Causes of High Relative Humidity Inside Air
Conditioned Buildings
Roger G.Morse AIA, Paul Haas CSP, CIH
Morse Zehnter Associates
![Page 2: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/2.jpg)
S. FLORIDA – AVE. AMBIENT 91 F dB / 78 F wB
16,000 HOURS ANNUALLY THAT wB > 66 F
THIS INDICATES A SIGNIFICANT PROBLEM WITH HIGH OUTDOOR HUMIDITY AND THEREFORE, HIGH INDOOR HUMIDITY
![Page 3: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/3.jpg)
![Page 4: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/4.jpg)
![Page 5: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/5.jpg)
Cause of High Relative Humidity Inside Air Conditioned Buildings
Study Included:• HVAC Equipment Diagnosis• Heat Gain Calculations• Field survey and logging of Temperature,
RH and Occupant Interviews• Maintenance / Mechanical Evaluations
![Page 6: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/6.jpg)
Study Parameters
• Forty-One (41) Schools Investigated– 228 Separate Air-Conditioned Buildings– 28 Elementary (ES), 7 Middle (MS), 3 High
Schools (HS) & 3 Vocational Centers (Ctr) – 1036 HVAC Systems:
631 Air Handling Units (AHU), 283 Fan Coil Units (FCU), 90 Unit Ventilators (UV) & 32 Heat Pumps (HP)
![Page 7: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/7.jpg)
Study Results
• After occupant interview, data logging was performed using HOBO™ H8 loggers for RH/Temp for one week.
• The logging and occupant interviews were followed up with detailed maintenance and mechanical assessments.
• A summary report which analyzed findings included a detail of the cause(s) of high RH.
![Page 8: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/8.jpg)
Causes of High Relative Humidity Inside Air Conditioned Buildings
Controls Which Affected Relative Humidity – 63 % had Malfunctioning or Misapplied
Dehumidification Enhancements – Face & Bypass, Supply Bypass etc.
– 93 % had a potential for uncontrolled humidity entering spaces through the lack of Outside Air Controls – Building Pressurization, Manual Dampers only, Exhaust Fans on 24 hrs.
![Page 9: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/9.jpg)
Age of Equipment and Maintenance
• HVAC Equipment Service Life (ASHRAE Recommendation ~ 20 years)
• 30 % - 20 years or the age was unknown• 13% - 15-20 years • 53% - 5-15 years • 4% - 0-5 years
![Page 10: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/10.jpg)
Commercial Dehumidification
• Commercial systems dehumidify by chilling air below the dew point
• Water condenses out on the fins of the cooling coil
• The leaving air has a reduced dew point and specific humidity
• The leaving air will be saturated and should have a relative humidity of about 100%
![Page 11: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/11.jpg)
Chilled Water SystemCHILLED WATER SYSTEM
FanConditionedAir
Vapor
HotVapor
Liquid
Heat Exchanger
Heat Exchanger
CoolingTower
Chilled Water
WarmerWater 52°
50°
Warm Water
Cooled Water
![Page 12: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/12.jpg)
Single Fan AC Unit
Condensate Drain Pan
Coil50° F
MixedAirChamber
AirDamper
Return
FreshAirDamper
Fres
h Ai
r
RoofOrWall
90° - 90% RH
Wet Side Dry Side
Filter Bank
SINGLE FAN AC UNIT
Supply Air
50° F100%RH
Supply Fan
Return Air 72° F 48% RH
![Page 13: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/13.jpg)
![Page 14: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/14.jpg)
Causes of High Relative Humidity
More Outside Air Than Capacity of System• Negatively Pressurized Building and/or
Cavities – 140 cases (21.41%)• Excessive or Uncontrolled Ventilation -
129 cases (19.72%) • Oversized Units – 118 cases (11.47%)• Partial Load with High Relative Humidity --
85 cases (8%)
![Page 15: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/15.jpg)
Face and By-Pass
DAMPERBYPASS
AIRRETURN
DAMPERBYPASS
AIRFRESH
COILCOOLING
![Page 16: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/16.jpg)
