centum vp installation guide
DESCRIPTION
centum vp installationTRANSCRIPT
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st , 2008
July 1st , 2008
CENTUM VP Installationon XP SP2
Technology Development Dept. Development GroupGlobal Engineering CenterIndustrial Automation Business Headquarters
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Preparation
CENTUM VP Software Medium (Medium model code: LHMKM30): 1 piece
CENTUM VP Software keycode FDC (Medium model code: LHMCM30)
External DVD-ROM drive (when there is only CD-ROM drive in the PC)
For this training, copy software medium and keycode files from DVD.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Flow
Start the installation
Installation ofWindows OS
Installation of Windows Security patch
Complete the installation
Setting of Windows(Display and UPS, etc.)
Installation of CENTUM VP Software
Setting/Installing of Network(Vnet and Ethernet, etc.)
Setting after the installation(Creation of account, UPS etc.)
Installation of USB driver for OPKB
Setting IT security
The part of gray boxes are in the scope of this document
Log on as an Administrator User
Please uninstall VP after the training
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Required Hardware/Software for VP
Item CENTUM VP R4.01 HISOS Windows Vista Business Edition SP1
Windows XP Professional SP2Windows Server 2003 SP2Windows Server 2003 R2 SP2
32bit OSSP2 or later SP2
CPU Intel Core Duo 2.13GHzXeon Dual Core 2.0GHz In case of [XP, 2003 Server]:(Normal PC) Intel Pentium4 2.8GHz(Industrial PC) Intel Pentium-M 1.6GHz
More than 2GBIn case of [XP, 2003 Server]:More than 1GB
Graphic memory: Min 128MBDirectX9 with WDDM driver
Be careful if a VP upgrading potential customer wants to keep existing PC (HIS) as it is.
Memory In case of XP or 2003 Server, memory is not so critical.
Graphic Board
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Required Hardware/Software for VP
Item CENTUM VP R4.01 HISHDD More than 40GB
(Space Disk: more than 20GB)
Drive DVD-ROM drive, FD drive
-SXGA(more than 1280*1024 more, True color)
-WXGS (option)(more than 1440*900 more, True color)
MouseControl Bus Card: VF701/VI701Ethernet port
VP System S/W shall be provided in DVD
Display
Others
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Software Operating Environment
CENTUM VP uses the following software:
Support target OS– Windows XP Professional SP2– Windows Vista Business Edition SP1– Windows 2003 Server SP2– Windows 2003 Server R2 SP2
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Flow
Start the installation
Start the installation
Installation ofWindows service pack
Installation of Windows Security patch
Complete the installation
Setting of Windows(Display and UPS, etc.)
Installation of CENTUM VP Software
Setting of Network(Vnet and Ethernet, etc.)
Setting after the installation(Creation of account, UPS etc.)
Installation of USB driver for OPKB
Setting IT security
The part of gray boxes are in the scope of this document
Login as Administrator
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting of Windows
1. File System1.1 Click My computer and then select the Property of
“C “drive for example , and confirm the file system is NTFS.
2. Setting of Virtual Memory
2.1 Select Start menu -> “Control Panel” -> “System”
2.2 Select “Advanced” tab.
2.3 Press “Settings” button on Performance.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting of Windows
2.4 Select “Advanced” tab.
2.5 Select “Change” button on Virtual memory.
2.4
2.5
2.6 Set up the recommended sizethat is equivalent to 3 times of main memory to "Initial size (MB)" and "Maxim size (MB)" in "pagingfile size for each drive".
2.6
2.7 Click “OK “button
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting of Windows
3. Setting of System Property
3.1 Select “Visual Effects” tab3.2 Select “Adjust for best
performance”
3.3 Click “OK “button
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting of Windows (OP for this training)
4. Property of Panel
4.1 Select Start menu -> “Control Panel” -> “Display”
4.2 select the "Desktop" tab and set "(None)" for "Background
4.3 Open the "Screen Saver" tab and set "(None)” for "Screen Saver".
4.4 Open "Settings" tab and set "Medium (16 bit)" for "Color quality".
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting of Windows
5. Setting of Power Options
5.1 Open the Property of the system Select Start menu -> “Control Panel”-> “ Power Options ”
“Power Schemes ” tab“ Turn off monitor " -> Never“ Turn off hard disks " -> Never “ System standby " -> Never“ System hibernates " -> Never
5.2 In the “Advanced ”tab" Power button on my computer" -> "Do nothing"
5.3 In the “ Hibernate ”tab"Enable hibernation" -> Do not check.
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Flow
Start the installation
Start the installation
Installation ofWindows service pack
Installation of Windows Security patch
Complete the installation
Setting of Windows(Display and UPS, etc.)
