Fixed-Mounted Circuit-Breaker Switchgear
Type 8DA and 8DB up to 40.5 kV, Gas-InsulatedMedium-Voltage Switchgear Catalog HA 35.11 2014
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
2/63
R
-HA35-170.tif
R-HA35-171.tif
R-HA35-132.tif
R-HA35-172.tif
ApplicationPublic power supplysystem
Application Industry
ApplicationOffshore and
industry
ApplicationTraction power supply
R-HA35-174.tif
R-HA35-173.tif
2 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
3/63
3Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Contents
Application Page
Versions, typical uses,ratings 4 and 5
Requirements
Features, safety, technology 6 and 7
Technical data
Electrical data 8 and 9Room planning 10 and 11Shipping data 12Classification 13
Dimensions
Front views, sections,floor openings, fixing points 14 to 25
Product range
Single-busbar panels 26 and 27Double-busbar panels 28 to 35
Design
Basic panel design 36 and 37Gas compartment scheme 38 and 39
Components
Vacuum circuit-breaker 40 and 41Three-position disconnector 42 and 43Control board 44Busbar, busbar components 45Current and voltage transformers 46 and 47Panel connection 48 and 49Panel connection (commercially availablecable plugs and bar connections) 50Indicating and measuring equipment 51 to 54
Protection, control, measuring andmonitoring equipment 55ANSI design 56 to 59
Standards
Standards, specifications, guidelines 60 and 61
First 8DA10 Year of manufacture 1982 62
Fixed-Mounted Circuit-Breaker Switchgear
Type 8DA and 8DB up to40.5 kV, Gas-InsulatedMedium-Voltage Switchgear
Catalog HA 35.11 2014
Invalid: Catalog HA 35.11 2012
www.siemens.com/medium-voltage-switchgear
The products and systems described in this catalogare manufactured and sold according to a certifiedmanagement system (acc. to ISO 9001, ISO 14001and BS OHSAS 18001).
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
4/63
4 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Versions
Application
R-HA
35-137.eps
Circuit-breaker panel 8DA10 Circuit-breaker panel 8DB10 Circuit-breaker panel 8DA11/12
R-HA
35-136.eps
R-HA
35-135.eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
5/63
5Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Typical uses, ratings
Application
Fixed-mounted circuit-breaker switchgear 8DA and 8DB isindoor, factory-assembled, type-tested, single-pole metal-enclosed, metal-clad, SF6-insulated switchgear for single-busbar and double-busbar applications, as well as fortraction power supply systems.
It is used in transformer and switching substations, e.g., in: Power supply companies Power stations
Cement industry
Automobile industry
Iron and steel works
Rolling mills
Mining industry
Textile, paper and food industries
Chemical industry
Petroleum industry
Pipeline installations
Offshore installations Electrochemical plants
Petrochemical plants
Shipbuilding industry
Diesel power plants
Emergency power supply installations
Lignite open-cast mines
Traction power supply systems.
1) 42 kV / 70 kV according to some national requirements2) 95 kV / 185 kV according to some nationa l requirement s
Electrical data (maximum values) and dimensions
Single-busbar and double-busbar switchgear
Rated voltage kV 12 24 36 40.5
Rated frequency Hz 50 / 60 50 / 60 50 / 60 50 / 60
Rated short-durationpower-frequency
withstand voltage kV 28 1) 50 70 85 2)Rated lightning impulsewithstand voltage kV 75 125 170 185
Rated peakwithstand current kA 100/104 100/104 100/104 100/104
Rated short-circuitmaking current kA 100/104 100/104 100/104 100/104
Rated short-timewithstand current 3 s kA 40 40 40 40
Rated short-circuitbreaking current kA 40 40 40 40
Rated normal currentof the busbar A 5000 5000 5000 5000
Rated normal currentof feeders A 2500 2500 2500 2500
Width mm 600 600 600 600Depth Single busbar mm Double busbar mm
16252665
16252665
16252665
16252665
Height Standard mm With high low-voltage
compartment mm
2350
2700
2350
2700
2350
2700
2350
2700
Single-pole and double-poletraction power supply switchgear
Rated voltage kV 17.5 27.5
Rated frequency Hz 16.7 50/60
Rated short-durationpower-frequencywithstand voltage kV 50 95
Rated lightning impulsewithstand voltage kV 125 200
Rated peakwithstand current kA 80 80
Rated short-circuitmaking current kA 80 80
Rated short-timewithstand current 3 s kA 31.5 31.5
Rated short-circuitbreaking current kA 31.5 31.5
Rated normal currentof the busbar A 3150 3150
Rated normal currentof feeders A 2500 2500
Width mm 600 600
Depth Single-pole traction
switchgear mm Double-pole traction
switchgear mm
865
1245
865
1245
Height Standard mm With high low-voltage
compartment mm
2350
2700
2350
2700
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
6/63
6 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Requirements
Environmental independence
The enclosed high-voltage part of 8DA and 8DB switchgearis suitable for applications under aggressive ambientconditions, such as: Saline air
Air humidity
Dust
Condensation.
It is tight to ingress of foreign objects, such as: Dust
Pollution
Small animals.
The application is independent of the site altitude.
Compact design
Thanks to the use of SF6insulation, compact dimensions arepossible.
Thus:
Existing switchgear rooms can be used effectively New constructions cost little
Costly city-area space is saved.
Maintenance-free design
Switchgear housings designed as sealed pressure systems,maintenance-free switching devices and enclosed cableplugs ensure: Maximum supply reliability
Personnel safety
Sealed-for-life design according to IEC 62271-200(sealed pressure system)
Reduced operating costs
Cost-efficient investment.
Innovation
The use of digital secondary systems and combinedprotection and control devices ensures Clear integration in process control systems
Flexible and highly simplified adaptation to new systemconditions and thus to cost-efficient operation.
