Protelindo Site ID
Protlindo Site Name
Date
Time WIB / WITA / WIT
Grounding Measurement : Ohm ( < 1 Ohm )
Grounding Well : Ohm ( < 1 Ohm )
Tower Leg : Ohm ( < 1 Ohm )
Fence : Ohm ( < 1 Ohm )
Genset Tank : Ohm ( < 1 Ohm )
Grounding Status :
Lightening Rod : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
BAR grounding tower : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
BAR grounding well : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
Down conductor Cable : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
Bolt Connection : OK NOK Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
Tower Type : SST Monopole Triangle Pole Mini Tower
Painting Condition : OK NOK Remark : ( tower loosen paint 70 % ), GALVANIS
Construction Condition : OK NOK Remark : ( paving down/ tower leg cracked ), ………….
Tower Cleaning : OK NOK Remark : ( cleaning from spider nest / bee / etc ), ………….
Tower Lamp / OBL : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….
Photo Sensor : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….
Base ServiceCHECK LIST PREVENTIVE MAINTENANCEMECHANICAL ELECTRICAL
: JAW-CJV-0004-D-P
: TEMBALANG (SEMARANG)
: 06/03/2012
: 10:18:00 AM
GROUNDING
……………………….
……………………….
0,33
0,36
N/A
TOWER
LIGHTING
Tower Lamp (OBL) Amount : 4 Unit
Yard Lamp Amount (Mercury & TL) : 1 Unit
Tower Lamp (OBL) Condition : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….
Yard Lamp Condition : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….
Site Photo Sensor : OK NOK N/A Remark : ( sensor respon checking ), ………….
Yard Lamp Shield : OK NOK N/A Remark : ( lamp shield checking broken / no ), …….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….
Site Cleaning : OK NOK Remark : ( cleaning for grass / garbage )……………………
Flume Cleaning : OK NOK Remark : ……………………
Paving Block or Gravel : OK NOK Remark : ……………………
Barbared Wire : OK NOK Remark : ……………………
Fence Door (Swing/Sliding) : OK NOK Remark : ……………………
ENVA Check Respons
Lightening Alarm : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Obstruction Light Failure : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Grounding System : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Fence Break : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
( HARI )
INSPECTION BY
LIGHTING
FENCE
ENVA STATUS
PT NOKIA SIEMENS NETWORK
Protelindo Site ID Date
Protlindo Site Name Time WIB / WITA / WIT
Operator
Equipment Type : Indoor Outdoor AC Amount : 2 unit
AC Mark : Daikin National Others / PANASONIC 1,5 PK
Broken AC YES NO YES NO YES NO YES NO
Power 1,5 1,5
Pressure 70 70
Current Max
Current Measurement
AC Indoor Condition OK NOK OK NOK OK NOK OK NOK
Pipe Condition OK NOK OK NOK OK NOK OK NOK
Auto Restart OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A
Switch Contactor OK NOK OK NOK OK NOK OK NOK
AC Temperature Setting OK NOK OK NOK OK NOK OK NOK
Room Temperature :
Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK
Shelter Roof : OK NOK N/A Remark : ( leak, broken ), ………….
Dinding Shelter : OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….
Room Cleaning : OK NOK Leak Remark : ……………………
Roof Cleaning : OK NOK Leak Remark : ……………………
Benzoic Spreading : OK NOK Remark : ( cleaning for grass / garbage )……………………
Door Hinge Lubrication : OK NOK Remark : ……………………
Shelter Foundation : OK NOK Remark : ……………………
Heat Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
6,72 8,28
Tenant CHECK LIST PREVENTIVE MAINTENANCEMECHANICAL ELECTRICAL
: JAW-CJV-0004-D-P : 06/03/2012
: TEMBALANG (SEMARANG) : 10:18:00 AM
: FLEXI
AIR CONDITIONER
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
AC Status
PK
Psi
According with data signed at AC Outdoor
Ampere
Leak / Not Leak
Leak / Not Leak
Operation
test switch
< 24 oC
20,7
EXHAUST FAN
SHELTER
Alarm System
GROUNDING
Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
Control Box : Ohm ( < 1 Ohm )
External Grounding Bar : Ohm ( < 1 Ohm )
Internal Grounding Bar : Ohm ( < 1 Ohm )
Base Frame Condition : OK NOK N/A Remark : ...............................
