chilled water / hot water belt drive · chilled water / hot water 600 through 10,000 cfm 600 -...
TRANSCRIPT
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-1-
BELT DRIVEProduct Specifications
Horizontal / VerticalChilled Water / Hot Water
600 THROUGH 10,000 CFM
600 - 10000 CFM HORIZONTAL(24ASHW - 240ASHW)
Features 2Specifications 3Nomenclature & Selection Procedure 424-60ASHW Physical Data 590-240ASHW Physical Data 624-60ASVW Physical Data 790-240ASVW Physical Data 8Mixing Dampers 9Electric Heat 10Spring Isolators 11Motor Control Box 12Blower Static 13Component Static Resistance 14Blower performance 15Cooling Performance 16-19Heating Performance 20-22Coil Connections 23
Table of Contents
600 - 10000 CFM VERTICAL(24ASVW - 240ASVW)
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-2-
FEATURESProduct SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
STANDARD FEATURES
Cabinets: External and internal parts are made with heavy gauge galvanized steel. Large access panels are provided to permit full access to internal components.
Insulation: 1” 1.5 lb density IAQ fiberglass insulation. Insulation meets the following requirements of ASTM C 1071, ASTM G 21, ASTM G22, NFPA 90A and UL-181.
Coils: Coils are staggered tube type constructed with seamless copper tubes and headers, corrugated alu-minum fins with straight edges. Coils are tested at 350 PSI for operation at 300 PSI.
Drain Pans: Sloped for positive drainage and fabri-cated of heavy gauge galvanized steel, and coated for corrosion protection.
Fan Wheels: Double width, double inlet, and forward curved, centrifugal type. Wheels are statically and dy-namically balanced for smooth, quiet operation.
Fan Housing: Constructed of heavy gauge galva-nized steel with die-formed inlet cones. Bearings are self-aligning, sealed cartridge, permanently lubricated ball bearings that are rubber mounted and provide an average life of 100,000 hours.
Motors and Drives: Belt drive motors are standard duty, 1725 RPM, open, drip-proof construction. Single-phase motors are resilient mount with automatic reset thermal protection. Motor sheaves are variable pitch, cast iron with a split-tapered hub. Standard motors are factory wired to a junction box.
Filters: 1” disposable type.
Mixing Boxes: 3/4” 1.5 lb density IAQ fiberglass insula-tion. Low leak damper assemblies are constructed of welded steel channel frames with 18 gauge galvanized steel blades, die formed stiffeners and full blade stop. Stainless steel side seals and vinyl blade seals, hardware is zinc plated with brass pivot points and bronze oilite bearings. Shafts shall be corrosion resistant steel.
OPTIONS
Cabinets: Insulated discharge plenum with factory mounted four way double deflection grille.
Insulation: 1” 3 lb density foil faced fiberglass board with sealed edges
Coils: Available coils are 2, 4, or 6 row for chilled water or hot water applications. 2-row hot water coils can be installed in preheat or reheat positions. LH or RH coil connections are available.
Drain Pans: Stainless Steel sloped for positive drain-age, and coated for corrosion protection.
Electric Heat: Discharge mounted electric heat available in a wide range of KW’s and voltages. Avail-able voltages are 120/1/60, 208/230/1/60, 277/1/60, 208/230/460/3/60, 575/3/60, 110/220/1/50, and 220/380/440-3-50.
Spring Isolators: Kits are available by unit size and coil rows with and without mixing boxes.
Motors and Drives: Two speed, TEFC, or (HE) high efficient. Available voltages are 120/1/60, 208/230/1/60, 277/1/60, 208/230/460/3/60, 575/3/60, 110/220/1/50, and 220/380/440-3-50.
Motor Control Box: For use with standard motors with internal overload protection. The 986FF control box is factory installed and wired. Features include a Disconnect switch, HOA switch, power fusing, motor contactor, 24V control transformer and low voltage terminal block.
Motor Control Starters: For use with non-standard motors without internal overload protection. The 986FR starter box is factory installed and wired. Features in-clude a non-fused disconnect switch with thru-the-door pad lockable handle, HOA switch, built-in overload and magnetic trip, 24V control transformer and low voltage terminal block.
Filters: 2” disposable or 2 “ pleated.
Mixing Boxes: Dampers can be positioned for rear/top or rear/bottom configurations.
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
GUIDESPECIFICATIONS
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
GUIDE SPECIFICATIONS
Contractor shall furnish and install high quality air handling units as indicated on plans. Sizes and capacities shall be shown in the Unit Schedule included on the drawings. All units shall be the products of Applied Environmental Air (AE-Air) series fan coils and listed by UL or ETLC (listed in accordance with UL 1995.) Units shall be designed, tested and manufactured in ac-cordance with ARI-410, 430, 440 and 350.
Cabinets shall be fabricated of lock forming quality (min) steel. External and internal parts are to be made with heavy gauge galvanized steel. Large access panels shall be provided to permit full access to internal components. The structural integrity of the cabinets shall remain unaf-fected by the removal of any or all access panels.
Insulation shall be blanket-type made from glass fibers bonded with a thermosetting resin. Insulation shall be one and-one-half pound density providing effective acoustical and thermal control, fire safety, and resistance to air erosion. This insulation must meet the requirements of ASTM C 1071, ASTM G 21, ASTM G22, NFPA 90A and UL-181.
Coils shall be of the staggered tube type constructed with seamless copper tubes and headers, and deep corrugated aluminum fins with straight edges. Manufacturer shall supply full depth collars, drawn in the fin stock to provide accurate control of fin spacing and completely cover the copper tubes to lengthen coil life. The tubes are to be mechanically expanded into the fins for a permanent primary to secondary surface bond, assuring maximum heat transfer efficiency. The coils are to be tested at 350 PSI for operation at 300 PSI gauge. The coils provided shall be suitable for the application and comply with the required performance as described in the Unit Schedule.
Drain pans shall be positive drainage and shall be fabricated of heavy gauge galvanized steel or optional 304 stainless steel and coated for corrosion protection.
Fan Wheels shall be double width, double inlet, forward curved, centrifugal type. They shall be statically and dynamically balanced for smooth, quiet operation. The housing shall be construct-ed of heavy gauge steel with die-formed inlet cones.
Motors and Drives: Belt drive motors are standard duty, 1725 RPM, open, drip-proof construc-tion. Single-phase motors are resilient mount with automatic reset thermal protection. Motor sheaves are variable pitch, cast iron with a split-tapered hub. Standard motors are factory wired to a junction box.
Filters are to be disposable type. They shall be center loading with an 85% arrestance efficien-cy. The filters shall be included in the units as an integral part of the cabinet with easy access provided by the manufacturer.
-3-
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-4-
Nom. CLG BTU’S (1,000’s)
Series
Commercial air handler
H-Horizontal air handler V-Vertical air handler Standard coil type: W = water
MODEL NUMBERING SYSTEM
Factory installed hot water coil options
120 A S H W 4 - # - 2
UNIT SELECTION PROCEDURE
INFORMATION REQUIRED FOR UNIT SELECTION
System Type ( circle one) : 2 - pipe (1 coil ) or 4 - pipe ( sep. htg. & clg. coils )
CFM ________ E.S.P. ____ MOTOR: HP:_________VOLTAGE:_______PHASE:________
COOLING: INDOOR: DB _________ WB _____________OUTDOOR: DB___________
TOTAL BTUH__________SENS. BTUH ____________ GPM __________EWT __________
HEATING: TOTAL BTUH ___________GPM___________EWT___________EAT___________
MISC: ___________
NOMENCLATURESELECTION PROCEDURE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Motor Options
Rows in coil: 2 = 2 rows 4 = 4 rows 6 = 6 rows
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-5-
��������������
����������������
������������
����������
��������������������������������������
�� �� �� �� �� �� �� �� � � � � � � � � � �
������� �� ������ �� ������ ����� ������ �� ������ ������ ������ ����� ����� ����� ������� � ������� �� ��
�� �� ������ ������ ������ ������ ������ ������ ������ ������ ����� ����� ����� ������� � ������� �� ��
�� ������ �� ������ ������ ������ �� ������ ������ ������ ����� ����� ����� ������� � ������� �� ��
�� ������ �� ������ �� ������ �� ������ ������ ������ ����� ����� ����� ������� � ������� �� ��
�� ������ �� ������ ����� ������ �� ������ �������� ������ ����� ����� ����� ������� � ������ �� ������
�� �� ������ ������ ������ ������ ������ ������ �������� ������ ����� ����� ����� ������� � ������ �� ������
�� ������ �� ������ ������ ������ �� ������ �������� ������ ����� ����� ����� ������� � ������ �� ������
�� ������ �� ������ �� ������ �� ������ �������� ������ ����� ����� ����� ������� � ������ �� ������
������ ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������
�������
�������
�������
�������
�������
�������
�������
K
F
HJ
E
C
BA
D
DDFF
EE
CC
BB
AIR FLOW
AA
G
2.003.50
3.501.00
AIR FLOW HH
GG
GENERAL SPECIFICATIONS
MODELNOM.COOLTONS
FACEAREASQ. FT.
TUBESIZE
BLOWERSIZE
FILTERSIZE
2 ROW COIL 4 ROW COIL 6 ROW COIL
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
24ASHW 2 2.05 3/8 9 x 6 16 x 25 7/8” O/D (SWT) 18 7/8” O/D (SWT) 185 7/8” O/D (SWT) 205
36ASHW 3 3.05 3/8 9 x 9 16 x 16 (2) 7/8” O/D (SWT) 22 7/8” O/D (SWT) 205 7/8” O/D (SWT) 225
48ASHW 4 4.0 3/8 10 x 10 16 x 20 (2) 7/8” O/D (SWT) 30 7/8” O/D (SWT) 240 7/8” O/D (SWT) 265
60ASHW 5 5.0 3/8 12 x 12 20 x 20 (2) 7/8” O/D (SWT) 38 1-1/8” O/D (SWT) 290 1-1/8” O/D (SWT) 310
NOTES: 1) All technical specifications subject to change without notice.
