    NTELSA ENERWIND - CENTELSA AEOLIC USE CABLES / CENTELSA ENERWIND -CENTELSA AEOLIC USE CAB

  • 7/30/2019 Centelsa Cable Eolico

    2/8

    Step-UpTransformer

    Step-UpSubstaon

    Juncon

    Box Boom

    Juncon

    Box (Top)

    Controller

    nerator

    Collecon

    Tower

    Cables

    Point

    ColleconPoint

    ColleconSystem

    Nearby TownCies

    ColleconSystem

    ColleconSystemCables

    Cables

    Cables

    TransmissionLines

  • 7/30/2019 Centelsa Cable Eolico

    3/8

    EOLIC POWER:

    In Greek Mithology, Aeolus was

    the ruler or keeper of the winds

    HARVESTING THE WIND

    A new approach to energy oers a clear path

    a more secure and prosperous future and a mo

    livable world. Increased use of wind, solar a

    other renewable energy sources will sp

    economic growth, protect consumers from pr

    spikes or supply shortages associated w

    global fuel markets, and dramatically reduce t

    pollution and global warming which harms oplanet.

    CENTELSA is committed to improving e

    vironmental quality and ensuring complian

    with all environmental requirements.

    believe that a secure and reliable energy syst

    is essential for economic development a

    protection of the environment.

    CENTELSA collaborates with costumers

    develop a exible delivery schedule that b

    meets the clients project and construct

    schedule. Additionally, CENTELSA provid

    engineering support to assist clients in alignicable specications with industry standards

    ensure they are specifying the optimal produ

    for specic application.

    Some projects where CENTELSAs cables w

    installed include Among other:

    Cedar Creek - Colorado

    Benton County - Indiana

    Fowler - Indiana

    Combine Hill - Oregon

    Grand Ridge - TexasInandale - Texas

    Papolote Creek - Texas

    Pyron - Texas

    Roscoe I & II - Texas

    Sweetwater - Texas

    Milford Corridor - Utah

    WIND: A LEADING SOURCE

    OF NEW ELECTRICITY

    GENERATION

    Wind energy has been historically used

    directly to propel salling ships or converted

    into mechanical energy for pumping water or

    grinding grain, but the principal application

    of wind power today is the generation ofelectricity: Large scale wind farms are

    typically connected to the local electric

    power transmission network, with dierent

    sizes turbines being used to provide

    electricity to isolated locations and the

    major cities worldwide. Wind energy as a

    power source is favored by many

    environmentalists as an alternative to fossil

    fuels, as it is plentiful, renewable, widely

    distributed, clean, and produces lower

    greenhouse gas emissions.

    Whether it is terrestrial or oshore wind

    farms requiring high-performance cables,CENTELSA oers a full array of cables needed

    for wind turbines to generate, distribute and

    transmit energy.

    Wind Power, RenewableEnergy For the Future

  • 7/30/2019 Centelsa Cable Eolico

    4/8

    CABLES FOR WIND ENERGY APPLICATIONS

    Plants and Headquarters: Calle 10 No 38 - 43 Urb. Industrial Acopi, Yumbo PBX: 608 3400

    www.centelsa.com.co / e-mail: [email protected]

    MEDIUM VOLTAGE CABLES 5 kV - 69 kV

    Applications: Power distribution in wind turbines for installation indoors or outdoors, wet or dry locations,in any raceways, cable tray, messenger supported wiring, underground ducts and direct buried.

    Compliance: AEIC CS8 - ICEA S-94-639 UL 1072

    LOW VOLTAGE ALUMINUM ALLOY POWER CABLES 600 & 2000 Volts.

    Applications: Power distribution in wind turbines, for generators and step-up transformers; indoors, in wet or

    dry locations, and in any raceway.

    Compliance: UL 44 UL VW-1 ICEA S 95-658/NEMA WC70 UL FT4

    LOW VOLTAGE POWER & CONTROL CABLES 600 & 2000 Volts.

    Applications: Power distribution in wind turbines, for controllers, high-speed shaft, and brakes; indoors or

    outdoors, in wet or dry locations, and in any raceway.

    Compliance: UL 44 UL 1277 - UL VW-1 ICEA S 95-658/NEMA WC70 UL FT4

    LOW VOLTAGE INSTRUMENTATION CABLES 300 & 600 Volts.

    Applications: Instrumentation circuits in wind turbines; for controllers, high speed shaft, and brakes; indoors or

    outdoors, in any raceway or underground duct, cable tray, direct buried, open runs, or supported by a messen-

    ger.

