- 1 -
TONG CONG TY THIET B IEN VIET NAM
CONG TY CPHN THIET B IENVIET NAM ELECTRICAL EQUIPMENT CORPORATION
ELECTRICAL EQUIPMENT JOINT STOCK COMPANY
MAY BIEN AP KHO LOAI UCCAST RESIN TRANSFORMER
CONG TY CPHN THIET B IEN- ELECTRICAL EQUIPMENT JOINT STOCK COMPANY
NG SO 9-KHU CONG NGHIEP 1 BIEN HOA-VIET NAM -NO.9 STREET BIEN HOA 1 INDUSTRIAL ZONE-VIETNAMTEL: (061)3 836139 -3836140 - 3836897 - 0903934918- FAX: 84-61-3836070Website: www.thibidi.com.vn - E-mail: [email protected]
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
2/23
- 2 -
1. May bien ap kho THIBIDI THIBIDIs Cast Resin Transformer 3
2. ng dungApplications 4
3. Cau truc Construction 5
4. Phu kienAccessories 6
5. Cong nghe Technology 8
6. Th nghiem Quality Assurance 9
7. Lap at va Hoat ongIntallation & Operation 9
8. Van chuyen va Lu khoHandling and Storage 17
9. Vn hnh & Bo dng Commissioning and Maintenance 18
10.c tnh kthut Technical Specification 20
11. Yu cu thng tin t hng Inquiry, Order 22
NI DUNG CONTENTS
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
3/23
- 3 -
11.. MMyybbiinnppkkhhTTHHIIBBIIDDIITTHHIIBBIIDDIIssCCaassttRReessiinnTTrraannssffoorrmmeerr
1.1. Chu la Fire resistantCuon day c uc bang nha Epoxy vi ac tnh khong bat la, t dap tat la va chongchay do tia la ien.The cast coil with Epoxy resin with non-flammable characteristics has a self-fire-extinguishing
performance, to be free from a fire from electrical sparks.
1.2. Lc ngn mch cao hn Higher short circuit strengthCuon day uc nha Epoxy co sc ben c va ien cao ket hp vi ket cau may vng
chac chu ng c lc do ngan mach gay ra, do va cham be ngoai va cac rung ongkhac thng.The cast coil with Epoxy resin with the high electrical and mechanical strength is manufactured in a
robust structure against an electromechanical force occurring during short circuit, external impacts,
and abnormal vibrations.
1.3. Chng m Moisture proofCuon day uc nha Epoxy lam tang sc ben chat cach ien va khong lam giam tnhcach ien chat do hi am gay ra va nhng phan ng lam lao hoa vat lieu cach ien,ngay ca sau mot thi gian dai khong bao dng.The cast coil with Epoxy resin has an enhanced dielectric strength and doesnt suffer from the
deterioration of dielectric property due to humidity and the aging effects of insulating materials, evenafter a long term without maintenance.
1.4. Kch thc gn Compact sizeKieu dang nho gon va trong lng nhe c the hien qua mau thiet ke, qua hnh dangcuon day c uc nha Epoxy di moi trng chan khong va vat lieu cach ien tot.Compact size and lightweight type can be embodied by designing and manufacturing the coil by casting
in a high vacuum using Epoxy resin and insulating materials with good dielectric strength.
1.5. Khnng qu ti cao High overload capabilityCuon day uc nha Epoxy co he so thi gian gia nhiet cao v the co the chu c squa tai cao hn.The cast coil with Epoxy resin has a high thermal time constant factor, therefore it can endure much
higher overloads for a short time.
1.6. Tn tht thp, n thp Low loss, low noiseTon that thap, o on thap c the hien bang viec s dung tole silic t ton that va vat lieu cach ientot.
Low-loss and low-noise are embodied through the optimal compact design using silicon steel of low-
loss and good insulating materials.
1.7. Bo dng ddngMaintenance freeKhong can kiem tra mc dau cung nh th nghiem mau dau.
No checking of oil level or no dielectric test oil.
Cuon day uc nha khong lam giam ac tnh cach ien do am t va o am, v the de dang kiem trava bao quan may bien ap ke ca cuon day.
The cast coil with Epoxy resin doesnt suffer from the deterioration of an insulating property due to
humidity and moisture, therefore it is easy to inspect and maintain a transformer including the coil.
1.8. Mi trng an ton Environmentally safeKhong phat sinh dau hay kh oc vao kh quyen.
No emit of oil or toxic gases into the atmosphere.
oi vi may bien ap dau th de b o nhiem moi trng hn do dau chay r ra.
Comparing to an oil-immersed transformer, it is free from an environmental pollution due to oil spill.
