Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 www.lightvoxstudio.com Date: January 18, 2019 Project: NAU Prochnow Renovation Project No.: 3001.17.03 / 09.031.171 CD Addendum 01 The following clarifications and/or revisions have been made to the 100% CD Issuance documents issued on December 31, 2018 for bidding. CLARIFICATIONS 1. Are we to provide the portable towerless lift and the portable stage chairs including the removable stage molding in alternate 4? Yes. These items should be included in Add Alt 04. The Lift model is Ascension Protégé 5442P with option compression tool kit (manufacturers spec has been attached). The stairs will be a wood substructure and will have treads and risers to match the stage finish. The exposed side skirt will match the stage skirt. 2. For note 9 on AD1.00 – it says patch and repair existing paneling surface. Is this referring to the wood paneling prior to refinishing it? Yes, we want the wood paneling surface to be free of defects that will telegraph through the paint finish. 3. Is note 14 included in base bid or alternate 5? Note 14 should be considered part of Add Alt 05 4. Are the stacking sliding doors to be included in the millwork scope in the lobby? Yes, they are part of this millwork and should be included in the millwork shop drawings. 5. Is the existing mahogany paneling stained PT-5 at back wall per A8.00 supposed to be in Alt 4? This doesn’t really match the scope description described in the specification book. Same with the tectum panels. Seems like these all need to be in ALT 3. The mahogany paneling and tectum panels in the auditorium are mislabeled in A8.00 and should be noted as Add Alt 03. 6. Please clarify the mechanical and plumbing work. This seems like a lot of new work or is it just trim replacement? Painting existing diffusers and replacing three supply grilles and 2 return grills. No plumbing work is anticipated. 7. Can you please clarify the WAP and fire alarm scope? This again is not mentioned in the specification book under ALT 1. Is this supposed to be included? This scope should be included in Add Alt 01. Ceiling mounted fire alarm and WIFI access point devices are indicated to be removed and re-installed for ceiling upgrades to the lobby ceiling. In addition the Command Center Panel will need to be moved to the south wall of the men’s restroom next to the door. 8. Are the portable lift and portable stairs by Owner? Or are they part of the bid? I don’t see any specs or details. The portable lift and temporary stairs are part of Add Alt 04 and are by contractor. The lift model and stair description is noted in clarification 1. 9. Where does the removal of the abandoned hose cabinet fit into the bid? Which alternate? Or base bid? This should be considered part of Add Alt 05

Upload: others

Post on 07-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 www.lightvoxstudio.com

Date: January 18, 2019 Project: NAU Prochnow Renovation Project No.: 3001.17.03 / 09.031.171 CD Addendum 01 The following clarifications and/or revisions have been made to the 100% CD Issuance documents issued on December 31, 2018 for bidding.

CLARIFICATIONS

1. Are we to provide the portable towerless lift and the portable stage chairs including the removable stage molding in alternate 4? Yes. These items should be included in Add Alt 04. The Lift model is Ascension Protégé 5442P with option compression tool kit (manufacturers spec has been attached). The stairs will be a wood substructure and will have treads and risers to match the stage finish. The exposed side skirt will match the stage skirt.

2. For note 9 on AD1.00 – it says patch and repair existing paneling surface. Is this referring to the wood paneling prior to refinishing it? Yes, we want the wood paneling surface to be free of defects that will telegraph through the paint finish.

3. Is note 14 included in base bid or alternate 5? Note 14 should be considered part of Add Alt 05

4. Are the stacking sliding doors to be included in the millwork scope in the lobby? Yes, they are part of this millwork and should be included in the millwork shop drawings.

5. Is the existing mahogany paneling stained PT-5 at back wall per A8.00 supposed to be in Alt 4? This doesn’t really match the scope description described in the specification book. Same with the tectum panels. Seems like these all need to be in ALT 3. The mahogany paneling and tectum panels in the auditorium are mislabeled in A8.00 and should be noted as Add Alt 03.

6. Please clarify the mechanical and plumbing work. This seems like a lot of new work or is it just trim replacement? Painting existing diffusers and replacing three supply grilles and 2 return grills. No plumbing work is anticipated.