    Compliance: UL 44 UL 2250 - UL VW-1 ICEA S 95-658/NEMA WC70 UL FT4

    Product Line Insulation Jacket NED Code Types Voltage and Temperature Ratings

    URD Underground distribution TR-XLPE OR EPR PE N/A 5 kV 69 kV, 90C & 105C

    Product Line Insulation Jacket NED Code Types Voltage andTemperature Ratings

    AEOLIC USE Premium (-40C, FT4) XLPE - UL TYPE RHW-2 600 V & 2000 V, 90C , -40C FT4

    AEOLIC USE Standard (-25C, FT2) XLPE - UL TYPE RHW-2 600 V & 2000 V, 90C , -25C FT2

    Product Line Insulation Jacket NED Code Types Voltage and Temperature RatingsPower and Control XLPE-FR CPE UL TYPE TC 600 V & 2000 V, 90C

    EPR CPE UL TYPE TC 600 V & 2000 V, 90C

    Product Line Insulation Jacket NED Code Types Voltage and Temperature RatingsInstrumentation UL TYPE-

    -

    -

    -

    PLTC & TC 300 V,90C

    UL TYPE PLTC & TC 300V, 90C

    BARE ALUMINUM TRANSMITION CABLES

    Applications: Set up substation applications as well as open- air high voltage power transmission to the grid.

    Compliances: Applicable ASTM

    Product Line Construction Jacket NED Code Types Voltage and Temperature RatingsBare Aluminum Overhead ACAR, ACSR, AAAC N/A N/A According Power Transmition System

  • 7/30/2019 Centelsa Cable Eolico

    5/8

    STANDARDS

    OPTIONAL CONSTRUCTIONS

    NOTE

    AEIC CS8, Specication for Extruded Dielectric

    Shielded Power Cables Rated 5 through 46 KV

    ICEA S-94-649, Concentric Neutral Cables Rated

    5 through 46 kV

    UL 1072, Medium-Voltage Power Cables

    Other concentric neutral conguration

    available upon request

    Copper grounding conductors available upon

    request

    No magnetic armour

    Optional insulation in EPR or HEPR

    Medium Voltage CableElectrical Distribution (XLPE - TR)CENTELSA ENERWIND

    COLLECTION SYSTEM CABLES

    XLPE - TR

    Insulation

    APPLICATION

    Medium voltage cables to connect individual

    wind turbine generators pad mount transform-

    ers to either the wind turbine generator or the

    collection interconnection.

    For indoor or outdoor installations, wet or dry

    locations, in a raceway, cable tray, messenger

    supported wiring, underground ducts and directburied.

    FEATURES

    CENTELSA Cables are manufactured and tested

    in accordance with the latest revisions of the

    following standards:

    Optional constructions and other not indicatedavailable upon request.

    IDENTIFICATION

    TEMPERATURE RATING

    CENTELSA ENERWIND MV cables meets or

    exceeds ICEA S-94-649 Standard

    XLPE-TR (Cross Linked Polyethylene - Tree

    Retardand) insulation meeting the require-

    ments of the referenced standards

    Water blocking conguration

    The jacket contains three longitudinally

    extruded red stripes, and inkjet marking on the

    cable Identication methods specied upon

    request.