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
4/23
- 4 -
22..nnggddnnggAApppplliiccaattiioonnss
Trong ta nh Inside buildings
Trong ng hm In tunnels
Trong nh my chbin thc phm In food processing plants
Trn tu b On ship
Trn khu cu trc On cranes
Trn sn ngoi khi On off-shore flatforms
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
5/23
- 5 -
33.. CCuuttrrccCCoonnssttrruuccttiioonn
1. Mc cu my Lifting lug 6. X kp li tole Frame
2. Li tole Core 7. Thanh ni pha Phase connection lead
3. Cun dy-Winding 8. u ni iu chnh Tap terminal link
4. u ct cao p HV terminal 9. Cn m Spacer
5. Chn my Base channel
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
6/23
- 6 -
44.. PPhhkkiinnAAcccceessssoorriieess
4.1. Phkin cbn Standard Accessories
u ct bn hLV terminal u ct bn cao HV terminal
u ni iu chnh c np bo v- Tapterminal link & protection cover
Mc cu Lifting lug
Tip a Grounding terminal Thanh ni pha Phase connection lead
ng ho nhit kthut sDigital thermometer
m chng rung Anti vibration pad
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
7/23
- 7 -
4.2. Phkin ty chn Optional Accessories
Bnh xe 2 chiu Bi-directional wheel Qut lm mt Cooling fan
Vtbo vEnclose
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
8/23
- 8 -
55.. CCnnggnngghh--TTeecchhnnoollooggyy
5.1. Li t
Loi t c lam t nhng la tole silic ac nh hng c bao ve bang oxit voc.S chon la cap tole, mau cat tole va
phng phap lap loi tole giup giam toithieu mc ton that va dong khong tai cungnh tao nen o on rat nho.Sau khi lap tole, e bao ve chong an mons dung nha alkyd cap F c say tronglo.Cat cheo 45 o, xep lp
Khong co ot lo tren xa, ket cau tam noi
5.1. Magnetic core
The magnetic core is made from laminations of
grain oriented silicone steel insulated with
mineral oxide.
The choice of the grade of steel, the cutting
pattern and the method of assembly minimizesloss level and no-load current with the effect of a
very low noise level.
Once assembled, it is corrosion protected using a
class F, oven-dried alkyd resin.
Mitred type adopts 45 degrees cuts, multistage
step-by-step stacking.
No punching holes on yokes, connecting plate
structure
5.2. Cun dy
Tat ca cuon day ha va cao clam bang ong la hoac nhom la. ien apgia lp la thap, trong khi kha nang chung lp la ln. ien ap chu xung cao.
ien khang cua ien ap cao va ha la giongnhau. Khong co goc xoan. Ampe vong cuaday cao va ha c thap nhat, cuon daychu kha nang ngan mach. Do o chungvan hanh tin cay.
uc nha epoxy luc chan khongcao, cuon day ha va cao co hieu suat ienva c tot. Phong ien cuc bo thap hn 5PC.
Cuon day ha va cao co the trang bthong gio qua theo yeu cau s tieu tannhiet. Nha cach ien be mat day trungbnh la 2 - 2,5 mm, am bao s tangnhieto va sc ben cua cuon day va vngchac tho 30 nam.
Bi v bot thach anh vao nhaepoxy va si thuy tinh ben trong em auva ngoai cuon day, chung co kha nangtieu tan nhiet, chong c o am va chongc ngon la. Khong can lo lang ve tonthng. Chung co the lam viec bnhthng di o am 100%. Hieu suat chong
5.2 Windings
All the low and high voltage windings aremade up of copper bands (foils) or aluminium
wire (foils) .Voltagebetween layers is low , while
layer capacity is great . Its lighting
impulsewithstand capacity is high . The reactance
of high and low voltage is the same . There is nohelical angle . For ampere turns of the high and
low voltage windings are best leveled, the
windings are capable of withstanding short
circuit . Therefore, they have high operating
reliability.
Molded with epoxy resin at high vacuum ,the high and low voltage windings have well
electrical and mechnical performance . Partial
discharge of them is less than 5pc.
High and low voltage windings can beequipped with ventilating air passages according
to requirements for heat dissipation. The isolating
resin on the surface is 2.0-2.5mm thick in average
, ensuring the temperature increase and strength
of the windings and securing the 30 years service
life .
Because of quartz powder on the epoxyresin and the glass-fiber net banded inside and
outside the windings , they have high heat-
dissipating ability , humidity-resistance and flame
resistance . There is no need to worry aboutcracking . They can work normally under the
humidity of 100% . Their flame-resistant
performance accords with the Britain BS7806F2.
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
9/23
- 9 -
c chay chap nhan theo BS7806F2. Ben trong cua cuon day ha va cao
c han t ong va ngan nga xung otvi chay nho.
Mc cach ien cap F va H. Giihan nhiet o soi va s ket hp thiet ketheo yeu cau cu the khach hang.
The interior of low and high voltagewindings are creadibly welded automatically and
protectively by argon with low resistance .
F and H stands for the two insulation levels. The temperature-rise limitation and voltage
combination can be designed according to the
customers specific requirements.