24ASHW - 60ASHWPHYSICAL DATA
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-6-
��������������
����������������
������������
����������
��������������������������������������
�� �� �� �� �� �� �� � � � � � � � � � � �
������� ������ �� �� ������ ������ �� ������ ������ ����� ������ ����� ������ ������ � ����� ������ ������ �
������ �� �� ������ ������ �� ������ ������ ����� ������ ����� ������ ������ � ����� ������ ������ �
������ �� ������ ������ ������ �� ������ ������ ����� ������ ����� ������ ������ � ����� ������ ������ ������
������ �� �� ������ ������ �� ������ ������ ����� ������ ����� ������ ������ � ����� ������ ������ ������
������ �� �� ������ ������ �� ������ ������� ����� ������ ����� ������ ������ � ������ ������ �������� �
������ �� �� ������ ������ �� ������ ������� ����� ������ ����� ������ ������ � ������ ������ �������� �
������ �� ������ ������ ������ �� ������ ������� ����� ������ ����� ������ ������ � ������ ������ �������� ������
������ �� �� ������ ������ �� ������ ������� ����� ������ ����� ������ ������ � ������ ������ �������� ������
������ ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������
����������������������������������������������������������������������
��������
��������
��������
�������
��������
��������
��������
D
CB
A
AIRFLOW
AA
KJ
H
E / F
CC FF
BB
EE
3.502.00
L
AIR FLOW
3.50 3.501.00 GG
HH
3.50
GENERAL SPECIFICATIONS
MODELNOM.COOLTONS
FACEAREASQ. FT.
TUBESIZE
BLOWERSIZE
FILTERSIZE
2 ROW COIL 4 ROW COIL 6 ROW COIL
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
90ASHW 7-1/2 7.5 1/2 15 x 15 24 x 25 (2) 1-3/8” O/D (SWT) 18 1-3/8” O/D (SWT) 450 1-1/8” O/D (SWT) 475
120ASHW 10 9.6 1/2 15 x 15 26 x 29 (2) 1-3/8” O/D (SWT) 22 1-3/8” O/D (SWT) 490 1-3/8” O/D (SWT) 535
180ASHW 15 14.3 1/2 15 x 12 (2) 20 x 36.5 (3) 1-3/8” O/D (SWT) 30 1-3/8” O/D (SWT) 670 1-3/8” O/D (SWT) 710
240ASHW 20 19.1 1/2 15 x 12 (2) 20 x 49 (3) 1-3/8” O/D (SWT) 38 1-3/8” O/D (SWT) 835 1-3/8” O/D (SWT) 880
NOTES: 1) All technical specifications subject to change without notice.
90ASHW - 240ASHWPHYSICAL DATA
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-7-
�������
�������
�������
��������������
�������
�������
�������
DISCHARGE AIRACCESS PANEL
ACCESSPANEL
DISCHARGE AIRACCESSPANEL
LEFT SIDEREAR
GG
CC
HH
DD
LBBFF
3/4
DISCHARGE AIRACCESSPANEL
3/4
AAEEM
RIGHT SIDE
C D
E
G
JK
H
F
ACCESSPANEL
AB
2.00
DISCHARGE AIRACCESSPANEL
ACCESSPANEL
FRONT
GENERAL SPECIFICATIONS
MODELNOM.COOLTONS
FACEAREASQ. FT.
TUBESIZE
BLOWERSIZE
FILTERSIZE
2 ROW COIL 4 ROW COIL 6 ROW COIL
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
24ASVW 2 2.05 3/8 9 x 6 16 x 25 7/8” O/D (SWT) 18 7/8” O/D (SWT) 185 7/8” O/D (SWT) 205
36ASVW 3 3.05 3/8 9 x 9 16 x 16 (2) 7/8” O/D (SWT) 22 7/8” O/D (SWT) 205 7/8” O/D (SWT) 225
48ASVW 4 4.0 3/8 10 x 10 16 x 20 (2) 7/8” O/D (SWT) 30 7/8” O/D (SWT) 240 7/8” O/D (SWT) 265
60ASVW 5 5.0 3/8 12 x 12 20 x 20 (2) 7/8” O/D (SWT) 38 1-1/8” O/D (SWT) 290 1-1/8” O/D (SWT) 310
NOTES: 1) All technical specifications subject to change without notice.
24ASVW - 60ASVWPHYSICAL DATA
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-8-
�������
��������
��������
��������
�������
��������
��������
��������
DISCHARGE AIRACCESS PANEL
ACCESSPANEL
DISCHARGE AIRACCESSPANEL
LEFT SIDEREAR
GG
CC
HH
DD
LBBFF
3/4
DISCHARGE AIRACCESSPANEL
3/4
AAEEM
RIGHT SIDE
C D
E
G
JK
H
F
ACCESSPANEL
AB
2.00
DISCHARGE AIRACCESSPANEL
ACCESSPANEL
FRONT
GENERAL SPECIFICATIONS
MODELNOM.COOLTONS
FACEAREASQ. FT.
TUBESIZE
BLOWERSIZE
FILTERSIZE
2 ROW COIL 4 ROW COIL 6 ROW COIL
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
MANIFOLDCONNECTION
SHIPWT.
90ASVW 7-1/2 7.5 1/2 15 x 15 24 x 25 (2) 1-3/8” O/D (SWT) 18 1-3/8” O/D (SWT) 450 1-1/8” O/D (SWT) 475
120ASVW 10 9.6 1/2 15 x 15 26 x 29 (2) 1-3/8” O/D (SWT) 22 1-3/8” O/D (SWT) 490 1-3/8” O/D (SWT) 535
180ASVW 15 14.3 1/2 15 x 12 (2) 20 x 36.5 (3) 1-3/8” O/D (SWT) 30 1-3/8” O/D (SWT) 670 1-3/8” O/D (SWT) 710
240ASVW 20 19.1 1/2 15 x 12 (2) 20 x 49 (3) 1-3/8” O/D (SWT) 38 1-3/8” O/D (SWT) 835 1-3/8” O/D (SWT) 880
NOTES: 1) All technical specifications subject to change without notice.
90ASVW - 240ASVWPHYSICAL DATA
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-9-
Dimensions:
1. Cabinet fully insulated - 3/4 inch.2. Galvanized steel cabinet on 24-240MB.3. Crank arms and linkage rod for damper connection are furnished. Connections can be made on either
side of mixing boxes. The balance of necessary linkage hardware, damper motor, and controls to be field supplied.
4. Dampers can be positioned for either rear/top or rear/bottom locations.5. 1” duct flanges provided on damper openings.6. Dampers have air seals on the edges for positive closing. 24-90MB have single horizontal damper blades.
120-240MB have double horizontal damper blades.7. When used with water coil units, a “freezestat” must be installed to prevent coil damage caused by low
ambient conditions.
Features:
MODELFORUNIT
MODELA B C D E F
DAMPERSIZE
(NOM)
SHIPPINGWEIGHT
24MB 24ASH, ASV 16 16-3/8 18-1/8 8 6 1-1/16 2-16 x 8 40
36MB 36ASH, ASV 16 16-3/8 27-5/8 8 6 1-1/16 2-26 x 8 58
48MB 48ASH, ASV 18 20-3/8 29-1/8 10 8 1-1/16 2-27 x 10 65
60MB 60ASH, ASV 18 20-3/8 36-1/8 10 8 1-1/16 2-34 x 10 78
90MB 90ASH, ASV 18 25-3/8 45-1/8 10 8 1-1/16 2-42 x 10 110
120MB 120ASH, ASV 20 30-3/8 48-1/8 12 10 1-1/16 2-46 x 12 135
180MB 180ASH, ASV 22 37-7/8 57-1/8 14 12 1-9/16 2-54 x 14 190
240MB 240ASH, ASV 22 50-1/2 57-1/8 14 24 1-9/16 2-54 x 14 210
MIXING BOXProduct Specifications
Horizontal / VerticalChilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-10-
