FEATURES
● Thermal isolating adapter betweenflange and actuator.
● Vent holes reducecondensation build-up.
● Easy direct coupling of actuator with a single screw.
● Forged brass valve body — no pin-hole leaks.
● Perpendicular mounting flange and square drive head eliminate lateral forces on the stem.
● Characterizing disc — made of Tefzel®known for excellent strength and chemical resistance.
● Blow-out proof stem with thrust-bearing Teflon® disc and double O-ring design ®
for long service life.*
● Teflon® seats with O-rings provide®
constant seating force against the ball and reduce torque requirement.
● Non-corroding chrome-plated brass or stainless ball.
● Actuator can be mounted in fourdifferent positions.
* Designed for service life of over 100,000 full cycles.Teflon® and Tefzel® are both registered trademarks of Dupont.
EQUAL PERCENTAGE VALVE CHARACTERISTIC
In order to ensure good stability of control, it is essential for a control valve to have an equal percentage characteristic.
This type of characteristic produces a linear variationin thermal output according to the amount of opening of the valve (also known as the systemcharacteristic). Under normal testing conditions a conventional ball valve exhibits an S-shaped characteristic. When it is installed in a real system, however, this characteristic is seriouslydeformed because, compared with its nominal
size, a ball valve possesses an extremely high flow coefficient. Whether used with or without pipe
reducers or a reduced bore, they do not normally allow stable regulation of the thermal capacity.
Belimo’s unique Characterized Control Valve™ (CCV) is very different. A special characterizing disc inside the valve gives it
an equal percentage characteristic which is comparable with that of a globe valve of the same nominal size. The flow (the Cv value) is reduced to the required value by a combination of the hole in the ball and the shaped aperture in the disc. The increase in flow as the valve is opened is very slow and controlled.
This produces better part-load behavior and improved stability ofcontrol while also optimizing energy consumption.
BENEFIT OF THE BELIMO CHARACTERIZING DISC
● Equal percentage flow characteristic.
● Excellent control stability assured with the characterizing disc.
● Cv values equal to Cv values of globe valves the same size.
● The need for multiple pipe reduction is usually eliminated.
● Better control prevents “hunting” of the control loop, increasinglife span of actuator and valve.
Patented Technology
Characterized Control Valves™ (CCV)
Features and Benefi ts
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
2
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
COORDINATED MOTORIZED OPERATION
The optimum functionality of the Belimo CCV is assured by properly coordinating its actuation with MFT. Specially developed rotary actuators provide the necessary precision for modulating, floating-point, and on/off methods of control.
All CCVs are supplied with the appropriate rotary actuator to provide the close-off and operation desired.
OPTIMIZED FOR CONTROL
The Belimo CCV marries known technology with an innovative development – the unique characterizing disc.
The marriage of CCV and MFT technologies has produced a range ofvaluable features which surpass the capabilities of globe valves at a very attractive price level:
● An equal-percentage valve characteristic● Unlike a globe valve, no sudden change in inlet flow upon opening● Excellent stability of control● Cv values comparable with those of globe valves of the same size
or larger● Higher close-off ratings than standard globe valves● 100% tight shut-off on two-way valves means NO leak-by unlike
globe valves that have ANSI IV shutoff (leakage rate of 0.01% of the Cv rating)
● Three-way valve can be piped in mixing or diverting application
B2 Series Two-way
B3 Series Three-wayMixing/Diverting
B6 Series Two-way Flanged
½” to 3”
Service: Chilled/hot water, 60% glycol
Cv Range 0.3-240
Material: Stainless trim or Brass trim
Control: On/Off, Floating, 2-10 VDC
Multi-Function Technology®
Spring Return or Non-Spring Return
Flow Characteristics of Conventional Ball Valvesversus BELIMO CHARACTERIZED CONTROL VALVES
Stablecontrol ishard toachieve
Desirablevalveauthority is notachieved
Desirable Equal Percent Flow and resulting heat output is achieved with linear results
Feature / Benefi tsCharacterized Control Valves™ (CCV)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
3
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Cv Maximum
RatingInches DN
mm2-WayCCV
Pressure Drop Across the Valve
1 psi 2 psi 3 psi 4 psi 5 psi 6 psi 7 psi 8 psi 9 psi 10 psi
0.3 ½” 15 B207(B) 0.3 0.4 0.5 0.6 0.7 0.7 0.8 0.8 0.9 0.90.46 ½” 15 B208(B) 0.5 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.50.8 ½” 15 B209(B) 0.8 1.1 1.4 1.6 1.8 2.0 2.1 2.3 2.4 2.51.2 ½” 15 B210(B) 1.2 1.7 2.1 2.4 2.8 2.9 3.2 3.4 3.6 3.81.9 ½” 15 B211(B) 1.9 2.7 3.3 3.8 4.2 4.7 5.0 5.4 5.7 6.03 ½” 15 B212(B) 3.0 4.2 5.2 6.0 6.8 7.3 7.9 8.5 9.0 9.5
4.7 ½” 15 B213(B) 4.7 6.6 8.1 9.4 11 12 12 13 14 157.4 ½” 15 B214(B) 7.4 10 13 15 17 18 20 21 22 2310 ½” 15 B215(B)* 10 14 17 20 22 24 26 28 30 324.7 ¾” 20 B217(B) 4.7 6.6 8.1 9.4 11 12 12 13 14 157.4 ¾” 20 B218(B) 7.4 10 13 15 17 18 20 21 22 2310 ¾” 20 B219(B) 10 14 17 20 22 24 26 28 30 3224 ¾” 20 B220(B)* 24 34 42 48 54 59 63 68 72 767.4 1” 25 B222 7.4 10 13 15 17 18 20 21 22 2310 1” 25 B223 10 14 17 20 22 24 26 28 30 3219 1” 25 B224 19 27 33 38 42 47 50 54 57 6030 1” 25 B225* 30 42 52 60 67 73 79 85 90 9510 1¼” 32 B229 10 14 17 20 22 24 26 28 30 3219 1¼” 32 B230* 19 27 33 38 42 47 50 54 57 6025 1¼” 32 B231 25 35 43 50 56 61 66 71 75 7937 1¼” 32 B232* 37 52 64 74 83 91 98 105 111 11719 1½”” 40 B238 19 27 33 38 42 47 50 54 57 6029 1½” 40 B239 29 41 50 58 65 71 77 82 87 9237 1½” 40 B240* 37 52 64 74 83 91 98 105 111 11729 2” 50 B248 29 41 50 58 65 71 77 82 87 9246 2” 50 B249 46 65 80 92 103 113 122 130 138 14557 2” 50 B250* 57 81 99 114 127 140 151 161 171 18065 2” 50 B251 65 92 113 130 145 159 170 194 195 20685 2” 50 B252 85 120 147 170 190 208 225 240 255 269120 2” 50 B253 120 170 208 240 268 294 318 339 360 380240 2” 50 B254* 240 339 416 480 537 588 635 679 720 75960 2½” 65 B261 60 85 104 120 134 147 159 170 180 19075 2½” 65 B262 75 106 130 150 168 194 198 212 225 237110 2½” 65 B263 110 156 191 220 246 269 291 311 330 348150 2½” 65 B264 150 212 260 300 335 367 397 424 450 474210 2½” 65 B265* 210 297 364 420 470 514 556 594 630 66470 3” 80 B277 70 99 121 140 157 172 185 198 210 221130 3” 80 B278 130 194 225 260 290 318 344 368 390 411170 3” 80 B280* 170 240 294 340 380 416 450 481 510 53860 2½” 65 B661 60 85 104 120 134 147 159 170 180 19075 2½” 65 B662 75 106 130 150 168 194 198 212 225 237110 2½” 65 B663 110 156 191 220 246 269 291 311 330 348150 2½” 65 B664 150 212 260 300 335 367 397 424 450 474210 2½” 65 B665* 210 297 364 420 470 514 556 594 630 66470 3” 80 B677 70 99 121 140 157 172 185 198 210 221130 3” 80 B678 130 194 225 260 290 318 344 368 390 411170 3” 80 B680* 170 240 294 340 380 416 450 481 510 53873 2½” 65 B6250S-070 73 103 126 145 159 175 187 205 212 22311 2½” 65 B6250S-110 110 156 191 220 244 266 282 296 312 32011 3” 80 B6300S-110 110 156 191 220 244 266 282 296 312 320
GPM = Cv x Δp *Models with no characterizing disc.The influence of the pipe geometry due to reduced flow is negligible for all valves 57 Cv and below with characterizing discs.
Sizing/SelectionCharacterized Control Valves™ (CCV)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
4
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
3-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
Cv Maximum
RatingInches DN
mm3-WayCCV
Pressure Drop Across the Valve
1 psi 2 psi 3 psi 4 psi 5 psi 6 psi 7 psi 8 psi 9 psi 10 psi
0.3 ½” 15 B307(B) 0.3 0.4 0.5 0.6 0.7 0.7 0.8 0.8 0.9 0.90.46 ½” 15 B308(B) 0.5 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.50.8 ½” 15 B309(B) 0.8 1.1 1.4 1.6 1.8 2.0 2.1 2.3 2.4 2.51.2 ½” 15 B310(B) 1.2 1.7 2.1 2.4 2.8 2.9 3.2 3.4 3.6 3.81.9 ½” 15 B311(B) 1.9 2.7 3.3 3.8 4.2 4.7 5.0 5.4 5.7 6.03 ½” 15 B312(B) 3.0 4.2 5.2 6.0 6.8 7.3 7.9 8.5 9.0 9.5
4.7 ½” 15 B313(B) 4.7 6.6 8.1 9.4 11 12 12 13 14 1510 ½” 15 B315(B)* 10 14 17 20 22 24 26 28 30 324.7 ¾” 20 B317(B) 4.7 6.6 8.1 9.4 11 12 12 13 14 157.4 ¾” 20 B318(B) 7.4 10 13 15 17 18 20 21 22 2324 ¾” 20 B320(B)* 24 34 42 48 54 59 63 68 72 767.4 1” 25 B322 7.4 10 13 15 17 18 20 21 22 2310 1” 25 B323 10 14 17 20 22 24 26 28 30 3230 1” 25 B325* 30 42 52 60 67 73 79 85 90 9510 1¼” 32 B329 10 14 17 20 22 25 27 28 30 3219 1¼” 32 B330 19 27 33 38 43 47 50 54 57 6025 1¼” 32 B331 25 35 43 50 56 61 66 71 75 7919 1½” 40 B338 19 27 33 38 43 47 50 54 57 6029 1½” 40 B339 29 41 50 58 65 71 77 82 87 9237 1½” 40 B340 37 52 64 74 83 91 98 105 111 11746 1½” 40 B341 46 65 80 92 103 113 122 130 138 14629 2” 50 B347 29 41 50 58 65 71 77 82 87 9237 2” 50 B348 37 52 64 74 83 91 98 105 111 11746 2” 50 B349 46 65 80 92 103 113 122 130 138 14657 2” 50 B350 57 81 99 114 128 140 151 161 171 18068 2” 50 B351 68 96 118 136 152 167 180 192 204 21583 2” 50 B352 83 117 144 166 186 204 220 235 249 263
GPM = Cv x Δp * = Models with no characterizing disc.The influence of the pipe geometry due to reduced flow is negligible for all valves 83 Cv and below with characterizing discs.
Sizing/SelectionCharacterized Control Valves™ (CCV)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
5
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
SET-UP
2-WAY VALVE 3-WAY VALVESPECIFY UPON ORDERING SPECIFY UPON ORDERING
NON-
SPRI
NG R
ETUR
NSt
ays
in L
ast P
ositi
on
TR24-3-T USTR24-3 USOn/Off orFloating Point Actuators
Power to pin 2 willdrive valve CCW.
Power to pin 3 willdrive valve CW.
Power to pin 2 willdrive valve CCW.
Power to pin 3 willdrive valve CW.
TR24-SR-T USTR24-SR USProportionalType Actuators
NC: Closed A to AB, willopen as voltage increases.
NO: Open A to AB, will closeas voltage increases.(Can be chosen with
switch inside terminalblock of actuator.)
NC: Closed A to AB, willopen as voltage increases.
NO: Open A to AB, will closeas voltage increases.(Can be chosen with
switch inside terminalblock of actuator.)
LRB24 (-3), MFT, SRLRX24 (-3), MFT, SRARB24 (-3), MFT, SRARX24 (-3), MFT, SRFloating Point orProportional Type Actuators
Power to pin 2 will drivevalve CW. Power to pin 3 will drive valve CCW. Theabove will function when
the directional switch is inthe “1” position, to reverse
select the “0” position.
NO: Open A to AB, will closeas voltage increases orpower applied. (Can bechosen with CW/CCW
switch.)
Power to pin 2 will drive valve CW. Power to pin 3will drive valve CCW. Theabove will function when
the directional switch is inthe “1” position, to reverse
select the “0” position.
NO: Open A to AB, will closeas voltage increases orpower applied. (Can be chosen with CW/CCW
switch.)
SPRI
NG R
ETUR
NNo
te F
ail P
ositi
on
TFX24 USLF24 USAF24 US
NO/FO Valve: Open A to ABwill drive closed.Spring Action:
Will spring open A to ABupon power loss.
NC/FC Valve: Closed A to ABwill drive open.Spring Action:
Will spring closed A to ABupon power loss.
NO/FO Valve: Open A to ABwill drive closed.Spring Action:
Will spring open A to ABupon power loss.
NC/FC Valve: Closed A to ABwill drive open.Spring Action:
Will spring closed A to ABupon power loss.
TF (-3), MFT, SRLF (-3), MFT, SRAF (-3), MFT, SRFloating Point orProportional Type Actuators
NC/FO Valve: Closed A to ABwill drive open.Spring Action:
Will spring open A to ABupon power loss.
NC/FC or NO/FCValve: Closed A to AB or
Open A to AB.(Can be chosen with
CW/CCW switch.)Spring Action:
Will spring closed A to ABupon power loss.
NC/FO Valve: Closed A to ABwill drive openSpring Action:
Will spring open A to ABupon power loss.
NC/FC or NO/FCValve: Closed A to AB
or Open A to AB.(Can be chosen with
CW/CCW switch.)Spring Action:
Will spring closed A to ABupon power loss.
NO/FO Valve: Open A to ABSpring Action:
Will spring open A to ABupon power loss.
(NO action can be chosenwith CW/CCW switch.)
NO/FO Valve: Open A to ABSpring Action:
Will spring open A to ABupon power loss.
(NO action can be chosenwith CW/CCW switch.)
GENERAL WIRING INSTRUCTIONS
WARNING The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit.
Always read the controller manufacturer's installation literature carefully before making any connections. Follow all instructions in thisliterature. If you have any questions, contact the controller manufacturerand/or Belimo.
Transformer(s)Belimo actuators require a 24 VAC class 2 transformer and draws amaximum of 10 VA per actuator. The actuator enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired.
– EMC directive: 89/336/EEC – Software class A: Mode of operation type 1 – Low voltage directive: 73/23/EEC
CAUTION It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. When these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification.
Set-up and Wiring InstructionsCharacterized Control Valves™ (CCV)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
6
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
FLOW PATTERNS
2-way Characterized Control Valves™ (Belimo B2 Series)(Belimo B6 Series)
Two-way valvesshould be installedwith the discupstream.
Flow direction
3-way Characterized Control Valves™ (Belimo B3 Series)MIXING DIVERTING
The A-port mustbe piped to the coilto maintain propercontrol.
INCORRECT PIPING
The A-port must be piped to the coil to maintain proper control.
Coil
Return
Three-WaWa Mixing y Mix Valve Piping Diagraping D m(2 Inputs(2 Inpu , 1 Outputput)
A
B
AB
Supply
Coil
Return
Three-Way Divery Div ting Valve Piping Diagramping Input, 2 Outputs(1 In uts)
A
B
AB
Supply
Note Valve Porting! The A-port must be piped to the coil! Not the B-port!Flow is not possible from A to B. If AB-port is not piped as the common port, the valve must be re-piped. It is good practice to install a balancing valve in the bypass line. These valves are intended for closed loop systems. Do not installin an open loop system or in an application that is open to atmospheric pressure.
OPERATION/INSTALLATION – CORRECT PIPING
2-way valves should be installed with the disc upstream. If installed with disc downstream, flow curve will be deeper. If installed “backwards” it is NOT necessary to remove and change. No damage or control problems will occur.
3-WAY VALVES MUST BE PIPED CORRECTLY. They can be mixing or diverting. Mixing is the preferred piping arrangement. The BELIMO Characterized Control Valve is a CONTROL valve, not a manual valve adapted for actuation. The control port is the A-port. It is similar to the globe valve in that the middle port is the B or bypass port. The common port AB is on the main opposite the A-port. These diagrams are for typical applications only. Consult engineeringspecification and drawings for particular circumstances.
REDUCED B-PORT FLOWNote: The B-port flow of the 3-way CCV is lower than that of the A-port. In most applications this is beneficial since the reduced flow compensates for the inexistent pressure drop across the coil in the bypass mode. Therefore, proper sizing is important to avoid flow noise in particular when the system is designed with constant speed pumps. Please refer to our valve sizing and selection guidelines.The flow velocity in the pipe upstream and downstream of the valve should be considered as well. The typical HVAC design maximum flow is 4 to 8 ft/s to avoid noise issues.Also, the pipe reduction factor must be considered and can be found on pages 3 and 4. Pipe reducers decrease the Cv value of a valve and consequently increase thepressure drop across the valve, a situation that could lead to noise or a lower than designed flow.
Flow, Operation and InstallationCharacterized Control Valves™ (CCV)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
7
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
B2 09 B LRX 24 -MFT
ValveB2 = 2-wayB3 = 3-wayB6 = 2-way Flanged Valve Size
07-80 = ½”-3”
Trim MaterialB = BrassBlank = Stainless Steel TrimSteel Trim
Actuator TypeNon-Spring ReturnTR…LRB…LRX…ARB…ARX…
LRQ... NRQ...Spring ReturnTF…LF…
AF...
Power Supply24 = 24 VAC/DC120 = 120 VAC*230 = 230 VAC
ControlBlank = On/Off, Floating-3 = Floating Point-SR = 2-10 VDC-MFT = Multi-Function Technology-MFT95 = 0-135 Ω
-T = Terminal Strip
-S = Built-inAuxiliarySwitchS it h
N4 = NEMA 4X, ULType 4X,IP 66/67Enclosure
NomenclatureCharacterized Control Valve™ (CCV)
ORDERING EXAMPLE
2
1 Choose the valve actuator combination.
+NO B209B+LRX24-MFT +Tagging (if needed)
Specify preference or confi guration.
3
Set-Up
5 Complete Ordering Example: B209B+LRX24-MFT+NO+A01
Does orderrequiretagging?
Tagging:Valves may betagged per customer specifi cation.
Example: AHU-1 FCU-2
4
For MFT orders only - select programming code
P-10001 (A01)
P-100xx (Axx) Control voltage applicationsP-200xx (Wxx) Pulse width modulation applicationsP-300xx (Fxx) Floating Point applicationsP-400xx (Jxx) On/Off applicationsX-XXXXX Create custom MFT confi guration codeX-XXXXX Create custom MFT confi guration in the fi eld with MFT-actuator PC software
Non-Spring ModelsNO = Normally OpenNC = Normally Closed
Spring Return ModelsNO/FO = Normally Open/Fail OpenNO/FC = Normally Open/Fail Closed
NC/FO = Normally Closed/Fail OpenNC/FC = Normally Closed/Fail Closed
See settingsRefers to valve ports A to AB.