66.. TThhnngghhiimm--TTeessttss
Tiu chun c cng nhn Recognized Standard(ISO 9001)
Thnghim thng thng Routine tests1. o in trcun dy 1. Measurements of winding resistance
2. o tsv thtu dy 2. Calibration of voltage ratio andvoltage vector relationship
3. o in trcch in 3. Measurement of insulation resistance
4. o tn tht c ti v trkhng 4. Measurement ofshort circuitimpedance and load losses
5. Tn tht khng ti v dng khng ti 5. Measurement ofno-load losses andcurrent
6. Thin p ngun ring bit 6. Separate-source power-frequencyvoltage withstand test
7. Thqu in p cm ng 7. Induced over discharge
Thnghim in hnh Type test
1. Thxung 1. Impulse test
2. Thtng nhit 2. Temperature rise test
Thc bit Special tests
1. Thdng ngn mch 1. Short circuit test
2. Thn 2. Noise level test
Thc bit khc Others
Nhng thc bit khc c ththchin theo yu cu ca khc hng.
Other special tests could be carried
out per requirements of customer.
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
10/23
- 10 -
77..LLppttvvhhoottnngg--IInnssttaallllaattiioonn&&OOppeerraattiioonn
7.1. Tng qut
Do khong co chat ien moi long va cach xl chay tuyet vi, khong can e phong chaynhng can lam theo nhng quy nh sau:Khong nen at may bien ap vung conguy c ngap lut.o cao khong qua 1000 met tr khi co ocao cao hn th c xac nh vao luc thamdo.Nhiet o moi trng gii han trongkhoang sau:- Nho nhat: -250C- Ln nhat: +400CNhiet o moi trng cho may bien ap khotieu chuan c thiet ke theo IEC726:
- Ln nhat: 400C- Trung bnh cua ngay: 300C- Trung bnh cua nam: 200CV tr thong gio phai giup tieu tan ton thattong cua may bien ap.Trong khong kh o nhiem nang (dau maygia cong kim loai, bui dan ien) khong khvao tiep xuc vi thiet b nen c lam sachneu co the (qua bo loc, loc au vao cua
khong kh ben ngoai qua ng ong).May bien ap ngay ca co vo bao ve IP21cung c thiet ke e lap at trong nha.Nen d phong cho cac au noi va cac loket noi.
Khong co vo bao ve (IP00) (Hnh 1)
Trong ket cau nay, may bien ap phai cbao ve chong lai nhng tiep xuc, va cham
trc tiep.Ngoai ra:Phai can than tranh nhng ni co ncri vao may (v du: hi nc ngng tu tng ong at ben tren)Duy tr khoang h toi thieu en tng xay,theo bang sau ay:
7.1. General information
Due to the absence of any liquid dielectric and
the excellent fire behaviour of transformers, no
anti-fire precautions are necessary providing
the following guidlines are followed:
The transformer should not be installed in a
flood hazard area.The altitude should not be above 1000 meters
unless a higher altitude is specified at the time
of inquiry
The ambient temperature for the transformer
to be within the following limits:
- Minimum: 250C
- Maximum: +400C
Standard transformers are designed in
accordance with IEC726 for an ambient
temperature of:
- Maximum: 400C
- Daily average: 300C
Yearly average: 200C
The local ventilation should allow the
dissipation of the transformer total losses.
In highly polluted atmospheres (metal
machining oil, conductive dust), the air coming
into contact with the device should if possible be
cleaned (filtering, inlet of outside air via aducting)
The transformer even with IP21 metal
enclosure is designed for an indoor installation.
Provision should be made for access to
connectors and tapping links.
Without enclosure (IP00) (figure 1)
In this configuration, the transformer must be
protected against direct contact.
In addition:Care must also be taken to eliminate risks of
water drops on the transformer (example:
condensation from overhead pipings).
Maintain minimum clearance to the walls
according to the following table:
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
11/23
- 11 -
Kch thc Dimensions(mm)
Cp cch inInsulation
(kV) Tng bao bcFull wall
Li thng giVentilation grill
12 120 300
17.5 220 300
24 220 300
Co vo bao ve (IP21) (Hnh 2)
Duy tr khoang cach toi thieu la 200mmt mat ngoai vo bao ve en tng xaydng e am bao u lam mat.
With IP21 metal enclosure (figure 2)
A minimum distance of 200mm between the
exterior of the enclosure and the walls of the
building should be maintained to ensure
adequate cooling.
Hnh 1 - Khong cch lp t khng c vbo vIP00Figure 1 Installation distance without enclosure IP00
X
X
X
X
Hnh 2 - Khong cch lp t c vbo v
Figure 2 installation distance with enclosure
500mm
200mm
HV
LV200mm
200mm
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
12/23
- 12 -
7.2. Thng gi
Xac nh chieu cao va dien tch lo thonggio
Trng hp lam mat t nhien (AN), sthong gio cua tram hay vo bao ve phai ambao tnh oi lu t nhien, lam tieu tan nhiet
sinh ra do ton that tong cong cua may.Trng hp tram khong u thong gio, sthong gio thch hp bao gom lng khong khmat lay vao qua tiet dien S ay tram valng khong kh lay ra qua tiet dien S phaoi dien ben tren, ng vi o cao H so vi loikhong kh vao (Hnh 1 va 2)e am bao lam mat co hieu qua cho maybien ap va s lu thong khong kh u, thcan phai gi mot khoang khong di aymay toi thieu la 150mm, bang cach lapnhng banh xe hay nhng con nang tngng.Chu y rang s lu thong khong kh b hanche se lam giam cong suat qua tai va congsuat thc cua may.