Dynabolt Condition : OK NOK N/A Remark : ...............................
Base Frame Foundation : OK NOK N/A Remark : ...............................
Phase Voltage R - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : V 380 V +/- 5% max 10 V
Phase Voltage S - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : V 380 V +/- 5% max 10 V
Phase Voltage T - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) : V
Phase Voltage R - S (350V - 400V) : V 380 V +/- 5% max 10 V KWH Meter Record :
AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
KWH Box Including Pole KWH : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition )
COS : OK NOK N/A Remark : ( clean, neat, broken )
PLN Power Supplied : kVA
MCB input :
MCB Condition : OK NOK NA
1 Phase : A pcs
3 Phases : A pcs
COS : A
PLN ID :
Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..……
Terminal / OKA : OK NOK NA ( Good Sealed ), ………..……
MCB : OK NOK NA ( Good Sealed ), ………..……
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
B. R, S & T Indicator Lamps are lit : OK NOK NA
MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..……
KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……
211 0
378
Measurement
0,39
0,37
0,53
OUTDOOR TYPE
KWH ELECTRICAL MEASUREMENT
217 371
216 373
35037
ELECTRICAL VISUAL CHECK
PLN VISUAL CHECK
52-3040397908
PLN FUNCTION TEST
PT NOKIA SIEMENS NETWORK
INSPECTION BY
23
……………… ………………
35 3
40
( HARI )
Protelindo Site ID Date
Protlindo Site Name Time WIB / WITA / WIT
Operator
Equipment Type : Indoor Outdoor AC Amount : …………. unit
AC Mark : Daikin National Others / ……………..
Broken AC YES NO YES NO YES NO YES NO
Power
Pressure
Current Max
Current Measurement
AC Indoor Condition OK NOK OK NOK OK NOK OK NOK
Pipe Condition OK NOK OK NOK OK NOK OK NOK
Auto Restart OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A
Switch Contactor OK NOK OK NOK OK NOK OK NOK
AC Temperature Setting OK NOK OK NOK OK NOK OK NOK
Room Temperature :
Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK
Shelter Roof : OK NOK N/A Remark : ( leak, broken ), ………….
Dinding Shelter : OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….
Room Cleaning : OK NOK Leak Remark : ……………………
Roof Cleaning : OK NOK Leak Remark : ……………………
Benzoic Spreading : OK NOK Remark : ( cleaning for grass / garbage )……………………
Door Hinge Lubrication : OK NOK Remark : ……………………
Shelter Foundation : OK NOK Remark : ……………………
Heat Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Tenant CHECK LIST PREVENTIVE MAINTENANCEMECHANICAL ELECTRICAL
: JAW-CJV-0004-D-P : 06/03/2012
: TEMBALANG (SEMARANG) : 10:18:00 AM
: ISAT
AIR CONDITIONER
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
AC Status
PK
Psi
According with data signed at AC Outdoor
Ampere
Leak / Not Leak
Leak / Not Leak
Operation
test switch
< 24 oC
EXHAUST FAN
SHELTER
Alarm System
GROUNDING
Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
Control Box : Ohm ( < 1 Ohm )
External Grounding Bar : Ohm ( < 1 Ohm )
Internal Grounding Bar : Ohm ( < 1 Ohm )
Base Frame Condition : OK NOK N/A Remark : ...............................
Dynabolt Condition : OK NOK N/A Remark : ...............................
Base Frame Foundation : OK NOK N/A Remark : ...............................
Phase Voltage R - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : V 380 V +/- 5% max 10 V
Phase Voltage S - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : V 380 V +/- 5% max 10 V
Phase Voltage T - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) : V
Phase Voltage R - S (350V - 400V) : V 380 V +/- 5% max 10 V KWH Meter Record :
AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
KWH Box Including Pole KWH : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition )
COS : OK NOK N/A Remark : ( clean, neat, broken )
PLN Power Supplied : kVA
MCB input :
MCB Condition : OK NOK NA
1 Phase : A pcs
3 Phases : A pcs
COS : A
PLN ID :
Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..……
Terminal / OKA : OK NOK NA ( Good Sealed ), ………..……
MCB : OK NOK NA ( Good Sealed ), ………..……
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
B. R, S & T Indicator Lamps are lit : OK NOK NA
MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..……
KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……
Measurement
0,37
-
N/A
OUTDOOR TYPE
KWH ELECTRICAL MEASUREMENT
212 0
212 0
212 0
0 2472
ELECTRICAL VISUAL CHECK
PLN VISUAL CHECK
N/A
PLN FUNCTION TEST
PT NOKIA SIEMENS NETWORK
INSPECTION BY
7,7
35 1
…………… …………..