    90C

    105C upon request

    Halogen and heavy metals free, black

    polyethylene extruded to ll jacket

    whit 3 red extruded stripes

    Semiconductive compound

    insulation shield

    Semiconductive compound

    conductor shield

    Concentric neutral. Soft

    Copper metallic shield,

    optional extruded to ll

    jacket

    Aluminum or

    Copper conductor

    blocked against moisture

    We

    ConnectTo

    TheFuture

    WithClean

    Energy

    We

    ConnectTo

    TheFuture

    WithClean

    Energy

  • 7/30/2019 Centelsa Cable Eolico

    6/8

    BuildingaN

    ewEnergyFutureProtect

    ingtheEnvir

    onment

    BuildingaN

    ewEnergyFutureProtect

    ingtheEnvironment

    Medium Voltage CableElectrical Distribution (XLPE - TR)CENTELSA ENERWIND

    COLLECTION SYSTEM CABLES

    ENERWIND 35 kV Electrical Distribution Cables Installed in Wind Farms

    345 mils (nominal) XLPE - TR Insulation

    ENERWIND 46 kV Electrical Distribution Cables Installed in Wind Farms

    445 mils (nominal) XLPE - TR Insulation

    Conductor Neutral CableJacket

    Extrudedto Fill

    Jacket

    Extrudedto Fill

    ApproximatedTotal

    Cable Weight

    Size Diameter

    Wires Size

    No. of Wires

    Outside

    Diameter

    Outside

    Diameter

    Thickness

    AWG/kcmil mils mm No.Size

    AWGmils mm mils mm lbs/1000 ft Kg/km

    1/0 362 9,2 19 FULL 16 14 1438 36,5 55 1,4 951 1415

    1/0 362 9,2 19 1/2 8 14 1438 36,5 55 1,4 855 1272

    1/0 362 9,2 19 1/3 6 14 1438 36,5 55 1,4 831 1237

    1/0 362 9,2 19 2/3 11 14 1438 36,5 55 1,4 891 1326

    3/0 456 11,6 19 FULL 16 12 1566 39,8 55 1,4 1228 1827

    3/0 456 11,6 19 1/2 13 14 1532 38,9 55 1,4 1048 1559

    3/0 456 11,6 19 1/3 9 14 1532 38,9 55 1,4 1000 1488

    4/0 512 13,0 19 FULL 20 12 1681 42,7 85 2,2 1454 2164

    4/0 512 13,0 19 1/2 16 14 1588 40,3 55 1,4 1169 1739

    4/0 512 13,0 19 1/3 11 14 1588 40,3 55 1,4 1109 1650

    350 661 16,8 37 1/3 18 14 1797 45,6 85 2,2 1512 2250

    350 661 16,8 37 1/6 9 14 1797 45,6 85 2,2 1404 2089

    500 789 20,1 37 1/3 16 12 1993 50,6 85 2,2 1940 2887

    500 789 20,1 37 1/6 13 14 1959 49,8 85 2,2 1750 2604

    750 968 24,6 61 1/6 19 14 2138 54,3 85 2,2 2223 3308

    750 968 24,6 61 1/12 10 14 2138 54,3 85 2,2 2115 3147

    1000 1118 28,4 61 1/6 16 12 2321 59,1 85 2,2 2725 4055

    1000 1118 28,4 61 1/12 13 14 2288 58,1 85 2,2 2528 3762

    1250 1250 31,8 61 1/6 20 12 2454 62,3 85 2,2 3058 4550

    1250 1250 31,8 61 1/12 16 14 2420 61,5 85 2,2 2817 4192

    Conductor Neutral Cable

    Approximated

    Cable Weight

    Total

    Size Diameter

    Wires Size

    No. of Wires Thickness

    AWG/kcmil mils mm No.Size

    AWGmils mm mils mm lbs/1000 ft Kg/km

    4/0 13,0 19 FULL 20 12 1877 47,7 85 2,2 1682 2503

    4/0 512

    512

    13,0 19 1/2 16 14 1843 46,8 85 2,2 1454 2164

    4/0 512 16,8 19 1/3 11 14 1843 46,8 85 2,2 1394 2074

    350 661 16,8 19 1/3 18 14 2026 51,5 85 2,2 1800 2678

    350 661 16,8 19 1/6 9 14 2026 51,5 85 2,2 1692 2518

    500 789 20,1 37 1/3 16 12 2188 55,6 85 2,2 2207 3284

    500 789 20,1 37 1/6 13 14 2155 54,7 85 2,2 2012 2994

    750 968 24,6 61 1/6 19 14 2333 59,3 85 2,2 2508 3732

    750 968 24,6 61 1/12 10 14 2333 59,3 85 2,2 2400 3571

    1000 1118 28,4 61 1/6 16 12 2517 63,9 85 2,2 3033 4513

    1000 1118 28,4 61 1/12 13 14 2483 63,1 85 2,2 2832 4214

    1250 1250 31,8 61 1/6 20 12 2649 67,3 85 2,2 3382 5032

    1250 1250 31,8 61 1/12 16 14 2616 66,4 85 2,2 3138 4669

  • 7/30/2019 Centelsa Cable Eolico

    7/8

    WindPower,R

    enewableE

    nergyForTheFuture

    Win

    dPower,RenewableEnergyForTheFuture

    AA-8000 ConductorXLPE Insulaton

    APPLICATION2000 V thermosetting cross-linked polyethylene

    insulated, UL listed E137698 cables used for power

    distribution in wind turbines (tower and collection

    system cables), for step-up transformers and

    generators, in indoors and outdoors, in wet and dry

    locations.

    FEATURES

    Meets FT4/UL ame test for Premium Gradeand FT2/UL ame test for Standard Grade

    Rated at -40C/90C for Premium Grade

    Rated at -25C/90C for Standard Grade

    Oil, grease, water, and abrasion resistant

    Smooth surface for reduced coecient of

    friction

    Low power factor

    IDENTIFICATION

    Marking over insulation:

    AEOLIC USE (PREMIUM) or (STANDARD) GRADE -

    RHH/RHW-2 (AA-8000) 2000 V 90C XLPE (-40C) or

    (-25C) (UL) E137698.