ELECTRIC HEATProduct SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
MODELS UNIT SIZE DESIGNATION W H Q Z U BD F R N T M
ASH/ASV 24 (2-TON) 26 9-1/8 11-1/8 18 17-5/8 18 4-1/2 1 0 0 0 4-1/2
ASH/ASV 36 (3-TON) 27 12-5/8 11-1/8 18 17-5/8 18 4-1/2 1 0 0 0 4-1/2
ASH/ASV 48 (4-TON) 28 14 12-1/8 18 21-1/8 18 4-1/2 1 0 0 0 7
ASH/ASV 60 (5-TON) 29 16-3/8 14-1/8 18 21-1/8 18 4-1/2 1 0 0 0 8
ASH/ASV 90 (7.5-TON) 30 19-1/2 16-5/8 18 26-1/8 18 4-1/2 1 0 0 0 7-1/2
ASH/ASV 120 (10-TON) 31 19-1/2 16-3/4 18 30-1/4 18 4-1/2 1 0 0 4 7-1/2
ASH/ASV 180 (15-TON) 32 18 18 4-1/2 1
ASH/ASV 240 (20-TON) 32 18 18 4-1/2 1
OPTIONS
NON-FUSED DISCONNECT
80/20 WIRE
STAINLESS TERMINALS
**MULTIPLE STAGES
**SCR CONTROL
**STEP CONTROLLER
WALL STAT
DUCT STAT
NOTE
**CONTACT FACTORY FOR THESE OPTIONS.
Options not available on all heaters
SINGLE POINT CONNECTION (CONTACTOR AND TERMINAL BOARD)PRIMARY AND SECONDARY CONTACTOR (DE-ENERGIZING)AUTO AND MANUAL LIMIT SWITCH (PILOT DUTY)HIGH NICKEL CHROME ALLOY RESISTANCE WIRE
HIGH AND LOW VOLTAGE TERMINAL BOARDTRANSFORMER (S4 VOLT SECONDARY)AIRFLOW SWITCH (NON ADJUSTABLE)POWER FUSING (PER NEC)
HEATER NOMENCLATURE
HEATER UNIT DESIGNATION KW STAGES VOLTAGE NF-DISCONNECT
H
UNIT SIZE DESIGNATIONKW CODE 1 = I-PHASE CODE
1KW 1.0 1 STAGE 208V 01 A =
24 (2 TON) 26 2KW 2.0 220V 21 40 AMPS
36 (3 TON) 27 3KW 3.0 240V 41
48 (4 TON) 28 1.5KW 1.5 277V 71
60 (5TON) 29 2.7KW 2.7 2 = 3-PHASE CODE B =
90 (7.5 TON) 30 3.4KW 3.4 2 STAGE 208V 03 48 AMPS
120 (10 TON) 31 240V 43
180 (15 TON) 32 KW ABOVE 9.9 MUST BE IN INCRE-MENTS OF 1.0 KW
380V 83
240 (20 TON) 32 460V 63 N =
NO DISCONNECT
H 28 5.0 1 41 A
EXAMPLE: MODEL # H 285.0141ADESCRIPTION: 48 (4 TON) 5KW 1 STAGE 240V/1PH 40 AMP NON-FUSED DISCONNECT
MUST INDICATE IF UNITS ARE HORIZONTAL OR VERTICAL
LEFT HAND OR RIGHT HAND CONNECTIONS
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-11-
SPRING ISOLATORSProduct SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
SPRING ISOLATOR KITS FOR BELT DRIVE PRODUCTS
NON-SEISMICHanger Selections for Ceiling Suspended Uints
NON-SEISMICBase Selection for Floor Mounted Units
ASHW/ASHX-HORIZONTAL SPRING ISOLATORS ASHW/ASHX-VERTICAL SPRING ISOLATORS
BNHS Spring & Elastomeric HS Spring HD Elastomeric SLF Free Standing Spring C Housed Spring ND Neoprene
UNIT MODELNUMBER
HANGER HANGER HANGERUNIT MODEL
NUMBER
MOUNTS MOUNTS MOUNTS
QTY & QTY & QTY & QTY & QTY & QTY &
SIZE SIZE SIZE SIZE SIZE SIZE
HORIZONTAL FAN & COIL SECTION - 4 ROW COIL VERTICAL FAN & COIL SECTION - 4 ROW COIL
24 ASHW FVI-1 4-X FVI-7 4-X FVI-13 4-A 24 ASVW FVI-59 4-A FVI-63 4-A FVI-67 4-A
36 ASHW FVI-1 4-X FVI-7 4-X FVI-13 4-A 36 ASVW FVI-59 4-A FVI-63 4-A FVI-67 4-A
48 ASHW FVI-2 4-X FVI-8 4-X FVI-13 4-A 48 ASVW FVI-60 4-A FVI-64 4-A FVI-67 4-A
60 ASHW FVI-2 4-X FVI-8 4-X FVI-13 4-A 60 ASVW FVI-60 4-A FVI-64 4-A FVI-67 4-A
90 ASHW FVI-3 4-X FVI-9 4-X FVI-14 4-B 90 ASVW FVI-61 4-A FVI-65 4-A FVI-68 4-B
120 ASHW FVI-3 4-X FVI-9 4-X FVI-14 4-B 120 ASVW FVI-61 4-A FVI-65 4-A FVI-68 4-B
180 ASHW FVI-4 4-A FVI-10 4-A FVI-15 4-B 180 ASVW FVI-62 4-A FVI-66 4-A FVI-69 4-B
240 ASHW FVI-5 4-A FVI-11 4-A FVI-15 4-B 240 ASVW FVI-62 4-A FVI-66 4-A FVI-69 4-B
HORIZONTAL FAN & COIL SECTION - 6 ROW COIL VERTICAL FAN & COIL SECTION - 6 ROW COIL
24 ASHW FVI-1 4-X FVI-7 4-X FVI-13 4-A 24 ASVW FVI-59 4-A FVI-63 4-A FVI-67 4-A
36 ASHW FVI-1 4-X FVI-7 4-X FVI-13 4-A 36 ASVW FVI-59 4-A FVI-63 4-A FVI-67 4-A
48 ASHW FVI-2 4-X FVI-8 4-X FVI-13 4-A 48 ASVW FVI-60 4-A FVI-64 4-A FVI-67 4-A
60 ASHW FVI-2 4-X FVI-8 4-X FVI-13 4-A 60 ASVW FVI-60 4-A FVI-64 4-A FVI-67 4-A
90 ASHW FVI-3 4-X FVI-9 4-X FVI-14 4-B 90 ASVW FVI-61 4-A FVI-65 4-A FVI-68 4-B
120 ASHW FVI-6 4-X FVI-12 4-X FVI-14 4-B 120 ASVW FVI-61 4-A FVI-65 4-A FVI-68 4-B
180 ASHW FVI-5 4-A FVI-11 4-A FVI-15 4-B 180 ASVW FVI-62 4-A FVI-66 4-A FVI-69 4-B
240 ASHW FVI-5 4-A FVI-11 4-A FVI-15 4-B 240 ASVW FVI-62 4-A FVI-66 4-A FVI-69 4-B
HORIZONTAL FAN & COIL SECTION - 4 ROW COIL WITH MIXING BOX VERTICAL FAN & COIL SECTION - 4 ROW COIL WITH MIXING BOX
24 ASHW FVI-16 6-X FVI-23 6-X FVI-30 6-A 24 ASVW FVI-70 6-A FVI-76 6-A FVI-82 6-A
36 ASHW FVI-16 6-X FVI-23 6-X FVI-30 6-A 36 ASVW FVI-70 6-A FVI-76 6-A FVI-82 6-A
48 ASHW FVI-17 6-X FVI-24 6-X FVI-30 6-A 48 ASVW FVI-71 6-A FVI-77 6-A FVI-82 6-B
60 ASHW FVI-18 6-X FVI-25 6-X FVI-30 6-A 60 ASVW FVI-72 6-A FVI-78 6-A FVI-83 6-B
90 ASHW FVI-19 6-X FVI-26 6-X FVI-31 6-B 90 ASVW FVI-73 6-A FVI-79 6-A FVI-83 6-B
120 ASHW FVI-19 6-X FVI-26 6-X FVI-31 6-B 120 ASVW FVI-74 6-A FVI-80 6-A FVI-83 6-B
180 ASHW FVI-20 6-A FVI-27 6-A FVI-32 6-B 180 ASVW FVI-75 6-A FVI-81 6-A FVI-84 6-B
240 ASHW FVI-21 6-A FVI-28 6-A FVI-32 6-B 240 ASVW FVI-75 6-A FVI-81 6-A FVI-84 6-B
HORIZONTAL FAN & COIL SECTION - 6 ROW COIL WITH MIXING BOX VERTICAL FAN & COIL SECTION - 6 ROW COIL WITH MIXING BOX
24 ASHW FVI-16 6-X FVI-23 6-X FVI-30 6-A 24 ASVW FVI-70 6-A FVI-76 6-A FVI-82 6-A
36 ASHW FVI-16 6-X FVI-23 6-X FVI-30 6-A 36 ASVW FVI-70 6-A FVI-76 6-A FVI-82 6-A
48 ASHW FVI-17 6-X FVI-24 6-X FVI-30 6-A 48 ASVW FVI-71 6-A FVI-77 6-A FVI-82 6-A
60 ASHW FVI-18 6-X FVI-25 6-X FVI-30 6-A 60 ASVW FVI-72 6-A FVI-78 6-A FVI-83 6-B
90 ASHW FVI-19 6-X FVI-26 6-X FVI-31 6-B 90 ASVW FVI-73 6-A FVI-79 6-A FVI-83 6-B
120 ASHW FVI-22 6-A FVI-29 6-A FVI-31 6-B 120 ASVW FVI-74 6-A FVI-80 6-A FVI-84 6-B
180 ASHW FVI-20 6-A FVI-27 6-A FVI-32 6-B 180 ASVW FVI-75 6-A FVI-81 6-A FVI-84 6-B
240 ASHW FVI-21 6-A FVI-28 6-A FVI-32 6-B 240 ASVW FVI-75 6-A FVI-81 6-A FVI-84 6-B
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Volt Phase HP FLA MCA Fuse Qty Part Number
115 1
1/4 5.8 10 20 1 986FF11M3M
1/3 7.2 15 26 1986FF11M4M
1/2 9.8 15 26 1
3/4 13.8 20 30 1 986FF11M5M
1 16.4 25 35 1986FF11M6M
1-1/2 20.0 25 35 1
2 24.0 30 30 1 986FF11M7M