Cong thc tnh thong gio (Hnh 1):
Va S=1.10xSP = Tong ton that co tai va khong tai, tnhbang kW 1200CS = Dien tch cua lo thong gio lay vao, tnhbang m2.S = Dien tch cua lo thong gio i ra, tnhbang m2.
H = o cao gia lo thong gio lay vao va i raCong thc nay phu hp vi nhiet o moitrng trung bnh la 200C va o cao di1000mV d:
- May bien ap co cong suat 1000kVA- P0=1780W, Pcc(120
0C)=9140W, ngha laP=10.9kWNeu o cao gia 2 lo =2m, th dien tch be
mat lo thong gio lay vao can thiet laS=1.4m2.Neu chung ta tng tng co tam li can tr
7.2. Ventilation
Determination of the height and area of
ventilation grills
In the general case of natural cooling (AN)
the ventilation of the substation or of the
enclosure must ensure by natural convection
the dissipation of the heat produced by the
transformers total losses.
In case of a no sufficiently ventilation
substation, appropriate ventilation will consist
of a fresh air intake opening of S section at the
bottom of the local and an air outgoing
opening S located above on the opposite wall
at height H meters above the intake opening
(figure 1 and 2).
To ensure efficient cooling of the
transformer and sufficient air circulation, it is
essential to maintain a minimum height of 150
mm under the live section, by installing castors
or an equivalent booster
It must be noted that restricted air
circulation reduces the transformers
continuous and short- term overload capacity.
Formula for ventilation (figure 1):
and S=1.10xS
P = sum of the transformers no-load and load
losses expressed in kW at 120C.
S = area of the lower air intake opening (allow
for mesh factor) expressed in m2.
S = area of the air outlet opening (allow for
mesh factor) expressed in m2.
H = height difference between the twoopenings expressed in metre.
This formula is valid for an average ambient
temperature of 200C and an altitude of 1000m
Example:
- one single transformer 1000kVA
- P0=1780W, Pccat 1200C =9140W,
i.e. P=10.9kW
If the distance between the grills=2m, then
S=1.4m2
of net surface area necessary.If we imagine a grill obstructing the air inlet by
30%; the air inlet grill surface area should
0.18PS H=
0.18PS H=
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
13/23
- 13 -
30% luong khong kh i vao, th dien tch bemat cua lo thong gio lay vao la 1.4mx1.4mva dien tch cua lo thong gio i ra la1.4mx1.5m.
Thong gio cng bc (Hnh 2):
Can thiet neu nhiet o moi trng tren 200Chay phong nho va kem thong thoang c
ng dung cho viec qua tai thng xuyen.Quat co the c ieu khien bi bo cam ngnhiet va hoat ong nh la quat hut thong gioat tren tran cua phongLu lng cua dong kh (m3/s) 200C=0.1xP; Trong o: P = Tong ton that co tai vakhong tai, tnh bang kW 1200C.
then be 1.4m x 1.4m, and that of the air outlet
should be 1.4m x1.5m.
Forced ventilation (figure 2):
Forced ventilation of the substation is
necessary for ambient temperatures above
200C or small or badly ventilated rooms for
applications with frequent overloads.
The fan can be controlled by a thermostat
controlled and operate as an extractor in the
top part of the room.
Advised flow (m3/second) at 20
0C =0.1xP
P = sum of the transformers no-load and load
losses expressed in kW at 120C.
Hnh 2 - Trm thng gi cng bcFigure 2 Substation forced ventilation
H
S
S
Hnh 1 - Trm thng gi tnhinFigure 2 Substation natural ventilation
H
S
S
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
14/23
- 14 -
7.3. Cc u ni
Cac au noi HV va LV i vao co the atben tren hay di ay.au noi ben MV c lam bang cap danien.au noi ben LV thong thng c lambang cap dan ien, nhng cung co thebang cach khac rat an toan dung Thanh
ong tien che (PBT).Cac trng hp cho thay dung day caphay thanh ong phai c nang tranhng suat c tren cac au cot HV hay LV,hay cac au cam HV.
au noi HV nen at ben tren thanh noitam giac. au noi LV nen at tai phan trencua may.
Chu y:
- Khoang cach gia day cap HV, thanhong noi va be mat cua boi day toi thieula 120mm ngoai tr tren be mat ben HV o khoang h toi thieu se c annh bi au cap HV.
- Khoang h en thanh tam giac HV benngoai cung phai toi thieu la 120mm.