7. Can you please clarify the WAP and fire alarm scope? This again is not mentioned in the specification book under ALT 1. Is this supposed to be included? This scope should be included in Add Alt 01. Ceiling mounted fire alarm and WIFI access point devices are indicated to be removed and re-installed for ceiling upgrades to the lobby ceiling. In addition the Command Center Panel will need to be moved to the south wall of the men’s restroom next to the door.

8. Are the portable lift and portable stairs by Owner? Or are they part of the bid? I don’t see any specs or details. The portable lift and temporary stairs are part of Add Alt 04 and are by contractor. The lift model and stair description is noted in clarification 1.

9. Where does the removal of the abandoned hose cabinet fit into the bid? Which alternate? Or base bid? This should be considered part of Add Alt 05

Page 2: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 www.lightvoxstudio.com

10. Where do the auditorium fire extinguishers/cabinets fit into the bid? Which alternate? Or base bid? These items should be included in Add Alt 03

11. Add Alternate 03 (in the Project Manual) includes re-staining of wood wall paneling and new acoustic wall panels in the auditorium, but Sheet A8.00 says that work is part of Add Alternate 04. Please clarify. This answer has been included in clarification 5

12. What finish does the exposed structural steel at the stage extension get? The exposed structural steel at the stage extension is not visible and can be left with the mill finish.

13. Is the vapor protection coating (and surface prep) required at all areas scheduled to receive carpet? The concrete slabs receiving a new floor finish need to be tested for moisture per spec division 09 0500 Part 3.1. If the moisture content exceeds the values noted in this section then the vapor protection coating will be required per this division.

14. Is Testing, Adjusting, Balancing required for this project? Sheet M0.00 states that it is required to achieve new airflow values, but I don’t see any airflow info on the drawings. Please clarify. This note is not applicable to this projects scope. Please disregard.

15. Sheet E7.00 says to refer to plans for FA device quantities and locations, but quantities and locations of existing/new FA devices are not obvious on the plans. Maybe I missed it… Are there any additions and/or modifications to the existing FA system in this project? If so, where is the scope of work spelled out? And would it be part of the Base bid? This answer has been included in clarification 7

16. Sheets MD1.00, M1.00 and M2.00 have a general note 1 that reads ‘Contractor shall review the schematic design scope of work shown on plan and provide owner budget pricing for each item noted. Where indicated as an alternate pricing item, contractor to provide alternate pricing results as a break-out item’. This note can be disregarded. Contractor to bid on items per the base scope and list of bid alternates noted in Division 00 and on documents.

DRAWINGS DELETED DRAWINGS (NONE) REVISED DRAWINGS Architectural (NONE) Mechanical (NONE)

Page 3: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 www.lightvoxstudio.com

Electrical SHEET ED1.01

1. Adds demolition of existing emergency light fixtures on wall of future millwork in lobby to Add Alt 1

SHEET E1.01 1. Adds new emergency light fixtures to new millwork 2. Adds TL4 lighting inside the millwork.

SHEET E5.00

1. EM light fixture added to schedule ADDITIONAL DRAWINGS (NONE) FORMS FS-13 A worksite hazard inspection has been completed by the NAU Material Safety Office for work related to project reference number 09.031.171. The reported findings, recommendations, and vendor acknowledgement form have been included. This form needs to be signed and submitted as part of the bid. Attachments: All sheets noted above, form FS-13, Protégé 5442 specs END

Page 4: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01
Page 5: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01
Page 6: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01
Page 7: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01
Page 8: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01
Page 9: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

