CMY-Y302-G2CMY-Y104-GCMY-Y108-GCMY-Y1010-GCMY-Y62-G-ECMY-Y100VBK2CMY-Y200VBK2CMY-Y300VBK2CMY-R100VBKCMY-R200VBKACH1ACOUSTIC KIT
PLP-6BASLP-2AAPAC-SH53TM-EPAC-SH59KF-EPLP-6BALMPLP-6BAJPAC-SA1ME-EPAR-SA9FA-ES70E40714
CMP-P40VLW-BCMP-P63VLW-BCMP-P100VLW-BCMP-P125VLW-BPAC-KH11OF
PMP-40BM
PAC-KE03DM-FPAC-KE04DM-FPAC-KE88LAFPAC-KE89LAFPAC-KE80TB-FPAC-KE140TB-F
CMY-R160-JCMY-Y102S-G
PAC-SE41TS-E
- Branch Pipe (Joint) for size 200 or below - total capacity of indoor units- Branch Pipe (Joint) for size 201-400 - total capacity of indoor units- Branch Pipe (Joint) for size 401-650 - total capacity of indoor units or first branch of P500-P650- Branch Pipe (Joint) for size 651 or above - total capacity of indoor units or first branch of P700-P1250- Branch Pipe (Header) for 4 branches- Branch Pipe (Header) for 8 branches- Branch Pipe (Header) for 10 branches- Branch Pipe for 2 branches (PUMY)- Twinning Kit for PUHY-P500-650YSHM-A / PUHY-EP400-650YSHM-A- Twinning Kit for PUHY-P700-900YSHM-A- Twinning Kit for PUHY-P950-1250YSHM-A / PUHY-EP700-900YSHM-A- Twinning Kit for PURY-P500-650YSHM-A / PURY-EP400-600YSHM-A- Twinning Kit for PURY-P700-800YSHM-A- PQFY Auto-Changeover controller- Acoustic kits for PUHY and PURY units
- Grille for PLFY-P-VBM-E- Grille for PLFY-P-VCM-E- Multi-function casement for PLFY-P-VBM-E- High efficiency filter for PLFY-P-VBM-E- Grille and infra-red controller for PLFY-P-VBM-E- Grille with filter lowering function for PLFY-P-VBM-E- ‘I See Sensor’ corner panel for PLFY-P-VBM-E- Infra-red signal receiver for PLFY-P-VBM-E- Infra-red Controller (PAR-SL97A-E) for PLFY-P-VBM-E
- Grille for PLFY-P20-40VLMD-E- Grille for PLFY-P50-63VLMD-E- Grille for PLFY-P80-100VLMD-E- Grille for PLFY-P125VLMD-E- OA duct flange for PLFY-P20-100VLMD-E
- Grille for PMFY-P-VBM-E
- Drain lift-up mechanism for PEFY-P-VMM-E- Drain lift-up mechanism for PEFY-P-VMH-E- Long life filter for PEFY-P80VMH-E- Long life filter for PEFY-P100-140VMH-E- Filter box for PEFY-P80VMH-E (necessary when long life filter is used)- Filter box for PEFY-P100-140VMH-E (necessary when long life filter is used)
- Joint pipe- Branch pipe
- Remote sensor
Outdoor Units
4-Way Blow Cassette Units
2-Way Blow Cassette Units
1-Way Blow Cassette Units
Ceiling Concealed Ducted Units
BC Controllers
Indoor Units
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
Constant &comfortableindoor climateswith the new City MultiYHM-A range
For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.
UNITED KINGDOM Mitsubishi Electric Europe Air Conditioning Systems DivisionTravellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. General enquiries Tel: 01707 282880 Fax: 01707 278674
IRELAND Mitsubishi Electric Europe Westgate Business Park, Ballymount, Dublin 24, Ireland. Tel: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531)
Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2008. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.
Printed in January 2008
SAP No. 212984
Telephone: 01707 282880Post Sales Technical Support: 0870 3000 300Spares and Warranty Support: 0870 3000 800
email: [email protected] web: www.mitsubishielectric.co.uk/aircon