Installation of CENTUM VP Software
Setting of Network(Vnet and Ethernet, etc.)
Setting after the installation(Creation of account, UPS etc.)
Installation of USB driver for OPKB
Setting IT security
The part of gray boxes are in the scope of this document
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Flow
Start the installation
Start the installation
Installation ofWindows service pack
Installation of Windows Security patch
Complete the installation
Setting of Windows(Display and UPS, etc.)
Installation of CENTUM VP Software
Setting of Network(Vnet and Ethernet, etc.)
Setting after the installation(Creation of account, UPS etc.)
Installation of USB driver for OPKB
Setting IT security
The part of gray boxes are in the scope of this document
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Flow
Start the installation
Start the installation
Installation ofWindows service pack
Installation of Windows Security patch
Complete the installation
Setting of Windows(Display and UPS, etc.)
Installation of CENTUM VP Software
Setting of Network(Vnet and Ethernet, etc.)
Setting after the installation(Creation of account, UPS etc.)
Installation of USB driver for OPKB
Setting IT security
The part of gray boxes are in the scope of this document
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Type
1. New InstallationThe New Installation is an installation that is newly executed to a PC in which CENTUM VP Software has not been installed. The keycode is required for the installation.
2.Version Up Installation CS3000 ---> CENTUM VPIn the Version Up Installation, the CENTUM VP Software is installed in PC in which CS3000 Software has already beeninstalled.
The keycode of CENTUM VP is required for the installation.
3. Revision Up InstallationIn the Revision Up Installation, the revision improvement of PC in which CENTUM VP has already been installed is executed. The keycode is not required when there is no additional package.
4.Re-InstallationIn the Re-Installation, the Software of the same revision is installed for repair purpose or etc. in PC in which theCENTUM VP has already been installed. The keycode of CENTUM VP is not required.
5.Add InstallationThe Add Installation is an installation that is executed for package adding purpose in PC in which the CENTUMVP has already been installed. The Software Medium of the same revision as the keycode of additional packageis required
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
Stat the Version UpInstallation
Version Up processing of CS3000 project database
Installation of CENTUM VP Software
Update of device driver
Restoration of Package Data
Backup ofPackage Data
Release of HIS automatic activation and CENTUM Desktop
Complete the Version UpInstallation
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Backup and Restoration of Package DataPackage Name Data to back up/restore
LHS1100LHM1101
Operation and Monitoring Basic Function It keeps the HIS setup information. Optionally, back up or restore the following definition. ・Trend/historical data・Set up information of HIS utility・Voice Message definition and Media Data・Context Menu definition
LHS1150 Remote Operation and Monitoring Server function Package The same as LHS1100
LHS4200 Consolidated Historical Message Viewer The Data stored in the Historical integrated server can be inherited. It requires to re-configure the storage location in each HIS.
LHS4700 Advanced Alarm Filter Package Export and Import of Alarm Filter definition are required.
LHS4800 Consolidated Alarm Management System (CAMS for HIS)
Optionally, back up/restore the following file.・CAMS configuration information
LHS6510 Long-Term Data Archive Package Inheritable by the Backup/Restore the long-term Data.
LHS6530 Report Package Inheritable by the Backup/Restore of Report definition file
LHS6600LHM6600
CS Batch 3000 Process management package No obvious referenceThe control recipe is not inherited.
LHS6710LHM6710
FCS Data setting/Acquisition Package (PICOT) Back up List of the definition Data is required.
LHS5100LHM5100
Builder basic function Back up/Restore the project database.
LHS5110 Access Control Package Re-configuration in the Access Control utility is required.(The definition is SVA so that the user can store/restore.)
LHS5150 Graphic builder The project database is inherited. (Back up the SVA file by the User)
LHS5160 CS Batch 3000 builder Back up/Restore the project database.
LHS5161 CS Batch 3000 Recipe management package Back up/Restore the recipe database.
LHS5170 FDA:21CFRpart11 support package Back up/Restore the database that was saved by FDA support.
LHS5030 C Language Development Environment Package for FCS Back up/Restore the files that were created by the User.
LFS1250 Generic Subsystem Gateway Package Back up/Restore the OPC server definition information and the Item definition information file.
LPC6900 SOE Server Backup/Restore the database of SOE server.