Ascension Protégé 5442P Model Series Vertical Portable Wheelchair Lift Product Specifications SECTION 14420 AND SECTION 14 42 00 PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. The product described herein, manufactured by Ascension, is a portable lifting device intended for use by individuals with disabilities. The lift shall be used only by individuals who are unable to negotiate stairs. The lift shall be unenclosed and self-contained, requiring no additional components or modifications of the using facility. The lift shall consist of a platform supported on an electro-hydraulic lifting mechanism with built-in casters for portability. The casters shall permit easy movement of the unoccupied lift over hard, level surfaces. With the casters removed, the lift shall rest firmly on any hard, level surface, and provide a stable base for operation of the lift. The lift shall be low profile (no machine tower) to maintain viewing lines. The lift shall provide for independent use by individuals with disabilities and include all operating and safety devices for compliance with ADA requirements as applicable to portable lifts. The lift shall have a slim profile platform frame to eliminate the need for a pit or access ramp on the lower landing side and facilitate easy entry into the lift directly at floor level by patrons. The lift shall provide adequate lifting force to raise the platform and occupant to a height suitable for access to most stages, platforms, or similar elevated surfaces. 1.2 QUALITY ASSURANCE A. Manufacturer shall maintain a quality management system certified to ISO 9001. B. Manufacturer shall have not less than twenty (20) years of experience in the design and manufacture of vertical wheelchair lifts. 1.3 WARRANTY A. Manufacturer shall provide a warranty for a period of ten (10) years on the drive train, four (4) years on all other components, and ninety (90) days on labor, starting from the date of installation. B. Extended warranty plans are available. PART 2 - PRODUCT 2.1 MANUFACTURER A. Ascension Protégé 5442P Model Series vertical portable wheelchair lift, manufactured by Ascension, 3526 E. Fort Lowell Rd., Tucson, AZ, 85716, Tel: 800-459-0400 or 520-881-3993, Fax: 520-881-4983, [email protected]. B. Manufacturer must be a registered U.S.-owned company, with manufacturing operations for this product located in the United States of America. C. Acceptance of other products is subject to compliance with specified requirements and owner or architect approval. 2.2 PHYSICAL CHARACTERISTICS A. Lifting capacity: 900 pounds [408 kg]. B. Weight of lift: 850 pounds maximum [386 kg]. C. Vertical speed: five (5) fpm (feet per minute) [1.5 m/min (meters per minute)]. D. Vertical travel: 4" to 42" [102 mm to 1067 mm], infinitely adjustable. E. Standard platform gate configuration: the upper landing platform gate shall be left-hinged when facing the lift from the upper landing; the lower landing platform gate shall be right-hinged when facing the lift from the lower landing. Contact Ascension for custom platform gate configurations. 2.3 DIMENSIONS A. Platform size: 36" x 54" [914 mm x 1372 mm] with 48" [1220 mm] high sidewalls and platform gates. B. Space requirements (operational, storage, and transport): 49" [1245 mm] high (in the down position), 61" [1549 mm] long, 48" [1219 mm] wide. C. No part of the lift shall stand over 49" [1245 mm] high when the platform is on the ground (except when equipped with optional stage guard).

PO Box 40020 Tucson, AZ 85717-0020 ● TEL: 800-459-0400 ● FAX: 520-881-4983 ● www.ascension-lift.com 06/29/18 Form 7.2.1.579B Rev: 2

Page 10: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

2.4 MATERIALS A. The platform frame, base frame, and lifting device shall be constructed from ASTM A 36, AISI 1018, or AISI 1020 Steel. B. The windows shall be fabricated from 1/4" [6 mm] thick high impact strength clear thermoplastic. C. The platform sheet metal and under-platform safety pan shall be aluminum alloy. 2.5 FINISH A. All metal components shall be thoroughly cleaned to remove any foreign substance. Exposed metal surfaces shall be finished with an oven-baked powder coating. Exposed base frame metal surfaces shall be hot-dip galvanized. B. Standard color is black; contact Ascension for custom color selection. 2.6 DRIVE CONFIGURATION A. Drive shall be direct-acting hydraulic. B. Both sides of lift platform shall be supported evenly by means of synchronized hydraulic cylinders. C. Hydraulic power unit shall be mounted on vibration-isolating supports designed to minimize vibration transmission and reduce frame-borne noise. 2.7 ELECTRICAL REQUIREMENTS A. Electric power requirements shall be compatible with 120VAC, 60 hertz, single phase, 15 amp service (option: international electrical configurations available). B. The lift shall be supplied with a three prong grounded electrical cord (20' [6.1 m] in length). C. The lift shall contain a Ground Fault Circuit Interrupter (GFCI). D. Motor shall be 1/2 hp,115V AC single phase (international configurations available). E. Control circuits shall be 24 VDC. F. Electrical components shall be UL listed and CSA registered. G. Electrical system shall be certified to ASME A17.5 by an independent testing laboratory. 2.8 SAFETY DEVICES The lift shall be constructed to meet the applicable requirements of ADAAG, ASME A17.1-1996 or older (PART XX, SECTION 2000), ASME A18.1, and ANSI A117.1 as they would apply to a portable lifting device. The lift shall include the following safety features for protection of the passenger and general public. A. Grounded electrical system. B. 24 VDC operating controls. C. Constant pressure operating switches. D. Emergency stop button at passenger control station. E. Electro-mechanical interlock to prevent accidental opening of lower landing platform gate. F. Gate switches to prevent platform movement if either platform gate is open. G. Lift platform stop height sensor. H. Under-platform safety pan that protects the area under the lift platform. I. 48" [1220 mm] high sidewalls and platform gates. J. Unobstructed view through transparent sidewalls and platform gates. K. Grab bar extending full length of inside wall. L. Slip resistant surfaces on platform floor and dock plate. M. Structural safety factors as specified in ASME A18.1. N. Self-closing platform gates. 2.9 PORTABILITY A. Casters shall be easily attached to the platform for portability and stored in the platform cabinet when not in use. Casters shall be 5" [127 mm] in diameter. The casters shall be capable of being installed without tools. When the casters are installed, the lift shall roll easily over any hard, smooth, level surface. The lift shall be capable of being moved by forklift or truck.