- Lp phu nha pha ngoai, hay s dungau cam plug-in khong bao ve chong laitiep xuc trc tiep va khong c chamvao may bien ap khi no co ien.
May khong co vo bao ve (IP00)
Tieu chuan au noi HV va LV- au day LV ra (hay vao) co the at pha
tren hay pha di (hnh 1 va 2)- au day HV ra (hay vao) co the at pha
tren hay pha di (hnh 1 va 2)Trong trng hp au day ra (hay vao) tpha di th can phai at mot mieng em
Noi HV bang au cam plug-in (hnh 3) Noi LV bang ong dan ien tien che(hnh 4)V tr lap at n gian hoa that nhieu neuco the, e viec ieu chnh, lap rap va thaod de dang.- May bien ap khi ban trang b san thanh
ong tien che- Kha nang ieu chnh lap at nay khoang
15mm cho 3 hng
- Viec noi va thao mat khoang mot gigiup dch vu cung cap lien tuc.
7.3. Connections
The incoming HV and LV connections can be
made from the top or the bottom.
MV side connections are made by cables
LV side connections are made conventionally by
cables, but can also be made using the very
safe alternative using Prefabricated Busbar
Trunking (PBT).
In all cases shown the cables or busbars must besupported to avoid mechanical stress on the HV
or LV terminals or HV plug in connectors.
The HV connections should be made to the top of
part of the delta connection bars. The LV
connections are made at the top of the
transformer.
Warning:
- The distance between HV cables or busbarsand the surface of the winding should be at
least 120 mm except on the flat face of the HVside where the minimum clearance will be set
by the HV terminal.
- The clearance to the outer HV delta bar shouldalso be a minimum of 120 mm.
- The resin coating, or the use of plug inconnectors does not give protection against
direct contact and the transformer must not be
touched when it is energized.
Without metal enclosure (IP00)
Standard HV and LV connections- The outgoing (or incoming) LV conductors can
be made from above or below (figures 1 and
2).
- The outgoing (or incoming) HV conductors canbe made from above or below (figures 1 and 2)
In case of an outgoing (or incoming) conductors
from below it is necessary to put a spacer
HV connections with plug in connectors (figure3)
LV connections using prefapricated electricalducting (figure 4)
On site installation is simplified as far as
possible, with very easy fitting, assembly and
dismantling:
- The transformer is delivered pre-equipped withthe PBT connection interface
- The possibility of adjusting on site by 15mm inall directions
- Connection and disconnection is achievedwithin an hour at most proving optimum
continuity of service.
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
15/23
- 15 -
May co vo bao ve IP21
Tieu chuan au noi HV va LV (Hnh 1&2).- au day LV ra (hay vao) phai i hng
len t au cot va nam di nap vo bao ve.au day LV khong bao gi i qua cuonday cao ap va vo bao ve.
- au day HV ra (hay vao) co the i quaben tren (hnh 1) hay pha di (hnh 2).
Noi au day HV t pha di- au day HV ra (hay vao) co the i pha
di en trc tiep au cot noi (hnh 2).
Trong trng hp nay au day i vaoc a qua canh ca pha di benphai nam pha HV.
With IP21 metal enclosure
Standard HV and LV connections (figures 1
and 2)- The outgoing (or incoming) LV conductors
must go upwards from the terminals under
the enclosure cover. The LV conductors
should never pass between the HV coils and
the enclosure.
- The outgoing (or incoming) HV conductorscan pass above (figure 1) or below (figure 2).
HV connection from below- The outgoing (or incoming) HV conductors
can come from below directly to the
connection terminal (figure 2). In this caseincoming conductors are passed through the
removable flap door located at the bottom on
nLV
HV
Cp Cables support
Hnh 1Tiu chun u ni HV & LV pha trnFigure 1 Standard HV and LV connections from above
nLV HV
Cp Cables support
Hnh 3Ni HV bng u ni cm plug-inFigure 3HV connections with plug in connectors
120
min
120min
Hnh 2Tiu chun u ni HV & LV pha diFigure 2 Standard HV and LV connections from below
120min
120min
Thanh mSpacer
HV
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
16/23
- 16 -
- Day cap HV phai c gi chat ben trongvo bao ve bang cai kep (hnh 2).
Nen xac nh tnh kha thi loai au noi e cos tng quan gia tiet dien va ban knhuon cong cap vi cho trong trong vo chebao ve. Noi HV bang au cam plug-in (hnh 3) Noi au LV bang ong dan ien tien che
(hnh 4)
Ch :
Can xac nh tnh phu hp cua hang mucbao ve IP21 sau khi a khoan tam emcach ien cho HV, LV va nhng phan khac.
the right HV side.
- The HV cables must be fastened inside theenclosure on clamp (figure 2).
It is advisable to verify the feasibility of this type
of connection in relation to the section and the
bending radius of cables and the space available
in the enclosure.
HV connection by plug in connector (figure3)
LV connections using prefapricated electricalducting (figure 4)
Warning:
It is necessary to verify conformity with the IP21
protection index after having drilled the
insulation gland plate for HV, LV and others.