Service life
Under normal operating conditions, the expected servicelife of gas-insulated switchgear 8DA and 8DB is at least35 years, probably 40 to 50 years, taking the tightness of
the enclosed high-voltage part into account. The service lifeis limited by the maximum number of operat ing cycles ofthe switching devices installed: For circuit-breakers, according to the endurance class
defined in IEC 62271-100
For three-position disconnectors and earthing switches,according to the endurance class defined in IEC 62271-102.
Personal safety
Safe-to-touch and hermetically sealed primary enclosure
All high-voltage parts including the cable terminations,busbars and voltage transformers are metal-enclosed
Capacitive voltage detecting system to verify safe isolationfrom supply
Operating mechanisms and auxiliary switches safely acces-sible outside the primary enclosure (switchgear housings)
Due to the system design, operation is only possible withclosed switchgear enclosure
Standard degree of protection IP 65 for all high-voltageparts of the primary circuit, IP 3XD for the switchgearenclosure according to IEC 60529
High resistance to internal arcs by logical mechanicalinterlocks and tested switchgear enclosure
Panels tested for resistance to internal faults up to 40 kA
Logical mechanical interlocks prevent maloperation
Make-proof earthing by means of the vacuum circuit-
breaker.
Security of operation
Hermetically sealed primary enclosure independent ofenvironmental effects (pollution, humidity and smallanimals)
Maintenance-free in an indoor environment according toIEC 62271-1
Two-phase and three-phase short-circuits between theprimary conductors are excluded by the single-poleprimary enclosure
In isolated or compensated systems, low-currentearth-fault currents are self-extinguishing
Operating mechanisms of switching devices accessibleoutside the primary enclosure (switchgear housings)
Metal-enclosed, plug-in inductive voltage transformersmounted outside the SF6switchgear housings
Current transformers as ring-core current transformersmounted outside the SF6switchgear housings
Complete switchgear interlocking system with logicalmechanical interlocks
Bolted switchgear housings sealed for life
Minimum fire load
Option: Aseismic design.
Reliability Type and routine-tested
Standardized, NC production processes
Quality assurance in accordance with DIN EN ISO 9001
More than 70,000 switchgear panels of Siemens inoperation worldwide for many years.
Features Safety
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
7/63
7Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Technology
Requirements
General
Single-pole enclosure of the primary part by modularswitchgear housings made of corrosion-resistantaluminum alloy
Insulating gas SF6 Three-position disconnector as busbar disconnector and
feeder earthing switch
Make-proof earthing by means of the vacuum circuit-breaker
Compact dimensions due to SF6insulation
Hermetically bolted switchgear housings made ofcorrosion-resistant aluminum alloy
Single-pole metal-enclosed, SF6-insulated busbars
Cable connection with inside-cone plug-in system, or forconnection of gas-insulated and solid-insulated bars
Wall-standing or free-standing arrangement
Installation and extension of existing switchgear at bothends without modification of existing panels.
Interlocks
According to IEC 62271-200
Logical mechanical interlocks prevent maloperation
Three-position disconnector can only be operated withcircuit-breaker in OPEN position
Circuit-breaker can only be operated with three-positiondisconnector in end position and operating lever removed
Locking device for circuit-breaker
Locking device for three-position disconnector
Feeder earthed locking device
Option: Electromagnetic interlocks.
Modular design
Replacement of the panel connection housings or thecircuit-breaker possible without interrupting busbaroperation
Low-voltage compartment removable, plug-in bus wires
Extension of double-busbar switchgear 8DB10 possiblewithout interrupting operation
Option: Extension of single-busbar switchgear 8DA10possible without interrupting operation.
Instrument transformers
Current transformers not subjected to dielectric stress
Metal-enclosed, plug-in and disconnectable voltagetransformers.
Vacuum circuit-breaker
Maintenance-free under normal ambient conditionsaccording to IEC 62271-1
No relubrication or readjustment
Vacuum interrupters sealed for life
Up to 10,000 operating cycles (maintenance-free)
Option: Up to 30,000 operating cycles(maintenance required).
Secondary systems
Customary protection, measuring and control equipment
Option: Numerical multifunction protection relay withintegrated protection, control, communication, operatingand monitoring functions
Can be integrated in process control systems.
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
8/63
8 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Electrical data, filling pressure, temperature for single-busbar and double-busbar switchgear
Technical data
Commonelectricaldata, fillingpressure andtemperature
Rated insulation level Rated voltage Ur kV 12 24 36 40.5
Rated short-duration power-frequencywithstand voltage Ud: phase-to-earth, open contact gap kV across the isolating distance kV
28 1)32 1)
50 2)602)
7080
85 3)90 3)
Rated lightning impulse withstand voltage Up: phase-to-earth, open contact gap kV
across the isolating distance kV
75
85
125
145
170
195
185 4)
2204)
Rated frequency fr Hz 50 / 60 50 / 60 50 / 60 50 / 60
Rated normal current Ir for the busbar9)
A A A A
A A
125020002500315040005000
125020002500315040005000
125020002500315040005000
125020002500315040005000
Rated filling level pre for the busbar 70 /120 kPa at 20 C
Minimum functional level pme 50/ 100 kPa at 20 C
Ambient air temperature 5 C to + 55 C
Data of the switchgear panels
Circuit-breakerpanel, discon-
nector panel6)
Rated normal current Ir9)
A
A
A A A
12501600
200023002500
12501600
200023002500
12501600
200023002500
12501600
200023002500
Rated short-time withstand current Ik tk= 3 s up to kA 40 40 40 40
Rated peak withstand current Ip5) up to kA 100/104 100/104 100/104 100/104
Rated short-circuit making current Ima5)
up to kA 100/104 100/104 100/104 100/104
Rated short-circuit breaking current Isc up to kA 40 40 40 40
Electrical endurance ofvacuum circuit-breakers
at rated normal current 10,000 operating cycles