PO Box 40020 Tucson, AZ 85717-0020 ● TEL: 800-459-0400 ● FAX: 520-881-4983 ● www.ascension-lift.com 06/29/18 Form 7.2.1.579 Rev: 2

Page 11: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

2.10 OPERATING CHARACTERISTICS A. Lift shall include three (3) constant pressure “UP/DOWN” switches, located outside of the platform at both ends and inside the platform. B. The passenger control station shall be provided with a separate “PUSH TO STOP” emergency button. The emergency stop button shall prevent any operation of the lift when actuated. C. The platform stop height shall be adjustable without the use of tools. D. Opening the upper landing platform gate shall deploy a dock plate that rests on the upper landing surface. The dock plate shall provide a smooth transition between the platform and the upper landing. Closing the upper landing platform gate shall retract the dock plate. E. The lower landing platform gate shall be provided with a mechanical interlock that prevents the platform gate from being opened whenever the platform is more than 2" [50 mm] above the full down position. 2.11 COMPRESSION CAPABILITY A. The lift shall be capable of being compressed to 33" [838 mm] wide to facilitate relocation through a 36" [914 mm] wide doorway. An additional tool kit from Ascension is recommended to facilitate compression of the lift. PART 3 - EXECUTION 3.1 INSTALLATION A. Set up lift for operation as described in manufacturer’s operating manual. B. If desired, lift may be anchored to floor surface using the 9/16” [14 mm] mounting holes provided in the base of the lift. 3.2 MAINTENANCE A. Maintenance of the lift shall consist of regular cleaning as deemed necessary by the using facility. General inspection, maintenance, and lubrication shall be specified in the manufacturer’s service manual. NOTE: This specification has been written to assist in preparing a detailed description of a portable wheelchair lift. Additional technical information may be obtained from Ascension. Specifications are also available electronically at www.ascension-lift.com. Specifications are subject to change. Patent information is available on the Ascension website: www.ascension-lift.com/patents

PO Box 40020 Tucson, AZ 85717-0020 ● TEL: 800-459-0400 ● FAX: 520-881-4983 ● www.ascension-lift.com 06/29/18 Form 7.2.1.579 Rev: 2

Page 12: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

LOBBY

101CW

VESTIBULE

102CW

WOMENS

1004CONCESSION

100

VESTIBULE

100CW

ELEVATOR

117CW

MENS

1002

AUDITORIUM

101

STAGE

102

GREENROOM

105

STORAGE

107

RISER

106

OFFICE

104

RECEIVING

103

STAGE

LIGHTS

DIMMER HOUSE LIGHTING

WIRING PULLBOX

DIMMER SWITCH

UL LISTED

TRANSFER RELAY

EMP

ATS

EX. PANEL

'HLTG'

14 14 14 14

17171717

16 16 16 16

15 15 15 16

13 13 15 15

13 13 13

DEMO EXISTING NEON COVE LIGHT FIXTURES

DEMO EXISTING NEON COVE LIGHT FIXTURES

1

EXIST. PANEL-SB

1 1

Re g

i st e

r ed

P r o f e s s i on a l Eng i ne e r ( El ec

t rical)Da t e

S i g n e d . . . . . . . . . .