*TF, LR and AR Series has 100 to 240 VAC nominal power supply.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
8
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
B2 Series, 2-Way, Characterized Control ValveChrome Plated Brass Ball and Brass Stem
Technical DataService chilled or hot water, 60% glycolFlow characteristic A-port equal percentage Action 90° rotationSizes ½”, ¾”Type of end fi tting NPT female endsMaterials:
BodyBallStemSeatsCharacterizing discPacking
forged brass, nickel platedchrome plated brassnickel plated brassPTFETefzel®2 EPDM O-rings, lubricated
Pressure rating 600 psi per EN 12266-1:2003Media temp. range 0°F to 212°F [-18°C to 100°C]Close off pressure 200 psiMaximum differential
pressure (ΔP)30 psi for typical applications
Leakage 0% for A to ABCv rating A-port: see product chart for valuesTefzel® is a registered trademark of DuPont
Dimensions
2Way
Valv
e-B2
07-B
220
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207B-B211B ½” 15 2.41” [61.1] 1.39” [35.2]B212B-B215B ½” 15 2.38” [60.4] 1.72” [43.7]B217B-B220B ¾” 20 2.73” [69.3] 1.81” [45.9]
Flow Patterns
ApplicationThis valve is typically used in air handling units on heating or cooling coils, andfan coil unit heating or cooling coils. Some other common applications includeUnit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable fl ow.
Valve Nominal Size Type Suitable ActuatorsCv Inches DN [mm] 2-way NPT Non-Spring Spring 0.3 ½ 15 B207B
TR S
erie
s
LR S
erie
s
TF S
erie
s
LF S
erie
s
0.46 ½ 15 B208B0.8 ½ 15 B209B1.2 ½ 15 B210B1.9 ½ 15 B211B3 ½ 15 B212B
4.7 ½ 15 B213B7.4 ½ 15 B214B10 ½ 15 B215B*4.7 ¾ 20 B217B7.4 ¾ 20 B218B10 ¾ 20 B219B24 ¾ 20 B220B*
*Models without characterizing disc
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
9
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
B3 Series, 3-Way, Characterized Control ValveChrome Plated Brass Ball and Brass Stem
Technical DataService chilled or hot water, 60% glycolFlow characteristic A-port equal percentage
B-port modifi ed for constant common port fl ow
Action 90° rotationSizes ½”, ¾”Type of end fi tting NPT female endsMaterials:
BodyBallStemSeatsCharacterizing discPacking
forged brass, nickel platedchrome plated brassnickel plated brassPTFETefzel®2 EPDM O-rings, lubricated
Pressure rating 600 psi per EN 12266-1:2003Media temp. range 0°F to 212°F [-18°C to 100°C]Close off pressure 200 psiMaximum differential
pressure (ΔP)30 psi for typical applications
Leakage 0% for A to AB<2.0% for B to AB
Cv rating A-port: see product chart for valuesB-port: 70% of A to AB Cv
Tefzel® is a registered trademark of DuPont
Dimensions
3Way
Valv
e-B3
07-B
320
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307B-B311B ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312B-B315B ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317B-B320B ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
Flow Patterns“B” Port mustbe piped to the
bypass leg.
ApplicationThis valve is typically used in air handling units on heating or cooling coils, andfan coil unit heating or cooling coils. Some other common applications includeUnit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant fl ow.
Valve Nominal Size Type Suitable ActuatorsCv Inches DN [mm] 3-way NPT Non-Spring Spring 0.3 ½ 15 B307B
TR S
erie
s
LR S
erie
s
TF S
erie
s
LF S
erie
s
0.46 ½ 15 B308B0.8 ½ 15 B309B1.2 ½ 15 B310B1.9 ½ 15 B311B3 ½ 15 B312B
4.7 ½ 15 B313B10 ½ 15 B315B*4.7 ¾ 20 B317B7.4 ¾ 20 B318B24 ¾ 20 B320B*
*Models without characterizing disc
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
10
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
B2 Series, 2-Way, Characterized Control ValveStainless Steel Ball and Stem
Technical DataService chilled or hot water, 60% glycolFlow characteristic A-port equal percentage Action 90° rotationSizes ½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½”, 3”Type of end fi tting NPT female endsMaterials:
BodyBallStemSeatsCharacterizing discPacking
forged brass, nickel platedstainless steelstainless steelPTFETefzel®2 EPDM O-rings, lubricated
Body Pressure rating600 psi*400 psi*
½” - 1¼” (B230)1¼” (B231) - 3”
Media temp. range 0°F to 212°F [-18°C to 100°C]Close off pressure
200 psi100 psi
½” - 2” (B250)2” (B251) - 3”
Maximum differentialpressure (ΔP)
30 psi for typical applications
Leakage 0% for A to ABCv rating A-port: see product chart for valuesTefzel® is a registered trademark of DuPont*Per EN 12266-1:2003
Dimensions
2Way
Valv
e-B2
07-B
220
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½ 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
ApplicationThis valve is typically used in air handling units on heating or cooling coils, andfan coil unit heating or cooling coils. Some other common applications includeUnit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable fl ow.
Valve Nominal Size Type Suitable ActuatorsCv Inches DN [mm] 2-Way NPT Non-Spring Spring 0.3 ½ 15 B207
TR S
erie
s
LR S
erie
s
NR..
.N4
Serie
s
TF S
erie
s
LF S
erie
s
0.46 ½ 15 B2080.8 ½ 15 B2091.2 ½ 15 B2101.9 ½ 15 B2113 ½ 15 B212
4.7 ½ 15 B2137.4 ½ 15 B21410 ½ 15 B215*4.7 ¾ 20 B2177.4 ¾ 20 B21810 ¾ 20 B21924 ¾ 20 B220*7.4 1 25 B22210 1 25 B22319 1 25 B22430 1 25 B225*10 1¼ 32 B22919 1¼ 32 B230*25 1¼ 32 B231
AR S
erie
s
AR..
.N4
Serie
s
AF S
erie
s
37 1¼ 32 B232*19 1½ 40 B23829 1½ 40 B23937 1½ 40 B240*29 2 50 B24846 2 50 B24957 2 50 B250*65 2 50 B25185 2 50 B252120 2 50 B253240 2 50 B254*60 2½ 65 B26175 2½ 65 B262110 2½ 65 B263150 2½ 65 B264210 2½ 65 B265*70 3 80 B277130 3 80 B278170 3 80 B280*
*Models without characterizing disc
Flow Patterns
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
11
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ApplicationThis valve is typically used in air handling units on heating or cooling coils, andfan coil unit heating or cooling coils. Some other common applications includeUnit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant fl ow.
B3 Series, Three Way, Characterized Control ValveStainless Steel Ball and Stem
Valve Nominal Size Type Suitable ActuatorsCv Inches DN [mm] 3-Way NPT Non-Spring Spring 0.3 ½ 15 B307
TR S
erie
s
LR S
erie
s
NR..
.N4
Serie
s
TF S
erie
s
LF S
erie
s
0.46 ½ 15 B3080.8 ½ 15 B3091.2 ½ 15 B3101.9 ½ 15 B3113 ½ 15 B312
4.7 ½ 15 B31310 ½ 15 B315*4.7 ¾ 20 B3177.4 ¾ 20 B31824 ¾ 20 B320*7.4 1 25 B32210 1 25 B32330 1 25 B325*10 1¼ 32 B329
AR S
erie
s
AR..
.N4
Serie
s
AF S
erie
s
19 1¼ 32 B33025 1¼ 32 B33119 1½ 40 B33829 1½ 40 B33937 1½ 40 B34046 1½ 40 B34129 2 50 B34737 2 50 B34846 2 50 B34957 2 50 B35068 2 50 B35183 2 50 B352
*Models without characterizing disc
Flow Patterns“B” Port mustbe piped to the
bypass leg.
Technical DataService chilled or hot water, 60% glycolFlow characteristic A-port equal percentage
B-port modifi ed for constant common port fl ow
Action 90° rotationSizes ½”, ¾”, 1”, 1¼”, 1½”, 2”Type of end fi tting NPT female endsMaterials:
BodyBallStemSeatsCharacterizing discPacking
forged brass, nickel platedstainless steelstainless steelPTFETefzel®2 EPDM O-rings, lubricated
Body Pressure rating600 psi*400 psi*
½” - 1”1¼” - 2”
Media temp. range 0°F to 212°F [-18°C to 100°C]Close off pressure
200 psi ½” - 2”Maximum differential
pressure (ΔP)30 psi for typical applications
Leakage 0% for A to AB<2.0% for B to AB
Cv rating A-port: see product chart for valuesB-port: 70% of A to AB Cv
Tefzel® is a registered trademark of DuPont*Per EN 12266-1:2003
Dimensions
3Way
Valv
e-B3
07-B
320
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]B329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
12
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
B6 Series, Two Way, Characterized Control ValveStainless Steel Ball and Stem
Technical DataService chilled or hot water, 60% glycolFlow characteristic A-port equal percentageAction 90° rotationSizes 2½”, 3”Type of end fi tting pattern to mate with ANSI 125 fl angeMaterials:
BodyBallStemSeatsCharacterizing discPacking
cast iron - GG25stainless steelstainless steelPTFEstainless steel2 EPDM O rings, lubricated
Pressure rating According to ANSI 125, standard class BMedia temp. range 0°F to 248°F [-18°C to +120°C]Close off pressure 100 psiMaximum differential
pressure (ΔP)58 psi
Leakage 0% for A to ABCv rating A-port: see product chart for values
Dimensions
A
B
B6_D
ims
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
ApplicationThis valve is typically used in air handling units on heating or cooling coils, andfan coil unit heating or cooling coils. Some other common applications includeUnit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant fl ow.
Valve Nominal Size Type Suitable ActuatorsCv Inches DN [mm] 2-way Flange Non-Spring Spring70 2½ 65 B6250S-070
AR
Serie
s
AF
Serie
s
110 2½ 65 B6250S-110110 3 80 B6300S-110
Flow Patterns
NOTES:1) Flange bolt pattern matches ANSI class 125 fl anges (not ANSI/ASME rated)2) Maximum allowable working pressure: 100 PSIG3) It is not recommended to connect raised-face fl anges to fl at-faced fl anges4) Materials: Flange: Cast Iron- GG25 Upstream Flange Insert: Brass
A
B
D
C
Flange Detail
Face Flange
Inches [mm] Face I.D. Bolt Circle Diameter
Total Flange Thickness
Bolt Hole Diameter
A B C D
2½" 2.50" [65] 5.5" [139.7] 0.79" [20] 0.75" [19.05]
3" 3" [80] 6" [152.4] 0.87" [22] 0.75" [19.05]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
13
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
B6 Series, Two Way, Characterized Control ValveStainless Steel Ball and Stem
Technical DataService chilled or hot water, 60% glycolFlow characteristic A-port equal percentageAction 90° rotationSizes 2½”, 3”Type of end fi tting pattern to mate with ANSI 125 fl angeMaterials:
BodyBallStemSeatsCharacterizing discPacking
forged brass, nickel platedstainless steelstainless steelPTFETefzel®2 EPDM O-rings, lubricated
Pressure rating 400 psi per EN 12266-1:2003Media temp. range 0°F to 212°F [-18°C to 100°C]Close off pressure 100 psiMaximum differential
pressure (ΔP)30 psi for typical applications
Leakage 0% for A to ABCv rating A-port: see product chart for valuesTefzel® is a registered trademark of DuPont
Dimensions
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
CCV-EXT – Extension kit will be automatically assembled with any Flanged CCV assembly.
Flange Detail
ApplicationThis valve is typically used in air handling units on heating or cooling coils, andfan coil unit heating or cooling coils. Some other common applications includeUnit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant fl ow.
Valve Nominal Size Type Suitable Actuators
Cv Inches DN [mm] 2-way Flange Non-Spring Spring
60 2½ 65 B661
AR S
erie
s
AF S
erie
s
75 2½ 65 B662110 2½ 65 B663150 2½ 65 B664210 2½ 65 B665*70 3 80 B677130 3 80 B678170 3 80 B680*
*Models without characterizing disc
Flow Patterns
C
A
B
D
F
E
Raised Face Flange
Inches [mm] Face I.D. Face O.D. Face Height Bolt Circle
DiameterTotal FlangeThickness
Bolt Hole Diameter
Bolt Holes
A B C D E F
2½” [65] 2.50” [63] 4.75” [120] 0.25” [6] 5.50” [140] 0.95” [24] 0.75” [19] 4
3” [80] 3.00” [75] 5.13” [130] 0.25” [6] 6.00” [152] 1.00” [25] 0.75” [19] 4NOTES:1) Flange bolt pattern matches ANSI class 125 fl anges (not ANSI/ASME rated)2) Maximum allowable working pressure: 100 PSIG3) It is not recommended to connect raised-face fl anges to fl at-fl aced fl anges
4) Materials: Flange: A 105 Carbon Steel (zinc plated) Raised Face: Brass (nickel plated)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
14
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
15
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Equal PercentageCharacteristic
CCV
Characterized Control Valve Product Range OverviewB2.., B3.., B6.., 2-way, 3-way, Stainless Steel Ball and Stem
ApplicationsWater-side control of heating and cooling systems, for AHUs, re-heat coils, fan coil units, unit ventilators and heat pumps.
Mode of OperationThe Characterized Control Valve is operated by a rotary actuator. The actuators are controlled by a standard voltagefor on/off control or a proportional signal or 3-point controlsystem which move the ball of the valve to the positiondictated by the control system.
Product FeaturesThe equal-percentage characteristic of the fl ow is ensuredby the integral characterizing disc. This characteristicprovides linear heating or cooling output from the coilimproving energy effi ciency and comfort.
Actuator Specifi cationsControl type On/Off, Floating Point, 2-10 VDC, Multi-Function Technology (MFT)Manual override TR, LR, AR, and AF seriesElectrical connection 3 ft [1m] cable with ½” conduit fi tting or covered screw terminal strip
Valve Specifi cationsService chilled or hot water, 60% glycolFlow characteristic A-port equal percentage B-port modifi ed for constant common port fl owAction max 90° rotationSizes ½” - 3”Type of end fi tting ½” - 3” NPT female ends 2½” - 3” ANSI 125 fl ange patternMaterials Body forged brass, nickel plated Ball stainless steel [BXXXB - chrome plated brass] Stem stainless steel [BXXXB - nickel plated brass] Seats PTFE Characterizing disc TEFZEL® stainless steel (B6250/300) Packing 2 EPDM O-rings, lubricatedPressure rating 2-way 3-way 600 psi ½” - 1¼” (B230) ½” - 1” 400 psi 1¼” (B231) - 3” 1¼” - 3”Media temp range 0°F to 212°F [-18°C to 100°C]Close-off pressure 2-way 3-way 200 psi ½” - 2” (B250) ½” - 2” 100 psi 2” (B251) - 3”, B6Maximum differential pressure (ΔP) 30 psi, 58 psi (B6250/300)Leakage 0% for A to AB < 2.0% for B to ABCv rating A port: see product chart above for values B port: 70% of A to AB CvTefzel® is a registered trademark of DuPont
Valve Nominal Size Type Suitable Actuators
Cv InchesDN
[mm]2-wayNPT
3-wayNPT
2-wayFlange
Non-SpringReturn
Spring Return
NEMA 4X
½ 15 B207(B) B307(B) –
TR S
erie
s
LR S
erie
s
TF S
erie
s
LF S
erie
s
NR S
erie
s
0.46 ½ 15 B208(B) B308(B) –
0.8 ½ 15 B209(B) B309(B) –
1.2 ½ 15 B210(B) B310(B) –
1.9 ½ 15 B211(B) B311(B) –
3 ½ 15 B212(B) B312(B) –
4.7 ½ 15 B213(B) B313(B) –
7.4 ½ 15 B214(B) –
10 ½ 15 B215(B)* B315(B)* –
4.7 ¾ 20 B217(B) B317(B) –
7.4 ¾ 20 B218(B) B318(B) –
10 ¾ 20 B219(B) –
24 ¾ 20 B220(B)* B320(B)* –
7.4 1 25 B222 B322 –
10 1 25 B223 B323 –
19 1 25 B224 –
30 1 25 B225* B325* –
10 1¼ 32 B229 B329 –
AR S
erie
s
AF S
erie
s
19 1¼ 32 B230* B330 –
25 1¼ 32 B231 B331 –
AR S
erie
s
37 1¼ 32 B232* –
19 1½ 40 B238 B338 –
29 1½ 40 B239 B339 –
37 1½ 40 B240* B340 –
46 1½ 40 B341 –
29 2 50 B248 B347 –
37 2 50 B348 –
46 2 50 B249 B349 –
57 2 50 B250* B350 –
65 2 50 B251 –
68 2 50 B351 –
83 2 50 B352 –
85 2 50 B252 –
120 2 50 B253 –
240 2 50 B254* –
60 2½ 65 B261 B661
70 2½ 65 B6250S-070
75 2½ 65 B262 B662
110 2½ 65 B263 B663, B6250S-110
150 2½ 65 B264 B664
210 2½ 65 B265* B665*
70 3 80 B277 B677
110 3 80 B6300S-110
130 3 80 B278 B678
170 3 80 B280* B680*
* Models without characterizing disc (B) Models with chrome plated brass ball and brass stem
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
16
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
TR24-3 Actuators, On-Off, Floating Point
ModelsTR24-3-T USTR24-3 US TR24-3-T US with 3 ft plenum rated cableTR24-3/300 US TR24-3-T US with 10 ft plenum rated cableTR24-3/500 US TR24-3-T US with 16 ft plenum rated cable
Technical DataControl On/Off, Floating PointNominal voltage 24 VAC 50/60 HzNominal voltage range 19.2…28.8 VACPower consumption 1 WTransformer sizing 1VA (class 2 power source)Electrical connection screw terminals accessible after removal of
small cover (3 ft, 10 ft, 16 ft cables optional) Input impedance 0.36 kΩAngle of rotation 90°Position indication integrated into handleManual override push down handleRunning time 90 seconds @ 60 hz, 108 seconds @ 50 hzHumidity 5 to 95% non-condensingAmbient temperature -22°F to 122°F (-30°C to 50°C)Storage temperature -40°F to 176°F (-40°C to 80°C)Housing NEMA 1/IP40Housing rating UL94-5V(B)Agency listing† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level Max. 35 db (A)Quality standard ISO 9001† Rated impulse voltage 330V, Control pollution degree 2, Type of action 1
Dimensions with 2-Way Valve
A
2.50[63.5]
3.25[82.6]
B
2.82[71.6]
D06
9
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
Dimensions with 3-Way Valve
A
2.50[63.5]
3.25[82.6]
B
2.82[71.6]
C
D07
2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
17
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2The common connection from the actuator must be connected to the Hot connection of the controller.
3Actuators with plenum rated cable do not have numbers on wires;use color codes instead.
44 The actuator Hot must be connected to the control board Hot.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
TR24-3 Actuators, On-Off, Floating Point
NOTE: TR24-3(-T) US cannot be wired in parallel with EEthemselves or any other actuator.
W18
7
Floating Control
W18
6
On/Off Control You may not use one wire control.