277 1
1/4 2.4 6 6 1
986FF71M2M1/3 3.0 6 6 1
1/2 4.1 6 6 1
3/4 5.7 10 10 1986FF71M3M
1 6.8 10 10 1
1-1/2 8.5 15 15 1986FF71M4M
2 10.0 15 15 1
208/230 1
1/4 2.9 6 6 2986FF31M2M
1/3 3.6 6 6 2
1/2 4.9 10 6 2986FF31M3M
3/4 6.9 10 10 2
1 8.2 15 10 2986FF31M4M
1-1/2 10.0 15 15 2
2 12.0 20 15 2 986FF31M5M
208/230 3
1/4 N/A
1/3 1.6 3 3 3 986FF33M1M
1/2 2.4 6 6 3986FF33M2M
3/4 3.5 6 6 3
1 5.6 10 10 3986FF33M3M
1-1/2 6.6 10 10 3
2 7.5 15 15 3986FF33M4M
3 10.6 15 15 3
5 16.7 25 20 3 986FF33M6M
460 3
1/4 N/A
1/3 0.8 3 3 3
986FF63M1M1/2 1.1 3 3 3
3/4 1.6 3 3 3
1 3.7 6 6 3
986FF63M2M1-1/2 3.0 6 6 3
2 3.7 6 6 3
3 4.8 10 10 3986FF63M3M
5 7.6 10 10 3
575 3
1/4 N/A
1/3 N/A
1/2 0.9 3 3 3986FF53M1M
3/4 1.3 3 3 3
1 1.7 3 3 3
986FF53M2M1-1/2 2.4 3 3 3
2 2.7 6 6 3
3 3.9 6 6 3
5 6.1 10 10 3 986FF53M3M
FEATURES
DISCONNECT SWITCH
HAND OFF AUTO (HOA) SWITCH
POWER FUSING
MOTOR CONTACTOR
24V TRANSFORMER
LOW VOLTAGE TERMINAL BLOCK
FACTORY MOUNTED AND WIRED
MOTOR CONTROL BOX
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
-12-
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-13-
SIZE BLOWER STATIC
24 1/4 HP 1/3 HP 1/2 HP 3/4 HP
TOTAL ROWS
700 800 900 700 800 900 700 800 900 700 800 900
2 0.13-0.80 0.00-0.63 0.00-0.44 0.36-1.23 0.29-1.03 0.21-0.83 0.64-1.62 0.59-1.62 0.54-1.52 0.90-1.62 0.87-1.62 0.84-1.61
4 0.04-0.71 0.00-0.52 0.00-0.30 0.27-1.14 0.18-0.92 0.07-0.69 0.55-1.53 0.48-1.51 0.40-1.38 0.81-1.53 0.76-1.51 0.70-1.47
6 0.00-0.61 0.00-0.41 0.00-0.16 0.17-1.04 0.07-0.81 0.00-0.55 0.45-1.43 0.37-1.40 0.26-1.24 0.71-1.43 0.65-1.40 0.56-1.33
8 0.00-0.53 0.00-0.29 0.00-0.02 0.09-0.96 0.00-0.69 0.00-0.41 0.37-1.35 0.25-1.28 0.12-1.10 0.63-1.35 0.53-1.28 0.42-1.19
AVAIL. TSP 0.37-1.04 0.33-0.92 0.28-0.77 0.60-1.47 0.58-1.32 0.54-1.16 0.88-1.86 0.88-1.91 0.87-1.85 1.14-1.86 1.16-1.91 1.17-1.94
36 1/3 HP 1/2 HP 3/4 HP
TOTAL ROWS
1000 1100 1200 1300 1000 1100 1200 1300 1000 1100 1200 1300
2 0.13-0.74 0.07-0.61 0.00-0.47 0.00-0.34 0.34-1.34 0.29-1.19 0.24-1.04 0.18-0.90 0.88-1.55 0.86-1.55 0.82-1.54 0.78-1.51
4 0.00-0.65 0.00-0.52 0.00-0.36 0.00-0.21 0.25-1.25 0.20-1.10 0.13-0.93 0.05-0.77 0.79-1.46 0.77-1.46 0.71-1.43 0.65-1.38
6 0.00-0.57 0.00-0.43 0.00-0.25 0.00-0.08 0.17-1.17 0.11-1.01 0.00-0.82 0.00-0.64 0.71-1.38 0.68-1.37 0.60-1.32 0.52-1.25
8 0.00-0.49 0.00-0.33 0.00-0.13 0.00-0.00 0.09-1.09 0.00-0.91 0.00-0.70 0.00-0.51 0.63-1.30 0.58-1.27 0.48-1.20 0.39-1.12
AVAIL. TSP 0.34-0.95 0.32-0.86 0.29-0.76 0.26-0.66 0.55-1.55 0.54-1.44 0.53-1.33 0.50-1.22 1.09-1.76 1.11-1.80 1.11-1.83 1.10-1.83
48 1/2 HP 3/4 HP 1 HP
TOTAL ROWS
1500 1600 1700 1500 1600 1700 1500 1600 1700
2 0.17-0.75 0.12-0.66 0.06-0.55 0.46-1.37 0.42-1.26 0.37-1.15 0.88-1.63 0.85-1.63 0.81-1.61
4 0.07-0.65 0.00-0.54 0.00-0.42 0.36-1.27 0.30-1.14 0.24-1.02 0.78-1.53 0.73-1.51 0.68-1.48
6 0.00-0.54 0.00-0.43 0.00-0.29 0.25-1.16 0.19-1.03 0.11-0.89 0.67-1.42 0.62-1.40 0.55-1.35
8 0.00-0.44 0.00-0.32 0.00-0.17 0.15-1.06 0.08-0.92 0.00-0.77 0.57-1.32 0.51-1.29 0.43-1.23
AVAIL. TSP 0.43-1.01 0.40-0.94 0.37-0.86 0.72-1.63 0.70-1.54 0.68-1.46 1.14-1.89 1.13-1.91 1.12-1.92
60 1/2 HP 3/4 HP 1 HP 1-1/2 HP
TOTAL ROWS
1900 2000 2100 1900 2000 2100 1900 2000 2100 1900 2000 2100
2 0.15-0.59 0.11-0.51 0.06-0.42 0.44-1.16 0.42-1.08 0.38-0.99 0.77-1.57 0.76-1.51 0.74-1.43 1.10-1.91 1.09-1.91 1.07-1.90
4 0.00-0.48 0.00-0.39 0.00-0.29 0.33-1.05 0.30-0.96 0.25-0.86 0.66-1.46 0.64-1.39 0.61-1.30 0.99-1.80 0.97-1.79 0.94-1.77
6 0.00-0.38 0.00-0.28 0.00-0.17 0.23-0.95 0.19-0.85 0.13-0.74 0.56-1.36 0.53-1.28 0.49-1.18 0.89-1.70 0.86-1.68 0.82-1.65
8 0.00-0.28 0.00-0.17 0.00-0.05 0.13-.085 0.08-0.74 0.00-0.62 0.46-1.26 0.42-1.17 0.37-1.06 0.79-1.60 0.75-1.57 0.70-1.53
AVAIL. TSP 0.42-0.86 0.40-0.80 0.38-0.74 0.71-1.43 0.71-1.37 0.70-1.31 1.04-1.84 1.05-1.80 1.06-1.75 1.37-2.18 1.38-2.20 1.39-2.22
90 3/4 HP 1 HP 1-1/2 HP 2 HP
TOTAL ROWS
2800 3000 3200 2800 3000 3200 2800 3000 3200 2800 3000 3200
2 0.00-0.73 0.00-0.51 0.00-0.30 0.38-1.17 0.33-0.92 0.27-0.70 0.63-1.80 0.59-1.74 --- 1.01-1.80 0.97-0.75 0.93-1.77
4 0.00-0.58 0.00-0.35 0.00-0.13 0.23-1.02 0.17-0.76 0.10-0.53 0.48-1.65 0.43-1.58 --- 0.86-1.65 0.81-1.63 0.76-1.60
6 0.00-0.43 0.00-0.18 0.00-0.00 0.08-0.87 0.00-0.59 0.00-0.34 0.33-1.50 0.26-1.41 --- 0.71-1.50 0.64-1.46 0.57-1.41
8 0.00-0.27 0.00-0.00 0.00-0.00 0.00-0.71 0.00-0.41 0.00-0.14 0.17-1.34 0.08-1.23 --- 0.55-1.34 0.46-1.28 0.37-1.21
AVAIL. TSP 0.34-1.09 0.33-0.91 0.31-0.74 0.74-1.53 0.73-1.32 0.71-1.14 0.99-2.16 0.99-2.14 --- 1.37-2.16 1.37-2.19 1.37-2.21
120 1-1/2 HP 2 HP 3 HP
TOTAL ROWS
3800 4000 4200 3800 4000 4200 3800 4000 4200
2 0.02-0.97 0.00-0.75 0.00-0.55 0.51-1.65 0.43-1.42 0.36-1.20 --- 0.92-1.52 0.85-1.47
4 0.00-0.80 0.00-0.57 0.00-0.35 0.34-1.48 0.25-1.24 0.16-1.00 --- 0.74-1.34 0.65-1.27
6 0.00-0.64 0.00-0.40 0.00-0.17 0.18-1.32 0.08-1.07 0.00-0.82 --- 0.57-1.17 0.47-1.09
8 0.00-0.47 0.00-0.21 0.00-0.00 0.01-1.15 0.00-088 0.00-0.61 --- 0.38-0.98 0.28-0.88
AVAIL. TSP 0.41-1.36 0.37-1.18 0.33-1.01 0.90-2.04 0.86-1.85 0.82-1.66 --- 1.35-1.95 1.31-1.93
180 2 HP 3 HP
TOTAL ROWS
5800 6000 6200 5800 6000 6200
2 0.24-0.92 0.20-0.77 0.16-0.63 0.50-1.62 0.46-1.60 0.42-1.47
4 0.06-0.74 0.00-0.58 0.00-0.43 0.32-1.44 0.27-1.41 0.22-1.27
6 0.00-0.57 0.00-0.40 0.00-0.24 0.15-1.27 0.09-1.23 0.00-1.08
8 0.00-0.40 0.00-0.22 0.00-0.05 0.00-1.10 0.00-1.05 0.00-0.89
AVAIL. TSP 0.66-1.34 0.64-1.21 0.62-1.09 0.92-2.04 0.90-2.04 0.88-1.93
240 3 HP 5 HP
TOTAL ROWS
7500 8000 8500 7500 8000 8500
2 0.08-0.79 0.00-0.45 0.00-0.13 0.20-1.79 0.07-1.71 0.00-1.39
4 0.00-0.61 0.00-0.26 0.00-0.00 0.00-1.61 0.00-1.52 0.00-1.18
6 0.00-0.45 0.00-0.08 0.00-0.00 0.00-1.45 0.00-1.34 0.00-0.99
8 0.00-0.31 0.00-0.00 0.00-0.00 0.00-1.31 0.00-1.17 0.00-0.79