.ON

FI

A

RI ZONA , U . S . A

.

ERT

C

ICATE

DeHAVEN

JOEL D.

30963

EXPIRES 3/31/2021

© L

IGH

T VO

X S

TUD

IO

NO. DESCRIPTION DATE

1729

eas

t osb

orn

road

, 2nd

flo

or,

phoe

nix,

ari

zona

850

16

PROJECT:

--

6 0

2

. 6

0

4 .

6

6 2

6

STUDIO

01/09/19

C:\

Rev

it Lo

cal F

iles\

MEP

18_

1700

2140

.00_

NA

U P

roch

now

_C

entr

al_

nata

lene

.r.t

so.r

vt1/

9/20

19 4

:09:

51 P

M

NAU [Prochnow]Auditorium

LEVEL 01 ELECTRICALLIGHTING DEMOLITION

PLAN

ED1.01

3001.17.03 / 09.031.171

317 W DUPONT AVENUEFLAGSTAFF, AZ 86011

12.31.18

NO R

HT

1/8" = 1'-0"1 LEVEL 01 - ELECTRICAL LIGHTING DEMOLITION PLAN

SHEET GENERAL NOTES :

A. DEMOLISH ALL EXISTING LIGHTING FIXTURES SHOWN ON THIS PLAN, U.N.O.

KEYNOTES:

1. ADD ALTERNATE #1: DEMOLISH ALL LIGHTING FIXTURES INDICATED WITHIN LOBBY AND LOBBY ENTRANCE AREA. FIELD VERIFY AND COORDINATE EXACT DEMOLITION REQUIREMENTS WITH OWNER AND ARCHITECT.

#

0' 4' 8' 16' 32'

SCALE: 1/8" = 1'-0"

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

405 BEAVER STREET, SUITE #8FLAGSTAFF, AZ 86001928.255.0410www.imegcorp.com

17002140.00

1 ADDENDUM 1 01.09.19

Page 13: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

J

J

J

J

J

J

3 33 3

D D D D

D

LOBBY

101CW

GREENROOM

105

OFFICE

104

STORAGE

107

RECEIVING

103

STAGE

102

RISER

106

AUDITORIUM

101

CONCESSION

100

MENS

1002

WOMENS

1004

VESTIBULE

100CW

ELEVATOR

117CW

VESTIBULE

102CW

TL2

TL2

TL5

TL5E

TL5

TL5E

TL5

TL5E

TL5

TL5E

X1-B

X1-B

TL5E

TL5

TL5E

TL5

TL5E

TL5

X1-B

TL5E

TL5

TL5

TL5E

TL5

TL5E

TL5

TL5ETL5E

TL5

TL5 TL5 TL5 TL5

TL5E

X1-B X1-B

TL5

TL5E TL5E

TL5 TL5

TL5E

TL5

TL5E

TL5ETL5ETL5ETL5E

TL5

TL5TL5

TL3 (TYP.) TL3 (TYP.)

TL2 (TYP.)

TL2 (TYP.)

TL4 (TYP.) TL4 (TYP.)

TL1 (TYP.)

TL4 (TYP.) TL4 (TYP.)

TL1 (TYP.) TL1 (TYP.)

TL1 (TYP)

TL1 (TYP). TL1 (TYP.)

TL6 TL6 TL61X1 X1

TL7 TL7

TL2

X1

EM

X1-B X1-B

TL20 TL20

X1

2

2

3

4

STAGE

LIGHTS

DIMMER HOUSE LIGHTING

WIRING PULLBOX

DIMMER SWITCH

UL LISTED

TRANSFER RELAY

EMP

ATS

EX. PANEL

'HLTG'

EX. PANEL 'B'

EXT.D/1/a

EXT.D/1/a

EXT.D/1/a

EXT.D/1/a

EXT.D/1/a

EXT.D/1/a

4

4

4

4

4

5

5

5 5

(a)(b)(c)(d)

(b)(b)

(c)

(d)

(c)

(c)

(c)

(d)

(d) (d)

(d) (c) (b) (a)

7(TYP.)

6 (TYP.)