W25
0
Triac Sink
W25
1
Triac Source
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
18
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
TR24-SR Actuators, Proportional
ModelsTR24-SR-T USTR24-SR US TR24-SR-T US with 3 ft plenum rated cableTR24-SR/300 US TR24-SR-T US with 10 ft plenum rated cableTR24-SR/500 US TR24-SR-T US with 16 ft plenum rated cable
Technical DataControl ProportionalNominal voltage 24 VAC 50/60 Hz, 24 VDCNominal voltage range 19.2…28.8 VAC, 21.6…28.8 VDCPower consumption 0.5 WTransformer sizing 1VA (class 2 power source)Electrical connection screw terminals accessible after removal of
small cover (3 ft, 10 ft, 16 ft cables optional) Input impedance 100 kΩAngle of rotation 90°Direction of rotation reversible with switch under coverPosition indication integrated into handleManual override push down handleRunning time 90 secondsHumidity 5 to 95% non-condensingAmbient temperature -22°F to 122°F (-30°C to 50°C)Storage temperature -40°F to 176°F (-40°C to 80°C)Housing NEMA 1/IP40Housing rating UL94-5V(B)Agency listing† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level max. 35 db (A)Quality standard ISO 9001† Rated impulse voltage 500V, Control pollution degree 2, Type of action 1
NOTE: Response sensitivity is 75mV
Dimensions with 2-Way Valve
A
2.50[63.5]
3.25[82.6]
B
2.82[71.6]
D06
9
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
Dimensions with 3-Way Valve
A
2.50[63.5]
3.25[82.6]
B
2.82[71.6]
C
D07
2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
19
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2Actuators with color coded wires are optional.Wire numbers are provided for reference.CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
TR24-SR Actuators, Proportional
W19
0
2 to 10 VDC Control of TR24-SR(-T) US
W19
1
4 to 20 mA Control of TR24-SR(-T) US
Direct/Reverse acting switch is under wiring cover.R = CW with decrease in signalL = CCW with decrease in signalNo feedback
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
20
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LR...24-3 Actuators, On/Off, Floating Point
ModelsLRB24-3-T LRX24-3-T w/Terminal Block LRB24-3 LRX24-3 w/3 ft. cableLRB24-3-S LRX24-3-S w/built-in Aux. Switch
Technical DataControl On/Off, Floating PointPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 1.5 W
holding 0.2 WTransformer sizing 2 VA (class 2 power source)Electrical connection
LRB24-3LRX24-3
½” conduit connector18 GA, plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationInput impedance 600 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time
LRB24-3LRX24-3
90 seconds, constant independent of load❑ 150 ❑ 95 ❑ 60 ❑ 45 ❑ 35 seconds,constant independent of load
Humidity 5 to 95% RH, non-condensing (EN 60730-1)Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing type NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level less than 35 dB (A)Quality standard ISO 9001
LR...24-3-TElectrical connection screw terminal (for 26 to 14 GA wire)
protected (NEMA 2, IP20)
LR...24-3-SAuxiliary switch 1 SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 100°† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
Dimensions with 2-Way Valve
D14
8-2W
-08
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D14
8-3W
-08
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.06” [52.2] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
21
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3Actuators are provided with color coded wires.Wire numbers are provided for reference.
4 Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
LR...24-3 Actuators, On/Off, Floating Point
W19
3-LR
-08
On/Off control
W12
3-LR
-08
Floating Point or On/Off control
Auxiliary switch
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
22
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LR...24-SR Actuators, Proportional
ModelsLRB24-SR-T LRX24-SR-T w/Terminal BlockLRB24-SR LRX24-SR w/3ft. cable
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 1.5 W
holding 0.4 WTransformer sizing 3 VA (class 2 power source)Electrical connection
LRB24-SRLRX24-SR
½” conduit connector18 GA, plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mAFeedback output U 1 to 10 VDC, max 0.5 mAInput impedance 100 kΩ (0.1 mA), 500 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time
LRB24-SRLRX24-SR
constant independent of load90 seconds❑ 150 ❑ 95 ❑ 60 ❑ 45 ❑ 35 seconds
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <35 dB(A)Quality standard ISO 9001
LR...24-SR-TElectrical connection screw terminal (for 26 to 14 GA wire)
protected (NEMA 2/IP20)† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
Dimensions with 2-Way Valve
D14
8-2W
-08
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D14
8-3W
-08
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.06” [52.2] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
23
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
5 Only connect common to neg. (–) leg of control circuits.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
LR...24-SR Actuators, Proportional
W26
5-LR
-08
2 to 10 VDC control
W26
5-LR
-08
4 to 20 mA control
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
24
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LR...120-3 Actuators, On/Off, Floating Point
ModelsLRB120-3 LRX120-3
Technical DataControl On/Off, Floating PointPower supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)Power consumption running 2 W
holding 0.5 WTransformer sizing 4 VA (class 2 power source)Electrical connection
LRB120-3LRX120-3
½” conduit connector18 GA, plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationInput impedance 600 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time
LRB120-3LRX120-3
90 seconds, constant independent of load❑ 150 ❑ 95 ❑ 60 ❑ 45 ❑ 35 seconds,constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <35 dB(A)Quality standard ISO 9001† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
Dimensions with 2-Way Valve
D14
9-2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D14
9
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.06” [52.2] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
25
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
W40
5
On/Off
W40
6
Floating Point or On/Off control
LR...120-3 Actuators, On/Off, Floating Point
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
26
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LR...120-SR Actuators, Proportional
ModelsLRB120-SRLRX120-SR
Technical DataPower supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)Power consumption running 2.5 W
holding 1 WTransformer sizing 4.5 VA (class 2 power source)Electrical connection
LRB120-SRLRX120-SR
½” conduit connector18 GA, plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mAFeedback output U 1 to 10 VDC, max 0.5 mAInput impedance 100 kΩ (0.1 mA), 500 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time
LRB120-SRLRX120-SR
constant independent of load90 seconds❑ 150 ❑ 95 ❑ 60 ❑ 45 ❑ 35 seconds
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <35 dB(A)Quality standard ISO 9001† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
Dimensions with 2-Way Valve
D14
9-2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D14
9
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
27
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
6 Only connect common to neg. (–) leg of control circuits.
7 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
151 LRB(X) can be supplied with both 120 VAC and 230 VAC.
1919 All 120 VAC and 230 VAC actuators use appliance rated cables.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
LR...120-SR Actuators, Proportional
15 2
1 Neutral
2 Hot +
N L1
H L2
6 1 Common
2 Hot +
3 Y Input, 2 to 10VControl Signal
2 to 10 VDCFeedback Signal
5 U Output, 2 to 10V
(–)
(+)(–)(+)
1 0
100 to 240 VAC
Cabl
e 2
Cabl
e 18
19
7
VDC/mA
W36
5
Proportional, 100 to 240V
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
28
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsLRB24-MFT Basic VersionLRX24-MFT Flexible Version
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2 W
holding 1.2 WTransformer sizing 6 VA (class 2 power source)Electrical connection
LRB24-MFTLRX24-MFT
½” conduit connector18 GA, plenum rated cable3 ft [1m]❑ 3 ft [1m] (default) ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationOperating range Y 2 to 10 VDC (default)
4 to 20 mAVariable (VDC, PWM, Floating Point, On/Off)
Feedback output U 2 to 10 Vdc, 0.5mA maxVDC Variable
Input impedance 100 kΩ (0.1 mA), 500 Ω1500 Ω (PWM, Floating Point, On/Off)
Angle of rotation 90° electronically variableadjustable with mechanical stop
Direction of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time 150 seconds (default)
Variable (35 to 150 secs)Humidity 5 to 95% RH non-condensing
(EN 60730-1)Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <35 dB(A)Quality standard ISO 9001† Rated impulse voltage 800V, Control pollution degree 3,
Type of action 1 (1.B for -S models)
LR...24-MFT Actuators, Multi-Function Technology
Dimensions with 2-Way Valve
D14
9-2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D14
9
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
29
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
4Position feedback cannot be used with Triac sink controller.The actuator internal common reference is not compatible.
6Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.
8Contact closures A & B also can be triacs.A& B should both be closed for triac source and open for triac sink.
9For triac sink the common connection from the actuatormust be connected to the hot connection.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
LR...24-MFT Actuators, Multi-Function Technology
W53
8
On/Off control
W53
8
Floating Point
W53
8
VDC/4-20 mA
W53
8
PWM
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
30
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
ModelsLRX24-PC
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2 W
holding 1.2 WTransformer sizing 5 VA (Class 2 power source)Electrical connection ½” conduit connector
18 GA plenum rated cable❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationOperating range Y 0 to 20V phasecutFeedback output U 2 to 10 Vdc, 0.5mA maxInput impedance 8 kΩ (50 mW)Angle of rotation 90°, adjustable with mechanical stop
electronically variableDirection of rotation reversible withPosition indication handleManual override external push buttonRunning time 150 seconds (default)Humidity 5 to 95% RH non-condensing
(EN 60730-1)Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <35 dB(A)Quality standard ISO 9001
Dimensions with 2-Way Valve
D14
9-2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D14
9
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
31
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
1
2
3
24 VAC Transformer
Blk (1) Common
Red (2) Hot +
Pnk (6) Y Input, 0 to 20V phasecut
Org (5) U Output, 2 to 10V
…PC
Line Volts
0 to 20 V Phasecut
Control Signal (–)
(+)
–
W18
5
LRX24-PC
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
32
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LRX24-MFT95 Actuators, 0 to 135 Ω, Proportional
ModelsLRX24-MFT95
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2 W
holding 1.2 WTransformer sizing 5 VA (Class 2 power source)Electrical connection ½” conduit connector
18 GA plenum rated cable❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationOperating range WRB 0 to 135 Ω Honeywell Electronic
Series 90, 0 to 135 Ω InputFeedback output U 2 to 10 Vdc, 0.5mA maxInput impedance 100 kΩ (0.1 mW)Angle of rotation 90°, adjustable with mechanical stop
electronically variableDirection of rotation reversible withPosition indication handleManual override external push buttonRunning time 150 seconds (default)
Variable (35 to 150 secs)Humidity 5 to 95% RH non-condensing
(EN 60730-1)Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <35 dB(A)Quality standard ISO 9001†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
Dimensions with 2-Way Valve
D14
9-2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D14
9
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
33
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
LRX24-MFT95 Actuators, 0 to 135 Ω, Proportional
22
22
2324
Line
Volts
Line
Volts
21
21
24 VAC Transformer
25
23
25
-MFT95 US
Blk (1) CommonRed (2) + Hot
Wht (3) WWht (4) RWht (5) BWht (6) ‘U5’ Output 2 to 10 VDC
-MFT95 US
Blk (1) CommonRed (2) + Hot
Wht (3) WWht (4) RWht (5) BWht (6) ‘U5’ Output 2 to 10 VDC
W01
9
To otheractuators
Series 90Controller
S963AMinimum Position
Potentiometer
H205 Change-over Controller
OccupiedContact
ShuntingResistor
W
W
W
R
R
RB
B
B
W01
7
22
21
23
24
Line
Volts
24 VAC Transformer
-MFT95 US
Blk (1) CommonRed (2) + Hot
Wht (3) W
Wht (4) R
Wht (5) B
Wht (6) ‘U5’ Output 2 to 10 VDC
Series 90 high limit control - 280
Series 90Controller
W
W
R
RB B
Provide overload protection and disconnect as required.
Actuators and controller must have separate transformers.
Consult controller instruction data for more detailedinformation.
Resistor value depends on the type of controller and thenumber of actuators. No resistor is used for one actuator.Honeywell® resistor kits may also be used.
To reverse control rotation, use the reversing switch.2524232221
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting
of this product, it may be necessary to work with live electri-cal components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electricalcomponents perform these tasks. Failure to follow all electricalsafety precautions when exposed to live electrical components could result in death or serious injury.
21
2222
2323
244
252
Switch A Switch B Damper Position
Damper Open
Damper Closed
The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.
W01
521
22
23
24
21
23
24
Blk (1) CommonRed (2) + Hot
Wht (3) WWht (4) RWht (5) BWht (6) ‘U5’ Output 2 to 10 VDC
A
B
A
B
Line
Volts
Line
Volts
Line
Volts
24 VAC Transformer
24 VAC Transformer
135
Controller
-MFT95 US
-MFT95 US
W
R
B
Blk (1) CommonRed (2) + Hot
Wht (3) WWht (4) RWht (5) BWht (6) ‘U5’ Output 2 to 10 VDC
Wiring multiple actuators to aSeries 90 controller using a minimum position potentiometer
High Limit Control
W01
6
22
21
23
24
Line
Volts
24 VAC Transformer
-MFT95 US
Blk (1) CommonRed (2) + Hot
Wht (3) W
Wht (4) R
Wht (5) B
Wht (6) ‘U5’ Output 2 to 10 VDCSeries 90 low limit control135 for 0 to 50% control280 for 0 to 100% control
Series 90Controller
W W
R
R
B
B
W_n
ew60
408_
5
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
34
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LRQ...24-1 Quick Running Actuators, On/Off
ModelsLRQB24-1 Basic VersionLRQX24-1 Flexible Version
Technical DataControl On/OffPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 12 W
holding 1.5 WTransformer sizing 18 VA (Class 2 power source)
20A @ 5ms maxElectrical connection
LRQB24-1LRQX24-1
½” conduit connector18 GA plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationInput impedance 600 ΩAngle of rotation max 95°, adjustable with mechanical stopDirection of rotation reversible withPosition indication handleManual override external push buttonRunning time
LRQB24-1
LRQX24-1
5 secondsconstant of independent load5 or 10 secondsconstant of independent load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <52 dB(A)Quality standard ISO 9001
Dimensions with 2-Way Valve
LRQ
_2_w
ay
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
LRQ
_3_W
ay
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
35
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.LRQ...24-1 Quick Running Actuators, On/Off
Wiring Diagrams
1 Provide overload protection and disconnect as required.
3 Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
W40
3-LR
Q-0
8
LRQ...24-1
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
36
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
ModelsLRQB24-MFT Basic VersionLRQX24-MFT Flexible Version
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 12 W
holding 1.5 WTransformer sizing 18 VA (Class 2 power source)
20A @ 5ms maxElectrical connection
LRQB24-MFTLRQX24-MFT
½” conduit connector18 GA plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mA (default)
Variable (VDC, On/Off)Feedback output U 2 to 10 Vdc, 0.5mA max
VDC VariableInput impedance 100 kΩ (0.1 mA), 500 Ω
1500 Ω (On-Off)Angle of rotation max 95°, adjustable with mechanical stopDirection of rotation reversible withPosition indication refl ective visual indicator (snap-on)Manual override external push buttonRunning time
LRQB24-MFT
LRQX24-MFT
5 secondsconstant of independent load5 or 10 secondsconstant of independent load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <52 dB(A)Quality standard ISO 9001
Dimensions with 2-Way Valve
LRQ
_2_W
ayA
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
LRQ
_3_W
ayA
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
37
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
5Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.
The ZG-R01 500 Ω resistor may be used.
WARNING Live Electrical Components!G During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
W39
9_08
VDC/4-20 mA
W39
9_08
On/Off control
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
38
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
NRQ...24-1 Quick Running Actuators, On/Off
ModelsNRQB24-1 Basic VersionNRQX24-1 Flexible Version
Technical DataControl On/OffPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 12 W
holding 1.5 WTransformer sizing 18 VA (Class 2 power source)Electrical connection
NRQB24-1NRQX24-1
½” conduit connector, 18 GA plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationInput impedance 600 ΩAngle of rotation max 95°, adjustable with mechanical stopDirection of rotation reversible withPosition indication refl ective visual indicator (snap-on)Manual override external push buttonRunning time
NRQB24-1NRQX24-1
constant of independent load5 seconds5, 10 or 15 seconds
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <52 dB(A)Quality standard ISO 9001Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
Dimensions with 2-Way Valve
NR
Q_2
_Way
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107] 2.21” [56.15]
Dimensions with 3-Way Valve
NR
Q_3
_Way
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
39
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.NRQ...24-1 Quick Running Actuators, On/Off
Wiring Diagrams
1 Provide overload protection and disconnect as required.
3 Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
W40
3-N
RQ
-08
NRQ...24-1
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
40
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
ModelsNRQB24-MFT Basic VersionNRQX24-MFT Flexible Version
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 12 W
holding 1.5 WTransformer sizing 18 VA (Class 2 power source)Electrical connection
NRQB24-MFTNRQX24-MFT
½” conduit connector, 18 GA plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mA (default)
Variable (VDC, On/Off)Feedback output U 2 to 10 Vdc, 0.5mA max
VDC VariableInput impedance 100 kΩ (0.1 mA), 500 Ω, 1500 Ω
(On/Off)Angle of rotation max 95°, adjustable with mechanical stop
electronically variableDirection of rotation reversible withPosition indication refl ective visual indicator (snap-on)Manual override external push buttonRunning time
NRQB24-MFTNRQX24-MFT
constant of independent load5 seconds5, 10 or 15 seconds
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <52 dB(A)Quality standard ISO 9001Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
Dimensions with 2-Way Valve
NR
Q_2
_Way
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107] 2.21” [56.2]
Dimensions with 3-Way Valve
NR
Q_3
_Way
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
41
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
5Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.
The ZG-R01 500 Ω resistor may be used.
WARNING Live Electrical Components!G During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
W39
9_08
VDC/4-20 mA
W39
9_08
On/Off control
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
42
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
NRB24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
ModelsNRB24-3-T N4 w/terminal blockNRB24-3-T N4H w/built in heater
Technical DataControl On/Off, Floating PointPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.0 W
holding 0.2 W Transformer sizing 4 VA (class 2 power source)Electrical connection screw terminal (for 26 to 14 GA wire)Overload protection electronic throughout 0° to 95° rotationInput impedance 600 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible withPosition indication visual pointerManual override external push buttonRunning time 90 seconds constant independent of loadHumidity 100% RH Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing type UL Type 4X/NEMA 4X/IP66 & IP67Housing material PolypropyleneAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Quality standard ISO 9001*Cannot be used with the CCV-EXT-KIT
Dimensions with 2-Way Valve
NE
MA
4 D
iagr
am
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
NE
MA
4 D
iagr
am 3
-Way
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
43
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3Actuators are provided with color coded wires.Wire numbers are provided for reference.
4 Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
NRB24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
W19
3-N
R-0
8
On/Off control
W12
3-N
R-0
8
Floating Point control
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
44
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Dimensions with 2-Way Valve
NE
MA
4 D
iagr
am
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
NE
MA
4 D
iagr
am 3
-Way
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
NRB24-SR-T N4 NEMA 4X Actuators, Proportional
ModelsNRB24-SR-T N4 w/terminal blockNRB24-SR-T N4H w/built in heater
Technical DataControl 2 to 10 VDC, 4 to 20 mAPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.5 W
holding 0.4 W Transformer sizing 5 VA (class 2 power source)Electrical connection screw terminal (for 26 to 14 GA wire)Overload protection electronic throughout 0° to 95° rotationInput impedance 100 kΩ (0.1mA), 500ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible withPosition indication visual pointerManual override external push buttonRunning time 90 seconds constant independent of loadHumidity 100% RH Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing type UL Type 4X/NEMA 4X/IP66 & IP67Housing material PolypropeleneAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Quality standard ISO 9001†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3*Cannot be used with the CCV-EXT-KIT
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
45
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
5 Only connect common to neg. (–) leg of control circuits.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
NRB24-SR-T N4 NEMA 4X Actuators, Proportional
W40
8-N
R-T
2 to 10 VDC control
W40
8-N
R-T
4 to 20 mA control
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
46
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsNRX24-MFT-T N4 w/terminal blockNRX24-MFT-T N4H w/built in heater
Technical DataControl 2 to 10 VDC, 4 to 20 mA (default)
Variable (VDC, PWM, Floating Point, On/Off)Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 3.5 W (1.25 W)
holding 1.25 W Transformer sizing 6 VA (class 2 power source)Electrical connection screw terminal (for 26 to 14 GA wire)Overload protection electronic throughout 0° to 95° rotationInput impedance 100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, Floating Point, On/Off)Angle of Rotation 95°, adjustable with mechanical stop
electronically variableDirection of Rotation reversible withPosition indication visual pointerManual override external push buttonRunning time 150 seconds (default)
constant independent of loadVariable (75 to 350 seconds)
Humidity 100% RH Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing type UL Type 4X/NEMA 4X/IP66 & IP67Housing material PolypropeleneAgency Listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Quality Standard ISO 9001†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3*Cannot be used with the CCV-EXT-KIT
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
Dimensions with 2-Way Valve
NE
MA
4 D
iagr
am
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
NE
MA
4 D
iagr
am 3
-Way
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
47
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
4Position feedback cannot be used with Triac sink controller.The actuator internal common reference is not compatible.
6Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.
8Contact closures A & B also can be triacs.A& B should both be closed for triac source and open for triac sink.
9For triac sink the common connection from the actuatormust be connected to the hot connection.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
W53
8
On/Off control
W53
8
Floating Point
W53
8
VDC/4-20 mA
W53
8
PWM
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
48
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
AR...24-3 Actuators, On/Off, Floating Point
ModelsARB24-3 ARB24-3-S w/built-in Aux. SwitchARX24-3 FlexibleARX24-3-S Flexible w/built-in Aux. Switch
Technical DataControl On/Off, Floating PointPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.5 W
holding 0.2 WTransformer sizing 5.5 VA (class 2 power source)Electrical connection
ARB24-3...ARX24-3...
