chatter - mjk automation:...

4
• Measuring levels, pressure, temparature, flow and more paramateres in wells, boreholes, sewers and rivers or lakes Ground water level monitoring. Chatter™ Data Logger is especially useful in places without main power supply, as it is developed for having a very long lifespan on the built-in battery. Storm flow logging, activated by level-trigger or analog limit. Logging of amount, durance and time of storm flows. Application General Chatter™ Data Logger is designed for monitoring drinking water and waste water installations. Chatter™ Data Logger has a built-in multi- channel data logger, a GSM / GPRS modem and a battery ensuring up to 5 - 10 years of continuous operation. The embedded software activates the required digital and analog inputs, and time-stamped data are stored at selectable intervals. Three different types of call can be selected; Data for standard SQL-database, SCADA system or as e-mail or SMS, and the calls can be scheduled to user controlled intervals, transferred using the GSM/GPRS net. Installation and configuration of data logging are very simple with the MJK user software. Data from the SQL database can be transferred to larger SCADA systems using Chatter CNS plug-in. Chatter™ Data Logger is available in two different versions: one for pipe mounting and one for wall mount. Transmits data and alarms to standard SQL database using GSM/GPRS network Transmits data and alarms to SCADA systems using Modbus® RTU protocol over GSM/GPRS network Data transmission by e-mail to up to four e-mail addresses: Data directly in the mail body Data as attached CSV file in the mail. Data file can be displayed by Chatter Link PC software Transmitslive data and alarms as SMS message to up to four recipients Alarms can be sent alone or along with other communication as SMS. Features Chatter EN 6.10 CHATTER DATASHEET 1402 DATASHEET 6.10 DATA LOGGER WITH INTEGRATED MODEM

Upload: vuanh

Post on 08-Mar-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

• Measuringlevels,pressure,temparature,flowandmoreparamateresinwells,boreholes,sewersandriversorlakes

• Groundwaterlevelmonitoring.Chatter™DataLoggerisespecially usefulinplaceswithoutmainpowersupply,asitisdevelopedfor havingaverylonglifespanonthebuilt-inbattery.• Stormflowlogging,activatedbylevel-triggeroranaloglimit. Loggingofamount,duranceandtimeofstormflows.

Application

GeneralChatter™DataLoggerisdesignedformonitoringdrinkingwaterandwastewaterinstallations.Chatter™DataLoggerhasabuilt-inmulti-channeldatalogger,aGSM/GPRSmodemandabatteryensuringupto5-10yearsofcontinuousoperation.

Theembeddedsoftwareactivatestherequireddigitalandanaloginputs,andtime-stampeddataarestoredatselectableintervals.Threedifferenttypesofcallcanbeselected;DataforstandardSQL-database,SCADAsystemorase-mailorSMS,andthecallscanbescheduledtousercontrolledintervals,transferredusingtheGSM/GPRSnet.

InstallationandconfigurationofdataloggingareverysimplewiththeMJKusersoftware.DatafromtheSQLdatabasecanbetransferredtolargerSCADAsystemsusingChatterCNSplug-in.

Chatter™DataLoggerisavailableintwodifferentversions:oneforpipemountingandoneforwallmount.

• TransmitsdataandalarmstostandardSQLdatabaseusingGSM/GPRSnetwork• TransmitsdataandalarmstoSCADAsystemsusingModbus®RTUprotocol overGSM/GPRSnetwork• Datatransmissionbye-mailtouptofoure-mailaddresses: • Datadirectlyinthemailbody • DataasattachedCSVfileinthemail. • DatafilecanbedisplayedbyChatterLinkPCsoftware• TransmitslivedataandalarmsasSMSmessagetouptofourrecipients• AlarmscanbesentaloneoralongwithothercommunicationasSMS.

Features

Chatter™

EN6.10CHATTERDATASHEET1402DATASHEET

6.10

DATALOGGERWITHINTEGRATEDMODEM

Chatter™ Data Logger

Specifications

Four-In-One

Chatter™ Data Logger

Powersupply Built-in3,6VDC,19Ahlithiumbattery

Performance Betterthan5years@1measurement/dayand1call/day

Clock Real-timeclock,24-hourclock

Memorystorage DBVersion:>100.000measuredvalues(date-andtime-stamped)RTUandE-mailversion:90.000measuredvalues(date-andtimestamped)

Logintervals 1,2,510min,1,2,4,8,12or24hours

EventLogintervals 1,2,510min,1,2,4,8,12or24hours

Callintervals 1,2,4,8,12or24hours,and10,25,50100,250,500or1000Logs

Communication Build-inGSM/GPRSquad-band850/900/1800/1900MHzmodemw/on-boardSIM-cardholder

ExternalCommunicationProtocol

MJKProprietaryprotokolforDBVersion,Modbus®RTU-mode,Modbus®TCPorCOMLI®forRTUversion

Interface1pcs.RS485forSerialDatainput1pcs.USB1,1typeminiB,female1pcs.MMCX,female,forantenna

Antenna Pipe:Built-inGSM/GPRSAntenna-Dualband,Amplification0dB,Frequency900/1800MHz