LV
HV
Cp
Cablessupport
Cp
Cablessupport
Hnh 3Ni HV bng u ni cm plug-inFigure 3HV connections with plug in connectors
n
Hnh 1Tiu chun u ni HV & LV pha trnFigure 1 Standard HV and LV connections from above
Cp
Cablessupport
Cp
Cablessupport
LV
HV
Hnh 2Tiu chun u ni HV & LV pha diFigure 2 Standard HV and LV connections from below
HV
Hnh 4-Ni LV bng PBT v vbo vFigure 4-LV connections with PBT and enclosure
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
17/23
- 17 -
88..VVnncchhuuyynnvvLLuukkhhoo--HHaannddlliinnggaannddSSttoorraaggee
Vn chuyn Handling
May bien ap c trang b cac phan d phonge van chuyen an toan.
Nang chuyen bang day (hnh 1)Dung 4 lo moc cau e nang may bien apkhong co vo bao ve va 2 patte cau cho maybien ap co vo bao ve. Day nang khong ctao thanh goc trong ln hn 600.
Nang chuyen bang xe nang (hnh 1&2)Trc tien kiem tra cong suat nang cua xenang. Neu phu hp, a cang nang vao diranh chan may sau khi thao ri con lan ra.
Keo dayKhi keo may bien ap co hay khong co vo bao
ve nen keo t chan may ben di. V mucch nay nen moi ben cua chan may co long knh 27mm. Co the keo theo 2 hng:doc theo truc chan may hay vuong goc vitruc chan may
Lap rap con lan Ca 2 viec nang chuyen bang day (hnh 1) Hay nang chuyen bang xe nang (hnh 1
& 2)
V tr cang nang luon nam di chan may- at go ke cao hn chieu cao con lan va
may bien ap ta len go ke.- nh v nhng cai kch oi va lay go ke ra.- Lap con lan vao ung v tr (con lan hai
chieu).- Ha thap va e cho may bien ap ta len
nhng con lan cua chung.
The transformers are equipped withprovisions for safe handling.
Lifting with slings (figure 1)
Lifting is carried out using the 4 lifting holes
for a transformer without an enclosure and by
2 lifting lugs in the case of a transformer withan enclosure. The slings should not form an
inside angle greater than 600.
Lifting with a fork lift truck (figure 1&2)
The lifting capacity of the fork lift truck should
first be checked. If suitable, the forks should be
inserted inside the base channels after
removing the rollers.
Towing
Towing the transformer with or without
enclosure should be done from the underbase.For this purpose hole of 27 mm. Diameter are
provided on every side of the
underbase.Towing can be done in two
directions: in the axis of the underbase and
perpendicular to that axis.
Fitting the rollers
Either by lifting with slings (figure 1)
or by lifting with a fork lift truck (figures1 and 2)
In this case position the lifting forks in theunderbase channels.
- Place timbers of greater height than therollers under the channels and lower the
transformer on to them.
- Position jacks and remove the timbers.- Attach the rollers in the desired position
(bidirectional rollers).
- Lower and remove allowing the transfomerto rest on its rollers.
Lu kho StorageMay bien ap phai c bao ve trong khotranh nc ri vao va cong viec phat sinh bui(xay dng nha, lam ng v.v...). Neu maybien ap khi giao hang co nap nha th phaigi nguyen nap nha nay trong thi gian lukho.
May bien ap co the lu tr nhiet o xuongen 250C.
The transformer should be protected in
storage from water drops and dust
generating work (masonry, sanding etc). If
the transformer is delivered with a plastic
cover which should be kept over the
equipment whilst it is in storage.
The transformer can be stored at a
temperature down to 250C.
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
18/23
- 18 -
99..VVnnhhnnhhvvbbooddnngg--CCoommmmiissssiioonniinnggaannddmmaaiinntteennaannccee
a vo vn hnh Commissioning
Kiem tra ni lap at may bien ap kho
ieu kien lap at: ni lap at phai sachva tranh b ngap nc, ac biet la khongat vao vung nc ri t tran nha. Phaico bien phap thong gio e giai thoat nhietphat ra t may bien ap.
Kiem tra may can cham soc trong thigian dai: khi nao bui bam tren may bienap tuy theo thi ky cham soc, loai tr buinay bang may hut bui hay thoi het buibang may nen va lam sach bang may hutbui.
Bao boc nha e ngan can bui, inh oc,
boulon, vong em lot vao v.v... phai gi(duy tr) en khi ong ien (cap nguon).(khi noi au cot th nhat va th hai, xerach tng phan).
Check points when installing a castresin transformer
Installing conditions : installing place must be
clean and free from care of submersion under
water, especially not exposed water drops from
a ceiling of it. There must be a ventilation
means for getting rid of the heat generated
from a transformer.
Check of a transformer being taken custody for
long term : When dusts are deposited on a
transformer according to long term custody,
eliminate dusts by a vacuum cleaner or blow
away dusts by compressor, and wipe it by a dry
duster.