½” conduit connector18 GA plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationInput impedance 600 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time
ARB24-3...ARX24-3...
90 seconds❑ 300 ❑ 150 ❑ 90 seconds,constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <45 dB(A)Quality standard ISO 9001
AR...24-3-SAuxiliary switch (-S models) 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0 to 90°† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
Dimensions with 2-Way Valve
A
B
3.3"[84]
2.49"[63.4]
8.5" [216]
1.35"[35]
3.46"[88]
D15
5
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D15
2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
49
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3For end position indication, interlock control, etc.,ARB24-3-S incorporates one built-in auxiliary switches:1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
4 Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
AR...24-3 Actuators, On/Off, Floating Point
424 VAC Transformer
a opena closed
The indication of direction is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
ARB24-3
a
Line Volts
–
1 0
W40
9
On/Off control
424 VAC Transformer
The indication of direction is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
ARB24-3
Line Volts
–
1 0
p j y
W41
1
Floating Point or On/Off control
ARB24-3-S
3S1
S2
S3
NC
NO0° to 95°
W41
0
Auxiliary switch
3.3"[84]
2.49"[63.4]
8.5" [216]
1.35"[35]
3.46"[88]
A
B
Dimensions with 2-Way Flanged Valve
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
A
B
D15
1B
6_D
ims
2
2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
50
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsARB24-SR ARX24-SR Flexible Version
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.5 W
holding 0.4 WTransformer sizing 5 VA (class 2 power source)Electrical connection ½” conduit connector
18 GA plenum rated cable❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mAFeedback output U 1 to 10 VDC, max 0.5 mAInput impedance 100 kΩ (0.1 mA), 500 ΩAngle of rotation 90°, adjustable with mechanical stopTorque 180 in-lb [20 Nm]Direction of rotation reversible with protectedPosition indication handleManual Override external push buttonRunning time
ARB24-SR...ARX24-SR...
90 seconds❑ 300 ❑ 150 ❑ 90 seconds,constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to +122°F [-30°C to +50°C]Storage temperature -40°F to +176°F [-40°C to +80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <45 dB(A)Quality standard ISO 9001† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
AR...24-SR Actuators, Proportional
Dimensions with 2-Way Valve
D15
2-2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
Dimensions with 3-Way Valve
D15
2
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
51
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
5 Only connect common to neg. (–) leg of control circuits.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
AR...24-SR Actuators, Proportional
2
3
24 VAC Transformer
Blk (1) Common
Red (2) Hot +
Wht (3) Y Input, 2 to 10V
Org (5) U Output, 2 to 10V
ARB24-SR
Line Volts
2 to 10 VDC
Control Signal (–)(+)
–
1 02 to 10 VDC
Feedback Signal
(–)(+)
W40
8
2 to 10 VDC control
To other actuators
3
5
24 VAC Transformer
Blk (1) Common
Red (2) Hot +
Wht (3) Y Input, 2 to 10V
Org (5) U Output, 2 to 10V
4 to 20 mAControl Signal
(–)(+)
Ω 500Ω
2
ARB24-SR
Line Volts
–
1 0
W40
8
4 to 20 mA control
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
52
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Dimensions with 2-Way Valve
D14
9-2A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D14
9A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
AR...120-3 Actuators, On/Off, Floating Point
ModelsARB120-3ARX120-3 Flexible Version
Technical DataControl On/Off, Floating PointPower supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)Power consumption running 3 W
holding 0.6 WTransformer sizing 7 VA (class 2 power source)Electrical connection
ARB120-3ARX120-3
½” conduit connector18 GA appliance rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationInput impedance 600 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time
ARB120-3ARX120-3
90 seconds❑ 300 ❑ 150 ❑ 95 seconds,constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <45 dB(A)Servicing maintenance freeQuality standard ISO 9001† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
53
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
AR...120-3 Actuators, On/Off, Floating Point
W41
4
On/Off control
W41
5
Floating Point or On/Off control
A
B
3.46"[88]
Dimensions with 2-Way Flanged Valve
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
A
B
D15
1_A
B6_
Dim
s
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
54
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Dimensions with 2-Way Valve
D14
9-2B
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
Dimensions with 3-Way Valve
D14
9A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
AR...120-SR Actuators
ModelsARB120-SRARX120-SR Flexible Version
Technical DataControl On/Off, Floating PointPower supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)Power consumption running 3 W
holding 0.6 WTransformer sizing 7.5 VA (class 2 power source)Electrical connection
ARB120-SRARX120-SR
½” conduit connector 18 GA plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationFeedback output U 1 to 10 VDC, max 0.5 mAInput impedance 600 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible with protectedPosition indication handleManual override external push buttonRunning time
ARB120-SRARX120-SR
90 seconds❑ 300 ❑ 150 ❑ 90 seconds,constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <45 dB(A)Servicing maintenance freeQuality standard ISO 9001† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
55
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.AR...120-SR Actuators
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
6 Only connect common to neg. (–) leg of control circuits.
7 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
151 ARB(X) can be supplied with both 120 VAC and 230 VAC.
1919 All 120 VAC and 230 VAC actuators use appliance rated cables.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
15 2
1 Neutral
2 Hot +
N L1
H L2
6 1 Common
2 Hot +
3 Y Input, 2 to 10VControl Signal
2 to 10 VDCFeedback Signal
5 U Output, 2 to 10V
(–)
(+)(–)(+)
1 0
100 to 240 VAC
Cabl
e 2
Cabl
e 18
19
7
VDC/mA
W36
5
Proportional, 100 to 240V
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
56
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsARB24-MFTARX24-MFT
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 4 W
holding 1.25 WTransformer sizing 6 VA (class 2 power source)Electrical connection
ARB24-MFTARX24-MFT
½” conduit connector18 GA plenum rated cable3 ft [1m]❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mA (default)
Variable (VDC, PWM, Floating Point, On/Off)Feedback output U 2 to 10 VDC, 0.5 mA max
VDC VariableInput impedance 100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, Floating Point, On/Off)Angle of rotation 95° electronically variableDirection of rotation reversible with protected Position indication handleManual override external push buttonRunning time
ARB24-MFTARX24-MFT
150 secondsVariable (90 to 350 seconds)
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line volt-age and/or –S versions
Noise level <45 dB(A)Quality standard ISO 9001† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
AR...24-MFT Actuators, Multi-Function Technology
Dimensions with 2-Way Valve
D14
9-2A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D14
9A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
57
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
4Position feedback cannot be used with Triac sink controller.The actuator internal common reference is not compatible.
6Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.
8Contact closures A & B also can be triacs.A& B should both be closed for triac source and open for triac sink.
9For triac sink the common connection from the actuatormust be connected to the hot connection.
AR...24-MFT Actuators, Multi-Function Technology
W53
8
On/Off control
W53
8
Floating Point
W53
8
VDC/4-20 mA
W53
8
PWM
A
B
3.46"[88]
Dimensions with 2-Way Flanged Valve
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
A
B
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
D15
1_A
B6_
Dim
s
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
58
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ARX24-PC Actuators, Phasecut
ModelsARX24-PC
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 4 W
holding 1.25 WTransformer sizing 5.5 VA (Class 2 power source)Electrical connection ½” conduit connector
18 GA plenum rated cable❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationOperating range Y 0 to 20V PhasecutFeedback output U 2 to 10 Vdc, 0.5mA max
VDC variableInput impedance 8 kΩ (50 mW)Angle of rotation 90°, adjustable with mechanical stop
electronically variableDirection of rotation reversible withPosition indication handleManual override external push buttonRunning time 150 seconds (default)Humidity 5 to 95% RH non-condensing
(EN 60730-1)Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <45 dB(A)Quality standard ISO 9001†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
Dimensions with 2-Way Valve
D14
9-2A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D14
9A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
59
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.ARX24-PC Actuators, Phasecut
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
1
2
3
24 VAC Transformer
Blk (1) Common
Red (2) Hot +
Pnk (6) Y Input, 0 to 20V phasecut
Org (5) U Output, 2 to 10V
…PC
Line Volts
0 to 20 V Phasecut
Control Signal (–)
(+)
–
W18
5
0 to 20V Phase Cut
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
60
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ARX24-MFT95 Actuators, 0 to 135 Ω
ModelsARX24-MFT95
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 4 W
holding 1.25 WTransformer sizing 6 VA (Class 2 power source)Electrical connection ½” conduit connector
18 GA plenum rated cable❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotationOperating range WRB 0 to 135 Ω Honeywell Electronic
Series 90, 0 to 135 Ω InputFeedback output U 2 to 10 Vdc, 0.5mA maxInput impedance 100 kΩ (0.1 mW)Angle of rotation 90°, adjustable with mechanical stop
electronically variableDirection of rotation reversible withPosition indication handleManual override external push buttonRunning time 150 seconds (default)
Variable (90 to 350 secs)Humidity 5 to 95% RH non-condensing
(EN 60730-1)Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA 2/IP54Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level <45 dB(A)Quality standard ISO 9001
LRX24-SR-TElectrical connection screw terminal (for 26 to 14 GA wire)
❑ protected (NEMA 2/IP20)†Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3.
Dimensions with 2-Way Valve
D14
9-2A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D14
9A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
61
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.ARX24-MFT95 Actuators, 0 to 135 Ω
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators and controller must have separate transformers.
3Consult controller instruction data for more detailed installationinformation.
4Resistor value depends on the type of controller and the number of actuators. No resistor is used for one actuator. Honeywell resistor kits may also be used.
5 To reverse control rotation, use the reversing switch.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Override
Switch A Switch B Damper Position
Damper Open
Damper Closed
The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.
1
3
4
1 Common
2 + Hot
3 W
4 R
5 B
6 ‘U5’ Output 2-10 VDC
…MFT95
A
B
LineVolts
24 VAC Transformer
135
1
2
3
4
1 Common
2 + Hot
3 W
4 R
5 B
6 ‘U5’ Output 2-10 VDC
…MFT95
AW
R
B
Controller
B
LineVolts
LineVolts
24 VAC Transformer
1
3
2
2
5
4
1 Common
2 + Hot
3 W
4 R
5 B
6 ‘U5’ Output 2-10 VDC
…MFT95
LineVolts
24 VAC Transformer
1
3
5
1 Common
2 + Hot
3 W
4 R
5 B
6 ‘U5’ Output 2-10 VDC
…MFT95 To otheractuators
Series 90Controller
S963AMinimum Position
Potentiometer
H205 Change-over Controller
OccupiedContact
ShuntingResistor
LineVolts
Wiring multiple actuators to a Series 90 controller using a minimum position potentiometer.
R B WB
R
W
WRB
Low Limit Control
1
2
3
5
1 Common
2 + Hot
3 W
4 R
5 B
6 ‘U5’ Output 2-10 VDC
…MFT95
LineVolts
24 VAC Transformer
W B RW
B
R
R
Series 90 low limit control135 for 0 to 50% control280 for 0 to 100% control
Series 90Controller
High Limit Control
1
2
3
5
1 Common
2 + Hot
3 W
4 R
5 B
6 ‘U5’ Output 2-10 VDC
…MFT95
LineVolts
24 VAC Transformer
W B
W
B R
R
Series 90 high limit control - 280
Series 90Controller
A
B
3.46"[88]
Dimensions with 2-Way Flanged Valve
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
A
B
D15
1_A
B6_
Dim
s
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
62
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsARB24-3-T N4 w/terminal blockARB24-3-T N4H w/built in heater
Technical DataControl On/Off, Floating PointPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.0 W
holding 0.2 W Transformer Sizing 5.5 VA (class 2 power source)Electrical Connection screw terminal (for 26 to 14 GA wire)Overload Protection electronic throughout 0° to 95° rotationInput Impedance 600 ΩAngle of Rotation 90°, adjustable with mechanical stopDirection of Rotation reversible withPosition indication visual pointerManual override external push buttonRunning time 90 seconds constant independent of loadHumidity 100% RH Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing type UL Type 4X/NEMA 4X/IP66 & IP67Housing material PolypropeleneAgency Listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3*Cannot be used with the CCV-EXT-KIT
ARB24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
Dimensions with 2-Way Valve
NE
MA
4 D
iagr
am_A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
NE
MA
4 D
iagr
am 3
-Way
_A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
63
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.ARB24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3For end position indication, interlock control, etc.,ARB24-3-S incorporates one built-in auxiliary switches:1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
4 Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
424 VAC Transformer
a opena closed
The indication of direction is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
ARB24-3
a
Line Volts
–
1 0
W40
9
On/Off control
424 VAC Transformer
The indication of direction is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
ARB24-3
Line Volts
–
1 0
p j y
W41
1
Floating Point or On/Off control
2
2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
64
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsARB24-SR-T N4 w/terminal blockARB24-SR-T N4H w/built in heater
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.5 W
holding 0.4 W Transformer sizing 5 VA (class 2 power source)Electrical connection screw terminal (for 26 tp 14 GA wire)Overload protection electronic throughout 0° to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mAInput impedance 600 ΩAngle of rotation 90°, adjustable with mechanical stopDirection of rotation reversible withPosition indication visual pointerManual Override external push buttonRunning time 90 seconds constant independent of loadHumidity 100% RH Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing type UL Type 4X/NEMA 4X/IP66 & IP67Housing material PolypropeleneAgency listings† cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Quality Standard ISO 9001†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3*Cannot be used with the CCV-EXT-KIT
ARB24-SR-T N4 NEMA 4X Actuators, Proportional
Dimensions with 2-Way Valve
NE
MA
4 D
iagr
am_A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
NE
MA
4 D
iagr
am 3
-Way
_A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
65
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
5 Only connect common to neg. (–) leg of control circuits.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
ARB24-SR-T N4 NEMA 4X Actuators, Proportional
W40
8-S
R-T
2 to 10 VDC control
W40
8-S
R-T
4 to 20 mA control
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
66
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsARX24-MFT-T N4 w/terminal blockARX24-MFT-T N4H w/built in heater
Technical DataControl 2 to 10 VDC, 4 to 20 mA (default)
Variable (VDC, PWM, Floating Point, On/Off)Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 4 W
holding 1.25 W Transformer sizing 6 VA (class 2 power source)Electrical connection screw terminal (for 26 tp 14 GA wire)Overload protection electronic throughout 0° to 95° rotationInput impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA 1500 Ω for PWM, fl oating point andon-off control
Angle of Rotation 95°, adjustable with mechanical stopelectronically variable
Direction of Rotation reversible withPosition indication visual pointerManual override external push buttonRunning time 150 seconds (default)
constant independent of loadVariable (75 to 350 seconds)
Humidity 100% RH Ambient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing type UL Type 4X/NEMA 4X/IP66 & IP67Housing material PolypropeleneAgency Listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Quality Standard ISO 9001† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1*Cannot be used with the CCV-EXT-KIT
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
Dimensions with 2-Way Valve
NE
MA
4 D
iagr
am_A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
NE
MA
4 D
iagr
am 3
-Way
_A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
67
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
4Position feedback cannot be used with Triac sink controller.The actuator internal common reference is not compatible.
6Control signal may be pulsed from either the Hot (source)or the Common (sink) 24 VAC line.
8Contact closures A & B also can be triacs.A& B should both be closed for triac source and open for triac sink.
9For triac sink the common connection from the actuatormust be connected to the hot connection.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
W53
8
On/Off control
W53
8
Floating Point
W53
8
VDC/4-20 mA
W53
8
PWM
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
68
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
TFX Actuators, On/Off
ModelsTFX24 US TFX120 USTFX24-S US TFX120-S US w/built-in Aux. Switch Technical DataControl On/OffPower supply
TFX24(-S) US 24VAC ± 20%, 50/60Hz24VDC ± 10%
TFX120(-S) US (nominal) 100 to 240 VAC, 50/60 Hz(tolerance) 85 to 265 VAC, 50/60 Hz
Power consumption running 2.5 Wholding 1.3 W
Transformer sizingTFX24(-S) US 5 VA (class 2 power source)TFX120(-S) US 5 VA (class 2 power source)
Electrical connection(-S models have 2 cables)
TFX... USTFX... /300 USTFX... /500 US
½” conduit connector18 GA appliance cable3 ft [1m]10 ft [3m]16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationAngle of rotation 95°Torque min. 18 in-lb [2 Nm]Direction of rotation reversible with protectedPosition indication visual indicator, 0° to 95° Running time motor <75 sec (0 to 18 in-lb)
spring <75 sec @ -22°F to 122°F [-20°C to 50°C]Humidity 5 to 95% RH non-condensingAmbient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA type 2/IP42Housing material UL94 - 5VAAgency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level (max) running <40 db (A)spring return <40 dB (A)
Quality standard ISO 9001
TFX...-SAuxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed
adjustable 0° to 95°† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
Dimensions with 2-Way Valve
6.28"[159.55]
2.93"[74.5]
2.40"[61]
B
A
3.05"[76.2]
94D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
Dimensions with 3-Way Valve
6.28"[159.55]
3.05"[76.2]
2.93"[74.5]
2.40"[61]
B
A
C
95D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
69
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
TFX Actuators, On/Off
1 Common
2 + Hot
2
24 VAC Transformer
TFX24 US
3
On/Off Wiring
1 Neutral
2 Hot
2
100 to 240 VAC
TFX120 US
N L1
H L2
On/Off Wiring
2TFX…-S US
S1
S2
S3
NC
NO0° to 95°
W24
8
Auxiliary Switch
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
70
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsTF24-3 USTF24-3-S US w/built-in Aux. Switch
Technical DataControl FloatingPower supply 24VAC ± 20%, 50/60HzPower consumption running 2.5 W
holding 1.0 WTransformer sizing 4 VA (class 2 power source)Electrical connection(-S models have 2 cables)
TF24-3 USTF24-3 /300 USTF24-3 /500 US
½” conduit connector18 GA plenum rated cable3 ft [1m]10 ft [3m]16 ft [5m]
Overload protection electronic throughout 0° to 95° rotationInput impedance 1000 Ω (0.6w) control inputsAngle of rotation 95°Torque min. 18 in-lb [2 Nm]Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicator, 0° to 95°Running time motor 95 sec constant, independent of load
spring <25 sec @ -4°F to 122°F [-20°C to 50°C]<60 sec @ -22°F [-30°C]
Humidity 5 to 95% RH non-condensingAmbient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA type 2/IP42Housing material UL94 - 5VAAgency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level (max) running <35 db (A)spring return 62 dB (A)
Quality standard ISO 9001
TF24-3-S USAuxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
TF24-3 Actuators, Floating Point
Dimensions with 2-Way Valve
6.28"[159.55]
2.93"[74.5]
2.40"[61]
B
A
3.05"[76.2]
94D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
Dimensions with 3-Way Valve
6.28"[159.55]
3.05"[76.2]
2.93"[74.5]
2.40"[61]
B
A
C
95D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
71
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3The common connection from the actuator must be connected to the Hot connection of the controller.
4 The actuator Hot must be connected to the control board common.
5For end position indication, interlock control, fan startup, etc.,TF24-3-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
7Actuators with plenum rated cable do not have numbers on wires; use color coded instead. Actuators with appliance rated cable use numbers.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
TF24-3 Actuators, Floating Point
Line Volts
The indication of direction is valid for switch position CW.
Blk (1) Common
Red (2) ~Wht (W3) ~
Or (W4) ~
24 VAC Transformer
TF24-3 (-S) US
bCCWCCWW
stop
a(3) (4)
stop stop stop
e
Direction of Rotation Switch
xxxx
xxxx
xx
xx
xx
xx
xxx
xxxx
xxxx
xx
xx
xx
xx
xxx
CCWSwitch
Positions
CCWCCW
a
b
7
W24
0
Floating point control
Blk (1) Common
Red (2) ~ Hot
Wht (W3) ~Or (W4) ~
ComHot
Controller
Line Volts
TF24-3 (-S) US
The indication of direction is valid for switch position CW.
2
24 VAC Transformer
7
W24
2
Triac source
Blk (1) Common
Red (2) ~ Hot
Wht (W3) ~Or (W4) ~
ComHot
Controller
Line Volts
TF24-3 (-S) US
The indication of direction is valid for switch position CW.