AVAIL. TSP 0.47-1.18 0.39-0.89 0.29-0.62 0.59-2.18 0.51-2.15 0.42-1.88
BLOWER STATICProduct SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-14-
* Wet Coil (Dry Coil P.D. = Wet P.D. x .70)
MODELNOMINAL
CFM
COMPONENT STATIC RESISTANCE (INCHES OF WATER)
CABINETCOOLING COIL* HEATING COIL
FILTER4 ROW 6 ROW 2 ROW
24ASHW /24ASVW
6007008009001000
0.090.100.110.120.13
0.140.180.230.280.33
0.220.270.340.420.50
0.070.090.120.140.18
0.040.050.060.070.08
36ASHW /36ASVW
10001100120013001400
0.090.100.110.120.13
0.170.190.230.260.30
0.250.280.340.390.45
0.080.100.120.130.15
0.040.050.060.070.08
48ASHW /48ASVW
14001500160017001800
0.090.100.110.120.13
0.180.200.230.250.28
0.270.310.340.380.42
0.090.100.110.120.13
0.050.060.060.070.08
60ASHW /60ASVW
18001900200021002200
0.100.110.120.130.15
0.200.210.230.250.28
0.280.310.340.370.40
0.090.100.110.120.13
0.050.060.060.070.08
MODELNOMINAL
CFM
COMPONENT STATIC RESISTANCE (INCHES OF WATER)
CABINETCOOLING COIL* HEATING COIL
FILTER4 ROW 6 ROW 2 ROW
90ASHW /90ASVW
25002750300032503500
0.120.140.160.170.19
0.260.300.340.390.44
0.390.450.510.580.65
0.130.160.180.210.24
0.040.050.060.070.08
120ASHW /120ASVW
34003700400043004600
0.140.150.170.190.21
0.290.330.370.410.45
0.430.480.540.610.67
0.140.160.190.210.24
0.050.060.070.080.09
180ASHW /180ASVW
52005600600064006800
0.160.170.190.210.23
0.300330.370.410.45
0.440.490.550.610.66
0.140.160.180.200.23
0.050.060.070.080.09
240ASHW /240ASVW
6000700080009000
10000
0.110.160.190.230.29
0.210.300.370.450.58
0.310.440.550.660.86
0.100.140.180.230.28
0.040.050.070.090.11
STATIC RESISTANCEProduct SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-15-
Notes: 1) Horsepower tabulated indicates minimum recommended motor H.P.2) Rated in accordance with ARI Standard 430.
2 - 5 TON FAN PERFORMANCE (ASHW and ASVW)
MODEL CFM FPM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.5 0.6 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0
RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP
24
600 300 770 1/6 840 1/6 990 1/4 1050 1/4 1105 1/4 1210 1/3 1310 1/3 1420 1/3 1510 1/2 --- ---
700 350 780 1/6 850 1/6 990 1/4 1040 1/4 1100 1/4 1200 1/3 1300 1/3 1405 1/2 1500 1/2 --- ---
800 400 800 1/4 860 1/4 990 1/4 1040 1/4 1100 1/3 1195 1/3 1295 1/2 1395 1/2 1470 1/2 --- ---
900 450 810 1/4 880 1/4 1000 1/4 1050 1/3 1100 1/3 1190 1/3 1290 1/2 1390 1/2 1460 1/2 --- ---
1000 500 830 1/4 900 1/4 1000 1/3 1060 1/3 1110 1/3 1200 1/2 1295 1/2 1390 1/2 1450 3/4 --- ---
36
1000 333 805 1/4 880 1/4 1000 1/3 1060 1/3 1110 1/2 1230 1/2 1335 1/2 1440 3/4 1540 3/4 --- ---
1100 367 810 1/4 890 1/3 1000 1/3 1050 1/2 1110 1/2 1215 1/2 1325 1/2 1425 3/4 1520 3/4 --- ---
1200 400 820 1/3 900 1/3 1005 1/2 1050 1/2 1110 1/2 1210 1/2 1315 3/4 1415 3/4 1500 3/4 --- ---
1300 434 840 1/3 905 1/3 1010 1/2 1060 1/2 1110 1/2 1220 1/2 1315 3/4 1410 3/4 1490 3/4 --- ---
1400 466 870 1/3 920 1/3 1020 1/2 1090 1/2 1120 1/2 1220 3/4 1320 3/4 1410 3/4 1500 3/4 --- ---
48
1400 350 720 1/3 775 1/3 870 1/3 910 1/2 955 1/2 1050 3/4 1135 3/4 1215 3/4 1300 1 1380 1
1500 375 740 1/3 785 1/2 875 1/2 920 1/2 960 1/2 1050 3/4 1135 3/4 1210 3/4 1295 1 1370 1
1600 400 750 1/2 800 1/2 890 1/2 925 3/4 970 3/4 1050 3/4 1140 3/4 1210 3/4 1290 1 1360 1
1700 425 770 1/2 810 1/2 895 1/2 930 3/4 980 3/4 1065 3/4 1140 3/4 1210 3/4 1290 1 1350 1
1800 450 785 1/2 825 1/2 910 1/2 945 3/4 985 3/4 1070 3/4 1150 3/4 1215 1 1280 1 --- ---
60
1800 360 580 1/2 630 1/2 725 1/2 770 3/4 820 3/4 900 3/4 975 3/4 1050 1 1125 1 1200 1-1/2
1900 380 580 1/2 630 1/2 725 1/2 775 3/4 815 3/4 895 3/4 970 3/4 1045 1 1120 1 1190 1-1/2
2000 400 590 1/2 635 1/2 730 1/2 770 3/4 815 3/4 890 3/4 965 1 1040 1 1110 1 1180 1-1/2
2100 420 600 1/2 640 1/2 730 3/4 770 3/4 815 3/4 885 3/4 960 1 1035 1 1105 1-1/2 1175 1-1/2
2200 440 600 1/2 645 1/2 735 3/4 775 3/4 815 3/4 885 3/4 960 1 1030 1 1100 1-1/2 1165 1-1/2
7-1/2 - 20 TON FAN PERFORMANCE (ASHW and ASVW)
MODEL CFM FPM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.5 0.6 0.8 0.9 1.2 1.4 1.6 1.8 1.9
RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP
90
2500 333 580 1/2 600 3/4 690 3/4 710 3/4 790 3/4 850 1 915 1-1/2 990 1-1/2 1030 1-1/2
2750 366 580 1/2 605 3/4 690 3/4 710 3/4 780 1 840 1 905 1-1/2 980 1-1/2 1020 1-1/2
3000 400 580 3/4 610 3/4 680 3/4 710 1 780 1 835 1-1/2 900 1-1/2 970 1-1/2 1010 1-1/2
3250 433 590 3/4 630 1 700 1 715 1 790 1-1/2 840 1-1/2 900 1-1/2 950 1-1/2 1005 2
3500 466 605 1 635 1 700 1 720 1 790 1-1/2 845 1-1/2 900 1-1/2 950 2 1005 2
120
3400 354 600 1 630 1 700 1 730 1-1/2 790 1-1/2 850 1-1/2 900 1-1/2 950 2 1005 2
3700 385 610 1 650 1 705 1-1/2 740 1-1/2 800 1-1/2 855 1-1/2 905 2 950 2 1005 2
4000 417 630 1-1/2 670 1-1/2 710 1-1/2 750 1-1/2 805 1-1/2 860 2 910 2 960 2 1005 2
4300 448 650 1-1/2 685 1-1/2 730 1-1/2 770 2 802 2 875 2 915 3 970 3 1010 3
4600 480 670 1-1/2 700 2 760 2 790 2 830 2 890 3 930 3 980 3 1015 3
180
5200 364 590 1-1/2 620 1-1/2 690 1-1/2 710 1-1/2 780 2 830 2 900 2 950 3 1000 3
5600 391 600 1-1/2 630 1-1/2 700 1-1/2 720 2 790 2 840 2 905 3 950 3 1000 3
6000 420 610 1-1/2 640 1-1/2 700 2 730 2 795 2 850 3 910 3 960 3 1000 3
6400 447 625 2 660 2 710 2 740 3 800 3 860 3 915 3 970 3 1000 5
6800 475 640 2 680 2 720 3 760 3 810 3 870 3 920 5 975 5 1005 5
240
6000 314 610 1-1/2 640 1-1/2 700 2 730 2 795 2 850 3 910 3 960 3 1000 3
7000 366 640 2 690 2 740 3 760 3 810 3 880 3 920 5 960 5 1000 5
8000 419 700 3 720 3 790 3 800 3 850 5 900 5 940 5 990 5 1020 5
9000 470 730 5 760 5 810 5 830 5 890 5 920 5 980 --- --- --- --- ---
10000 500 800 5 820 5 880 5 900 5 --- --- --- --- --- --- --- --- --- ---
FAN PERFORMANCEProduct Specifications
Horizontal / VerticalChilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-16-
24ASHW ENT.WTR.
oF
C.F.M.