Mounting InPipewithinnerdiameterØ63-Ø106mmoronawall

Enclosure IP67

Materials Pipe:PC-ASA(top)andaluminium(base)Wall:Glas-reinforcedPC(polycarbonate)

Temperaturerange -20…60°C

Airhumidity Max.95%relative

Weight Pipemounting:1,8kgWallmounting:0,7kg

CEapprovals EN61000-6-1:2007,EN61000-6-3:2007

Input and Output 4AI/4DI/1RS485

Digitalinputs 4pcs.2-5VDC(min.timeforstate1second)

Analoginputs 4pcs.0-2,5VDC

SerialDatainput 1pcs.RS-485Modbus®comportformax.4unitsModbus®RTU-mode,9600baud,2-wireRS-485,Mastermode,Function3,Readonly

PowersupplyforI/O1pcs.3,6VDC1pcs.3,6VDCON/OFF-controlled1pcs.5VDCON/OFF-controlled,option+10or+15VDC.

Accuracy AI:Betterthan±1%FS

Resolution AI:10bit,inputimpedance:min.10Kohm

Database Server

Serverrequirements MicrosoftServer2008R2,IISv.7(InternetInformationServices)MicrosoftSQLDatabase2008R2ExpressEdition

Networkrequirements. MPLS/APN(Multi-ProtocolLabelSwitching)orinternetaccess

Asourproductsaredevelopedcontinously,wereservetherigthtomakeanychangeswithoutpriornotice.

AsaRTUwithdirectcommunicationtoaScadasystem.

Datacanbesentine-mailstoastandardemailaddress.

Chatter™DataLoggermeasuresandstoresdatainthedataloggerandcantransmitin4differentmodes:

Chatter™DataLoggercansendalarmsandstatusofthemeasurementsasSMSmessages

SendsdatatoaSQLdatabase,wheremeasurementsandalarmscanbetransferredtoe.g.aScadasystem

Chatter™ Data LoggerElectrical Connections

USBUSB

SIM card

ON OFF

Battery

ANT.1

ANT.2 ANT.3

DI 1

DI 2

DI 3

DI 4

AI 1

AI 2

AI 3

AI 4

GN

D

GN

D

+5/

10/

15V

GN

D

3V6-

A

GN

D

GN

D

A B GN

D

3V6-

B

GN

D

RS485

Accessories Chatter Link™

Designedforforsetup,configurationandviewingonlinedatathroughUSBconnection.

Expert Digital Hydrostatic Level transmitters.

• HydrostaticPiezo-resistiverelativemeasuringprinciple.

• RS485digitaloutput,Modbus,levelandTemperaturesignals.

• Measuringrange:0–3m…300m(0-10ft..1000ft)

• Supplyvoltage:3,5-12VDC• Accuracy,betterthan±0.25%FS@+10to30°C

Dimensions

144

156

Ø20

83 79150 mm

101 mm

190 mm

Ø 63 - 106 mmIndre rørdiameter

190

150

101

Inner Pipe dia.Ø 63 - Ø106

Wallmounting:

Pipemounting:

Chatter™ Data Logger

Order Numbers Chatter™ Data Logger

204105 Chatter™DataLoggerGSM/GPRSfortubemounting

204110 Chatter™DataLoggerGSM/GPRSforwallmounting

204122 Chatter™DataLoggerGSM/GPRSforwallmounting,10-30VDC(3,7VLi-Ion)

204125 Chatter™DataLoggerGSM/GPRSforwallmounting,230VAC/12VDC

Accessories

840134 Chatter™SystemSoftwareDVD

840400 ChatterLink™

840128 Chatter™DataLoggerNotificationSystem.MustrunonthesameserverasChatterDBSystem

840135 Chatter™DataLoggerSetupTool

521751 MountingwedgekitfortubeØ63-92mm,3x3pcs.Metal,wedgesizes:1,2,3and4

521752 MountingwedgekitfortubeØ84-106mm,3x3pcs.Metal,wedgesizes:4,5and6

521755 Wedgescrews,kitwith3pcs.

521757 Padlockbracket,Ø8mm

521760 GasketforChatter™DataLoggerbase/tube

521761 GasketforChatter™DataLoggertop/base

521762 GasketforChatter™DataLoggercoverplate

550246 Battery3.6V,19Ah

569108 Screw,self-tapping,KB50x14

569123 Screw,self-tapping,KB35x7

571055 Rubberband,60mm,folded

691095 USBCable,Mini/USB

691098 USBplug,minitominiforpanelmounting,IP67

Antennas Seedatasheet:EN6.26GSM-GPRSAntennasDatasheet

ExpertHydrostaticLevelTransmitters Seedatasheet:EN2.75ExpertDatasheet

MJKAutomationApSByageren7DK-2850NærumDenmark

Tel +4545560656Fax+4545560646

www.mjk.com

C

ERT I F I E D

IS

O 9001-2008

Connect,MµConnect,Chatter,MagFlux,Oxix,pHixcompact,ShuttleandSuSixareregistreredtrademarksofMJKAutomationApS.©2013Xylem,Inc.