2
3
4
24 VAC Transformer
7
W24
3
Triac sink with separate transformers
TF24-3-S US
5S1
S2
S3
NC
NO0° to 95°
W24
1
Auxiliary switch
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
72
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
TF24-SR US Actuators, Proportional
ModelsTF24-SR USTF24-SR-S US w/built-in Aux. Switch
Technical DataControl ProportionalPower supply 24 VAC ± 20%, 50/60 Hz
24 VDC ± 10%Power consumption running 2.5 W
holding 1.0 WTransformer sizing 4 VA (class 2 power source)Electrical connection(-S models have 2 cables)
TF24-SR USTF24-SR /300 USTF24-SR /500 US
½” conduit connector18 GA plenum rated cable3 ft [1m]10 ft [3m]16 ft [5m]
Electrical protection actuators are double insulatedOverload protection electronic throughout 0° to 95° rotationOperating range Y 2 to 10 VDC, 4 to 20 mAInput impedance 100k Ω (0.1mA), 500 ΩAngle of rotation 95°Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicator, 0° to 95°Running time motor 95 sec constant, independent of load
spring <25 sec @-4°F to 122°F [-20°C to 50°C]<60 sec @-22°F [-30°C]
Humidity 5 to 95% RH non-condensingAmbient temperature -22°F to 122°F [-30°C to 50°C]Storage temperature -40°F to 176°F [-40°C to 80°C]Housing NEMA type 2/IP42Housing material UL94 - 5VAAgency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level (max) running <35 db (A)spring return <62 dB (A)
Quality standard ISO 9001
TF24-SR-S USAuxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
Dimensions with 2-Way Valve
6.28"[159.55]
2.93"[74.5]
2.40"[61]
B
A
3.05"[76.2]
94D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
Dimensions with 3-Way Valve
6.28"[159.55]
3.05"[76.2]
2.93"[74.5]
2.40"[61]
B
A
C
95D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
73
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
4Up to 4 actuators may be connected in parallel. With 4 actuators wired to one 500 Ω resistor, a +2% shift of control signal may be required. Power consumption must be observed.
3 Actuators may also be powered by 24 VDC.
5 Only connect common to neg. (—) leg of control circuits.
6Actuators with plenum rated cable do not have numbers on wires;use color codes instead.
7For end position indication, interlock control, fan startup, etc.,TF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A (0.5A ) @250 VAC, UL listed, adjustable 0° to 95°.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
TF24-SR US Actuators, Proportional
1
6
2
3
24 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input, 2 to 10V
TF24-SR US
Line Volts
2 to 10 VDCControl Signal (–)
(+)
W24
5
2 to 10 VDC control
4
To other actuators
6
3
5
24 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input, 2 to 10V
4 to 20 mAControl Signal
(–)(+)
Ω 500Ω
2
TF24-SR US
Line Volts
1
W24
6
4 to 20 mA control
TF24-SR-S US
7S1
S2
S3
NC
NO0° to 95°
Auxiliary switch
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
74
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsTF24-MFT US
Technical DataControl MFTPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.5 W
holding 1.0 WTransformer sizing 4 VA (class 2 power source)Electrical connection ½” conduit connector
3 ft [1m], 18 GA plenum rated cableOverload protection electronic throughout 0° to 95° rotationOperating range Y* 2 to 10 VDC, 4 to 20 mA (default)
Variable (VDC, PWM, Floating Point, On/Off)Feedback output U* 2 to 10 VDC, 0.5 mA maxInput impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA 1500 Ω for PWM, fl oating point andon-off control
Mechanical angle of rotation* 95°Angle of Rotation Adaptation* Off (Default)Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicator, 0° to 95° Override control* Min. (Min Position) = 0%
- ZS (Mid. Position) = 50%- Max. (Max. Position) = 100%
Running time motor* 95 sec constant independent of loadspring <25 sec @-4°F to 122°F [-20°C to 50°C]
<60 sec @-22°F [-30°C]Humidity 5 to 95% RH, non-condensingAmbient temperature -22 to 122° F (-30 to 50° C)Storage temperature -40 to 176° F (-40 to 80° C)Housing NEMA 2/IP42Housing material UL 94-5VAAgency listings† cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/EC and 2006/95/EC for line voltage and/or –S versions
Noise level (max) running <35 dB (A) spring return <65 dB (A)
Quality standard ISO 9001* Variable when confi gured with MFT options† Rated impulse voltage 0.8 kV, Control pollution degree 3, Type of action 1.AA.
TF24-MFT US Actuators, Multi-Function Technology
Dimensions with 2-Way Valve
6.28"[159.55]
2.93"[74.5]
2.40"[61]
B
A
3.05"[76.2]
94D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]
Dimensions with 3-Way Valve
6.28"[159.55]
3.05"[76.2]
2.93"[74.5]
2.40"[61]
B
A
C
95D
09
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
75
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
4 ZG-R01 may be used.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
W02
5
4 to 20 mA Control Signal
TF24-MFT US Actuators, Multi-Function Technology
W02
4
2 to 10 VDC Control Signal
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
76
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsLF24 USLF24-S US w/built-in Aux. SwitchLF120 USLF120-S US w/built-in Aux. Switch
Technical DataControl On/Off, FloatingPower supply
LF24(-S) US 24 VAC ± 20% 50/60 Hz24 VDC ± 10%
LF120(-S) US 120 VAC ± 10% 50/60 HzPower consumption
LF24(-S) US running 5 Wholding 2.5 W
LF120(-S) US running 5.5 Wholding 3.5 W
Transformer sizingLF24(-S) US 7 VA, class 2 power sourceLF120(-S) US 7.5 VA, class 2 power source
Electrical connection(-S models have 2 cables)
½” conduit connector3 ft [1m], 18 GA appliance cable
Electrical protection 120V actuators double insulatedOverload protection electronic throughout rotationAngle of rotation 95° Spring return direction reversible with CW/CCW mountingPosition indication visual indicator 0° to 90°Running time motor <40 to 75 sec. (on-off)
spring <25 sec. @-4°F to 122°F [-20°C to 50°C]<60 sec. @-22°F [-30°C]
Ambient temperature -22° F to 122° F [-30° C to 50° C]Housing NEMA 2 Agency listings† cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level (max) running <30 db(A)
spring return 62 dB(A)Quality standard ISO 9001
LF...-S USAuxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
LF Actuators, On/Off
Dimensions with 2-Way Valve
7.64"[194]
3.625"[92]
3.7"[94]
2.28"[58]
B
A
D07
3
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D02
6
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
77
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption must be observed.
3 Actuator may also be powered by 24 VDC.
4For end position indication, interlock control, fan startup, etc.,LF24-S US and LF120-S US incorporates a built-in auxiliary switch:1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
LF Actuators, On/Off
1 Common
2 + Hot
2
24 VAC Transformer
LF24 US
Line Volts 3
W04
7
On/Off wiring for 24 VDC
W04
9-LF
-08
On/Off wiring for 120 VDC
W04
8-A
UX
Auxiliary Switch
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
78
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsLF24-3 USLF24-3-S US w/built-in Aux. Switch
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 2.5 W
holding 1WTransformer sizing 5 VA (class 2 power source)Electrical connection(-S models have 2 cables)
½” conduit connector3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotationInput impedance 1000 Ω (0.6w) control inputs Angle of rotation 95° Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicator 0° to 90°Running time motor 150 sec. constant independent of load
spring <25 sec. @ -4°F to 122°F [-20°C to 50°C]<60 sec. @ -22°F [-30°C]
Humidity 5 to 95% RH non-condensingAmbient temperature -22° F to 122° F [-30° C to 50° C]Storage temperature -40° F to 176° F [-40° C to 80° C]Housing NEMA type 2/IP54 Housing material zinc coated metalAgency listings cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level (max) running <30 db(A)
spring return 62 dB(A)Servicing maintenance freeQuality standard ISO 9001
LF24-3-S USAuxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
LF24-3 Actuators, Floating Point
Dimensions with 2-Way Valve
7.64"[194]
3.625"[92]
3.7"[94]
2.28"[58]
B
A
D07
3
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D02
6
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
79
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption must be observed.
3 Actuators may also be powered by 24 VDC.
4The common connection from the actuator must be connected to theHot connection of the controller.
5 The actuator Hot must be connected to the control board common.
6For end position indication, interlock control, fan startup, etc.,LF24-3-S US incorporates one built-in auxiliary switch: 1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
8Actuators with plenum rated cable do not have numbers on wires;use color coded instead. Actuators with appliance rated cable usenumbers.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
2 8324 VAC Transformer
a opena closed
The indication of direction is valid for switch position CW.
Blk (1) Common
Red (2) +
Wht (3) +
Grn (4) +
LF24-3(-S) USCW CCW
a
Line Volts
W06
1
On/Off control
Line Volts
The indication of direction is valid for switch position CW.
Blk (1) Common
Red (2) +
Wht (3) +
Grn (4) +
24 VAC Transformer
LF24-3(-S) US
CW CCW
a
b
8
bCCC WCWW
stop
a(3) (4)
stop stop stop
Installation Side
Direction of Rotation Switch
xxxx
xxxx
xx
xx
xx
xx
xxx
xxxx
xxxx
xx
xx
xx
xx
xxx
CCWSwitch
Positions
CCC WCW
W05
2
Floating Point control
LF24-3-S US
6S1
S2
S3
NC
NO0° to 95°
W05
3
Auxiliary switch
Blk (1) Common
Red (2) + Hot
Wht (3) +
Grn (4) +
ComHot
Controller
Line Volts
CW CCW
LF24-3(-S) US
The indication of direction is valid for switch position CW.
2
24 VAC Transformer
8NGnents! ting, hooting be h live Have
ectrician o has n
hese all
utions electrical ult in .
W05
4
Triac source
Blk (1) Common
Red (2) + Hot
Wht (3) +
Grn (4) +
ComHot
Controller
Line Volts
CW CCW
LF24-3(-S) US
The indication of direction is valid for switch position CW.
2
4
5
24 VAC Transformer
8Gents! ng, ooting e ive
Have trician
has
ese ll ons
ectrical t in
W05
5
Triac sink
Blk (1) Common
Red (2) + Hot
Wht (3) +
Grn (4) +
ComHot
Controller
Line Volts
CW CCW
LF24-3(-S) US
The indication of direction is valid for switch position CW.
2
5
24 VAC Transformer
Line Volts
24 VAC Transformer
8s!
ing
e ve cian s
e
s rical
n
W05
6
Triac sink with separate transformers
LF24-3 Actuators, Floating Point
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
80
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsLF24-SR USLF24-SR-S US w/built-in Aux. Switch
Technical DataControl ProportionalControl signal 2 to 10 VDC
4 to 20 mA (with 500 Ω resistor)Power consumption running 2.5 W
holding 1 WTransformer sizing 5 VA, class 2 powerElectrical connection(-S models have 2 cables)
½” conduit connector3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotationFeedback output 2 to 10 VDCInput impedance 100 kΩAngle of rotation 95° Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicatorRunning time motor 150 sec. independent of load (proportional)
spring <25 sec. @ -4°F to 122°F [-20°C to 50°C]<60 sec. @ -22°F [-30°C]
Ambient temperature -22° F to 122° F [-30° C to 50° C]Housing NEMA 2 Agency listings cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level (max) running <30 db(A)
spring return 62 dB(A)Quality standard ISO 9001
LF24-SR-S USAuxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
LF24-SR Actuators, Proportional
Dimensions with 2-Way Valve
7.64"[194]
3.625"[92]
3.7"[94]
2.28"[58]
B
A
D07
3
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]B212(B)-B215(B) ½” 15 2.38” [60.4] 1.72” [43.7]B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D02
6
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B C
B307(B)-B311(B) ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312(B)-B315(B) ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317(B)-B320(B) ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
81
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel. Up to 4 actuators may beconnected in parallel. With 4 actuators wired to one 500 Ω resistor, a+2% shift of control signal may be required. Power consumption must be observed.
3 Actuators may also be powered by 24 VDC.
4Actuators with plenum rated cable do not have numbers on wires; use color codes instead.
5 Only connect common to neg. (–) leg of control circuits.
6For end position indication, interlock control, fan startup, etc.,LF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
7 The LF24-SR-S US wire 5 is white.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
LF24-SR Actuators, Proportional
1
4
7
2
3
24 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input, 2 to 10V
Grn (5) U Output, 2 to 10V
LF24-SR US
Line Volts
2 to 10 VDCControl Signal (–)
(+)
CW CCW
W05
7
2 to 10 VDC control
4
To other actuators
3
5
24 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input, 2 to 10V
Grn (5) U Output, 2 to 10V
4 to 20 mAControl Signal
(–)(+)
2 to 10 VDCFeedback Signal
(–)(+)
Ω 500Ω
2
LF24-SR US
CW CCW
Line Volts
1
4 to 20 mA control
LF24-SR-S US
6S1
S2
S3
NC
NO0° to 95°
W05
8
Auxiliary switch
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
82
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsLF24-MFT US LF24-MFT-S US w/built-in Aux. Switch
Technical DataControl MFTControl signal 2 to 10 VDCPower consumption running 2.5 W
holding 1 WTransformer sizing 5 VA (class 2 power source)Electrical connection(-S models have 2 cables)
½” conduit connector3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotationFeedback output 2 to 10 VDC, 0.5 mA maxInput impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20mA750 Ω for PWM 500 Ω for on/off and fl oating point
Angle of rotation 95° Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicatorRunning time motor 150 sec. independent of load
(proportional, default)spring <25 sec. @-4°F to 122°F [-20°C to 50°C]
<60 sec. @-22°F [-30°C]Ambient temperature -22° F to 122° F [-30° C to 50° C]Housing NEMA 2 Agency listings cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level (max) running <30 db(A)
spring return 62 dB(A)Quality standard ISO 9001
LF24-MFT-S USAuxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
LF24-MFT Actuators, Multi-Function Technology
Dimensions with 2-Way Valve
7.64"[194]
3.625"[92]
3.7"[94]
2.28"[58]
B
A
D07
3
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]B217-B220 ¾” 20 2.73” [69.3] 1.81” [45.9]B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Dimensions with 3-Way Valve
D02
6
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB307-B311 ½” 15 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]B312-B315 ½” 15 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]B317-B320 ¾” 20 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]B322-B325 1” 25 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
83
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel if not mechanically mounted tothe same shaft. Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
4 IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).
5 Triac A and B can also be contact closures.
6Control signal may be pulsed from either the Hot (Source) orCommon (Sink) 24 VAC line.
7Position feedback cannot be used with Triac sink controller.The actuators internal common reference is not compatible.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
LF24-MFT Actuators, Multi-Function Technology
(1) Common
(2) Hot
(3) Y Input
(5) U Output
Line Volts
24 VAC/DC Transformer
CCW CW
…MFT
aPosition
Feedback VDC (+)
(–)
W04
3
On/Off control
(1) Common
(2) + Hot
(3) Y Input
(5) U Output
Line Volts
24 VAC Transformer (AC only)
CCW CW
(+)
(–)
6
7
…MFT
Position
Feedback VDC
W04
1
PWM, triac source and sink
W30
2
Floating Point control
Proportional 2 to 10 or 4 to 20 mA control signal
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
84
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsAF24 US AF24-S US w/built-in Aux. SwitchesAF120 US AF120-S US w/built-in Aux. Switches
Technical DataControl On/OffPower consumption
AF24(-S) US running 5 W holding 1.5 W
AF120(-S) US running 6 W holding 2.3 W
Transformer sizingAF24(-S) US 10 VA (class 2 power source)AF120(-S) US 11 VA (class 2 power source)
Electrical connection(-S model has 2 cables)
½” conduit connector3 ft [1m], 18 GA appliance cables
Electrical protection 120 V actuators double insulatedOverload protection electronic throughout 0° to 95° rotationAngle of rotation 95°Position indication visual indicatorManual override hex crankRunning time motor 150 sec. independent of load
spring <20 sec.Ambient temperature -22° F to 122° F [-30° C to 50° C]Housing NEMA 2 / IP54Agency listings cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level max. 45 dB(A)
AF...-S USAuxiliary switches 2 x SPDT, 7A (2.5A) @ 250 VAC, UL
listed, one switch is fi xed at +5°, one is adjustable 25° to 85° (double insulated)
AF Actuators, On/Off
Dimensions with 2-Way Valve
D07
7
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D02
7
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
85
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption must be observed.
3 Actuators may also be powered by 24 VDC.
4
For end position indication, interlock control, fan startup, etc., AF24-S US incorporates two built-in auxiliary switches: 2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed, one switch is fi xed at +5°, one is adjustable 25°to 85°.
Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
AF Actuators, On/Off
1 Common
2 + Hot
2
24 VAC Transformer
AF24 US
Line Volts 3
p j y
W19
4
On/Off Wiring for 24 VDC
W00
3-A
F-0
8
On/Off Wiring for 120 VDC
W19
5-A
UX
Auxiliary Switches
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
10.47"[266]
3.86"[98]
3.66"[93]
2.24"[57]
B
A
Dimensions with 2-Way Flanged Valve
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
A
B
D10
0B
6_D
ims
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
86
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ModelsAF24-SR US
Technical DataControl ProportionalPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 6 W
holding 2 WTransformer sizing 10 VA, class 2 powerElectrical connection ½” conduit connector
3 ft [1m], 18 GA appliance cableOverload protection electronic throughout 0° to 95° rotationFeedback output 2 to 10 VDC, 0.5 mA maxAngle of rotation 95°Direction of Rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicatorManual override hex crankRunning time motor 150 sec. independent of load
spring <20 sec.Ambient temperature -22° F to 122° F [-30° C to 50° C]Housing NEMA 2, IP54Agency listings cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level max. 45 dB(A)
AF24-SR Actuators, Proportional
Dimensions with 2-Way Valve
D07
7_A
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
Dimensions with 3-Way Valve
D02
7
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
87
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2CAUTION Equipment damage!Actuators may be connected in parallel.Power consumption must be observed.
3 Actuators may also be powered by 24 VDC.
5 Only connect common to neg. (–) leg of control circuits.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
AF24-SR Actuators, Proportional
Control Signal (+)2 to 10 VDC
(–)
1 Common
2 + Hot
3 Y Input, 0 to 10V
5 U Output 2 to 10V
2
3
24 VAC Transformer
AF24-SR US
Line Volts
W19
6
Proportional 2 to 10 VDC control signal
1 Common
2 + Hot
3 Y Input, 0 to 10V
5 U Output 2 to 10V
24 VAC Transformer
5
3
2
Control Signal (+)4 to 20 mA (–)
Feedback Signal (+)2 to 10 VDC (–)
Ω 500Ω
Line Volts
AF24-SR US
Proportional 4 to 20 mA control signal
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
88
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
AF Actuators, Multi-Function Technology
ModelsAF24-MFT USAF24-MFT-S US w/built-in Aux. Switches
Technical DataControl MFTControl signal 2 to 10 VDC, (4 to 20 mA with 500 Ω resistor)Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 6 W
holding 2.5 WTransformer sizing 10 VA, class 2 powerElectrical connection(-S model has 2 cables)
½” conduit connector3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout rotationFeedback output 2 to 10 VDC, 0.5 mA max (variable)Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA750 Ω for PWM1500 Ω for on/off and fl oating point
Angle of rotation 95°Direction of Rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicatorManual override hex crankRunning time motor 150 sec. independent of load, default
(variable, 75 to 300 sec.)spring <20 sec.
Ambient temperature -22° F to 122° F [-30° C to 50° C]Housing NEMA 2 / IP54Agency listings cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level max. 45 dB(A)
AF24-MFT-S USAuxiliary switches 2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed,
one switch is fi xed at +5°, one is adjustable 25° to 85° (double insulated)
Dimensions with 2-Way Valve
D07
7
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D02
7
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
89
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
2 CAUTION Equipment damage!Actuators may be connected in parallel if not mechanically mounted tothe same shaft. Power consumption and input impedance must be observed.
3 Actuators may also be powered by 24 VDC.
4IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).