EX EX

EXIST. PANEL-SB

EX

EX

EX

EX

EXEX

EX EX

TL48

a

aEMEM

1

Re g

i st e

r ed

P r o f e s s i on a l Eng i ne e r ( El ec

t rical)Da t e

S i g n e d . . . . . . . . . .

.ON

FI

A

RI ZONA , U . S . A

.

ERT

C

ICATE

DeHAVEN

JOEL D.

30963

EXPIRES 3/31/2021

© L

IGH

T VO

X S

TUD

IO

NO. DESCRIPTION DATE

1729

eas

t osb

orn

road

, 2nd

flo

or,

phoe

nix,

ari

zona

850

16

PROJECT:

--

6 0

2

. 6

0

4 .

6

6 2

6

STUDIO

01/09/19

C:\

Rev

it Lo

cal F

iles\

MEP

18_

1700

2140

.00_

NA

U P

roch

now

_C

entr

al_

nata

lene

.r.t

so.r

vt1/

9/20

19 4

:09:

49 P

M

NAU [Prochnow]Auditorium

LEVEL 01 ELECTRICALLIGHTING PLAN

E1.01

3001.17.03 / 09.031.171

317 W DUPONT AVENUEFLAGSTAFF, AZ 86011

12.31.18

NO R

HT

1/8" = 1'-0"1 LEVEL 01 - ELECTRICAL LIGHTING & SYSTEM PLAN

KEYNOTES:

1. PROVIDE NEW ELECTRICAL WORK INDICATED WITHIN LOBBY AND LOBBY ENTRANCE AREAS AS ADD ALTERNATE #1.

2. PROVIDE NEW ELECTRICAL WORK ASSOCIATED WITH FIXTURE TYPE TL2 AS PART OF ADD ALTERNATE #2.

3. PROVIDE NEW ELECTRICAL WORK ASSOCIATED WITH FIXTURE TYPE TL4 AS PART OF ADD ALTERNATE #3.

4. PROVIDE A 250W,120/12V REMOTE TRANSFORMER FOR LIGHTING FIXTURE TYPE TL1 AS SHOWN AND CONNECT TO EXISTING FLOOR MOUNTED JUNCTION BOX WITH EXISTING 120V CIRCUIT. REFERENCE LIGHTING FIXTURE SCHEDULE FOR POWER SUPPLY CATALOG NUMBER.

5. PROVIDE NEW LIGHTING FIXTURE. CONNECT TO NEW SWITCH AS INDICATED AND CONNECT TO EXISTING 120V CIRCUIT.

6. PROVIDE 0-10V DIMMER CONTROL SWITCHES (AS SHOWN) AND CONNECT TO 3-WAY CONTROLS LOCATED AT THE STAGE. COORDINATE EXACT LOCATION WITH OWNER/USER PRIOR TO FINAL INSTALLATION.

7. PROVIDE A 3-WAY PRESET ON/OFF SWITCH AND CONNECT TO DIMMER(S) LOCATED IN CONTROL BOOTH AREA.

8. MOUNT LIGHTING FIXTURE TYPE 'TL4' BELOW FINISH MILL WORK AND ROUTE TO NEW DIMMER SWITCH LOCATED IN CONCESSION AREA. REFERENCE SHEET A1.10 DETAIL 19 FOR ADDITIONAL MOUNTING INFORMATION. COORDINATE ALL MOUNTING WITH ARCHITECT PRIOR TO ROUGH-IN AND FINAL INSTALLATION.

9. MOUNT LIGHTING FIXTURE TYPE 'EM' ON FINISH MILL WORK. COORDINATE FINAL MOUNTING HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN.

#

SHEET GENERAL NOTES :

A. ALL NEW LIGHTING FIXTURES SHALL BE CONNECTED TO EXISTING LIGHTING CIRCUITS AND CONTROLS EXCEPT AS OTHERWISE NOTED.

B. THE EMERGENCY AND EXIT LIGHTS ARE TO BE RECONNECTED TO THE EXISTING CIRCUIT(S).

0' 4' 8' 16' 32'

SCALE: 1/8" = 1'-0"

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

405 BEAVER STREET, SUITE #8FLAGSTAFF, AZ 86001928.255.0410www.imegcorp.com

17002140.00

1

1 ADDENDUM 1 01.09.19

Page 14: CD Addendum 01 - in.nau.edu | Northern Arizona University · 2019-01-22 · Union Workspace: 1729 E. Osborn Rd, Phoenix, AZ 85016 o.602.604.6626 f.602.230.0535 Electrical SHEET ED1.01

Re g

i st e

r ed

P r o f e s s i on a l Eng i ne e r ( El ec

t rical)Da t e

S i g n e d . . . . . . . . . .