at rated short-circuit breaking current 50 breaking operations
Rated filling level pre for feeders 70/ 120 kPa at 20 C
Minimum functional level pme 50/ 100 kPa at 20 C
Bus section-alizer, bus
coupler7)
Rated normal current Ir9)
A A
A A
12502000
23002500
12502000
23002500
12502000
23002500
12502000
23002500
Rated short-time withstand current Ik tk= 3 s up to kA 40 40 40 40
Rated peak withstand current Ip5) up to kA 100/104 100/104 100/104 100/104
Rated short-circuit making current Ima5) up to kA 100/104 100/104 100/104 100/104
Rated short-circuit breaking current Isc up to kA 40 40 40 40
Electrical endurance ofvacuum circuit-breakers
at rated normal current 10,000 operating cycles
at rated short-circuit breaking current 50 breaking operations
Rated filling level pre for feeders 70/ 120 kPa at 20 C
Minimum functional level pme 50/ 100 kPa at 20 C
Cable connec-tion panel,meteringpanel
Rated normal current Ir8)9) A
A A A
1250160020002500
1250160020002500
1250160020002500
1250160020002500
Rated short-time withstand current Ik tk= 3 s up to kA 40 40 40 40
Rated peak withstand current Ip5) up to kA 100/104 100/104 100/104 100/104
Rated filling level pre for feeders 70/ 120 kPa at 20 C
Minimum functional level pme 50/ 100 kPa at 20 C
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
9/63
9Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Electrical data, filling pressure, temperature for single-poleand double-pole traction power supply switchgear
Technical data
Common electricaldata, fillingpressure andtemperature
Rated insulation level Rated voltage Ur kV 17.5 27.5
Nominal voltage according to IEC 60850/EN 50163 kV 15 25
Rated short-duration power-frequencywithstand voltage Ud: phase-to-earth, open contact gap kV across the isolating distance kV
5060
95110
Rated lightning impulse withstand voltage Up: phase-to-earth, open contact gap kV across the isolating distance kV
125145
200220 4)
Rated frequency fr Hz 16.7 50/60
Rated normal current Ir for the busbar9) A
A A A
1250200025003150
1250200025003150
Rated filling level pre for the busbar 70 /120 kPa at 20 C
Minimum functional level pme 50/ 100 kPa at 20 C
Ambient air temperature 5 C to +55 C
Data of the switchgear panels
Circuit-breakerpanel, disconnec-tor panel
Rated normal current Ir9) A
A A A A
12501600200023002500
12501600200023002500
Rated short-time withstand current Ik tk= 3 s up to kA 31.5 31.5
Rated peak withstand current Ip5) up to kA 80 80/82
Rated short-circuit making current Ima5) up to kA 80 80/82
Rated short-circuit breaking current Isc up to kA 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal current 20,000 operating cycles
at rated short-circuit breaking current 50 breaking operations
Rated filling level pre for feeders 70 /120 kPa at 20 C
Minimum functional level pme 50/ 100 kPa at 20 C
Bus sectionalizer Rated normal current Ir9) A
A A
A
125020002300
2500
125020002300
2500Rated short-time withstand current Ik tk= 3 s up to kA 31.5 31.5
Rated peak withstand current Ip5) up to kA 80 80/82
Rated short-circuit making current Ima5) up to kA 80 80/82
Rated short-circuit breaking current Isc up to kA 31.5 31.5
Electrical endurance ofvacuum circuit-breakers
at rated normal current 20,000 operating cycles
at rated short-circuit breaking current 50 breaking operations
Rated filling level pre for feeders 70 /120 kPa at 20 C
Minimum functional level pme 50/ 100 kPa at 20 C
Footnotes for pages 8 and 9
1) Higher values of the rated short-duration power-frequency withstand voltage available with:
- 42 kV for phase-to-earth and open contact gap, as well as- 48 kV across the isolating distance
2) Higher values of the rated short-duration power-frequency withstand voltage available with:- 65 kV for phase-to-earth and open contact gap, as well as- 75 kV across the isolating distance
3) Higher values of the rated short-duration power-frequency withstand voltage available with:- 95 kV for phase-to-earth and open contact gap, as well as- 110 kV across the isolating distance
4) Higher values of the rated lightning impulse withstand voltage available with:- 190 kV for phase-to-earth and open contact gap, as well as- 230 kV across the isolating distance
5) Higher value applies to 60 Hz
6) Disconnector panel available for single-busbar switchgear 8DA10
7) Bus coupler available for double-busbar switchgear 8DB10
8) Rated normal current Irfor cable connection panels9) Maximum permissible normal current dependent on ambient air temperature
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
10/63
10 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Room planning
Technical data
Wall-standing arrangement (top view) Free-standing arrangement (top view)
Room planning for single-busbar switchgear 8DA10
Room planning for traction power supply switchgear 8DA12
Room planning for traction power supply switchgear 8DA11
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
11/63
11Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Switchgear installation
Wall-standing arrangement without rear wall (IAC FL)
Free-standing arrangement without rear wall (IAC FL)
Free-standing arrangement with rear wall (IAC FLR).
Room dimensions
See dimension drawings above.Room height: 2900 mm.If there are any busbar components, the minimum roomheight may have to be higher.For switchable busbar components in 8DB10, free-standingarrangement is required.
Door dimensions
The door dimensions depend on the dimensions of theindividual panels (see pages 14 to 25).
Switchgear fixing
For floor openings and fixing points of the switchgear,see pages 14 to 25
Foundations: Steel girder construction Steel-reinforced concrete with foundation rails,
welded or bolted on.
Panel dimensions
See pages 14 to 25.
* Depending on nationalrequirements
** Lateral wall distance 500 mm optionally required on the left
or on the right
*** Lateral minimum wall distance
100 mm optionally possibleon the left or on the right
Room planning
Technical data
Wall-standing arrangement (top view) Free-standing arrangement (top view)
Room planning for double-busbar switchgear 8DB10
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
12/63
12 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Shipping data
Technical data
Transport
Single-busbar switchgear 8DA10and traction power supplyswitchgear 8DA11/12 is deliveredin transport units comprising upto four panels.