    Additional information and optional markings upon

    TEMPERATURE RATING

    UL Type PREMIUM RHHW/RHW-2 Rated

    at -40C/90C

    UL Type STANDARD RHHW/RHW-2

    Rated at -25C/90C

    STANDARDSLow voltage AEOLIC USE UL Type RHHW/RHW-2

    AA-8000 cables are manufactured and tested in

    accordance with the latest revisions of the

    following standards:

    ASTM B800 Standard Specication for 8000

    Series Aluminum Alloy Wire for Electrical

    Purposes-Annealed and Intermediate Tempers.

    ASTM B801 Standard Specication for

    Concentric-Lay-Stranded Conductors of 8000

    Series Aluminum Alloy for Subsequent Covering

    or Insulation.

    UL 44 Thermoset-Insulated Wires and Cables.

    UL 854 Service-Entrance Cables (for USE-2)NFPA70: National Electrical Code.

    OPTIONAL CONSTRUCTIONS

    EPR InsulationMaterial can be produced at specic

    lengths upon request

    NOTE

    Optional constructions and other not indicated

    available upon request.

    TOWER SYSTEM CABLESLow Voltage Aluminum Alloy (AA - 8000) Power CablePremium & Standard Grade RHHW/RHW-2 2000 VCENTELSA AEOLIC USE

    request

  • 7/30/2019 Centelsa Cable Eolico

    8/8

    FromN

    ature

    ,CleanEnergyTodayForOurFutureGen

    erations

    FromN

    ature

    ,CleanEnergyTodayForOurFutureGenerations

    STANDARD GRADE FT2, -25C

    RHHW/RHW-2 8000 Series Aluminum Alloy 2000 V 90C XLPE

    PREMIUM GRADE FT4, -40C

    RHHW/RHW-2 8000 Series Aluminum Alloy 2000 V 90C XLPE

    Low Voltage Aluminum Alloy Power CablePremium & Standard Grade (AA - 8000) RHHW/RHW-2 2000 VCENTELSA AEOLIC USE

    TOWER SYSTEM CABLES

    Size

    Diameter

    Insulation

    Thickness

    Outside Diameter Cable WeightTotal Approximated

    AWG orkcmil

    mils mm mils mm mils mm lbs /1000 ft kg/km

    2 268,1 6,81 70 1,8 414 10,5 96

    1/0 335,4 8,52 90 2,3 524 13,3 152

    2/0 376,8 9,57 90 2,3 566 14,4 183

    3/0 423,2 10,75 90 2,3 612 15,5 221

    4/0 475,2 12,07 90 2,3 664 16,8 267

    250 521,7 13,25 105 2,7 742 18,8 329

    300 571,7 14,52 105 2,7 792 20,1 383

    400 659,8 16,76 105 2,7 88 1 22,4 490

    500 737,8 18,74 105 2,7 958 24,3 595

    750 909,4 23,1 120 3,0 1161 29,5 887

    900 996,5 25,31 120 3,0 124 8 31,7 1044

    1000 1050,4 26,68 120 3,0 1302 33,1 1148

    143

    226

    272

    329

    397

    490

    570

    729

    885

    1320

    1553

    1708

    Size

    Conductor

    Diameter

    Insulation

    Thickness

    Cable

    Outside Diameter Cable Weight

    Total Approximated

    AWG or

    kcmil mils mm mils mm mils mm lbs /1000 ft kg/km

    2 268,1 6,81 70 1,8 414 10,5 108

    1/0 335,4 8,52 90 2,3 524 13,3 172

    2/0 376,8 9,57 90 2,3 566 14,4 205

    3/0 423,2 10,75 90 2,3 612 15,5 245

    4/0 475,2 12,07 90 2,3 664 16,8 294

    250 521,7 13,25 105 2,7 742 18,8 363

    300 571,7 14,52 105 2,7 792 20,1 420

    400 659,8 16,76 105 2,7 88 1 22,4 531

    500 737,8 18,74 105 2,7 958 24,3 640

    750 909,4 23,1 120 3,0 1161 29,5 951

    900 996,5 25,31 120 3,0 124 8 31,7 1113

    1000 1050,4 26,68 120 3,0 1302 33,1 1220

    161

    256

    305

    365

    437

    540

    625

    790

    952

    1415

    1656

    1815

    Conductor

    Values here indicated are subject to normal manufacturing and/or standards tolerances.

    Values here indicated are subject to normal manufacturing and/or standards tolerances.