.ON

FI

A

RI ZONA , U . S . A

.

ERT

C

ICATE

DeHAVEN

JOEL D.

30963

EXPIRES 3/31/2021

© L

IGH

T VO

X S

TUD

IO

NO. DESCRIPTION DATE

1729

eas

t osb

orn

road

, 2nd

flo

or,

phoe

nix,

ari

zona

850

16

PROJECT:

--

6 0

2

. 6

0

4 .

6

6 2

6

STUDIO

01/09/19

C:\

Rev

it Lo

cal F

iles\

MEP

18_

1700

2140

.00_

NA

U P

roch

now

_C

entr

al_

nata

lene

.r.t

so.r

vt1/

9/20

19 4

:09:

49 P

M

NAU [Prochnow]Auditorium

ELECTRICAL SCHEDULES

E5.00

3001.17.03 / 09.031.171

317 W DUPONT AVENUEFLAGSTAFF, AZ 86011

12.31.18

REFER TO SPECIFICATION SECTIONS LIGHTING [16510 26 51 00] [AND EMERGENCY LIGHTING EQUIPMENT 16535 26 52 00] FOR ADDITIONAL INFORMATION AND REQUIREMENTS.INTERIOR CORRELATED COLOR TEMPERATURE 3000 AND 3500K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 85, UNLESS NOTED OTHERWISE.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATIONSHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIRE MOUNTINGHEIGHTS.

DMX - DIGITAL MULTIPLEX EM - EMERGENCY BATTERY ML - MULTI-LEVEL SWITCHING O - OTHER (SEE DESCRIPTION)

DALI - DIGITAL ADDRESSABLE ELV - ELECTRONIC LOW VOLTAGE LINE - LINE VOLTAGE DIMMING REM - REMOTE

0-10V - 0-10V DIMMING EB - ELECTRONIC HL - HIGH/LOW (100%/50%) STEP DIM MV - MULTI-VOLTAGE ELECTRONIC

(TYPE) DRIVER:

PL - POLE O - OTHER (SEE DESCRIPTION) DLED - DYNAMIC TUNABLE LED WLED - WARM DIM LED

P - PERIMETER WL - WALL OLED - ORGANIC LED RLED - RETROFIT LED

FR - FLANGED RECESSED UC - UNDER CABINET TLED - TUBULAR LED LAMP RGBA - COLOR CHANGING + AMBER

CV - COVE SU - SURFACE LED - LIGHT EMITTING DIODE RGBW - COLOR CHANGING + WHITE

CL - CEILING SURFACE SP - SUSPENDED (TYPE) LED RGB - COLOR CHANGING LED

(MTG) MOUNTING: RE - RECESSED (WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP

CFSA - COLOR-FINISH SELECTION BY ARCHITECT [DESIGN SPECIFIC BLANKS]

PAF - PAINT AFTER FABRICATION WW - WALL WASH K - KSH12 .125" ACRYLIC O - OTHER (SEE DESCRIPTION)

FINISH: VWD - VERY WIDE G - TEMPERED GLASS SS - SEMI-SPECULAR CLEAR

RS - REGRESSED STEEL V - ANSI/IES TYPE 5 DISTRIBUTION WD - WIDE F - FROSTED ACRYLIC R - HIGH IMPACT DR ACRYLIC

RA - REGRESSED ALUMINUM IV - ANSI/IES TYPE 4 DISTRIBUTION MD - MEDIUM C - CLEAR ALZAK P - POLYCARBONATE

FS - FLAT STEEL III - ANSI/IES TYPE 3 DISTRIBUTION SP - SPOT B - BAFFLE/LOUVER N - NONE

FA - FLAT ALUMINUM II - ANSI/IES TYPE 2 DISTRIBUTION NSP - VERY NARROW SPOT A - .125" ACRYLIC M - MATTE DIFFUSE CLEAR

(DESC) DOOR: DISTRIBUTION: BEAMWIDTH: (L/L) LENS/LOUVER: K19 - KSH19 .156" ACRYLIC

LED LUMINAIRE SCHEDULE

ITEM DESCRIPTION L/L MTG

DIMENSIONS WATT LED DRIVER

APPROVED MANUFACTURERL W H DIA.ANSI

WATTS PER TYPE QTY VOLTS TYPE

EM EMERGENCY LIGHTING FIXTURE WITHINTEGRAL BATTERY PACK.