LPC6920 SOE Viewer Backup the configuration files.
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Data to back up while operating CS3000
1.Backup and Restoration of long-term storage DataBack up the storage Data by using the archive function of Long-Term Data Archive Package.At this time, also back up the following file and return it to the same location after changing into CENTUM VP.\\<computer name>\LTDATA\LOG\BKHLogFile.txtIt can be referred as a Retrieve Data after the version up to the CENTUM VP.
2.Backup of Report definitionCopy the definition in each Report to other Medium by using the copy function of the Report Package.
3.Backup of Advanced Alarm Filter definitionBack up the filter definition by using the export function of Alarm Filter definition.
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Data to back up while it is in an off-line state1. Database related to HIS
Backup the HIS related files such as "Voice message", "Trend", "Recipe/Control recipe" and so on.
<CS3000 installation folder>\his\database : Voice messages, etc.<CS3000 installation folder>\his\recipe : Recipes and Control
recipes<CS3000 installation folder>\his\save : Long-term, Closed data,
Scheduler, etc.<CS3000 installation folder>\his\Trend : Trend data<CS3000 installation folder>\his\spconf : Right click menu, etc.<CS3000 installation folder>\his\Media\User : Media data
The tokuchu files are located in the following folder. Please confirm to tokuchu responsible department whether tokuchu program can use these restored files after installation.
<CS3000 installation folder>\his\spconf<CS3000 installation folder>\his\user
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Data to back up while it is in an off-line state2. Backup and Restore for CAMS for HIS
Set CAMS to invalid before backup CAMS data.Backup all files located in the following folder.CAMS folder: <CS3000 installation folder>\CAMS
If CAMS historical data is not necessary, files in the following folder are unnecessary.CAMS historical data folder: <CS3000 installation folder>\CAMS\hist
Restore CAMS data before setting CAMS to enable.Copy all backuped files to <CENTUM VP installation filder>.
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Data to back up while it is in an off-line state3. When using the Access Control function, FDA function
When the “engineers' account files for referencing” specified by the Access Control utility is placed under the CS3000 installation folder, back up the files under the folder.
At that time, make a file called “EngPassword2.odc” writable. Restore the file after the installation of CENTUM VP, and reconfigure by the Access Control utility
4. FCS Data setting / Data of PICOT Acquisition Package
Back up the definition file in the following folder of this Package.<CS3000 installation folder>\his\users\save\BKUPICOT
After the installation of CENTUM VP, restore the backed up files to the following folder. <CENTUM VP installation folder>\his\users\save\BKUPICOT
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Data to back up while it is in an off-line state
5. Data of Generic Subsystem Gateway Package
Back up the definition file in the following folder of GSGW, and restore it after the Version Up.
OPC server definition information file: <CS3000 installation folder>\apcs\GPLS\BKEOPCSVRDef.csv
Item definition information file:<CS3000 installation folder>\apcs\GPLS\BKEOPCITEMDef.csv
After the installation finished,restore these back up datato the appropriated location
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
Stat the Version UpInstallation
Version Up processing of CS3000 project database
Installation of CENTUM VP Software
Update of device driver
Restoration of Package Data
Backup ofPackage Data
Release of HIS automatic activation and CENTUM Desktop
Complete the Version UpInstallation
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Release of HIS automatic activation and CENTUM Desktop
Do not Check
WindowsStandard
Select Start menu Program YOKOGAWA CENTUM HIS Utility
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
Stat the Version UpInstallation
Version Up processing of CS3000 project database
Installation of CENTUM VP Software
Update of device driver
Restoration of Package Data
Backup ofPackage Data
Release of HIS automatic activation and CENTUM Desktop
Complete the Version UpInstallation
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Update of Device Driver
Installation Control Bus Driver USB driver for OPKB
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
Stat the Version UpInstallation
Version Up processing of CS3000 project database
Installation of CENTUM VP Software
Update of device driver
Restoration of Package Data
Backup ofPackage Data
Release of HIS automatic activation and CENTUM Desktop
Complete the Version UpInstallation
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
1. Log-on as an Administrator User2. Terminate all of running applications3. Set up the Software Medium of CENTUM VP to the DVD ROM
drive. 4. Click “CENTUM VP Software” button to start the installation
of the CENTUM VP Software5. Following window comes up
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
6. CENTUM VP requires the following software..Net Framework 3.0MSXML 6.0 SP1When the above software has not been installed in , following window popped up.