40
( HARI )
Protelindo Site ID Date
Protlindo Site Name Time WIB / WITA / WIT
Operator
Equipment Type : Indoor Outdoor AC Amount : …………. unit
AC Mark : Daikin National Others / ……………..
Broken AC YES NO YES NO YES NO YES NO
Power
Pressure
Current Max
Current Measurement
AC Indoor Condition OK NOK OK NOK OK NOK OK NOK
Pipe Condition OK NOK OK NOK OK NOK OK NOK
Auto Restart OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A
Switch Contactor OK NOK OK NOK OK NOK OK NOK
AC Temperature Setting OK NOK OK NOK OK NOK OK NOK
Room Temperature :
Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK
Shelter Roof : OK NOK N/A Remark : ( leak, broken ), ………….
Dinding Shelter : OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), ………….
Room Cleaning : OK NOK Leak Remark : ……………………
Roof Cleaning : OK NOK Leak Remark : ……………………
Benzoic Spreading : OK NOK Remark : ( cleaning for grass / garbage )……………………
Door Hinge Lubrication : OK NOK Remark : ……………………
Shelter Foundation : OK NOK Remark : ……………………
Heat Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Tenant CHECK LIST PREVENTIVE MAINTENANCEMECHANICAL ELECTRICAL
: JAW-CJV-0004-D-P : 06/03/2012
: TEMBALANG (SEMARANG) : 10:18:00 AM
: TSEL
AIR CONDITIONER
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
AC Status
PK
Psi
According with data signed at AC Outdoor
Ampere
Leak / Not Leak
Leak / Not Leak
Operation
test switch
< 24 oC
EXHAUST FAN
SHELTER
Alarm System
GROUNDING
Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
Control Box : Ohm ( < 1 Ohm )
External Grounding Bar : Ohm ( < 1 Ohm )
Internal Grounding Bar : Ohm ( < 1 Ohm )
Base Frame Condition : OK NOK N/A Remark : ...............................
Dynabolt Condition : OK NOK N/A Remark : ...............................
Base Frame Foundation : OK NOK N/A Remark : ...............................
Phase Voltage R - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : V 380 V +/- 5% max 10 V
Phase Voltage S - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : V 380 V +/- 5% max 10 V
Phase Voltage T - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) : V
Phase Voltage R - S (350V - 400V) : V 380 V +/- 5% max 10 V KWH Meter Record :
AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ………
KWH Box Including Pole KWH : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition )
COS : OK NOK N/A Remark : ( clean, neat, broken )
PLN Power Supplied : kVA
MCB input :
MCB Condition : OK NOK NA
1 Phase : A pcs
3 Phases : A pcs
COS : A
PLN ID :
Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..……
Terminal / OKA : OK NOK NA ( Good Sealed ), ………..……
MCB : OK NOK NA ( Good Sealed ), ………..……
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
B. R, S & T Indicator Lamps are lit : OK NOK NA
MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..……
KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……
Measurement
0,33
0,42
N/A
OUTDOOR TYPE
KWH ELECTRICAL MEASUREMENT
212 0
213 0
212 0
0 1311
ELECTRICAL VISUAL CHECK
PLN VISUAL CHECK
N/A
PLN FUNCTION TEST
PT NOKIA SIEMENS NETWORK
INSPECTION BY
7,7
16 2
…………… ……………
40
( HARI )
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK
PREVENTIVE MAINTENANCEPHOTO REPORT Base Service
Foto A - 1 Foto A - 2Tampak halaman site sebelum dibersihkan Tampak halaman site setelah dibersihkan
Foto A - 3 Foto A - 4Tampak tower bagian atas (tampak mounting & lampu halaman) Tampak tower bagian bawah (tampak pedestal/kaki tower)
Foto A - 5 Foto A - 6Tampak pagar / tembok Tampak paving block / gravel
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK
PREVENTIVE MAINTENANCEPHOTO REPORT Base Service
Foto B - 1 Foto B - 2Status grounding - Tampak lightning rod (Splitzen) Status grounding - Grounding ke Pagar