O WL 8 1/2" 2 1/4" 5" 2 W LED 2 120 V EM DUAL-LITE: EV-4-D-I-02WAL-B

TL1 LED CARPET AISLE LIGHTING, SURFACEMOUNTED

O O 0" 1 29/32" 1/2" 0" 0.25 W FT LED 0 120 V DR TEMPO INDUSTRIES: GUARDIAN SERIES2100-21-12-BK-A-C; POWER SUPPLY#PWR-TO25012/2

TL2 CHANNEL FLEXABLE LED STRIP, 30 DEGREEPOLYCARBONATE CHANNEL MOUNTINGTRACK, SURFACE MOUNTED

O O 0" 5/8" 11/16" 0" 13 W FT LED 0 120 V DR ACCLAIM LIGHTING: FLEX ONE HOINTERIOR, FLEX GRAZE

TL3 CHANNEL FLEXABLE LED STRIP, 60 DEGREEPOLYCARBONATE CHANNEL MOUNTINGTRACK

O O 0" 5/8" 11/16" 0" 13 W FT LED 0 120 V DR ACCLAIM LIGHTING: FLEX ONE HOINTERIOR, FLEX GRAZE

TL4 MINI CHANNEL FLEXABLE LED STRIP,POLYCARBONATE CHANNEL MOUNTINGTRACK

O O 0" 39/64" 15/64" 0" 13 W FT LED 0 120 V DR ACCLAIM LIGHTING: FLEX ONE HOINTERIOR, FLEX MINI CHANNEL

TL5 CYLINDER DOWNLIGHT, SEMI-SPECULARFINISH TRIM, BLACK HOUSING

O SP 1'-7 1/2" 6" 106 W LED 1 120 V DR GOTHAM: ICOCYL-30-85-6AR-70D-120-EZB-PM-DBL

TL5E CYLINDER DOWNLIGHT, SEMI-SPECULARFINISH TRIM, BLACK HOUSING

O SP 1'-7 1/2" 6" 106 W LED 1 120 V DR/EM GOTHAM: ICOCYL-30-85-6AR-70-120-EZB-PM-DBL-EM

TL6 COPPER ARTICHOKE WITH LED LAMP O SP 0" 1'-6 29/32" 1'-7 1/2" 1'-6 29/32" 100 W LED 1 120 V STILNOVO: LN28648COPPER WITH LEDE26 (100W EQUIVALENT AND 2700K)

TL7 TRACK MOUNTED ACCENT LIGHTINGFIXTURE

O CL 3'-0 5/8" 5 1/4" 7" 0" 25 W LED 1 120 V DR AFX: CHRF4400L30SN

TL20 DOWNLIGHT WITH MEDIUM DISTRIBUTION,CLEAR TRIM AND SEMI-SPECULAR FINISH

O RE 0" 0" 6 5/8" 4" 13 W LED 1 120 V DR GOTHAM: EVO-35/10-4AR-MD-LSS-277-EZ1

X1 EMERGENCY EXIT SIGN WITH BATTERYBACK-UP

O 11 3/4" 2" 7 5/8" 1 W LED 1 120 V EM LITHONIA: LQM-S-W-R-120-ELN-SD

X1-B EMERGENCY EXIT SIGN WITH BATTERYBACK-UP

O WL 11 3/4" 2" 7 5/8" 1 W LED 1 120 V EM LITHONIA: LQM-S-B-R-120-ELN-SD

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

405 BEAVER STREET, SUITE #8FLAGSTAFF, AZ 86001928.255.0410www.imegcorp.com

17002140.00

1

1 ADDENDUM 1 01.09.19