7. Without setting the keycode FDC to the Floppy diskdrive, the following dialog is displayed.
Sample
Ensure ONLY Keycode FDC/USB drive is inserted
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
8. Specify the folder path in which the keycode file exists.
9. “Welcome to the Install Shield Wizard for YOKOGAWA CENTUM VP”dialog is displayed.
Click “Next“ Button
This training keycode file should be located under “C” drive directly.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
10.
11.
The dialog to input the install destination folder is displayed.
Click “Next“ Button
Enter your name and Company Name information and Click “Next” button
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
12.
13.
14.
The dialog to input ID numberis displayed.
Click “Next“ Button
Click “No” button
Click “Next” button
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
15.
16.
Click “Next“ Button
Enter your HIS station name
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
17.
18.
The dialog to confirm the description of the installation settings is displayed.Click Next to follow the instruction displayed on the screen.
Installation of VP will start.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
19. Choose “Yes”, and press “Finish”to exit the installation
VP installation is finished
Please uninstall VP after the training
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
Stat the Version UpInstallation
Version Up processing of CS3000 project database
Installation of CENTUM VP Software
Update of device driver
Restoration of Package Data
Backup ofPackage Data
Release of HIS automatic activation and CENTUM Desktop
Complete the Version UpInstallation
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Version Up processing of CS3000 project database
1.The name of TOP folder in which old CS3000 has been installed is changed to the name with “_bak”
2. After the installation of CENTUM VP, CENTUMVP folder is generated.
3. Please moved the project database prepared by ETC to the following location. (install folder)\CENTUMVP\eng\bkproject\VP_PJT
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Version Up processing of CS3000 project database3. Go through
“All programs” in the start menu -> “YOKOGAWA CENTUM”, and activate “Project's Attribution Utility”Register the project as ”Default Project” into the project list.
4. Go through “All programs” in the start menu -> “YOKOGAWA CENTUM”, and activate “System View”.Revise project information window comes.
5. After the data base has been converted to R4.01 version , below guideline window appears. This window appears when CS3000 HIS has registered.
OP
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Version Up processing of CS3000 project database
5. Click OK
<About Conversion>
All HIS database can be converted by usingHIS Database Conversion Tool from Tools menu / HIS Database Conversion Tool
CS3000 graphic file can be converted to VP Graphic file by using Graphic File Converter tool , which launch fromYOKOGAWA CENTUM / Graphic File Converter
OP
OP
6. Start “System View” from Start menu.Confirm if the CENTUM VP is installed well.After confirmation, please close “System View”.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Installation Procedure CS3000 ---> CENTUM VP
Stat the Version UpInstallation
Version Up processing of CS3000 project database
Installation of CENTUM VP Software
Update of device driver
Restoration of Package Data
Backup ofPackage Data
Release of HIS automatic activation and CENTUM Desktop
Complete the Version UpInstallation
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Restoration of Package Data
Restore the Data of each Package that is Backed up of Package Data
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Flow
Start the installation
Start the installation
Installation ofWindows service pack
Installation of Windows Security patch
Complete the installation
Setting of Windows(Display and UPS, etc.)
Installation of CENTUM VP Software
Setting of Network(Vnet and Ethernet, etc.)
Setting after the installation(Creation of account, UPS etc.)
Installation of USB driver for OPKB
Setting IT security
The part of gray boxes are in the scope of this document
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security
The Setting IT Security utility is started by clicking “Setting IT Security” in the CENTUM VP installer menu.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security
1.Select the security type appropriate to the IT operation mode,and click "Next" button.
Select this when configuring IT Security in each PC without using the Windows domain controller. The user account will be managed in each PC.
Select this when managing the user and group of the account by the Windows domain controller. It is necessary to create the group and user account by the domain controller before conducting this Setting Security.
Set the Access permission of shared file or the Connection setup of DCOM to the same Security level as the CS3000 or earlier version. Windows Firewall becomes invalid. Apply this Setting Security when connecting to other systems such as PRM, ProSafe-RS with no Security, or PC component of old revision CS3000.
In this training,select this item
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security2. All security setting items are to set to this security setting utility3. After setting, progress bar appears
4. Following window comes if the CENTUM account had existed.
5. The following dialog appears. Click "OK" button and reboot the PC.
This is the end of the Setting IT Security.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
CENTUM VP Software Installation Flow
Start the installation
Start the installation
Installation ofWindows service pack
Installation of Windows Security patch
Complete the installation
Setting of Windows(Display and UPS, etc.)