Double-busbar switchgear8DB10 is delivered in transportunits comprising up to threepanels.Please observe the following: Transport facilities on site
Transport dimensions andtransport weights
Size of door openings inbuilding.
Packing
Means of transport: Truck
Panels on pallets Open packing with PE
protective foil.
Means of transport: Ship andairplane
Panels on pallets In closed crates with sealed
upper and lower PE protectivefoil
With desiccant bags With sealed wooden base Max. storage time: 6 months.
Long-time packing Panels on pallets
In closed crates with sealed,aluminum-coated PEprotective foil
With desiccant bags With sealed wooden base Max. storage time: 12 months.
1) Average values with LV compartment 850 mm depending on thedegree to which panels are equipped
Transport dimensions, transport weights 1)
Panel widths Transport dimensionsWidth x Height x Depth
Transport weightwith packing
Transport weightwithout packing
mm mm mm mm approx. kg approx. kg
Single-busbar switchgear 8DA10Means of transport: Truck
1 600 1764 2550 1870 850 750
2 600 1764 2550 1870 1700 1500
3 600 2400 2550 1870 2550 2250
4 600 2964 2550 1870 3400 3000
Means of transport: Ship and airplane
1 600 1764 2700 1888 850 750
2 600 1764 2700 1888 1700 1500
3 600 2400 2700 1888 2550 2250
4 600 2964 2700 1888 3400 3000
Double-busbar switchgear 8DB10
Means of transport: Truck
1 600 1870 2550 3124 1300 1200
2 600 1870 2550 3124 2600 2400
3 600 2416 2550 3124 3900 3600
Means of transport: Ship and airplane
1 600 1888 2850 3124 1300 1200
2 600 1888 2850 3124 2600 2400
3 600 2440 2850 3124 3900 3600
Traction power supply switchgear 8DA11/12Means of transport: Truck
1 600 1764 2550 1870 600 500
2 600 1764 2550 1870 1200 1000
3 600 2400 2550 1870 1800 1500
4 600 2964 2550 1870 2400 2000
Means of transport: Ship and airplane
1 600 1764 2700 1888 600 500
2 600 1764 2700 1888 1200 1000
3 600 2400 2700 1888 1800 1500
4 600 2964 2700 1888 2400 2000
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
13/63
13Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Classification
Technical data
Classification of 8DA and 8DB switchgear according to IEC 62271-200
Design and construction
Partition class PM (metallic partition)
Loss of service continuity category LSC 2
Accessibility to compartments
(enclosure)Busbar compartmentSwitching-device compartmentLow-voltage compartmentCable compartment
Tool-basedTool-basedTool-basedTool-based
Internal arc classification
Designation of the internal arcclassification IACIAC class for:Wall-standing arrangementFree-standing arrangement
IAC A FL 40 kA, 1 sIAC A FLR 40 kA, 1 s
Type of accessibility A
F L R
Switchgear in closed electrical service location, accessfor authorized personnel only according to IEC 62271-200FrontLateralRear (for free-standing arrangement)
Rated short-time withstand current 40 kA
Rated duration of short-circuit 1 s
Classification of 8DA and 8DB switchgear according to IEEE Std C37.20.7 -2007
Internal arc classification
Designation of the internal arcclassification IACIAC class for:Wall-standing arrangementFree-standing arrangement
Type 1B 40 kA, 0.5 sType 2B 40 kA, 0.5 s
Type of accessibility
Type 1B Type 2B
Switchgear in closed electrical service location,access for authorized personnel only according
to IEEE Std C37.20.7-2007FrontFront, lateral, rear (for free-standing arrangement)
Rated short-time withstand current 40 kA
Rated duration of short-circuit 0.5 s
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
14/63
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
15/63
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
16/63
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
17/63
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
18/63
18 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
DimensionsFront views, sections, floor openings, fixing points for 8DB10
Circuit-breaker panel up to 2500 A
Bus coupler up to 2500 A
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
19/63
19Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
DimensionsFront views, sections, floor openings, fixing points for 8DB10
Bus sectionalizer with panel connection up to 2500 A (busbar system 1 and 2)
Bus sectionalizer up to 2500 A (busbar system 1 and 2)
Legend and footnotes
for pages 18 and 19
1Fixing hole for26 mm x 45 mm
2 Base frame
3Floor opening forhigh-voltage cables
4 Area for floor openings
for control cables
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
20/63
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
21/63
Front views, sections, floor openings, fixing points for 8DB10
21Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Dimensions
Legend and footnotes
for pages 20 and 21
1Fixing hole for26 mm x 45 mm
2 Base frame
3Floor opening forhigh-voltage cables
4 Area for floor openings
for control cables
Cable connection panel up to 2500 A
Bus sectionalizer up to 2500 A (busbar system 1 and 2)
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
22/63
22 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Dimensions
Metering panel
Dummy panel
Front views, sections, floor openings, fixing points for 8DB10
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
23/63
23Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Dimensions
Legend and footnotes
for pages 22 and 23
1Fixing hole for26 mm x 45 mm
2 Base frame
3Floor opening forhigh-voltage cables
4 Area for floor openings
for control cables
Front views, sections, floor openings, fixing points for 8DB10 ANSI
Example: Circuit-breaker panel
with three-position disconnector
at the feeder (option) up to
2000 A
Example: Circuit-breaker panel with
disconnector bypass up to 2000 A
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
24/63
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
25/63
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
26/63
26 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Single-busbar panels 8DA10
Product range
Three-positiondisconnector
Vacuumcircuit-breaker
Plug-in voltagetransformer (directlyplugged or withcable connection)
Voltage transformerwith or withoutthree-position dis-connector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-positiondisconnector
Surge arrester
Panel connectionwith inside-cone plugor bar connection
Zero-sequencecurrent transformer
Top-mounted bussectionalizer
HA35-2679
eps
Circuit-breaker panel Disconnector panel
Bus sectionalizer (2 panels)
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
27/63
27Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Single-busbar panels 8DA10
Product range
Three-positiondisconnector