5 Triac A and B can also be contact closures.
6Control signal may be pulsed from either the Hot (Source) orCommon (Sink) 24 VAC line.
7Position feedback cannot be used with Triac sink controller.The actuators internal common reference is not compatible.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to2 to 10 VDC, up to 2 actuators may be connected in parallel.Meets cULus or UL and CSA requirements without theneed of an electrical ground connection.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
AF Actuators, Multi-Function Technology
(1) Common
(2) Hot
(3) Y Input
(5) U Output
Line Volts
24 VAC/DC Transformer
CCW CW
…MFT
aPosition
Feedback VDC (+)
(–)
W04
3
On/Off control
(1) Common
(2) + Hot
(3) Y Input
(5) U Output
Line Volts
24 VAC Transformer (AC only)
CCW CW
(+)
(–)
6
7
…MFT
Position
Feedback VDC
W04
1
PWM, triac source and sink
W30
2
Floating Point control
Proportional 2 to 10 or 4 to 20 mA control signalW
195-
AU
XM
FT
Auxiliary Switches
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
10.47"[266]
3.86"[98]
3.66"[93]
2.24"[57]
B
A
Dimensions with 2-Way Flanged Valve
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
A
B
D10
0B
6_D
ims
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
90
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
AF24-MFT95 US Actuator, Proportional Potentiometric Control
ModelAF24-MFT95 US
Technical DataPower supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%Power consumption running 6 W
holding 2 WTransformer sizing 10 VA, class 2 powerElectrical connection ½” conduit connector
3 ft [1m], 18 GA appliance cableOverload protection electronic throughout 0 to 95° rotationOperating range WRB 0 to 135 Ω Honeywell electronic series 90,
or a 0 to 135 Ω inputFeedback output 2 to 10 VDC, 0.5 mA maxAngle of rotation 95°Direction of Rotation spring reversible with CW/CCW mounting
motor reversible with built-in Position indication visual indicatorManual override hex crankRunning time motor 150 sec. constant, default
(variable, 75 to 300 sec.)spring <20 sec. spring return fail safe position
Humidity 5 to 95% RH non-condensingAmbient temperature -22° F to 122° F [-30° C to 50° C]Storage temperature -40° F to 176° F [-40° C to 80° C]Housing NEMA 2 / IP54Agency listings cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93Noise level max. 45 dB(A)
AF24-MFT95-S USAuxiliary switches 2 x SPDT, 7A (2.5A) @ 250 VAC, UL listed,
one switch is fi xed at +5°, one is adjustable 25° to 85° (double insulated)
Dimensions with 2-Way Valve
D07
7
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A BB231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Dimensions with 3-Way Valve
D02
7
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CB329-B331 1¼” 32 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]B338-B341 1½” 40 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]B347-B352 2” 50 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
91
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Wiring Diagrams
1 Provide overload protection and disconnect as required.
2 Actuators and controller must have separate transformers.
3Consult controller instruction data for more detailed installationinformation.
4 To reverse control rotation, use the reversing switch.
5Resistor value depends on the type of controller and the number ofactuators. No resistor is used for one actuator. Honeywell resistorkits may also be used.
WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualifi ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
AF24-MFT95 US Actuator, Proportional Potentiometric Control
Switch A Switch B Damper Position
Damper Open
Damper Closed
The direction of rotation switch is set so that the fail safe position and the position of the damper is closed with no signal at wire R.
1
3
4
1 Common, Blk
2 + Hot, Red
3 W, Wht
4 R, Wht
5 B, Wht
6 ‘U5’ Output 2-10 VDC
AF24-MFT95 US
A
B
Line Volts
24 VAC Transformer
135Ω
1
2
3
4
1 Common, Blk
2 + Hot, Red
3 W, Wht
4 R, Wht
5 B, Wht
6 ‘U5’ Output 2-10 VDC
AF24-MFT95 US
AW
R
B
Controller
B
Line Volts
Line Volts
24 VAC Transformer
W01
5
Override of AF24-MFT95 US
1
2
3
4
1 Common, Blk
2 + Hot, Red
3 W, Wht
4 R, Wht
5 B, Wht
6 ‘U5’ Output 2-10 VDC
AF24-MFT95 US
Line Volts
24 VAC Transformer
W B RW
B
R
R
Series 90 low limit control 135Ω for 0 to 50% control 280Ω for 0 to 100% control
Series 90 Controller
W01
6
1
2
3
4
1 Common, Blk
2 + Hot, Red
3 W, Wht
4 R, Wht
5 B, Wht
6 ‘U5’ Output 2-10 VDC
AF24-MFT95 US
Line Volts
24 VAC Transformer
W B
W
B R
R
Series 90 high limit control - 280Ω
Series 90 Controller
W01
7
AF24-MFT95 US used with a Series 90 controllerand a Series 90 low limit control
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B CCV-EXTB661-B665 2½” 65 7.54” [192] 3.50” [89] 2.00” [50]B677-B680 3” 80 7.93” [202] 3.75” [96] 2.00” [50]
10.47"[266]
3.86"[98]
3.66"[93]
2.24"[57]
B
A
Dimensions with 2-Way Flanged Valve
Valve Nominal Size Dimensions (Inches [mm])Valve Body Inches DN [mm] A B
B6250 2½" 65 5.37” [136.5] 4.45” [113]B6300 3" 80 6.61” [168] 4.45” [113]
A
B
D10
0B
6_D
ims
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
92
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
W02
0
Typical wiring diagrams for multiple actuators usedwith the W973, W7100 and T775 controllers.
AF24-MFT95 US Actuator, Proportional Potentiometric Control
W01
8
Wiring multiple actuators to a Series 90 controller.
W01
9
Wiring multiple actuators to a Series 90 controllerusing a minimum position potentiometer.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
93
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ApplicationThe CCV-EXT-KIT can be used with most CCV’s* and PICCV in orderto achieve a large clearance over the pipe. The Extension Kit will provide an additional 2” of space between the top of the valve and the base of the actuator. bracket is made from aluminum and is not intended as a thermal block.
– Extension kit will be automatically assembled with anyFlanged CCV assembly.
1.65"1.65"
2"
Accessories
Technical DataExtension Height 2"Total Weight 0.7 lb
MaterialExtension Housing Aluminum - AnodizedShaft Stainless SteelThreaded Hardware Stainless SteelBearing Oilite® BearingRetaining Clip Stainless Steel
TR LRB (X) ARB (X) TF LF AFExtension BracketCCV-EXT-Kit ● ● ● ● ● ●
* Cannot be used with N4 actuators.* Available for previous NF assemblies.* CCV-EXT-KIT cannot be used with any valve smaller than the
B212(B) and B312(B).
gg Available for SpringAvailable for Springand Non-Spring and Non SpringActuators
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
94
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
AccessoriesZS-CCV... New Characterized Control Valve Weather Shield
ApplicationThe ZS-CCV... weather shield provides moderate protection for valves which are mounted outdoors. This product is designed as a water tight enclosure. The housing allows easy mounting over the actuator, whileallowing easy viewing of the actuator in operation. Weather shield for PICCV/CCV to provide protection for actuators in outdoor applications.
SpecificationsCover PETG with UV resistant smoke tintPerimeter Gasket Silicon RubberRubber Gasket Silicon RubberSpring Clips Stainless SteelTemperature limitations: -22˚F to 122˚F (-30˚C to 50˚C)( )Plate (ZS-CCV-100)( ) AluminumPlate Galvaneal w/black powder coat
Part Number ActuatorZS - CCV - 90 AFZS - CCV - 100 LRB(X), ARX( )
Part Number L W HZS - CCV - 90 16.25” [413][ ] 8.75” [222][ ] 4.5” [114][ ]ZS - CCV-100 15.67” [398][ ] 7.61” [193][ ] 4.0” [102][ ]
Parts ListCover including Rubber Perimeter Gasket, Rubber GasketBack Plate Anti-Rotation Post with screw and lock washerValve GasketAssorted Cap plugs for unused holes
Screws AF - 2 bolts with nylon insert locking nutsLRB(X), ARX - 1 screw, 1 washer
No weather shield available at this time for the TF and TR actuators. Designed for NEMA 4 specifi cations.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
95
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
ApplicationThe S1A and S2A auxiliary switches are used to indicate when adesired position of a valve is reached or to interface additional controls for a specific control sequence.
OperationThe S1A and S2A auxiliary switches are mounted onto the direct coupledactuator. The switches are modular units that mount directly onto LR and AR type actuators and are locked into place by guiding grooves on the sides of the actuator.
A driver disk is attached to the actuator handle and offers directtransmission of the actuator position to the micro switch cams. The switching points can be set over the full scale of 0 to 1 simply byadjusting the slotted discs.
AccessoriesAuxiliary Switches S1A, S2A
For the non-spring return direct-coupled actuators
TypesS1A 1 SPDT 3 ft, 18 GA Appliance CableS1A/300 1 SPDT 6 ft, 18 GA Appliance CableS1A/500 1 SPDT 10 ft, 18 GA Appliance Cable
S2A 2 SPDT 3 ft, 18 GA Appliance CableS2A/300 2 SPDT 6 ft, 18 GA Appliance CableS2A/500 2 SPDT 10 ft, 18 GA Appliance Cable
Technical Data S1A S2ANumber of Switches 1 SPDT 2 SPDTWeight 4.6 oz [130 g][ ] 6.0 oz [170 g][ ]
Switching Capacity 3A (0.5A), 250 VAC( )Switching Point Adjustable over Full Rotation (0° to 95°)( )Pre-Setting With Scale PossibleHumidity 5 to 95% RH non-condensingAmbient Temperature -22°F to 122°F [-30°C to +50°C][ ]Storage Temperature -40°F to 176°F [-40°C to 80°C][ ]Housing NEMA 2 / IP54Housing Rating UL94-5VAServicing Maintenance FreeAgency Listings cULus acc. to UL60730-1
CE according to 73/23/EECQuality Standard ISO 9001
Wiring DiagramMounting Instructions1. Press down the manual override button and rotate the actuator
fully counter clockwise.2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.4. Check for correct mating of the adaptor to the switch.5. Adjust switch dials as necessary.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
96
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
AccessoriesFeedback Potentiometer P...AFor the non-spring return direct-coupled actuators
ApplicationThe P…A feedback potentiometers are used with LR and AR actuators to provide a resistive signal which varies with valve position.
The P…A units are applied with commercial proportional temperature controllers to provide feedback of the valve position, or with electric or electronic meters to provide position indication. The signal can also be used as a positioner for parallel operation of multiple actuators.
OperationThe P…A feedback potentiometers are mounted onto the direct coupled actuator. The switches are modular units that mount directly onto LR and AR type actuators and are locked into place by guiding grooves on thesides of the actuator.
A driver disk is attached to the actuator handle and offers directtransmission of the actuator position to the micro switch cams.
TypesP140A Feedback Potentiometer 140 ΩP200A Feedback Potentiometer 200 ΩP500A Feedback Potentiometer 500 ΩP1000A Feedback Potentiometer 1000 ΩP2800A Feedback Potentiometer 2800 ΩP5000A Feedback Potentiometer 5000 ΩP10000A Feedback Potentiometer 10000 Ω
Technical Data P...AResistance Values As AboveOutput 1 WTolerance ± 5%Linearity ± 2%Resolution Min. 1%Residual Resistance max. 5% On Both SidesElectrical Connection 3 ft, 18 GA Appliance Cable
½" Conduit ConnectorHumidity 5 to 95% RH non-condensingAmbient Temperature -22°F to 122°F [-30°C to 50°C][ ]Storage Temperature -40°F to 176°F [-40°C to 80°C][ ]Housing NEMA 2 / IP54Housing Rating UL94-5VAServicing Maintenance FreeAgency Listings cULus acc. to UL60730-1
CE according to 73/23/EECQuality Standard ISO 9001Weight 4.6 oz [130 g][ ]
Wiring Diagram
Mounting Instructions1. Press down the manual override button and rotate the
actuator fully counter clockwise.2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.4. Check for correct mating of the adaptor to the switch.5. Adjust switch dials as necessary.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
97
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
5. Shut terminal top and screw on conduit connector.
Mounting the Terminal Cover1. Attach terminal cover to actuator, if not done already.2. Slide the conduit fi tting and correct size rubber seal onto wire.3. Wire up actuator using the terminal strips.
Wiring AccessoriesProtective Terminal Cover
For the non-spring return direct-coupled actuators
ApplicationBelimo non-spring return actuators with terminal strips are can be converted from NEMA 1/IP20 to NEMA 2/IP54 using the protective terminal cover ZS-T.
The ZS-T terminal cover accessory consists of:• Terminal Cover• Conduit Fitting• Rubber Seal for Wire Diameter 4-6• Rubber Seal for Wire Diameter 6-8
TerminalCover Conduit
Fitting
RubberSeals
4. Fit rubber seal into slot of terminal cover.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
98
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Configuration(Substitute ‘V’ for ‘P’ for
NV[F] actuators)Code
Control MotionList Price
Input Range Position Feedback Running Time† Torque % Adaptation
Volta
ge
P-10001 A01 2.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10002 A02 0.0 to 10.0 VDC 0.0 to 10.0 VDC 150 100 Manual ●
P-10003 A03 2.0 to 10.0 VDC 0.0 to 5.0 VDC 150 100 Manual ●
P-10004 A04 4.0 to 7.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10005 A05 6.0 to 9.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10006 A06 10.5 to 13.5 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10007 A07 0.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10009 A09 5.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10010 A10 5.0 to 10.0 VDC 0.0 to 10.0 VDC 150 100 Manual ●
P-10013 A13 0.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10015 A15 2.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10016 A16 2.0 to 6.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10017 A17 6.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10018 A18 14.0 to 17.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10020 A20 9.0 to 12.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10028 A28 0.0 to 10.0 VDC 0.0 to 10.0 VDC 100 100 Manual ●
P-10031 A31 0.0 to 4.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10063 A63 0.5 to 4.5 VDC 0.5 to 4.5 VDC 150 100 Manual ●
P-10064 A64 5.5 to 10.0 VDC 5.5 to 10.0 VDC 150 100 Manual ●
PWM
P-20001 W01 0.59 to 2.93 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20002 W02 0.02 to 5.00 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20003 W03 0.10 to 25.50 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20004 W04 0.10 to 25.60 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20005 W05 0.10 to 5.20 sec. 0.0 to 5.0 VDC 150 100 Manual ●
Floa
ting
Poin
t P-30001 F01 Floating point 2.0 to 10.0 VDC 150 100 Manual ●
P-30002 F02 Floating point 0.0 to 10.0 VDC 150 100 Manual ●
P-30003 F03 Floating point 2.0 to 10.0 VDC 100 100 Manual ●
P-30004 F04 Floating point 0.0 to 5.0 VDC 100 100 Manual ●
P-30005 F05 Floating point 0.0 to 10.0 VDC 100 100 Manual ●
P-30006 F06 Floating point 0.0 to 5.0 VDC 150 100 Manual ●
On/O
ff
P-40001 J01 On/Off 2.0 to 10.0 VDC 75 100 Manual ●
P-40002 J02 On/Off 2.0 to 10.0 VDC 150 100 Manual ●
P-40003 J03 On/Off 2.0 to 10.0 VDC 75 100 Manual ●
P-40004 J04 On/Off 0.0 to 5.0 VDC 100 100 Manual ●
P-40005 J05 On/Off 0.0 to 10.0 VDC 100 100 Manual ●
*P-10001 is the default confi guration.
Example: AF24-MFT US is the basic model. Add the P… pre-set MFT confi guration number and list price to the actuator when ordering, as needed. Note: V-codes used for NV…Series actuator. All other MFT actuators use P-codes.Note: Most popular confi gurations available at no additional cost. Note: If the confi guration needed is not listed, please fi ll in pg 239 or call Customer Service.Note: For Non-Spring Return Actuators the 3-digit code can be used in place of the P… pre-set MFT confi guration number.
MFT Standard Confi guration
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
99
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
PRODUCTS
MODEL Base Actuator Codes Control Input Feedback Running Time Angle of
Rotation/Stroke Power Supply VA Rating Weight (lb)List Price(add to valve
assembly
45 in
-lb [5
Nm
]
LRX24-3 LR000 On/Off, Floating Point — 95 (Default) 95 deg 24 VAC/DC 3 1.08 ●
LRX24-SR LR030 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 24 VAC/DC 3 1.08 ●
LRX24-PC LRXX0† 0-20 V Phasecut 2-10 VDC 95 (Default) 95 deg 24 VAC/DC 3 1.08 ●
LRX24-MFT LR100 2-10 VDC (Default) 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 3 1.08 ●
LRX24-MFT95 LRXX0† 0 to 135 Ohm 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 3 1.08 ●
LRX120-3 LR060 On/Off, Floating Point — 95 (Default) 95 deg 120-240 VAC 3 1.08 ●
LRX120-SR LR450 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 120-240 VAC 3 1.08 ●
180
in-lb
[20
Nm] ARX24-3 AR000 On/Off, Floating Point — 95 (Default) 95 deg 24 VAC/DC 5 1.08 ●
ARX24-SR AR030 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 24 VAC/DC 5 1.08 ●
ARX24-PC ARXX0† 0-20 V Phasecut 2-10 VDC 95 (Default) 95 deg 24 VAC/DC 5 1.08 ●
ARX24-MFT AR100 2-10 VDC (Default) 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 5 1.08 ●
ARX24-MFT95 ARXX0† 0 to 135 Ohm 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 5 1.08 ●
ARX120-3 AR060 On/Off, Floating Point — 95 (Default) 95 deg 120-240 VAC 5 1.08 ●
ARX120-SR AR450 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 120-240 VAC 5 1.08 ●† For correct code please call Belimo Customer service 800-543-9038
Configuration(Substitute ‘V’ for ‘P’ for
NV[F] actuators)Code
Control MotionList Price
Input Range Position Feedback Running Time† Torque % Adaptation
Volta
ge
P-10001 A01 2.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●*P-10002 A02 0.0 to 10.0 VDC 0.0 to 10.0 VDC 150 100 Manual ●
P-10003 A03 2.0 to 10.0 VDC 0.0 to 5.0 VDC 150 100 Manual ●
P-10004 A04 4.0 to 7.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10005 A05 6.0 to 9.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10006 A06 10.5 to 13.5 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10007 A07 0.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10009 A09 5.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10010 A10 5.0 to 10.0 VDC 0.0 to 10.0 VDC 150 100 Manual ●
P-10013 A13 0.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10015 A15 2.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10016 A16 2.0 to 6.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10017 A17 6.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10018 A18 14.0 to 17.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10020 A20 9.0 to 12.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10028 A28 0.0 to 10.0 VDC 0.0 to 10.0 VDC 100 100 Manual ●
P-10031 A31 0.0 to 4.0 VDC 2.0 to 10.0 VDC 150 100 Manual ●
P-10063 A63 0.5 to 4.5 VDC 0.5 to 4.5 VDC 150 100 Manual ●
P-10064 A64 5.5 to 10.0 VDC 5.5 to 10.0 VDC 150 100 Manual ●
PWM
P-20001 W01 0.59 to 2.93 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20002 W02 0.02 to 5.00 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20003 W03 0.10 to 25.50 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20004 W04 0.10 to 25.60 sec. 2.0 to 10.0 VDC 150 100 Manual ●
P-20005 W05 0.10 to 5.20 sec. 0.0 to 5.0 VDC 150 100 Manual ●
Floa
ting
Poin
t P-30001 F01 Floating point 2.0 to 10.0 VDC 150 100 Manual ●
P-30002 F02 Floating point 0.0 to 10.0 VDC 150 100 Manual ●
P-30003 F03 Floating point 2.0 to 10.0 VDC 100 100 Manual ●
P-30004 F04 Floating point 0.0 to 5.0 VDC 100 100 Manual ●
P-30005 F05 Floating point 0.0 to 10.0 VDC 100 100 Manual ●
P-30006 F06 Floating point 0.0 to 5.0 VDC 150 100 Manual ●
On/O
ff
P-40001 J01 On/Off None 75 100 Manual ●
P-40002 J02 On/Off 2.0 to 10.0 VDC 150 100 Manual ●
P-40003 J03 On/Off None 75 100 Manual ●
P-40004 J04 On/Off 0.0 to 5.0 VDC 100 100 Manual ●
P-40005 J05 On/Off 0.0 to 10.0 VDC 100 100 Manual ●*P-10001 is the default confi guration.