Foto B - 5 Foto B - 6Pengukuran grounding - Grounding ke Pagar Pengukuran grounding - Grounding ke kaki tower
Foto B - 3 Foto B - 4Status grounding - Down Conductor cable Status grounding - Bolt Connection
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK
PREVENTIVE MAINTENANCEPHOTO REPORT Base Service
Foto C - 1 Foto C - 2Pengukuran grounding - Tangki genset (if any) Pengukuran grounding - Box control
N/A
Tampak Access Lease Area Site View - Tampak Atas (Sisi -1)
Foto C - 3 Foto C - 4OBL - Berfungsi dengan baik Yard Lamp - Berfungsi dengan baik
Foto C - 5 Foto C - 6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK
Site View - Tampak Atas (Sisi - 2) Safety Tools (Safety belt, helm, sepatu, sarung tangan)
PREVENTIVE MAINTENANCEPHOTO REPORT Base Service
Foto D - 1 Foto D - 2
N/A
Foto D - 5 Foto D - 6
Foto D - 3 Foto D - 4Tampak warning sign board (if any)
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Foto A-1 Foto A-2Tampak Bagian Luar Shelter Tampak Bagian Dalam Shelter
Foto A-3 Foto A-4Tampak Cable Tray Tampak Lampu di dalam shelter
Foto A-6 Foto A-5Tampak Lampu di luar shelter Tampak frame FEP
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
Tampak Grounding di dalam shelter Tampak pondasi shelter
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Foto B-1 Foto B-2
Foto B-5 Foto B-6Tampak DC Fan Tampak Smoke & Heat detector
Foto B-3 Foto B-4Tampak Fire Extinguisher Tampak Panel Alarm
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
Foto C-1 Foto C-2Tampak AC Indoor Tampak AC Outdoor
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Pengukuran - Tekanan AC Pengukuran - Temperature Shelter
Foto C-5 Foto C-6Pengukuran - Tegangan R - N (Panel KWH) Pengukuran - Tegangan S - N (Panel KWH)
Foto C-3 Foto C-4
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Foto D-1 Foto D-2Pengukuran - Tegangan T - N (Panel KWH) Pengukuran - Tegangan R - S (Panel KWH)
Pengukuran - Tegangan G- N (Panel KWH) Pengukuran - Tegangan R - N (Panel ACPDB)
Foto D-3 Foto D-4Pengukuran - Tegangan S - T (Panel KWH) Pengukuran - Tegangan R - T (Panel KWH)
Foto D-5 Foto D-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
Pengukuran - Tegangan S - N (Panel ACPDB) Pengukuran - Tegangan T - N (Panel ACPDB)
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Foto D-1 Foto D-2
Pengukuran - Tegangan R - T (Panel ACPDB) Pengukuran - Tegangan G - N (Panel ACPDB)
Foto D-3 Foto D-4Pengukuran - Tegangan R - S (Panel ACPDB) Pengukuran - Tegangan S - T (Panel ACPDB)
Foto D-5 Foto D-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Foto E-1 Foto E-2Status grounding - Control Box Status grounding - External Grounding Bar
Pengukuran grounding - External Grounding Bar Pengukuran grounding - Internal Grounding Bar
Foto E-3 Foto E-4Status grounding - Internal Grounding Bar Pengukuran grounding - Control Box
Foto E-5 Foto E-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
Tampak Pole KWH Box Kondisi KWH Panel (Keadaan tertutup)
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Foto F-1 Foto F-2
Foto F-5 Foto F-6Kondisi Segel pada Terminal KWH Kondisi Segel pada KWH Meter Record
Foto F-3 Foto F-4Kondisi KWH Panel (Keadaan terbuka) Kondisi MCB KWH Meter
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantIndoor
Foto G-1 Foto G-2Kondisi segel pada MCB KWH meter KWH meter record
Foto G-5 Foto G-6
Foto G-3 Foto G-4ID Pelanggan
Protelindo ID : JAW-CJV-0004-D-P Date
Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto A-1 Foto A-2Tampak Kondisi Base Frame Tampak Kondisi Dyna Bolt
: 06/03/2012
Pengukuran - Tegangan S - N (Panel KWH) Pengukuran - Tegangan T - N (Panel KWH)