Vacuumcircuit-breaker
Plug-in voltagetransformer (directlyplugged or withcable connection)
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-positiondisconnector
Panel connectionwith inside-cone plugor bar connection
HA35-2679
eps
Metering panel Cable connection panel
Bus sectionalizer (2 panels)
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
28/63
28 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Double-busbar panels 8DB10
Product range
Three-positiondisconnector
Vacuumcircuit-breaker
Plug-in voltagetransformer (directlyplugged or withcable connection)
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-positiondisconnector
Surge arrester
Panel connectionwith inside-cone plugor bar connection
Zero-sequencecurrent transformer
Top-mountedbus sectionalizer
HA35-2679
eps
Circuit-breaker panel Bus coupler
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
29/63
29Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Double-busbar panels 8DB10
Product range
Three-positiondisconnector
Plug-in voltagetransformer(directly plugged)
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-positiondisconnector
Panel connectionwith inside-cone plugor bar connection
HA35-2679
eps
Cable connection panelMetering panel
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
30/63
Bus sectionalizer (busbar system 1 and 2)
30 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Double-busbar panels 8DB10
Product range
Three-positiondisconnector
Vacuumcircuit-breaker
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-position
disconnector
Panel connectionwith inside-cone plugor bar connection
Zero-sequencecurrent transformer
HA35-2679
eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
31/63
Bus sectionalizer (busbar system 1)
31Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Double-busbar panels 8DB10
Product range
Three-positiondisconnector
Vacuumcircuit-breaker
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-position
disconnector
HA35-2679
eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
32/63
Bus sectionalizer (busbar system 2)
32 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Double-busbar panels 8DB10
Product range
Three-positiondisconnector
Vacuumcircuit-breaker
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-position
disconnector
HA35-2679
eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
33/63
Bus sectionalizer (busbar system 1 and 2)
33Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Double-busbar panels 8DB10
Product range
Three-positiondisconnector
Vacuumcircuit-breaker
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-position
disconnector
HA35-2679
eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
34/63
34 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Double-busbar panels 8DB10
Product range
Bus sectionalizer (busbar system 1 and 2)
Three-positiondisconnector
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-positiondisconnector
HA3
5-2679
eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
35/63
35Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Single-pole and double-pole single-busbar panels 8DA11/12
Product range
Single-pole circuit-breaker panel Double-pole circuit-breaker panel
Three-positiondisconnector
Vacuumcircuit-breaker
Plug-in voltagetransformer (directlyplugged or withcable connection)
Voltage transformerwith or withoutthree-positiondisconnector
Current transformer
Capacitive voltagedetecting system
Busbar earthing switch
and make-proof
earthing switch
Busbar connectionwith or withoutthree-positiondisconnector
Surge arrester
Panel connectionwith inside-cone plugor bar connection
Zero-sequencecurrent transformer
Top-mountedbus sectionalizer
HA35-2679
eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
36/63
36 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Design
Insulating system Switchgear housing filled with SF6gas Features of SF6gas: Non-toxic Odorless and colorless Non-inflammable Chemically neutral Heavier than air Electronegative (high-quality
insulator) Pressure of the SF6gas in the
switchgear housing dependent onthe electrical ratings (relativepressure at 20 C):
Rated filling level: 70 kPa to 120 kPa Design pressure: 190 kPa Design temperature of the SF6gas:
90 C Operating pressure of bursting disc:
300 kPa
Bursting pressure: 600 kPa Gas leakage rate: < 0.1 % per year.
Panel design Factory-assembled, type-tested Single-pole metal-enclosed,
metal-clad Hermetically bolted switchgear
housings made of corrosion-resistant aluminum alloy
Switchpanel poles arranged onebehind the other
Maintenance-free in an indoor environ-ment (IEC 62271-1)
Degree of protection
IP 65 for all high-voltage parts ofthe primary circuit
IP 3XD for the switchgear enclosure Option: IP 31D for the switchgear
enclosure Option: IP 41 for the low-voltage
compartment Vacuum circuit-breaker Three-position disconnector for
disconnecting and earthing Make-proof earthing by means of
the vacuum circuit-breaker Cable connection with inside-cone
plug-in system according to
EN 50 181 Wall-standing or free-standingarrangement
Instrument transformers removable,as they are located outside the gascompartments
Subframe, front cover, rear coverand end walls powder-coated incolor light basic (SN 700)
Low-voltage compartment remov-able, plug-in bus wires
Standardized production processesand certified quality and environ-mental management system accord-
ing to ISO 9001 and ISO 14001.
Panel design (examples)
Legend for 8DA10 and
8DB10
1Low-voltagecompartment
2Electronic control board,e.g. multifunctionprotection
3Operating mechanismand interlock for three-position disconnector,as well as mechanicalposition indicatorsfor three-positiondisconnector andcircuit-breaker
4Manometer for gasmonitoring of feeder
gas compartments5Circuit-breaker operating
mechanism6Voltage detecting system
8DA10
Panel for single-busbar switchgear
8DB10
Panel for double-busbar switchgear
Basic panel design
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
37/63
37Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Single-pole and double-pole design
for AC traction power supply
Typical uses
Single-pole and double-pole panels8DA11/12 for the supply of over-
head contact line sections in ACtraction power supply systems
Double-pole panels 8DA12 forapplication in traction power supplysystems with autotransformers, e.g.for high-speed railway traffic.
Panel design
Panel design based on standardversion of single-busbar switchgear8DA10.
8DA11
Single-pole switchgear panel fortraction power supply.
8DA12
Double-pole switchgear panel fortraction power supply.