24ASHW4 / 24ASVW4 (4 ROW COIL) 24ASHW6 / 24ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
6008001000
3.0 1.219.621.723.2
13.916.518.7
13.014.515.5
14.916.617.7
12.114.516.6
9.911.011.8
3.0 1.322.324.926.7
15.718.821.6
14.916.617.8
17.019.020.4
13.616.519.1
11.412.713.6
6008001000
6.0 4.424.829.032.5
15.919.222.1
8.39.710.8
18.922.224.8
13.716.719.3
6.37.48.3
5.0 3.326.931.334.9
17.521.224.6
10.812.513.9
20.624.026.6
15.018.421.5
8.29.6
10.7
6008001000
9.0 9.326.731.836.3
16.620.323.6
5.97.18.1
20.424.327.7
14.317.620.4
4.55.46.2
7.0 6.129.635.239.8
18.522.826.5
8.410.011.4
22.626.930.4
15.919.623.0
6.47.78.7
45
6008001000
3.0 1.217.919.921.3
13.315.818.1
12.013.314.2
13.715.217.5
11.614.017.5
9.110.111.7
3.0 1.320.522.824.5
14.918.020.8
13.715.216.4
15.617.421.4
13.115.921.4
10.411.614.2
6008001000
6.0 4.422.726.629.8
15.118.321.1
7.68.99.9
17.420.322.7
13.116.018.5
5.86.87.6
5.0 3.324.728.732.0
16.620.223.5
9.911.512.8
18.922.024.4
14.317.620.6
7.58.89.8
6008001000
9.0 9.324.529.233.3
15.819.322.5
5.46.57.4
18.722.325.4
13.616.819.5
4.25.05.6
7.0 6.127.132.336.5
17.521.625.2
7.79.2
10.4
20.724.627.9
15.118.722.0
5.97.08.0
50
6008001000
3.0 1.215.216.918.1
12.314.817.0
10.211.312.1
11.612.814.6
10.912.814.6
7.88.69.7
3.0 1.317.419.420.9
13.816.819.5
11.612.913.9
13.315.617.8
12.215.617.8
8.910.411.9
6008001000
6.0 4.419.322.625.3
13.816.819.5
6.47.58.4
14.717.319.3
12.014.817.2
4.95.86.4
5.0 3.321.024.427.2
15.118.621.7
8.49.8
10.9
16.018.720.8
13.216.319.2
6.47.58.3
6008001000
9.0 9.320.824.828.3
14.317.620.6
4.65.56.3
15.919.021.6
12.515.518.1
3.54.24.8
7.0 6.123.127.431.1
15.919.723.2
6.67.88.9
17.620.923.7
13.817.220.3
5.06.06.8
36ASHW
ENT.WTR.
oF
C.F.M.
36ASHW4 / 36ASVW4 (4 ROW COIL) 36ASHW6 / 36ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
100012001400
4.0 2.029.631.433.1
21.924.426.7
14.815.716.6
22.624.025.3
19.221.523.7
11.312.012.7
4.0 2.735.638.040.5
25.428.431.5
17.819.020.2
27.229.130.9
22.125.027.7
13.614.515.5
100012001400
8.0 7.539.043.046.5
25.428.731.6
9.810.711.6
29.832.835.5
22.024.927.6
7.48.28.9
7.0 7.545.049.753.9
29.033.036.6
12.914.215.4
34.438.041.2
25.028.531.8
9.810.811.8
6008001000
12.0 16.342.647.552.0
26.830.433.7
7.17.98.7
32.536.339.7
23.126.329.2
5.46.06.6
10.0 14.549.555.560.9
31.035.339.3
9.911.112.2
37.842.446.5
26.530.333.9
7.68.59.3
45
100012001400
4.0 2.027.228.830.4
21.023.425.8
13.614.415.2
21.722.025.0
18.520.725.0
10.411.012.5
4.0 2.732.634.937.1
24.227.330.3
16.317.418.6
24.936.728.4
21.324.026.8
12.513.314.2
100012001400
8.0 7.535.839.442.6
24.227.330.2
8.99.910.7
27.330.132.6
21.023.926.4
6.87.58.1
7.0 7.541.345.649.5
27.631.334.9
11.813.014.1
31.534.837.8
23.927.230.4
9.010.010.8
6008001000
12.0 16.339.043.647.7
25.528.932.1
6.57.37.9
29.833.336.4
22.025.127.9
5.05.56.1
10.0 14.545.450.955.9
29.233.437.3
9.110.211.2
34.738.942.7
25.228.932.3
6.97.88.5
50
100012001400
4.0 2.023.124.525.8
19.521.924.2
11.512.212.9
17.219.120.8
17.219.120.8
8.69.5
10.44.0 2.7
27.729.731.6
22.425.428.3
13.914.815.8
21.223.626.0
19.823.626.0
10.611.813.0
100012001400
8.0 7.530.433.536.2
22.225.127.9
7.68.49.1
23.225.627.7
19.422.124.6
5.86.46.9
7.0 7.535.138.842.1
25.228.732.1
10.011.112.0
26.829.632.1
22.025.228.2
7.78.59.2
6008001000
12.0 16.333.237.140.5
23.226.429.4
5.56.26.8
25.328.331.0
20.323.225.8
4.24.75.2
10.0 14.538.643.347.5
26.530.434.1
7.78.79.5
29.533.036.3
23.126.529.8
5.96.67.3
24ASHW - 30ASHWCOOLING PERFORMANCE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-17-
48ASHW
ENT.WTR.
oF
C.F.M.
48ASHW4 / 48ASVW4 (4 ROW COIL) 48ASHW6 / 48ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
140016001800
6.0 3.942.945.146.5
31.033.635.9
14.315.015.5
32.834.535.5
27.229.631.6
10.911.511.8
5.0 2.345.647.548.7
33.836.739.3
18.219.019.5
34.836.337.2
29.632.334.7
13.914.514.9
140016001800
10.0 10.352.656.459.7
34.737.940.7
10.511.311.9
40.243.145.6
30.132.935.5
8.08.69.1
8.0 5.557.060.763.7
38.241.744.9
14.215.215.9
43.546.348.7
33.136.239.2
10.911.612.2
140016001800
13.0 17.056.360.865.0
36.139.642.8
8.79.410.0
43.046.549.6
31.234.337.1
6.67.17.6
11.0 10.163.668.673.1
40.944.848.5
11.612.513.3
48.652.455.8
35.238.742.0
8.89.510.1
45
140016001800
6.0 3.939.441.442.6
29.732.334.5
13.113.814.2
30.131.632.6
26.128.530.5
10.010.510.9
5.0 2.341.843.644.7
32.435.337.8
16.717.417.9
31.933.339.6
28.531.239.6
12.813.315.8
140016001800
10.0 10.348.351.854.7
33.026.138.9
9.710.410.9
36.939.541.8
28.831.534.1
7.47.98.4
8.0 5.552.355.758.4
36.439.842.9
13.113.914.6
39.942.544.6
31.734.737.6
10.010.611.2
140016001800
13.0 17.051.655.859.6
34.337.640.7
7.98.69.2
39.442.645.5
29.832.735.5
6.16.67.0
11.0 10.158.463.067.0
38.842.646.2
10.611.412.2
44.648.151.2
33.536.940.2
8.18.79.3
50
140016001800
6.0 3.933.535.236.2
27.630.132.2
11.211.712.1
24.226.128.0
24.226.128.0
8.18.79.3
5.0 2.335.537.138.0
30.232.935.5
14.214.615.2
28.430.733.0
28.430.733.0
11.412.313.2
140016001800
10.0 10.341.044.046.5
30.333.235.9
8.28.89.3
31.333.635.5
26.629.331.7
6.36.77.1
8.0 5.544.447.349.7
33.436.639.7
11.111.812.4
33.936.137.9
29.332.335.0
8.59.09.5
140016001800
13.0 17.043.947.450.7
31.434.537.4
6.87.37.8
33.536.238.7
27.530.332.9
5.25.66.0
11.0 10.149.653.557.0
35.439.042.4
9.011.810.4
37.940.943.5
30.934.137.2
6.97.47.9
60ASHW
ENT.WTR.
oF
C.F.M.