MFT Programming Codes, Flexible Products
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
100
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Name _______________________________________________________________________________
Company ____________________________________________________________________________
Address _____________________________________________________________________________
City _______________________________________ State _____________Zip _____________________
Phone _____________________________________ Fax _______________________________________
Email _____________________________________
FIELD LABELING: LBL-MFT
❑ Custom configuration labels required 1-3/8” X 1-¼” orange labels preprinted to your specifications 12 label sets per sheet. Includes configuration code and wiring labels.
#1 Select an Actuator(use one sheet for each unique actuator/configuration)
Quantity❑ AF24-MFT US ______❑ AF24-MFT-S US ______❑ NF24-MFT US ______❑ LF24-MFT US ______❑ LF24-MFT-S US ______❑ AF24-MFT95 US ______❑ NV24-MFT US ______❑ NVF24-MFT US ______❑ NVF24-MFT-E US ______❑ NVFD24-MFT US ______❑ NVFD24-MFT-E US ______❑ GMX24-MFT ______❑ GMX24-MFTX1 ______
(-S=Auxiliary Switch)
Quantity❑ AMX24-MFT ______❑ AMX24-MFTX1 ______❑ NMX24-MFT ______❑ NMX24-MFTX1 ______❑ LMX24-MFT ______❑ LMX24-MFTX1 ______❑ LRX24-MFT ______❑ GMX24-MFT95 ______❑ AMX24-MFT95 ______❑ NMX24-MFT95 ______❑ LMX24-MFT95 ______❑ LHX24-MFT ______❑ LUX24-MFT ______
#2 gCreate a Custom Configuration
1 Angle of rotation setting
Deactivated (Default) The following settings - refer to the full angle of rotation of 95º.
Activated The following settings - are automatically adapted to the effectivemechanical angle of rotation.
Manual triggering by pressing the push button twice.
Automatic triggering each time the unit is powered upor by pressing the push button twice.
2 Control Types
VDC PWM Floating Point On/Off
2 – 10 0.2 to 5.0 seconds
0 – 10 0.1 to 25.5 seconds
Variable 0.59 to 2.93 seconds
Start . Variable
Stop . Start .
Stop .
3 Feedback Signals U5
Position Feedback U DC 2...10 V (Default)
Position Feedback U DC 0...10 V
Position Feedback U Start DC . V (0...8 V) The finish mustbe at least 2 V above the start!Finish DC . V (2...10 V)
4 Running Time
150 seconds (Default)
Running time seconds (75...300 seconds) (in 5 second increments)
Note: The sound power level [dB(A)]increases when the running timeis below 150 seconds.
LM 35…150 secondsNM 45…170 secondsAM 90…300 secondsGM 90…300 secondsOthers 75…300 seconds
5 Override control andelectronic angle ofrotation limiting
Min. (min. position) = % (0...100%) (beginning of working range) default 0
ZS (intermediate position) = % (0...100%) (0% = Min.; 100% = Max.) default 50
Max. (max. position) = % (0...100%) (end of working range) default 100
Custom MFT Confi guration Order FormFAX: USA Toll Free 1-800-228-8283
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
101
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.Actuator/Valve Specifi cation
Section 230900 – INSTRUMENTATION AND CONTROL FOR HVACPART 1 – GENERAL
The following addition should be made to 1.2.B.
1.2 SUMMARY
B. Related Sections include the following:3. Division 23 Section “Hydronic Piping” for requirements for piping
packages for control valves.
The following replaces the noted specification sections, except as noted.
2.15 ACTUATORS
A. Electronic Damper Actuators: 1. Manufactured, brand labeled or distributed by BELIMO.2. Size for torque required for damper seal at load conditions. 3. Coupling: V-bolt dual nut clamp with a V-shaped, toothed cradle. 4. Mounting: Actuators shall be capable of being mechanically and
electrically paralleled to increase torque if required. 5. Overload Protection: Electronic overload or digital rotation-sensing
circuitry without the use of end switches to prevent any damage tothe actuator during a stall condition.
6. Fail-Safe Operation: Mechanical, spring-return mechanism 7. Power Requirements (Spring Return): 24 [120] [230] V ac,
maximum 10 VA at 24-V ac or 8 W at 24-V dc.8. Proportional Actuators shall be fully programmable. Control input,
position feedback and running time shall be factory or fieldprogrammable by use of external computer software Diagnosticfeedback shall provide indications of hunting or oscillation,mechanical overload and mechanical travel. Programming shall bethrough an EEPROM without the use of actuator mountedswitches.
9. Temperature Rating: -22 to +122ºF -30 to +50ºC [-58 to +122ºF -50 to +50ºC]
10. Housing: Minimum requirement NEMA type 2 (4/4X) / IP54 (IP67) mounted in any orientation.
11. Agency Listing: ISO 9001, cULus, and CSA C22.2 No. 24-93.12. The manufacturer shall warrant all components for a period of 5
years from the date of production, with the first two yearsunconditional.
B. Electronic Valve Actuators:1. Manufactured, brand labeled or distributed by BELIMO.2. Size for torque required for valve close off at 150 percent of total
system (head) pressure for two-way valves; and 100 percent ofpressure differential across the valve or 100 percent of total system(pump) head differential pressure for three-way valves.
3. Coupling: Directly couple end mount to stem, shaft, or ISO-style direct-coupled mounting pad.
4. Mounting: Actuators shall be capable of being mechanically and electrically paralleled to increase torque if required.
5. Overload Protection: Electronic overload or digital rotation-sensing circuitry without the use of end switches to deactivate the actuatorat the end of rotation.
6. Fail-Safe Operation: Mechanical, spring-return mechanism. Internal chemical storage systems, capacitors, or other internalnon-mechanical forms of fail-safe operation are not acceptable.
7. Power Requirements: Maximum 10 VA at 24-V ac or 8 W at 24-V dc.
8. Maximum 1 VA at 24-V ac or 1 W at 24-V dc.9. Temperature Rating: -22 to +122ºF -30 to +50ºC [-58 to +122ºF
-50 to +50ºC].10. Housing: Minimum requirement NEMA type 2 / IP54 mounted in
any orientation.11. Agency Listing: ISO 9001, cULus, and CSA C22.2 No. 24-93.12. The manufacturer shall warrant all components for a period of 5
years from the date of production, with the first two years unconditional.
C. Terminal Unit Actuators:1. Manufactured, brand labeled or distributed by BELIMO.2. Close-Off (Differential) Pressure Rating: 200 psi.3. Coupling: V-bolt dual nut clamp with a V-shaped, toothed cradle or
an ISO-style direct-coupled mounting pad.4. Power Requirements: 24V-ac/dc.5. Temperature Rating: -22 to +122ºF -30 to +50ºC.6. Housing Rating: Minimum UL94-5V(B) flammability.7. Agency Listing: CE, UL 60730-1A/-2-14, CAN/CSA E60730-1,
CSA C22.2 No. 24-93, CE according to 89/336/EEC.8. The manufacturer shall warrant all components for a period of 5
years from the date of production, with the first two years unconditional.
D. Industrial Actuators (ONLY TO BE USED WITH 2.16.I Butterfly Valves – Resilient Seat and 2.16.J Butterfly Valves – High Performance.)1. Manufactured, brand labeled or distributed by BELIMO.2. The combination of valve and actuator shall meet the close-off
requirements as specified in Section 2.16.H – Butterfly Valves.3. Coupling: ISO 5211 mounting standards.4. Overload Protection: A self resetting thermal switch embedded in
the motor. 5. Manual Override: Actuator shall be equipped with a hand wheel or
shaft for manual override to permit operation of the actuator in theevent of an electrical power failure
6. Power Requirements: 24VAC [120VAC] [230VAC] 1 pH.7. Auxiliary Switches: 2 SPDT rated 3A at 250 VAC.8. Temperature Rating: -22 to +150ºF -30 to +65ºC.9. Housing: Minimum requirement NEMA type 4X/ IP67 with an
industrial quality coating. Actuator shall have an internal heater toprevent condensation within the housing. A visual indicationbeacon shall indicate position status of the device.
10. Agency Listing: ISO, CE, CSA11. The manufacturer shall warrant for 2 years from the date of
production.
2.16 CONTROL VALVES
A. Manufacturer:1. Manufactured, brand labeled or distributed by BELIMO.
B. Control Valves: Factory fabricated of type, body material, and pressureclass based on maximum pressure and temperature rating of piping system, unless otherwise indicated.
C. The manufacturer shall warrant all components for a period of 5 yearsfrom the date of production, with the first two years unconditional(except as noted).
D. Pressure Independent Control Valves 1. NPS 2 and Smaller: Forged brass body rated at no less than 400
PSI, chrome plated brass ball and stem, female NPT union ends, dual EPDM lubricated O-rings and TEFZEL characterizing disc.
2. Accuracy: The control valves shall accurately control the flow from0 to 100% full rated flow with an operating pressure differential range of 5 to 50 PSID across the valve.
3. Flow Characteristics: Equal percentage characteristics.4. Close-Off Pressure Rating: 200 PSI.5. All actuators shall be electronically programmed by use of external
computer software for the adjustment of flow. Programming using actuator mounted switches or multi-turn actuators are not acceptable. [Actuators for 3-wire floating (tri-state) on ½” – 1” pressure independent control valves shall fail in place and have a mechanical device inserted between the valve and theactuator for the adjustment of flow.] [Actuators for two-position ½’-1” pressure independent control valves shall failin place and have a mechanical device inserted between thevalve and the actuator for the adjustment of flow.] [Actuatorsshall be provided with an auxiliary switch to prove valveposition.]
6. The actuator shall be the same manufacturer as the valve,integrally mounted to the valve at the factory with a single screw on a four-way DIN mounting-base.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
102
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Actuator/Valve Specifi cation
7. The control valve shall require no maintenance and shall not include replaceable cartridges.
8. The manufacturer shall warrant all components for a period of 5 years from the date of production, with the first two years unconditional.
9. The use of pressure independent valves piped in parallel toachieve the rated coil flow shall be permitted. Actuators shall be electronically programmed to permit sequencing the flow with asingle control output point. The use of external devices to permitsequencing is not acceptable.
10. NPS 2” and smaller pressure independent control valves for individual coil control shall be provided as part of a pipe package supplied by the valve manufacturer. The supply side of the coilshall contain an integrated isolation ball valve/manual air vent[strainer/shut-off valve/drain] with a P/T port. The return side shall contain a union fitting with a P/T port, pressure independent control valve, an integrated isolation ball valve/manual air vent with a P/T port. Shut-off valves as an integrated part of the pressureindependent control valve are prohibited. [A [12”] [24”] flexiblehose set shall be provided for each coil supply and returnconnection for all pipe packages.]
SPECIFYING PRESSURE INDEPENDENT CONTROL VALVES REQUIRE THE FOLLOWING ADDITIONS TO SECTIONS 232113 AND 230593.
To be inserted into Section 232113 – HYDRONIC PIPING
2.6 CONTROL VALVES
K. Calibrated Balancing Valves and Automatic Flow-Control Valves shallnot be required on devices where pressure independent controlvalves are installed.
To be inserted into Section 230593 – TESTING, ADJUSTING, ANDBALANCING FOR HVAC
3.11 PROCEDURE FOR HYDRONIC SYSTEMS
H. Systems installed with pressure independent control valves shall notrequire hydronic system balancing. [Flow shall be verified and adjusted for the pressure independent valve assembly (valve and actuator combination) for field conditions using thepressure independent control valve manufacturer’s documented procedure for [10%] [20%] [25%] <Insert Percentage> of the totalinstalled product. Exact locations of tested product to be coordinated with the design engineer.]
E. Characterized Control Valves: 1. NPS 2 and Smaller: Nickel-plated forged brass body rated at no
less than 400 psi, stainless steel ball and blowout proof stem,female NPT end fittings, with a dual EPDM O-ring packing design, fiberglass reinforced Teflon seats, and a TEFZEL flow characterizing disc. [NPS ¾” and Smaller for Terminal Units: Nickel plated forged brass body rated at no less than 600 psi,chrome plated brass ball and blowout proof stem, female NPTend fittings, with a dual EPDM O-Ring packing design, fiberglass reinforced Teflon seats, and a TEFZEL flow characterizing disc.]
2. NPS 2-1/2 and 3: GG25 cast iron body according to ANSI Class125, standard class B, stainless steel ball and blowout proof stem,flange to match ANSI 125 with a dual EPDM O-ring packingdesign, PTFE seats, and a stainless steel flow characterizing disc.
3. Sizing: a. Two-Position: Line size or size using a pressure differential of 1psi. b. Two-Way Modulating: [3 psig] 5 psig or twice the load pressure
drop, whichever is more. c. Three-Way Modulating: Twice the load pressure drop, but not
more than [3 psig] 5 psig.4. Close-Off Pressure Rating: 100 PSI. [NPS ¾” and Smaller for
Terminal Units: 200 PSI.]5. The actuator shall be the same manufacturer as the valve,
integrally mounted to the valve at the factory with a single screw on
a four-way DIN mounting-base.6. NPS 2” and smaller characterized control valves for individual coil
control shall be provided as part of a pipe package supplied by the valve manufacturer. The supply side of the coil shall contain astrainer/shut-off ball valve/drain [an integrated isolation ball valve/manual air vent] with a P/T port. The return side of the coil shallcontain a union fitting with a P/T port, characterized control valve, anintegrated manual balancing valve/union/isolation ball valve/manualair vent with P/T port. Shut-off valves as an integrated part of thecharacterized control valve are prohibited. [For 3-way installations, supply an integrated 100% port isolation valve/manual air ventwith a P/T port for field installation in the bypass of the circuit.] [A [12”] [24”] flexible hose set shall be provided for each coil supply and return connection for all pipe packages.]
F. Steam system characterized control valves shall have the followingcharacteristics:
1. NPS 1 and Smaller: Nickel-plated forged brass body rated at noless than 600 psi, stainless steel ball and blowout proof stem,female NPT end fittings, with a dual EPDM O-ring packing design,fiberglass reinforced PTFE Teflon seats, and a PTFE Teflon flowcharacterizing disc.
2. Sizing: 15PSIG or less inlet steam pressure.a. Two-Position: Line size or sized using 10% of inlet gauge
pressure.b. Modulating: Pressure drop shall be 80% of inlet gauge
pressure. 3. Close-Off Pressure Rating: 200 PSI. 4. The actuator shall be the same manufacturer as the valve,
integrally mounted to the valve at the factory with a single screw on a four-way DIN mounting-base.
5. Flow Characteristics: Equal percentage characteristics.
G. Hydronic system globe valves shall have the following characteristics:1. NPS 2 and Smaller: ANSI Class 250 bronze body, stainless steel
stem, brass plug, bronze seat, and a TFE packing.2. NPS 2-1/2 and Larger: ANSI Class 125 [250] cast iron body,
stainless steel stem, bronze plug, bronze seat, and a TFE V-ring packing.
3. Sizing: a. Two-Position: Line size or size using a pressure differential of 1 psi.b. Two-Way Modulating: [3 psig] 5 psig or twice the load pressure
drop, whichever is more.c. Three-Way Modulating: Twice the load pressure drop, but not
more than [3 psig] 5 psig.4. Flow Characteristics: Two-way valves shall have equal percentage
characteristics; three-way valves shall have linear characteristics.5. Close-Off Pressure Rating: Combination of actuator and trim shall
provide minimum close-off pressure rating of 150 percent of totalsystem head pressure for two-way valves and 150 percent of the design pressure differential across the three-way valves.
6. Two- and three-way globe valves shall be used only if characterized control valves do not fit the sizing criteria orapplication.
H. Steam system globe valves shall have the following characteristics:1. NPS 2 and Smaller: ANSI Class 250 bronze body; stainless steel
seat, stem and plug; and a TFE packing.2. NPS 2-1/2 and Larger: ANSI Class 125 [250] cast iron body;
stainless steel seat, stem and plug; and a TFE V-ring packing.3. Sizing:
a. Two-Position: Line size or sized using 10% of inlet gaugepressure.
b. Modulating: 15 PSIG or less inlet steam pressure, the pressure drop shall be 80% of inlet gauge pressure. Higher than 15PSIG inlet steam pressure the pressure drop shall be 42% ofthe inlet absolute pressure.
4. Flow Characteristics: Linear or equal percentage characteristics.5. Close-Off Pressure Rating: Combination of actuator and trim shall
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
103
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.Actuator/Valve Specifi cation
provide minimum close-off pressure rating of 150 percent of operating (inlet) pressure.
I. Butterfly Valves – Resilient Seat: 1. NPS 2 to 12: Valve body shall be full lugged cast iron 200 psig
body with a 304 stainless steel disc, EPDM seat, extended neck and shall meet ANSI Class 125/150 flange standards. Disc-to-stem connection shall utilize an internal spline. The shaft shall be supported at four locations by RPTFE bushings.
2. NPS 14 and Larger: Valve body shall be full lugged cast iron 150 psig body with a 304 stainless steel disc, EPDM seat, extended neck and shall meet ANSI Class 125/150 flange standards. Disc-to-stem connection shall utilize a dual-pin method to prevent the disc from settling onto the liner. The shaft shall be supported at four locations by RPTFE bushings.
3. Sizing: a. Two-Position: Line size or size using a pressure differential of 1
psi.b. Modulating: [3 psig] 5 psig or twice the load pressure drop,
whichever is more. Size for the design flow with the disc in a 60-degree-open-position with the design velocity less than 12 feet per second.
4. Close-Off Pressure Rating: NPS 2-12” 200 psi bubble tight shut-off. NPS 14 and larger, 150 psi bubble tight shut-off.
J. Butterfly Valves – High Performance: 1. Valve body shall be full lugged carbon steel ANSI Class 150 [300]
body with a 316 stainless steel disc without a nylon coating, RTFE seat, and be ANSI Class 150300 flange standards. Blowout-proof shaft shall be 17-4ph stainless steel and shall be supported at four locations by glass-backed TFE bushings. Valve packing shall beChevron TFE and shall include fully adjustable packing flange andseparable packing gland. Valve body shall have long stem design to allow for 2” insulation (minimum). Valve face-to-face dimensionsshall comply with API 609 and MSS-SP-68. Valve assembly shall be completely assembled and tested, ready for installation.
2. Sizing: a. Two-Position: Line size or size using a pressure differential of 1
psi.b. Modulating: [3 psig] 5 psig or twice the load pressure drop,
whichever is more. Size for the design flow with the disc in a 60-degree-open-position with the design velocity less than 32 feet per second.
3. Flow Characteristics: Modified equal percentage, unidirectional.4. Close-Off Pressure Rating: 150 [285] psi bubble tight shut-off.5. Media Temperature Range: ANSI Class 150 [300] limitations.6. Max Differential Pressure: 285 psi @ 100 deg F for ANSI 150 (725
psi @ 100 deg F for ANSI 300).
K. Zone Valves (On/Off Two-Position Applications):1. NPS 1 and Smaller: Forged brass body rated at no less than 300
psi, stainless steel stem, female, NPT union or sweat with astainless steel stem and EPDM seals.
2. Sizing: a. Two-Position: Line size or size using a pressure differential of 1 psi.
3. Close-Off Pressure Rating: Combination of actuator and trim shall provide minimum close-off pressure rating of 150 percent of totalsystem head pressure for two-way valves and 125 percent of the design pressure differential across the three-way valves.