Basic panel design
Design
Panel design (examples)
Legend for 8DA11
and 8DA12
1Low-voltagecompartment
2Electronic control board,e.g. multifunctionprotection
3Operating mechanismand interlock for three-position disconnector,as well as mechanicalposition indicatorsfor three-positiondisconnector andcircuit-breaker
4Manometer for gasmonitoring of feeder
gas compartments5Circuit-breaker operating
mechanism6Voltage detecting system
8DA11
Single-pole switchgear panel for traction power supply
8DA12
Double-pole switchgear panel for traction power supply
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
38/63
Gas compartment scheme
Sealed pressure system (accordingto IEC 62271-1)
No refilling required throughoutthe entire service life
Gas compartments distributed toseveral areas
Gas pressure manometers arrangedat the switchgear front
Gas pressure can be read with secu-rity even without auxiliary voltagesupply
SF6gas filling equipment with non-return valve arranged at the switch-gear front beside the associatedgas pressure manometer
Gas pressure manometers with twosignaling contacts for gas pres-
sure too low / gas pressure too highindication
Option: Gas pressure manometerswith three signaling contacts forgas pressure too low / very low andgas pressure too high indication
Option: Gas pressure manometerswith temperature and pressurecompensation.
Arrangement of gas compartments in 8DA10
Single-busbar panel 8DA10
Single-busbar switchgear 8DA10
Gas-tight
bushing
Bushingpervious to gas
Legend for 8DA10
1 Busbar L1 (manometer B11)2 Busbar L2 (manometer B12)3 Busbar L3 (manometer B13)4 Circuit-breaker L1, L2, L3 (manometer B0)5 Top-mounted bus sectionalizer L1, L2, L3
(manometer B16)
38 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Gas compartment scheme of 8DA10
Design
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
39/63
Double-busbar panel 8DB10
Double-busbar switchgear 8DB10
Gas-tight
bushing
Bushingpervious to gas
Arrangement of gas compartments in 8DB10
Legend for 8DB10
1 Busbar system 1, L1 (manometer B11)2 Busbar system 1, L2 (manometer B12)3 Busbar system 1, L3 (manometer B13)4 Busbar system 2, L1 (manometer B21)5 Busbar system 2, L2 (manometer B22)6 Busbar system 2, L3 (manometer B23)7 Three-position disconnector, busbar system 1, L1, L2, L3
(manometer B1)8 Disconnector, busbar system 2, L1, L2, L3 (manometer B2)9 Circuit-breaker L1, L2, L3 (manometer B0)10 Top-mounted bus sectionalizer, busbar system 1, L1, L2, L3
(manometer B16)11 Top-mounted bus sectionalizer, busbar system 2, L1, L2, L3
(manometer B26)
39Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
DesignGas compartment scheme of 8DB10
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
40/63
40 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Features
According to IEC 62271-100 (for standards, see page 60)
Application in hermetically bolted switchgear housings inconformity with the system
Vacuum interrupter in SF6-filled switchgear housing
Maintenance-free for indoor installation according toIEC 62271-1
Individual secondary equipment
A metal bellows is used for gasketless separation betweenthe SF6insulation and the vacuum (already used withsuccess for over 2 million vacuum interrupters).
Trip-free mechanism
The vacuum circuit-breaker is fitted with a trip-freemechanism according to IEC 62271-100.
Switching duties and operating mechanisms
The switching duties of the vacuum circuit-breaker aredependent, among other factors, on its type of operating
mechanism.Motor operating mechanism Motor-operating stored-energy mechanism For auto-reclosing (K) For synchronization and rapid load transfer (U)Further operating mechanism features Located outside the switchgear housings in the operating
mechanism box and behind the control board
Stored-energy spring mechanism for 10,000 operating cycles
Optional:Stored-energy spring mechanism for 30,000 operating cycles.
Operating mechanism functions
Motor operating mechanism1)(M1 *)In the case of motor operating mechanism, the closing springis charged by means of a motor and latched in the chargedposition (spring charged indication is visible). Closing iseffected either by means of an ON pushbutton or a closingsolenoid. The closing spring is recharged automatically (forauto-reclosing).
Endurance class of circuit-breaker
Function Class Standard Property of 8DA and 8DB
BREAKING M2 IEC 62271-100 10,000 times mechanically withoutmaintenance
E2 IEC 62271-100 10,000 times rated normal currentwithout maintenance50 times short-circuit breakingcurrent without maintenance
C2 IEC 62271-100 Very low probability of restrikes
Operating times
Closing time Closing solenoid < 95 ms
Opening time 1stshunt release2ndshunt releaseUndervoltage release
< 65 ms< 55 ms< 55 ms
Arcing time at 50 Hz at 60 Hz
< 15 ms< 12 ms
Break time at 50 Hz 1stshunt release2ndshunt releaseUndervoltage release
< 80 ms< 70 ms< 70 ms
Dead time 300 msTotal charging time < 15 s
Vacuum circuit-breaker
Components
Circuit-breaker operating mechanism 3AH49for 8DA and 8DB
1 ON pushbutton2 Auxiliary switch S1
3 Closing coil for CLOSE 4 Tripping coil for OPEN 5 OFF pushbutton
6 Operating shaft for circuit-breaker 7 Opening spring 8 Operations counter 9 Position indicator for circuit-breaker10 Closing spring charged / not charged indicator11 Auxiliary switch12 Closing spring13 Gear with hand crank coupling14 Rating plate
R-HA35
-138.eps
14
12
10
11
7
8
9
132
1
34
5
6
Abbreviations for switching duties:U = Synchronization and rapid load transferK = Auto-reclosing
1) Motor rating at 24 V to 250 V DC: max. 650 W 110 V and 240 V AC: max. 850 VA* Item designation
For further technical data and description of typicalapplications, please refer also to Catalog HG 11.04
3AH4 Vacuum Circuit-Breakers
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
41/63
41Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Vacuum circuit-breaker
Components
Secondary equipment
The scope of the secondary equipment of the vacuumcircuit-breaker depends on the type of application and offersa wide range of possible variations, allowing almost everyrequirement to be satisfied.
Closing solenoid Type 3AY15 10 (Y9 *)
For electrical closing.
Shunt releases
Types: Standard: 3AY15 10 (Y1 *) Option: 3AX11 01 (Y2 *), with energy store
Tripping by protection relay or electrical actuation.