A vinyl package for preventing from inserting
of dusts, screws, nuts, washers and etc, must be
maintained until power is on after installation.
(when connection of 1st and 2nd terminals,
tear off partly)
Momen xoan au cot noi ong Torque for copper Terminal connection
n v- unit (N.m)Bulng Bolt M10 M12 M16Mmen Torque 10 20 35
i m nng ca xe nngFork lift truck lifting
60
maximum
Hnh 1-Nng bng dy v xe nng
Figure 1-Lifting with slings or fork lift truck
Con lnroll
Hnh 2-Lp rp con ln
Figure 2-Fitting the rollers
Kch ijack
GkTim
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
19/23
- 19 -
Momen xoan au cot noi thep- Torque for steel Terminal connection
n v- unit (N.m)Bulng Bolt M10 M12 M16 M20Mmen Torque 20 35 80 160
Kiem tra trc khi a ien vao
Lay bao boc nha, va kiem tra tnh trangau noi, khoang cach canh ien, conhng chat la hay khong, trang thiet b cob h hai hay khong, va momen cuaboulon.
Kiem tra au noi ieu chnh phu hp vinhan may hay khong.
Check points before receiving power
Get rid of a vinyl package, and check
connection status, insulating separation,
distance, whether alien substances remain,
whether a component is damaged, and bolt
torque.
Check whether tap connections accord with
that of a label.
o ien tr cach ien s dung ong ho o ohm (DC 1000V Megger) nh sau:Measure insulations using an insulation ohmmeter(DC 1000V Megger) like below:
V tr oMeasuring point
Gia tr gii hanLimit value
Cuon cao atHigh voltage coil grounding 250 MohmCuon ha at
Low voltage coil grounding50 Mohm
Cuon cao - cuon haHigh voltage coil Low voltage coil
250 Mohm
Khi gia tr o c thap hn cac gia trtren, kiem tra o am, neu ung, say kholai, va o ien tr cach ien lai lan na.Tuy nhien neu viec o ien tr cach ienvan thap hn gia tr gii han xin lien hevi dch vu sau ban hang.
When measuring values are below than above
values, check humidity, and if it is, get rid of
humidity by dryer, and measure an insulation
resistance again. Nevertheless if a measured
insulation resistance is below than the limit
value, contact with the A/S (after-sale service)
department.
Bo dng Maintenance
Trong tnh huong may ang van hanh,
thoi sach bui bang may nen kh kho moinam. Thi ky lam sach tuy thuoc vaohoan canh. Kiem tra cac boulon bat maybang c-le can lc trong luc thc hiencong viec bao dng.
In case of general operating circumstance, get
rid of dusts and blow away over deposited
dusts by dry compressor every year. Cleaning
term depends on circumstances. Check
engagements of bolts by a torque wrench
during performing a maintenance work
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
20/23
- 20 -
1100..ccttnnhhkktthhuuttTTeecchhnniiccaallSSppeecciiffiiccaattiioonnss
Tiu chun chto : IEC-60076-11-2004 Manufacture Standard:IEC-60076-11-2004
Cng sut : 400kVA n 2500kVA Capacity : 400kVA to 2500kVA
Tn s: 50Hz Frequency : 50Hz
in p scp : 22-15KV hoc 22KVhoc 35 KV
Primary voltage : 22-15KV or 22KV
or 35KV
in p thcp : 0,4kV Secondary voltage : 0.4kV
iu chnh : 2x2,5% Tappings : 2x2.5%
Cp cch in : Cp F Insulation class : F class
tng nhit : 1000
K Temperature rise : 1000
K
L
H
A W
Dng in A
(Rated Current)
Kch thc bao(mm)
(Main dimensions)
Cng sutKVA
(Rated
Capacity) I1(22kV) I11(15kV) I2(0,4kV)
Tn haokhng
ti
P0(W)
(No-loadlosses)
Tn haongn mch1200CPk120(load
losses)
in pngn mch
Uk(%)
(Impedance
voltage)
Trnglng
G(kg)(Weight)
W L H A
400 10,5 15,4 909,3 1660 2620 3,8 2350 920 1610 1630 820
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
21/23
- 21 -
560 14,7 21,6 909,3 1660 5135 5,3 2350 920 1610 1630 820
630 16,5 24,2 909,3 1660 6500 6 2350 920 1610 1630 820
750 19,7 28,9 1082,5 2050 8500 6 2450 920 1650 1760 820
1000 26,2 38,5 1443,4 2415 10000 6 2950 920 1680 1800 820
1250 32,8 48,1 1804,2 2785 11500 6 3600 920 1840 1860 820