Foto A-3 Foto A-4Tampak Pondasi Base Frame Pengukuran - Tegangan R - N (Panel KWH)
Foto A-6 Foto A-5
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
Pengukuran - Tegangan R - S (Panel KWH) Pengukuran - Tegangan S - T (Panel KWH)
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto B-1 Foto B-2
Foto B-5 Foto B-6Pengukuran - Tegangan R - N (Panel ACPDB) Pengukuran - Tegangan S - N (Panel ACPDB)
Foto B-3 Foto B-4Pengukuran - Tegangan R - T (Panel KWH) Pengukuran - Tegangan G- N (Panel KWH)
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
Foto C-1 Foto C-2Pengukuran - Tegangan T - N (Panel ACPDB) Pengukuran - Tegangan R - S (Panel ACPDB)
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Pengukuran - Tegangan S - T (Panel ACPDB) Pengukuran - Tegangan R - T (Panel ACPDB)
Foto C-5 Foto C-6Pengukuran - Tegangan G - N (Panel ACPDB) Status grounding - Control Box
Foto C-3 Foto C-4
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto D-1 Foto D-2Status grounding - External Grounding Bar Status grounding - Internal Grounding Bar
NA
Pengukuran grounding - Internal Grounding Bar Tampak Pole KWH Box
Foto D-3 Foto D-4Pengukuran grounding - Control Box Pengukuran grounding - External Grounding Bar
Foto D-5 Foto D-6
NA
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
Kondisi KWH Panel (Keadaan tertutup) Kondisi KWH Panel (Keadaan terbuka)
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto E-1 Foto E-2
Foto E-5 Foto E-6Kondisi Segel pada KWH Meter Record Kondisi segel pada MCB KWH meter
Foto E-3 Foto E-4Kondisi MCB KWH Meter Kondisi Segel pada Terminal KWH
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
Foto F-1 Foto F-2KWH meter record ID Pelanggan
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
N/A
Foto F-5 Foto F-6
Foto F-3 Foto F-4
Protelindo ID : JAW-CJV-0004-D-P Date
Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
: 06/03/2012
Foto A-1 Foto A-2Tampak Kondisi Base Frame Tampak Kondisi Dyna Bolt
Foto A-3 Foto A-4Tampak Pondasi Base Frame Pengukuran - Tegangan R - N (Panel KWH)
Foto A-6 Foto A-5Pengukuran - Tegangan S - N (Panel KWH) Pengukuran - Tegangan T - N (Panel KWH)
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto B-1 Foto B-2Pengukuran - Tegangan R - S (Panel KWH) Pengukuran - Tegangan S - T (Panel KWH)
Foto B-3 Foto B-4Pengukuran - Tegangan R - T (Panel KWH) Pengukuran - Tegangan G- N (Panel KWH)
Foto B-5 Foto B-6Pengukuran - Tegangan R - N (Panel ACPDB) Pengukuran - Tegangan S - N (Panel ACPDB)
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto C-1 Foto C-2Pengukuran - Tegangan T - N (Panel ACPDB) Pengukuran - Tegangan R - S (Panel ACPDB)
Foto C-3 Foto C-4Pengukuran - Tegangan S - T (Panel ACPDB) Pengukuran - Tegangan R - T (Panel ACPDB)
Foto C-5 Foto C-6Pengukuran - Tegangan G - N (Panel ACPDB) Status grounding - Control Box
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto D-1 Foto D-2Status grounding - External Grounding Bar Status grounding - Internal Grounding Bar
NA
Foto D-3 Foto D-4Pengukuran grounding - Control Box Pengukuran grounding - External Grounding Bar
Foto D-5 Foto D-6Pengukuran grounding - Internal Grounding Bar Tampak Pole KWH Box
NA
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto E-1 Foto E-2Kondisi KWH Panel (Keadaan tertutup) Kondisi KWH Panel (Keadaan terbuka)
Foto E-3 Foto E-4Kondisi MCB KWH Meter Kondisi Segel pada Terminal KWH
Foto E-5 Foto E-6Kondisi Segel pada KWH Meter Record Kondisi segel pada MCB KWH meter
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012
Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL
PREVENTIVE MAINTENANCEPHOTO REPORT
TenantOutdoor
Foto F-1 Foto F-2KWH meter record ID Pelanggan
N/A
Foto F-3 Foto F-4
Foto F-5 Foto F-6