Undervoltage release
Type 3AX11 03 (Y7 *)
Comprising:
Energy store and unlatching mechanism Electromagnetic system, which is permanently connected
to voltage while the vacuum circuit-breaker is closed;tripping is initiated when this voltage drops
Connection to voltage transformers possible.
Anti-pumping
Function: If constant CLOSE and OPEN commands arepresent at the vacuum circuit-breaker at the same time,the vacuum circuit-breaker will return to the open positionafter closing. It remains in this position until a new CLOSEcommand is given. In this manner, continuous closing andopening (= pumping) is avoided.
Circuit-breaker tripping signal
For electrical signaling (as pulse > 10 ms), e.g. to remotecontrol systems, in the case of automatic tripping(e.g. protection)
Via limit switch (S6 *) and cutout switch (S7 *).
Varistor module
To limit overvoltages to approx. 500 V for protectiondevices (when inductive components are mounted in thevacuum circuit-breaker)
For auxiliary voltages 60 V DC.
Auxiliary switch Type 3SV9 (S1 *)
Standard: 12 NO + 12 NC.
Position switch
Type 3SE4 (S4 *)
For signaling closing spring charged.
Mechanical interlock
Mechanical interlocking to the three-position disconnector
During operation of the three-position disconnector,the vacuum circuit-breaker cannot be operated.
Operating cycle diagram
Examples
Electrical data (curve 1)
Rated short-circuit breaking current 25 kARated normal current 1250 A
Electrical data (curve 2)
Rated short-circuit breaking current 31.5 kARated normal current 2000 A
Rated operating sequences
Rapid load transfer (U): O-t-CO-t-CO (t = 0.3 s, t = 3 min)Auto-reclosing (K): O-t-CO-t-CO (t = 0.3 s, t = 3 min)
O = OPEN operationCO = CLOSE operation with subsequent OPEN operation at
the shortest internal close-open time of the vacuumcircuit-breaker
Possible release combinations
Release1 2 3 4
1st shunt release type type 3AY15 10 2ndshunt release type type 3AY11 01
Undervoltage release type 3AX11 03
Abbreviations: NO = normally open contactNC = normally closed contact * Item designation
Electrical data (curve 3)
Rated short-circuit breaking current 40 kARated normal current 2500 A
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
42/63
42 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Features
Rated normal currents up to 2500 A
Up to 2000 operating cycles for the disconnector
Option: Up to 3000 operating cycles for the disconnector
Up to 1000 operating cycles for the earthing switch
Option: Up to 2000 operating cycles for the earthing switch Operating shaft and contact blades with common centerof rotation and reliable switch position up to the operatingfront of the panel
Gas-tight bushings separate the busbar and circuit-breakerhousings underneath the busbar disconnector contacts
Cable connection and circuit-breaker housings can beremoved without interrupting busbar operation
Maintenance-free.
Switch positions
CLOSED, OPEN, EARTHED or READY-TO-EARTH
CLOSED: Contact blades connected with the busbar:
Main circuit closed between busbar and circuit-breaker OPEN: Main circuit open between busbar and circuit-
breaker: Test voltages for isolating distances are withstood
READY-TO-EARTH: Contact blades connected with theearthing contact
EARTHED: Feeder earthed and short-circuited by closingthe circuit-breaker.
Operating mechanism
Only permissible operations possible due to logicalmechanical interlocks
Mechanically coupled position indicator
Separate operating shafts for the DISCONNECTING,EARTHING and READY-TO-EARTH functions
With manual operating mechanism
Option: With motor operating mechanismMotor rating at 24 V to 250 V DC: max. 100 W 110 V to 240 V AC: max. 130 VA
Same sense of rotation for the switching operations ofthe CLOSE or OPEN functions.
Position indicators of 8DA10
for three-position disconnectorand vacuum circuit-breaker
Feeder OPEN
Feeder CLOSED
Feeder READY-TO-EARTH
Feeder EARTHED
ComponentsThree-position disconnector
Endurance class of three-position disconnector
Function Class Standard Property of 8DA and 8DB
DISCONNECTING M1 IEC 62271-102 2000 times mechanical lywithout maintenance
READY-TO-EARTH 1000 times mechanicallywithout maintenance
EARTHING E2 1) IEC 62271-102 50 times rated short-circuit making current Imawithout maintenance
Endurance class of make-proof earthing switch
Function Class Standard Property of 8DA and 8DB
EARTHING E1 IEC 62271-102 1000 times mechanicallywithout maintenance2 times rated short-circuit making current Imawithout maintenance
1) By closing the circuit-breaker
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
43/63
43Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Position indicators of 8DB10
for three-position disconnectorand vacuum circuit-breaker
Feeder OPEN
Feeder busbar system 1 CLOSED
Feeder busbar system 2 CLOSED
Feeder READY-TO-EARTH
Feeder EARTHED
Three-position disconnector
Components
Interlocks
Selection of permissible switchingoperations by means of a controlgate with mechanically interlockedvacuum circuit-breaker
Selection of permissible switchingoperations in double-busbarswitchgear additionally by meansof a control gate with mechanicallyinterlocked vacuum circuit-breaker
Corresponding operating shafts arenot released at the operating frontuntil they have been pre-selectedwith the control gate
Operating lever cannot be removeduntil switching operation has beencompleted
Circuit-breaker cannot be closed
until the control gate is in neutralposition again
Option: Switchgear interlockingsystem with electromechanicalinterlocks (mechanical interlockingfor manual operation remains).
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
44/63
44 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Control board
Components
Features
Mechanical control board below thelow-voltage compartment
Actuations directly at the operatingmechanisms
Mechanical position indicatorsintegrated in the switchgear front
Unambiguous assignment ofactuating openings and controlelements to the correspondingposition indicators
Ergonomic height of all controlelements.