1600 42 61,6 2309,4 3255 13500 6 4460 920 1990 1930 820
2000 52,5 77 2886,8 3990 15000 6 5200 1170 2060 1950 1070
2500 65,6 96,2 3608,4 4680 18500 6 6200 1170 2230 2040 1070
Dng inA
(Rated Current)
Kch thc bao(mm)
(Main dimensions)
Cng sutKVA
(Rated
Capacity) I1(35kV)
I2(0,4kV)
Tn haokhng ti
P0(W)(No-load
losses)
Tn haongn mch1200CPk120(load
losses)
in pngn mch
Uk(%)(Impedance
voltage)
Trnglng
G(kg)(Weight)
W L H A
750 12.3 1082.5 2430 8400 6 3500 960 1880 1740 820
1000 16.4 1443.4 2700 9660 6 4100 920 1940 1890 820
1250 20.6 1804.2 3150 13400 6 4640 920 1970 1980 820
1600 26.3 2309.4 3600 14100 6 4970 1170 2030 2140 1070
2000 32.9 2886.8 4230 16600 6 5940 1170 2120 2280 1070
2500 41.2 3608.4 4950 20000 6 7210 1310 2240 2280 1070
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
22/23
- 22 -
1111..YYuuccu thng tin t hngIInnqquuiirryy,,OOrrddeerr
Tit mc Ni dung Items ContentLoi TypeCong sut KVA Rated capacity KVASo pha 03 Number of
phasesThree phases
Tan so 50 Hz Frequency 50 Hzien ap s cap( KV)
15 22 35 22&15Hoac khac
HV ratedvoltage (KV)
15 22 35 22&15others
Nac ieu chnhben s cap
5 2x2,5%Hoac khac
HV tappingrang
5 2x2,5%Hoac khac
ien ap th cap(KV)
0.4 0.69 LV ratedvoltage (KV)
0.4 0.69
Phng phapieu chnh
Khong bo ieu chnh
Co bo ieu chnh
Changingmethod
With off-circuit tap changingWith on-circuit tap changing
To au day Dyn-11 Yyn-0Yd-11 Ynd-11
Connectionsymbol
Dyn-11 Yyn-0Yd-11 Ynd-11
ien ap nganmach (%) 4 6 8
Short-circuitimpedance(%) 4 6 8
Cac dung sai theo tieu chuan IEC - Tolerances in accordance with IEC standard
1. a.Tong ton hao +10% tong ton hao 1. a.Total losses +10% Tolal losses
b. Ton hao khongtai hoac co tai:
+15% ton hao khongtai hoac co tai vi ieukien la dung sai tongton that khong vtqua.
b.load or no-load loss: +15% of each load or no-
load losses, provied that the
tolerance for total losses is
not exceeded
2.T le ien ap 2.Voltage ratio
T le ien ap danhnh ( nac nhmc)
Di cac gia tr sau:
a. +0.5% gia tr nhmc qui nh
b. ty le phan tram cuat le ien ap qui nhtng ng 1/10 cuaphan tram ien apngan mach nh mco c
Rated voltage ratio (on
principal tapping)
The lower of the folowing
values:
a. +0.5% for principal value
b. 1/10 of actual
percentage impedance on
the principal tapping
T le ien ap nacieu chnh khac: +1% tr cac trnghp ngoai le ac biet
Voltage ratio on other
tapping
+1% except special cases
3.ien ap ngan machtai dong ien nh mc
10% 3.Short-circuit voltage atrated current
10%
4. ien ap ngan machtai nhng nac ieuchnh khac
15% gia tr cho phepoi vi nac ieu chnhnay
4.Short-circuit voltage at
other tappings15% rated value for this
tapping
5.Dong khong tai +30% dong khong taiqui nh
5.No-load current +30% rated no-load current
6.Mc o on Khong co dung sai 6.Noise level No tolerance
-
8/13/2019 Catalogue Mba Kho Ge 2009 4
23/23
Cap cach ienF H
Insulationclass F H
Phng phaplam mat
T nhienQuat cng bc
Coolingmethod
Air natural(AN)(AN)/Air-forced(AF)
Cap bao ve IP00 IP20 IP30 IP23 Protectiondegree
IP00 IP20 IP30 IP23
Vat lieu votu Thep vi sn tnh ien
Thep khong r
Enclosure
material
Steel sheet(with static paint)
Stainless steel sheetong ho nhieto va hop ieukhien nhiet o
ong ho nhiet o
ong ho ieu khien nhiet oKhong
Temperature thermometer
Temperature controllerNone
Quat Co Khong Fan Yes NoHnh thc cuaien ap ha i ra
Thong thngKhac
Form ofoutgoing
ConventionalOther
o cao
so vimatncbienNhieto lnnhatNhieto nhonhat
Tnh
trangchung
Trongnha/Ngoaitri
Thap hn hoac bang 1000
40
-5 ( trong nha) -30(ngoaitri)
Trong nha Ngoai tri
Service
conditions
1000 and lower
40
-5 (indoors) -30(outdoors)
Indoor outdoor
ong goi PackingSo lng athang ( May)
Quantitiesordered(unit)
Thi gian giaohang
Time ofdelivery
Phng tien
giao hang
Delivery taking
Van chuyen Transportationiem giao hang Delivery pointac iem khac Miscellaneous