60ASHW4 / 60ASVW4 (4 ROW COIL) 60ASHW6 / 60ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
180020002200
6.0 1.848.749.049.6
37.439.341.3
16.216.316.5
37.237.443.1
33.034.843.1
12.412.514.4
6.0 1.657.557.858.8
43.045.347.8
19.219.319.6
43.944.244.9
37.739.942.3
14.614.715.0
180020002200
11.0 5.763.666.769.4
43.045.948.5
11.612.112.6
48.650.953.0
37.440.042.4
8.89.39.6
9.0 3.469.672.174.6
47.650.753.7
15.516.016.6
53.255.157.0
41.444.246.9
11.812.212.7
180020002200
16.0 11.670.675.379.4
45.749.152.3
8.89.49.9
53.957.560.6
39.542.645.4
6.77.27.6
12.0 5.977.381.585.4
50.754.357.8
12.913.614.2
59.162.365.2
43.847.050.2
9.810.410.9
45
180020002200
6.0 1.844.745.045.5
35.937.939.9
14.915.015.2
34.137.139.2
31.837.839.2
11.412.413.1
6.0 1.652.753.153.9
41.243.646.0
17.617.718.0
40.340.548.3
36.338.548.3
13.413.516.1
180020002200
11.0 5.758.461.263.7
41.043.846.4
10.611.111.6
44.646.748.6
35.838.440.7
8.18.58.8
9.0 3.463.866.268.5
45.448.451.4
14.214.715.2
48.850.552.3
39.642.445.1
10.811.211.6
180020002200
16.0 11.664.869.172.9
43.446.749.8
8.18.69.1
49.552.755.6
37.740.743.5
6.26.67.0
12.0 5.971.074.878.3
48.251.755.1
11.812.513.1
54.257.159.8
41.845.048.0
9.09.5
10.0
50
180020002200
6.0 1.838.038.239.2
33.635.539.2
12.712.713.1
29.131.032.7
29.131.032.7
9.710.310.9
6.0 1.644.845.145.8
38.340.743.2
14.915.015.3
35.538.040.2
35.538.040.2
11.812.713.4
180020002200
11.0 5.749.652.054.1
37.740.442.9
9.09.59.8
37.939.741.3
33.235.738.0
6.97.27.5
9.0 3.454.356.258.2
41.844.747.6
12.112.512.9
41.443.044.5
36.839.542.1
9.29.59.9
180020002200
16.0 11.655.158.761.9
39.742.945.8
6.97.37.7
42.144.847.3
34.837.640.2
5.35.65.9
12.0 5.960.363.666.6
44.147.450.7
10.110.611.1
46.148.650.9
38.641.644.5
7.78.18.5
48ASHW - 60ASHWCOOLING PERFORMANCE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-18-
90ASHW
ENT.WTR.
oF
C.F.M.
90ASHW4 / 90ASVW4 (4 ROW COIL) 90ASHW6 / 90ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
250030003500
10.0 2.280.485.289.4
60.267.674.7
16.117.017.9
61.465.076.5
52.859.676.5
12.313.015.3
11 1.694.2100.3106.6
66.674.983.3
17.118.219.4
71.976.681.4
58.065.673.3
13.113.914.8
250030003500
15.0 4.796.3104.5111.2
66.374.882.7
12.813.914.8
73.579.884.9
57.665.372.5
9.810.611.3
21 5.5120.7133.4144.9
77.287.898.0
11.512.713.8
92.2101.9110.1
66.375.884.8
8.89.710.5
250030003500
22.0 9.8108.1119.3128.8
71.080.689.4
9.810.811.7
82.691.198.3
61.369.877.8
7.58.38.9
31 11.5133.3149.6164.1
82.494.4105.7
8.69.610.6
101.8114.2125.3
70.380.990.9
6.67.48.1
45
250030003500
10.0 2.273.878.182.0
57.865.072.0
14.815.616.4
56.363.469.6
50.963.469.6
11.312.713.9
11 1.686.492.097.8
63.671.880.0
15.716.717.8
66.070.374.7
55.763.270.7
12.012.813.6
250030003500
15.0 4.788.395.8102.0
63.371.679.3
11.812.813.6
67.573.277.9
55.262.869.8
9.09.810.4
21 5.5110.8122.4132.9
73.283.493.3
10.611.712.7
84.693.5101.5
63.172.381.2
8.18.99.7
250030003500
22.0 9.899.2109.4118.1
67.576.785.3
9.09.910.7
75.883.690.2
58.566.874.6
6.97.68.2
31 11.5122.3137.2150.6
77.889.4100.2
7.98.99.7
93.4104.8115.0
66.776.986.6
6.06.87.4
50
250030003500
10.0 2.262.766.469.6
53.760.869.6
12.513.313.9
47.252.858.0
47.252.858.0
9.410.611.6
11 1.673.578.283.1
58.866.774.7
13.414.215.1
56.162.568.5
51.862.568.5
10.211.412.5
250030003500
15.0 4.775.181.586.7
58.366.273.7
10.010.911.6
57.462.263.3
51.358.563.3
7.68.38.4
21 5.594.2104.1113.0
66.676.385.7
9.09.910.8
71.979.586.3
58.066.775.2
6.87.68.2
250030003500
22.0 9.884.393.0100.4
61.770.578.7
7.78.59.1
64.471.076.7
54.061.969.3
5.96.57.0
31 11.5103.9116.6128.0
70.481.291.4
6.77.58.3
79.489.197.7
61.070.679.7
5.15.76.3
120ASHW
ENT.WTR.
oF
C.F.M.
120ASHW4 / 120ASVW4 (4 ROW COIL) 120ASHW6 / 120ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
340040004600
12.0 2.0104.7107.3111.7
80.087.795.9
17.417.918.6
79.982.098.5
70.377.598.5
13.313.716.4
15 1.7130.7136.7143.5
91.5100.9110.7
17.418.219.1
99.8104.4109.6
79.688.397.3
13.313.914.6
340040004600
21.0 5.8132.7142.6151.4
90.7100.9110.5
12.613.614.4
101.3108.9115.7
78.788.096.7
9.710.411.0
25 4.7158.3172.3184.8
102.5114.8126.5
12.713.814.8
120.9131.6141.2
88.299.2109.8
9.710.511.3
340040004600
30.0 11.4145.5159.4171.6
95.8107.4118.2
9.710.611.4
111.1121.8131.0
82.793.1
102.8
7.48.18.7
35 9.1173.2192.0208.4
108.7122.8135.9
9.911.011.9
132.3146.6159.2
92.9105.4117.1
7.68.49.1
45
340040004600
12.0 2.096.098.5
102.5
76.884.592.6
16.016.417.1
73.382.589.5
67.882.589.5
12.213.814.9
15 1.7119.9125.4131.6
87.496.7106.3
16.016.717.5
91.695.8
100.5
76.485.093.8
12.212.813.4
340040004600
21.0 5.8121.7130.9138.9
86.596.4
105.8
11.612.513.2
93.0100.0106.1
75.484.493.0
8.99.5
10.125 4.7
145.2158.1169.6
97.3109.2120.6
11.612.613.6
110.9120.7129.5
84.194.8105.1
8.99.7
10.4
340040004600
30.0 11.4133.5146.3157.4
91.0102.3112.8
8.99.810.5
102.0111.7120.2
79.089.198.5
6.87.48.0
35 9.1158.9176.1191.2
102.8116.3129.0
9.110.110.9
121.3134.5146.0
88.4100.4111.7
6.97.78.3
50
340040004600
12.0 2.081.683.789.5
71.679.289.5
13.613.914.9
62.168.874.6
62.168.874.6
10.311.512.4
15 1.7101.9106.6111.9
80.689.899.1
13.614.214.9
77.883.690.9
71.083.690.9
10.411.112.1
340040004600
21.0 5.8103.5111.2118.1
79.689.198.2
9.910.611.2
79.085.084.3
70.078.784.3
7.58.18.0
25 4.7123.4134.4144.1
88.7100.1110.9
9.910.711.5
94.3102.6110.1
77.487.697.5
7.58.28.8
340040004600
30.0 11.4113.5124.3133.8
83.394.0
103.9
7.68.38.9
86.795.0102.2
73.082.591.5
5.86.36.8
35 9.1135.1149.7162.5
93.2105.9117.9
7.78.69.3
103.1114.4124.1
81.092.3103.0
5.96.57.1
90ASHW - 120ASHWCOOLING PERFORMANCE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-19-
180ASHW - 240ASHWCOOLING PERFORMANCE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
180ASHW
ENT.WTR.
oF
C.F.M.
180ASHW4 / 180ASVW4 (4 ROW COIL) 180ASHW6 / 180ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
520060006800
18.0 2.0155.0157.4164.0
120.4130.2141.4
17.217.518.2
118.4134.8145.0
105.9134.8145.0
13.215.016.1
20 1.7184.0188.1197.4
133.8145.0158.2
18.418.819.7
140.5143.6150.8
116.9127.4139.5
14.114.415.1
520060003800
30.0 5.3194.3205.7216.6
135.3148.2160.7
13.013.714.4
148.4157.1165.4
117.7129.5140.9
9.910.511.0
30 3.6218.3230.7244.4
147.2161.3175.8
14.615.416.3
166.8176.2186.6
127.4140.3153.5
11.111.712.4
520060006800
42.0 10.1214.9231.9246.5
143.3158.2172.1
10.211.011.7
164.1177.1188.3
124.0137.4149.9
7.88.49.0
40 6.3240.6259.1276.5
156.2172.5188.4
12.013.013.8
183.8197.9211.2
134.4149.0163.3
9.29.910.6
45
520060006800
18.0 2.0142.2144.4150.5
115.7125.5136.6
15.816.016.7
108.6122.6131.8
102.2122.6131.8
12.113.614.6
20 1.7168.8172.6181.1
128.1139.2152.2
16.917.318.1
128.9131.8156.4
112.4122.9156.4
12.913.215.6
520060006800
30.0 5.3178.3188.7198.7
129.1141.7154.0
11.912.613.2
136.1144.1151.7
112.9124.4135.6
9.19.6
10.130 3.6
200.3211.7224.2
140.1153.9168.2
13.414.114.9
153.0161.7171.2
121.9134.5147.4
10.210.811.4
520060006800
42.0 10.1197.2212.8226.2
136.4150.8164.3
9.410.110.8
150.6162.5172.7
118.6131.6143.8
7.27.78.2
40 6.3220.8237.8253.7
148.2164.0179.4
11.011.912.7
168.6181.6193.8
128.2142.4156.3
8.49.19.7
50
520060006800
18.0 2.0120.8122.6131.8
108.0122.6131.8
13.413.614.6
93.4102.1109.8
93.4102.1109.8
10.411.312.2
20 1.7143.5146.7153.9
118.7129.8142.5
14.314.715.4
110.8121.4130.4
110.8121.4130.4
11.112.113.0
520060006800
30.0 5.3151.5160.4168.9
119.1131.3143.2
10.110.711.3
115.7122.5122.8
104.9116.1122.8
7.78.28.2
30 3.6170.3179.9190.6
128.6142.0155.7
11.412.012.7
130.0137.4145.5
112.8125.0137.5
8.79.29.7
520060006800
42.0 10.1167.6180.8192.2
125.1138.8151.7
8.08.69.2
128.0138.1146.8
109.7122.1133.8
6.16.67.0
40 6.3187.7202.1215.6
135.2150.3165.0
9.410.110.8
143.3154.3164.7
118.0131.6144.9
7.27.78.2
240ASHW
ENT.WTR.
oF
C.F.M.