Installation of CENTUM VP Software
Setting of Network(Vnet and Ethernet, etc.)
Setting after the installation(Creation of account, UPS etc.)
Installation of USB driver for OPKB
Setting IT security
The part of gray boxes are in the scope of this document
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting after the installation
1. Setting of Windows- Creation of User Account- Setting of Windows Operating Environment- Procedure of adding SQL server account in the SOE Package
2. Setting of UPS (uninterruptible power supply) - Command for UPS Management of CENTUM VP
3. Setting of the package specific
For more specific information , please refer to the Installation Manual.
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
When the Security type is the Windows domain environment, the user account is to be created by the Windows domain controller. If necessary, by the Windows domain controller, create a user such as the one with the Operation and Monitoring authority, the one with the Engineering privilege, or the one with the privilege of OPC connection.
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
1) Log on to Windows with administrator's privilege.2) Right click “My Computer”, then choose “Manage”
from the menu. “Computer Management” window displays.3) Choose “Local Users and Groups” displayed in the left pane,
then open the “Users” folder and select a “New user” on right click menu.
Setting IT Security - Creation of user account -
1. The user account is to be created on each local PC.
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
Enter user name and their passwordto create new user
And also PW neverexpires.
User information for trainingfor Operator
User names: OPE01 Password : 012008Ope
for EngineerUser name : ENG01 Password : 012008Eng
for Engineering administratorUser names : ENGAD01 Password : 012008Engad
for MaintenanceUser names : MNT01 Password : 012008Mnt
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
User information for trainingfor Operator
User names: OPE01 Password : 012008Ope
for EngineerUser name : ENG01 Password : 012008Eng
for Engineering administratorUser names : ENGAD01 Password : 012008Engad
for MaintenanceUser names : MNT01 Password : 012008Mnt
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
User information for trainingfor Operator
User names: OPE01 Password : 012008Ope
for EngineerUser name : ENG01 Password : 012008Eng
for Engineering administratorUser names : ENGAD01 Password : 012008Engad
for MaintenanceUser names : MNT01 Password : 012008Mnt
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
User information for trainingfor Operator
User names: OPE01 Password : 012008Ope
for EngineerUser name : ENG01 Password : 012008Eng
for Engineering administratorUser names : ENGAD01 Password : 012008Engad
for MaintenanceUser names : MNT01 Password : 012008Mnt
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
2. Double Click “OPE01" user and select "Member Of" tab
3. Select Users and Click “Add” button.
User Group for trainingOPE01 : CTM_OPERATORENG01 : CTM_ENGINEER
ENGAD01 : CTM_ENGINEER_ADMAdministrator
MNT01 : CTM_MAINTENACEAdministrator
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
4.Select “Advanced” tab
5.Click “Find Now”
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
6. Select “CTM_OPERATOR “ for users group
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
7. Select other three user groups which the newly-added user for ENG01, ENGAD01 and MNT01 to belong.
User Group for trainingOPE01 : CTM_OPERATORENG01 : CTM_ENGINEERENGAD01 : CTM_ENGINEER_ADMMNT01 : CTM_MAINTENACE
This is the end of the Setting after the installation
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Setting IT Security - Creation of user account -
An account name of “CENTUM” is automatically created, and the password has been set to “Yokogawa1” by the default.Select the password of “CENTUM” account for “Password never expires”.Because the download to HIS, Sequence table, or status display of SFC will not operate properly if the password is expired.
1. Log on to Windows with administrator's privilege.
2. Right click “My Computer”, then choose “Manage”from the menu. “Computer Management” window displays.
3. Choose “Local Users and Groups” displayed in the left pane, then open the “Users” folder and select a user.
4. Select “Password never expires” and click “OK”.
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Uninstallation of CENTUM VP
1.The Uninstallation of CETUM VP Software can be conductedfrom “Add or Remove Programs”. Select “Remove”
2. To manually delete the files which were not deleted by the Uninstallation operation, delete all files placed by using explorer.
- Program file%SystemDrive%\Program Files\YOKOGAWA
- The application data(For Vista): %SystemDrive%\Program Data\Yokogawa(For XP): %SystemDrive%\Documents and Settings\All Users\Application Data\Yokogawa
- CENTUM VP project data base etc.CENTUM VP installation folder e.g. C:\CENTUMVP
OP
Yokogawa Global Engineering Center Rev.0Copyright © Yokogawa Electric CorporationJuly 1st, 2008
Our commitment Your future
Thank you for your attention