![Page 17: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/17.jpg)
![Page 18: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/18.jpg)
Coil Capacity Inadequate
• Coil Too Warm During Partial Load Conditions (14.53%)
– Coil inadequate for latent loads (too few rows)– Frequently due to excessive outside air– Stratification of air through coil
![Page 19: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/19.jpg)
![Page 20: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/20.jpg)
Temperature Controls That Caused RH Problems
• Modulating Chilled Water Valve (11.93%)
– Constant Ventilation with Continuous Fan Operation and Cycling Cooling
– Chilled Water Reset
![Page 21: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/21.jpg)
![Page 22: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/22.jpg)
![Page 23: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/23.jpg)
Correct Lack of Coil Capacity
• Replace Coil• Precondition outside air• Eliminate Chilled Water Reset• Replace modulated CW valves with on-off
valves• Install dehumidification enhancing features
![Page 24: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/24.jpg)
Exhaust Fans On 24 Hrs
Building envelope
![Page 25: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/25.jpg)
![Page 26: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/26.jpg)
Condition Outside Air
Intentional opening
![Page 27: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/27.jpg)
![Page 28: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/28.jpg)
Positively Pressurize Building
• Precondition fresh air 10% greater than exhaust air
• Avoid plenum returns – use ducted returns• Avoid supply ducts in unconditioned attics• Seal wall cavities from ceiling plenum• Use PM automatic damper controls
![Page 29: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/29.jpg)
Special Cases :
• Fan Coil Units with Filter Grille
• Unit Ventilators
![Page 30: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/30.jpg)
![Page 31: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/31.jpg)
![Page 32: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/32.jpg)
ASHRAE – Environmental and Ventilation Requirements
• ASHRAE 55-1992 “Thermal Environmental Conditions for Human Occupancy.”
• ANSI/ASHRAE 62-1999 “Ventilation for Acceptable Indoor Air Quality.”
![Page 33: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/33.jpg)
Findings from Study
ASHRAE ‘Compliance’• 25 of 41 schools studied had HVAC
equipment installed with a capacity of 5 CFM OA / person
• 3 of 41 schools had HVAC equipment installed with 15 CFM OA / person
• 13 schools had mixed capacity when new additions were made
![Page 34: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/34.jpg)
Findings from Study
High Relative Humidity• Analysis of Relative Humidity and Temperature
Logs proved to be a powerful tool • Misapplied or Malfunctioning Dehumidification
Enhancement to HVAC Equipment often led to high Relative Humidity
• The lack of Outdoor Air Control appeared to be the most consistent cause of high RH either in conjunction with mechanical issues or separately
![Page 35: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/35.jpg)
Recommendations for Future Study
• IEQ Conditions with ventilation for occupants at 5 CFM / person
• Maintenance and Retrofit of HVAC Equipment
• Building Envelope contribution to Relative Humidity
![Page 36: Causes of High Relative Humidity Inside Air Conditioned Buildings](https://reader033.vdocuments.mx/reader033/viewer/2022051302/5881e5c01a28abeb198b6f11/html5/thumbnails/36.jpg)
AcknowledgementAcknowledgement
•• THANKS TO MR. LEE KENDRICK THANKS TO MR. LEE KENDRICK WHO AT 86 YEARS OLD IS STILL AN WHO AT 86 YEARS OLD IS STILL AN IMPORTANT INFLUENCE FOR IMPORTANT INFLUENCE FOR INDUSTRIAL HYGIENISTS IN INDUSTRIAL HYGIENISTS IN UNDERSTANDING “THE CAUSE AND UNDERSTANDING “THE CAUSE AND CURE OF MOLD IN BUILDINGS” CURE OF MOLD IN BUILDINGS”