4. The actuator shall be the same manufacturer as the valve, integrally mounted to the valve at the factory.
5. The manufacturer shall warrant all components for a period of 2years from the date of production.
6. All zone valves for individual coil control shall be provided as part of a pipe package supplied by the valve manufacturer. The supply side of the coil shall contain a strainer/shut-off ball valve/drain [an integrated 100% port isolation valve/manual air vent] with a P/Tport. The return side of the coil shall contain a union fitting with a P/T port, zone valve, an integrated manual balancing valve/union/isolation ball valve/manual air vent with P/T port. Shut-off valves as an integrated part of the zone valve are prohibited. [A [12”] [24”]flexible hose set shall be provided for each coil supply and return connection for all pipe packages.]
To be inserted into Section 233300 – AIR DUCT ACCESSORIES
2.8 SMOKE DAMPERS
Replace with the following:
I. Damper Motors:1. Manufactured, brand labeled or distributed by BELIMO.2. Size for torque required for damper seal at load conditions with one
actuator per damper section. Mechanically paralleled or‘piggybacked’ actuators are not permitted.
3. Coupling: V-bolt dual nut clamp with a V-shaped toothed cradle. Aluminum clamps or set screws are not acceptable.
4. Overload Protection: Microprocessor or an electronic based motor controller providing burnout protection if stalled before full rotation is reached. The actuator shall be electronically cut off at full open to eliminate noise generation with the holding noise level to beinaudible.
5. Power Requirements: 0.23A (running) and 0.09A (holding) at 24V-ac or 27 VA (running) and 10 VA (holding) at 120V-ac.
6. Actuator timing shall be15 sec [75 sec] [local codes]. 7. Temperature Rating: Actuator shall have a UL555S listing by the
damper manufacturer for 350ºF [250ºF].8. [Proportional Smoke Damper Actuators shall meet all
requirements specified above and shall modulate 0-100% openin response to a 2-10vdc or 4-20mA control signal. A 2-10vdc feedback output shall provide a 2-10vdc signal for position indication.a. Power Requirements (Proportional): Maximum (running) 12
VA at 24-V ac or 8 W at 24-V dc. Maximum (holding) 5VA at 24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall beprovided for override operation of the actuator on a loss ofpower.]
9. [Balancing Smoke Damper Actuators shall meet all requirements specified above and shall include an integral adjustable maximum opening potentiometer for airflowadjustment. a. Power Requirements (Balancing): Maximum (running) 9.5
VA at 24-V ac or 6 W at 24-V dc. Maximum (holding) 5VA at 24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall beprovided for override operation of the actuator on a loss ofpower to the actuator.]
The following replaces item 2.8.K.1
1. Auxiliary switches for [signaling] [fan control] [or] [positionindication].
2.9 COMBINATION FIRE AND SMOKE DAMPERS
O. Damper Motors:1. Manufactured, brand labeled or distributed by BELIMO.2. Size for torque required for damper seal at load conditions.3. Coupling: V-bolt dual nut clamp with a V-shaped toothed cradle.
Aluminum clamps or set screws are not acceptable.4. Overload Protection: Microprocessor or an electronic based motor
controller providing burnout protection if stalled before full rotation is reached. The actuator shall be electronically cut off at full open to eliminate noise generation with the holding noise level to beinaudible.
5. Power Requirements: 0.23A (running) and 0.09A (holding) at 24V-ac or 27 VA (running) and 10 VA (holding) at 120V-ac.
6. Actuator timing shall be 15 sec [75 sec] [local codes]. 7. Temperature Rating: Actuator shall have a UL555S and UL555S
listing by the damper manufacturer for 350ºF [250ºF].8. [Proportional Combination Fire and Smoke Damper Actuators
shall meet all requirements specified above and shall
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
104
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Actuator/Valve Specifi cation
modulate 0-100% open in response to a 2-10vdc or 4-20mA controlsignal. A 2-10vdc feedback output shall provide a 2-10vdc signal for position indication.a. Power Requirements (Proportional): Maximum (running) 12 VA at
24-V ac or 8 W at 24-V dc. Maximum (holding) 5VA at 24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall beprovided for override operation of the actuator on a loss of power.]
9. [Balancing Combination Fire and Smoke Damper Actuators shallmeet all requirements specified above and shall include an integraladjustable maximum opening potentiometer for airflow adjustment. a. Power Requirements (Balancing): Maximum (running) 9.5 VA at
24-V ac or 6 W at 24-V dc. Maximum (holding) 5VA at 24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall beprovided for override operation of the actuator on a loss of power to the actuator.]
The following replaces item 2.9.Q.1
1. Auxiliary switches for [signaling] [fan control] [or] [position indication].2. Housing: Steel housing, aluminum is unacceptable.3. Agency Listing: ISO 9001, UL873, or UL60730. 4. The manufacturer shall warrant all components for a period of 5 years
from the date of production, with the first two years unconditional.
NOTE TO SPECIFIER
Any (or all) of the following manufacturers are listed per UL555S with Belimo actuators: Air Balance, Arlan, E.H. Price, Greenheck, Leader, Lloyd Industries, Nailor, Pottorff, Prefco, Ruskin and Safe-Air.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
105
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.Terms and Conditions of Sale of Warranty
I. General1.1. The following Terms and Conditions of Sale (“Terms”) apply to the sale of products described in this Product Guide (“Products”). As used herein, “Seller” or “Belimo” refers to Belimo Aircontrols (USA) Inc. or Belimo Aircontrols (CAN) Inc., as applicable, and “Client” refers to the individual or business entity that purchases theProducts from Seller. These Terms shall apply unless the parties mutually agree to different terms and memorialize such agreement in a writing signed by both Client and Seller.
II. Price2.1. The Seller’s price for Products (the “Price”) is net, F.O.B. Point of Origin, and is calculated in US currency for sales made by Belimo Aircontrols (USA), Inc. and calculated in Canadian currency for sales made by Belimo Aircontrols (CAN) Inc.2.2. The Price, unless otherwise agreed upon, does not include freight and packaging (wooden crates, pallets, etc), the costs ofwhich will be charged to Client at cost for each shipment and shallbe payable with payment of the Price.2.3. Orders for Products with a net value of less than US$300 (CAN$450) will be subject to a US$20 (CAN$35) handling fee (the “Handling Fee”). The Handling Fee will not be charged for ordersof Products with a net value equal to or greater than US$300 (CAN$450) or for Products ordered through Seller’s internet order-ing system at: www.belimo.com.2.4. Seller reserves the right to make partial deliveries of orders of Products, each of which deliveries may be invoiced separately by Seller.2.5. The Price does not include charges for wiring diagrams, instal-lation, and commissioning, which will be charged to Client sepa-rately and will be payable on demand.
III. Payment3.1. Invoices are payable in US currency for sales made by Belimo Aircontrols (USA), Inc. and in Canadian currency for sales made by Belimo Aircontrols (CAN) Inc. and are due no later than 30 days from the date of invoice, without any deductions.3.2. If Client fails to pay the entire invoice balance within 60 days from the date of the invoice, Client will be subject to an interest charge of 2% per month (or the maximum rate permitted by law, whichever is less) on the outstanding unpaid balance due to Seller.3.3. Clients who maintain outstanding balances for 45 days or more after the date of invoice may be subject to restricted shipments of Products or may be required to pay for all future deliveries ofProducts on a cash-on-delivery basis.
IV. Title and Risk4.1. Title to all Products shall remain with Seller and shall not pass to Client until Seller has received full payment for the Products.
V. Damage or Loss in Transit5.1. Seller assumes no liability for damage or loss of shipment of Products, which risk shall at all times remain with the carrier. All shipments must be unpacked and examined by Client immediately upon receipt. Any external evidence of loss or damage must benoted on the freight bill accompanying the shipment of Products or carrier’s receipt and signed by the carrier’s agent at the time ofdelivery. Failure to do so will result in the carrier’s refusal to honorany claim relating to damage of Products. Client must also notify Seller of such damage by providing Seller with a copy of the freightbill or damage report so that Seller can file a claim for loss or dam-age in transit with the carrier. If the damage does not become apparent until the shipment is unpacked, customer must make arequest for inspection by the carrier’s agent and file with the carrier within 15 days after receipt of product and notify Seller of the same.Seller is not liable for consequential damage to Client’s property ora third-party’s property resulting from the installation of damaged Products.
VI. Delivery 6.1. Seller undertakes to make every attempt to adhere to its stated
delivery parameters and to make a timely delivery of the Productsbut does not guarantee any delivery specifications. Each contract entered into for the purchase of Products is not cancelable nor is Seller liable for any direct or indirect losses that may arise, for anyreason whatsoever, due to Seller’s failure to meet any stated orassumed delivery schedules.
VII. Return of Goods 7.1. Products received by Client cannot be returned unless: (i)
Client alerts Seller that it intends to return such Products, (ii) Selleragrees to accept the return of such Products, (iii) Client obtains a Return Material Authorization (“RMA”) number from Seller for thereturn of such Products, and (iv) Client follows all return instruc-tions provided by the Seller. The RMA number must be clearly written on the outside of all packaging for any returned Products. Only Products returned to proper the location as instructed bySeller and identified with an RMA number will be considered for credit.
7.2. Only Products that are returned in original packaging may be accepted for return. Such returned Products must be received in good condition, adequate for resale as new Products to qualify forcredit. Client will be responsible for payment of a restocking chargefor all returned Products in an amount no less than 20% of the invoice value of the Products (“Restocking Charges”). All return Products must be shipped to Seller at Client’s cost.
7.3. Returns that result from Seller errors will be credited in full and will not be subject to Restocking Charges.
VIII. WarrantyVIII.A 5-year Warranty 8.1. Products that are listed in this Product Guide as carrying a
5-year warranty and shipped after May 1, 2000 to a location in theUnited States or Canada shall carry a 5-year warranty. The 5-year warranty is unconditional for the first two years from the date of production of the Products. After the first two years from the dateof Production, the warranty shall be conditional and the warranty coverage shall not apply to damage to Products caused by ordi-nary wear and tear, negligence or improper use by Client, or other causes beyond the control of the Seller. Product -specific terms of warranty with regard to warranty period or conditions of warranty may apply to certain specified Products as stated in the documen-tation for those Products.
VIII.B 2-year Conditional warranty 8.2. Products that are listed in this Product Guide as carrying a
2-year warranty and shipped after May 1, 2005 to a location in theUnited States or Canada shall carry a 2-year warranty. The 2-year warranty is conditional and the warranty coverage shall not apply to damage to Products caused by ordinary wear and tear, negli-gence or improper use by Client, or other causes beyond the con-trol of the Seller. Product -specific terms of warranty with regard to warranty period or conditions of warranty may apply to certain specified Products as stated in the documentation for those Products.
VIII.C General Warranty Terms 8.3. Seller’s warranty may be null and void in the event of any: (a)
modification or unauthorized repairs of Products by Client, (b)unauthorized incorporation or integration of Products into or with Client’s equipment, (c) use of Products in an unauthorized manner,or (d) damage to Products not caused by Seller.
8.4. Client must promptly notify Seller of Products’ alleged defect and provide Seller with other evidence and documentation reason-ably requested by Seller. Before removing Products from service, Client should contact a Seller-authorized support technician bycalling Belimo customer service. The contact information for Belimo customer service is listed on the back page of Belimo’s
( ) yProduct Guide and Price List (“PGPL”) or may be found at www.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
106
L300
34 -
07/0
9 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
Terms and Conditions of Sale of Warranty
belimo.com. Belimo customer service will work with field techni-cians to troubleshoot problems. Many problems can be resolvedover the phone.
8.5. If a problem cannot be resolved over the phone, an RMA num-ber will be issued by Seller for return of the Products. Prior toreturning any Products under a warranty, Client must obtain an RMA number from Seller, along with shipping instructions for the return. The RMA number must be clearly written on the outside of the box containing the returned Products. Only Products returned to the proper location and identified with an RMA number will beaccepted by the Seller.8.6. All returned Products should be packaged appropriately to prevent further damage. Seller reserves the right to refuse any returned material if improperly packaged or labeled (without an RMA number). Products returned without proper RMA documenta-tion will void Seller’s warranty.
8.7. Products found to be defective for which a warranty is appli-cable will either be replaced or repaired at the Seller’s discretion.Seller is not responsible for charges that Client may incur as aresult of the removal or replacement of Products.
8.8. Repaired or replacement Products are shipped from Seller via ground shipment. Other shipping methods are available at the sole expense of the Client.
8.9. Repaired, replaced or exchanged Products will carry a war-ranty for a period of time equal to the greater of: (i) the remainder of the original 5-year warranty or 2-year warranty that was appli-cable to the repaired, replaced or exchanged Products, or (ii) six months, effective from the date the repaired, exchanged orreplaced Products are shipped by Seller (the “Replacement Warranty Period”).
8.10. Advanced replacement Products for Products covered under warranty may be obtained from Seller after the Belimo customer service troubleshooting process has been completed. For indus-trial products (such as butterfly valves), a purchase order is required. The purchase order will be credited upon the receipt and verification by Seller of the returned defective Products. For non-industrial products, an invoice will be issued and shall be due andpayable is the returned Products are not received by Seller within 60 days from the date of that the replacement Products are shipped. Additional charges may apply if the nature of the problem has been misrepresented by Client.
8.11. Both the conditional and unconditional warranties cover the Products only, and do NOT cover labor associated with the trouble-shooting, removal or replacement of such Products.
8.12. New Products ordered in an attempt to circumvent the war-ranty process may NOT be reimbursed if, upon receipt of returned Products, it is determined that the defect in the returned Products is actually field related, or the Products have been returned for cosmetic reasons only.
8.13. Advanced replacement Products for butterfly valve actuators may not be new, but have been verified by the Seller for electrical and mechanical operation. Such Products carry the full warranty for the entire Replacement Warranty Period.
IX. No Warranty for Non-HVAC Application 9.1. All Seller warranties shall extend only to HVAC use of the
Products. If Products are used in non-HVAC application (e.g., air-craft, industrial processes, etc.), Seller’s warranties shall not cover such Products. Client will be solely responsible for any damage to or malfunction of Products or for any damage resulting from such use of Products.
X. Liability Disclaimer 10.1. These Terms constitute the entire understanding and agree-
ment between Seller and Client regarding the warranties that coverProducts and supersedes all previous understandings, agree-ments, communications and representations. Seller shall not be responsible for and Client does not have any right to make any claim for, damage that occurs to any property other than Products.
Seller shall in no way be responsible for any costs incurred by Client in the determination of the causes of damage to any of Client’s property, for expert opinions, or for any punitive or special,incidental or consequential damages of any kind whatsoever.
10.2. Seller shall not be liable for any damage resulting from or contributed by Client or third parties acting within the scope of responsibility of Client or such third party when:
1. Products are used for non-HVAC applications, such as in air-crafts, industrial processes, etc.;
2. Client uses the Products without complying with applicable law or institutional regulations or Belimo data and installation sheets or Client uses the Products without following goodindustry practice;
3. Products are used by personnel who have not received suitable instruction; or
4. Products are modified or repaired without the written approval of Seller.
When requested to do so, Client shall immediately release Seller in full from any possible third party claims resulting in connection with the circumstances listed above. This also applies to claims inconnection with product liability.
10.3. If Client becomes aware that any third party has made or appears likely to make any claim regarding Products (including,without limitation, regarding Product defects or rights infringed by Products), then Client shall immediately inform Seller and afford to Seller all assistance that Seller may require to enforce its rights anddefend such claim.
XI. Proper Law and Jurisdiction 11.1. All sales of Products under these Terms and the warranties
described herein shall be governed by the laws of the State of Connecticut, and the parties agree to submit to the exclusive juris-diction of the Federal and state courts located in the State of Connecticut with respect to any dispute arising from the subjectmatter hereof. The parties hereby waive all rights to a jury trial inconnection with any claims relating to the subject matter hereof.
ACR Supply Company Inc.2719 Hillsborough RoadDurham, NC 27705Phone: 919-286-2228With branches in NC
Aireco Supply9120 Washington BoulevardSavage, MD 20763-0414Phone: 301-953-8800With branches in MD, VA
Amcon Controls, Inc.11906 Warfield StreetSan Antonio,TX 78216Phone: 210-349-6161With a branch in Houston, TX
Applied AutomationA Wilson Mohr Company3186 South Washington Street, #230Salt Lake City, UT 84115Phone: 801-486-6454
Boston Aircontrols, Inc.8 Blanchard RoadBurlington, MA 01803Phone: 781-272-5800
Charles D. Jones Co.445 Bryant Street, Unit #1Denver, CO 80204-4800Phone: 800-777-0910With branches in CO, MO, KS
Climatic Control Div/ICD5061 W. State StreetMilwaukee, WI 53208Phone: 800-242-1656With branches in WI
Cochrane Supply and Engineering, Inc.30303 Stephenson HighwayMadison Heights, MI 48071-1633Phone: 800-482-4894With branches in MI and Maumee, OH
Columbus Temperature Control1053 E. 5th AvenueColumbus, OH 43201Phone: 800-837-1837
Controlco5600 Imhoff Drive, Suite GConcord, CA 94520Phone: 925-602-7728With branches in CA, NV
Edward C. Smyers & Co.223 Fort Pitt BoulevardPittsburgh, PA 15222-1505Phone: 412-471-3222
Engineered Control Systems4805 N.W. 79th AvenueSuite 11Miami, FL 33166Phone: 305-418-8901With branches in FL
First Source Distributors, LLC710 Peninsula Lane, Suite ECharlotte, NC 28273Phone: 800-670-5977
G & O Thermal Supply5435 N. Northwest HighwayChicago, IL 60630Phone: 773-763-1300With branches in IL
Industrial Controls Distributors LLC1776 Bloomsbury AvenueWanamassa, NJ 07712Phone: 800-631-2112With branches inGA, KY, IN, MA, ME, NC, NY, OH, PA, TN
Interstate HVAC Controls30 Vineland StreetBrighton, MA 02135 Phone: 617-782-9000
Jackson Controls1708 E. 10th StreetIndianapolis, IN 46201Phone: 317-231-2200
M & M Controls9E West Aylesbury RoadTimonium, MD 21093Phone: 410-252-1221With a branch in Alexandria, VA
MICONTROLS, Inc.6516 5th Place SouthSeattle, WA 98124Phone: 800-877-8026With branches in WA, OR
Meier Supply123 Brown StreetJohnson City, NY 13790 Phone: 607-797-7700With branches in NY, PA
Minvalco, Inc.3340 Gorham AvenueMinneapolis, MN 55426-4267Phone: 952-920-0131With branches in MN
RSD/Refrigeration Supply Distribution 26021 Atlantic Ocean DriveLake Forest, CA 92630Phone: 949-380-7878With branches inCA, NV, OR, AK, AZ, ID, UT, WA, MT
Saint Louis Boiler Supply, Co. 617 Hanley Industrial CourtSt. Louis, MO 63144Phone: 314-962-9242
South Side Control Supply, Co. 488 N. Milwaukee AvenueChicago, IL 60610-3923Phone: 312-226-4900With branches in IL, IN
Stromquist and Company4620 Atlanta RoadSmyrna, GA 30080Phone: 404-794-3440With a branch in Orlando, FL
Temperature Control Systems10315 Brockwood RoadDallas, TX 75238Phone: 214-343-1444With branches in OK, TX
Tower Equipment Co., Inc.1320 West Broad StreetStratford, CT 06615Phone: 800-346-4647
Twinco Supply Corporation55 Craven StreetHuntington Station, NY 11746-2143Phone: 800-794-3188With branches in NY
US
A
CA
NA
DA For a complete list of distributors
in Canada, please visit our website: www.belimo.caor call toll free: 866-805-7089
Belimo Platinum Distributors
BELIMO AmericasUSA Locations, 43 Old Ridgebury Road, Danbury, CT 06810Tel. 800-543-9038, Fax 800-228-8283, [email protected]
1675 East Prater Way, Suite 101, Sparks, NV 89434Tel. 800 987-9042, Fax 800-987-8875, [email protected]
Canada Locations, 14/16 – 5716 Coopers Avenue, Mississauga, Ontario L4Z 2E8Tel. 866-805-7089, Fax 905-712-3124, [email protected]
Latin America Customer Service, Tel. 203-791-8396, Fax 203-791-9139, [email protected]
Belimo worldwide: www.belimo.com