120ASHW4 / 120ASVW4 (4 ROW COIL) 120ASHW6 / 120ASVW6 (6 ROW COIL)
G.P.M.WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIRG.P.M.
WTR.P.D.FT.
80oF DB/67
oF WB ENT.
AIR75
oF DB/63
oF WB ENT.
AIR
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
TOTALMBH
SENS.MBH
TEMP.RISE
42
600080001000
40.0 5.2242.2276.0299.0
164.0198.0228.0
12.113.814.9
185.0210.0228.0
142.0173.0200.0
9.210.511.4
40 5.2268.0308.0337.0
177.0215.0250.0
13.415.416.9
205.0235.0258.0
152.0187.0219.0
10.211.712.9
600080001000
50.0 8.0259.0300.0330.0
170.0207.0329.0
10.412.013.2
198.0229.0252.0
147.0180.0209.0
7.99.2
10.150 8.0
289.0337.0375.0
185.0227.0264.0
11.613.515.0
221.0258.0287.0
159.0196.0230.0
8.810.311.5
600080001000
60.0 11.3270.0316.0351.0
175.0214.0247.0
9.010.511.7
206.0241.0268.0
151.0185.0216.0
6.98.08.9
60 11.3304.0360.0405.0
191.0236.0276.0
10.112.013.5
233.0275.0309.0
164.0203.0239.0
7.89.2
10.3
45
600080001000
40.0 5.2222.0253.0274.0
156.0189.0219.0
11.112.613.7
170.0193.0209.0
136.0166.0193.0
8.59.7
10.540 5.2
246.0282.0309.0
168.0205.0239.0
12.314.115.5
188.0216.0236.0
145.0179.0210.0
9.410.811.8
600080001000
50.0 8.0238.0275.0302.0
162.0198.0229.0
9.511.012.1
181.0210.0231.0
141.0173.0201.0
7.38.49.2
50 8.0265.0309.0344.0
175.0216.0252.0
10.612.413.8
202.0236.0263.0
151.0188.0221.0
8.19.5
10.5
600080001000
60.0 11.3248.0290.0322.0
166.0203.0237.0
8.39.710.7
189.0221.0246.0
144.0177.0207.0
6.37.48.2
60 11.3279.0330.0371.0
181.0224.0263.0
9.311.012.4
213.0252.0283.0
156.0194.0229.0
7.18.49.4
50
600080001000
40.0 5.2189.0215.0233.0
143.0175.0204.0
9.410.711.6
144.0164.0175.0
126.0155.0175.0
7.28.28.7
40 5.2209.0240.0263.0
153.0189.0222.0
10.512.013.1
169.0183.0201.0
134.0167.0201.0
8.09.2
10.0
600080001000
50.0 8.0202.0234.0257.0
148.0182.0212.0
8.19.310.3
154.0178.0182.0
130.0161.0182.0
6.27.17.3
50 8.0225.0263.0293.0
160.0198.0233.0
9.010.511.7
178.0201.0223.0
140.0174.0205.0
7.18.08.9
600080001000
60.0 11.3211.0246.0274.0
152.0187.0219.0
7.08.29.1
161.0188.0210.0
132.0164.0193.0
5.46.36.9
60 11.3237.0281.0315.0
164.0205.0242.0
7.99.4
10.5
187.0214.0241.0
146.0179.0212.0
6.27.18.0
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-20-
36ASHW4 / 36ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
100012001400
4.0 2.075.583.991.7
140135131
142138134
100012001400
8.0 7.583.994.7105.1
148143140
159156154
100012001400
12.0 16.386.898.9110.1
150146143
165163162
24HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
600800
10003.0 0.9
33.338.442.9
121115110
158154151
600800
10006.0 3.2
36.643.249.0
126120115
168166164
600800
10009.0 6.7
37.945.351.8
128122118
172170168
24ASHW4 / 24ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
6008001000
3.0 1.247.556.464.3
143135130
148142137
6008001000
6.0 4.452.063.273.3
150143138
163159156
6008001000
9.0 9.353.665.876.8
153146141
168165163
36HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
100012001400
4.0 1.653.358.765.4
119115112
153150148
100012001400
8.0 6.159.466.272.5
125121118
165164162
100012001400
12.0 13.161.568.775.4
127123120
170168167
48ASHW4 / 48ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
140016001800
6.0 3.9106.3114.9123.3
140137133
145142139
140016001800
10.0 10.3114.9125.3135.3
146143140
157155153
140016001800
13.0 17.0118.0129.4140.0
148145142
162160158
48HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
140016001800
5.0 2.072.878.082.7
118115113
151149147
140016001800
8.0 4.879.285.491.4
122119117
160159157
140016001800
12.0 10.483.390.297.0
125122120
166165164
24 - 48HEATING PERFORMANCE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-21-
60ASHW4 / 60ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
180020002200
6.0 1.8128.0136.2143.8
136133131
137135132
180020002200
11.0 5.7142.6152.9162.6
143141138
154152150
180020002200
16.0 11.6149.6160.8171.4
147144142
161160159
60HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
180020002200
6.0 3.193.198.2103.1
118116113
149147145
180020002200
9.0 6.6100.4106.5112.6
122119117
158156155
180020002200
12.0 11.5104.4111.0117.7
124121120
163162160
90ASHW4 / 90ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
250030003500
10.0 2.2207.8232.4255.2
147142137
138133129
250030003500
15.0 4.7222.4251.1278.5
152148144
150146143
250030003500
22.0 9.8232.8265.1295.7
156152148
159156153
90HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
250030003500
8.0 1.0146.2160.5171.5
124120115
143140137
250030003500
14.0 2.8162.3180.4196.2
130126122
157154153
250030003500
21.0 6.1171.1191.2209.1
133129125
164162160
120HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
340040004600
11.0 1.0198.5215.8229.4
124120116
144140138
340040004600
18.0 2.8217.8239.8257.8
129125122
156153151
340040004600
25.0 5.3227.8251.9272.0
132128125
162160158
120ASHW4 / 120ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
340040004600
12.0 2.0273.2302.6328.3
144140136
135130125
340040004600
21.0 5.8301.4337.0370.7
152148144
151148145
340040004600
30.0 11.4314.4352.9389.8
146152148
159156154
60 - 120HEATING PERFORMANCE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-22-
180 - 240HEATING PERFORMANCE
Product SpecificationsHorizontal / Vertical
Chilled Water / Hot Water
180HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
520060006800
17.0 1.9308.7332.3352.6
125121118
144141138
520060006800
25.0 4.1332.3360.2386.1
129125123
153151149
520060006800
35.0 8.0347.8378.5407.5
132128125
160158157
180ASHW4 / 180ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
520060006800
18.0 2.0411.0449.4483.2
143139136
134130126
520060006800
30.0 5.3450.7496.9540.5
150147143
150147144
520060006800
42.0 10.0471.7521.8570.0
154150148
157155153
240HWK (2 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
6000800010000
15.0 0.9323369415
120113108
137131125
6000800010000
25.0 2.3361420457
126119112
151146144
6000800010000
35.0 4.3382449494
192122116
158154152
240ASHW4 / 240ASVW4 (4 ROW COIL)
180OF ENTERING WATER TEMPERATURE
CFM GPMWTR.P.D.FT.
TOTALMBH
LVG.AIROF
LVG.WTR
OF
6000800010000
40.0 5.2547664768
154147141
153147142
6000800010000
50.0 8.0561687799
157150144
158153148
6000800010000
60.0 11.3571702819
158151146
161157153
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-23-
CONDENSATE DRAIN CONNECTION ENTERING
HOT WATER
LEAVINGHOT WATER
LEAVINGCHILLED WATER
ENTERINGCHILLED WATER
AIRFLOWAIRFLOW
CONDENSATE DRAIN CONNECTION
LEAVINGCHILLED WATER
ENTERINGCHILLED WATER
AIRFLOW
LEAVINGHOT WATER
AIRFLOW
HORIZONTAL RIGHT HAND COIL
CONNECTIONS
HORIZONTAL LEFT HAND COIL
CONNECTIONS
ELECTRICAL
AIRFLOW
AIRFLOW
ENTERING CHILLED WATER
CONDENSATE DRAIN CONNECTION
LEAVING HOT WATER
ENTERING HOT WATER
CONDENSATE DRAIN CONNECTION
ENTERING CHILLED WATER
LEAVING CHILLED WATER
LEAVING CHILLED WATER
ELECTRICAL
AIRFLOW
AIRFLOW
VERTICAL RIGHT HAND COIL CONNECTIONS
VERTICAL LEFT HAND COIL CONNECTIONS
CONNECTIONSProduct Specifications
Horizontal / VerticalChilled Water / Hot Water
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Catalog No. AShw609 (replaces ashw107)
BELT DRIVEProduct Specifications
Horizontal / VerticalChilled Water / Hot Water
-24-