Interlocking
Panel-internal mechanical interlocks
Operation of three-position discon-nector (CLOSED, OPEN, EARTHED or
READY-TO-EARTH) Vacuum circuit-breaker interlockedmechanically
Control gate for opening the actuat-ing openings (with single-busbarsystems it can only be operated ifthe interrogation lever (4) is pusheddownwards)
Actuating openings (2, 3 and 8)cannot be opened as long as thevacuum circuit-breaker is in CLOSEDposition
Operating lever can be inserted
when the actuating openings areopen
Operating lever cannot be removedbefore the definite end positionof the disconnecting or earthingfunction is reached
Feeder de-earthing is secured by thevacuum circuit-breaker
electrically via the auxiliary switch mechanically through the lever (14)
of the mechanical circuit-breakertripping block.
A Operating mechanism of the three-position disconnector
1 CLOSED/OPEN position indicator for disconnecting function of three-position disconnector2 Actuating opening for earthing function3 Actuating opening for disconnector function4 Interrogation lever
5 CLOSED/OPEN position indicator for earthing function of three-position disconnector6 CLOSED/OPEN position indicator for vacuum circuit-breaker7 CLOSED/OPEN position indicator for 2nddisconnector in double-busbar systems8 Actuating opening for 2nddisconnector in double-busbar systems9 Control gate for selecting the three-position disconnector or the disconnector in double-
busbar systems10 Control gate for opening the actuating openings (with single-busbar systems it can only be
operated if the interrogation lever (4) is pushed downwards)
Single-busbar panels 8DA10
Double-busbar panels 8DB10
B Operating mechanism of the vacuum circuit-breaker
11 Mechanical ON pushbutton for vacuum circuit-breaker12 Actuating opening for manual charging of the circuit-breaker operating spring13 Mechanical OFF pushbutton for vacuum circuit-breaker14 Lever for locking the vacuum circuit-breaker against de-earthing15Circuit-breaker spring charged indicator16 CLOSED/OPEN position indicator for vacuum circuit-breaker
17 Operations counter for vacuum circuit-breaker
1
42
10
10
3
11
13
14
56
12
15
16
17
A
B
R-HA35-139.eps
15
5
1
2
63
16
17
A
B
7
8
11
13
14
9
12
R-HA35-140.eps
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
45/63
45Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Busbar, busbar components
Components
Busbar features
Single-pole enclosure withmodular switchgear housingsmade of corrosion-resistantaluminum alloy
Continuous SF6insulation
without plug-in connectionsor adapters
No alteration of the insulat-ing medium throughout thecomplete busbar assembly
Up to 4000 A with copper barconnection in one busbarhousing
5000 A with copper barconnection in two busbarhousings (twin busbar).
Design of busbar components
The busbars of single-busbarswitchgear 8DA and double-busbar switchgear 8DB can beequipped with the followingbusbar components: Plug-in, metal-enclosed
busbar voltage transformerswith or without three-posi-tion disconnector
Busbar current transformers
Busbar connection with cableplug, or with solid-insulated
or gas-insulated bar connec-tion, with or without three-position disconnector
Busbar earthing switch ormake-proof earthing switch
Capacitive voltage detectingsystem according toIEC 61243-5 or IEC 61958
Top-mounted bus sectional-izer for distribution into twobusbar sections without addi-tional switchgear panels andspace requirements.
Busbar versions
Busbar version up to 3150 A
Example 8DA10Busbar version 4000 A
Example 8DA10
Busbar version 5000 A (twin busbar)
Example 8DA10Busbar version 5000 A (twin busbar)
Example 8DB10
Busbar components
Busbar connection with cable plug size S2
or size S3Busbar connection with solid-
insulated or gas-insulated bar
Top-mounted bus sectionalizer
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
46/63
46 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Current transformers
Components
Features
According to IEC 61869-2
Designed as ring-core currenttransformers, single-pole
Free of dielectrically stressedcast-resin parts (due todesign)
Insulation class E
Inductive type
Certifiable
Climate-independent
Secondary connection bymeans of a terminal strip inthe low-voltage compartmentof the panel
Cast-resin insulated.
Installation
Arranged outside theprimary enclosure(switchgear housing).
Current transformer installation (basic scheme)
* Further electrical data on request
Electrical data *
Designation Type 4MC4
Operating voltage max. 0.8 kV
Rated short-duration power-frequency withstand voltage(winding test)
3 kV
Rated frequency 50 / 60 Hz
Rated continuousthermal current
max. 1.2 rated current(primary)
Rated thermalshort-time current,max. 3 s
max. 40 kA
Rated current dynamic primary
secondary
unlimited40 A to2500 A1 A and 5 A
Designation Type 4MC4
Multiratio (secondary) 200 A 100 A
to 2500 A 1250 A
Core data accordingto rated primary current:Measuring core Rating Class Overcurrent
factorProtection core Rating Class Overcurrent
factor
max. 3 cores
2.5 VA to 30 VA0.2 to 1FS 5, FS 10
2.5 VA to 30 VA5 P or 10 P10 to 30
Permissible ambientair temperature
max. 60 C
Insulation class E
Current transformers
B Current transformer in bus sectionalizerand bus coupler (type 4MC4_40)
C1Feeder current transformer(type 4MC4_90)
C2Feeder current transformer(type 4MC4_40)
D Feeder current transformer(type 4MC4_10)
E Busbar current transformer(type 4MC4_40)
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
47/63
47Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Voltage transformer installation (basic scheme)
Voltage transformers
Components
Features
According to IEC 61869-3
Single-pole, plug-in design
Connection system withplug-in contact accordingto EN 50181
Inductive type
Safe-to-touch due to metalenclosure
Certifiable
Climate-independent
Secondary connection bymeans of plugs in the low-voltage compartment of thepanel
Cast-resin insulated.
Installation
Arranged outside theprimary enclosure (switch-gear housing).
Mounting locations
On the busbar
At the panel connectionhousing.
Voltage transformer types
Busbar voltage transformers4MT3 and 4MU4 Pluggable on the busbar with
plug-in system according toEN 50181
No separate metering panelrequired
Option: Three-positiondisconnector for busbarvoltage transformer CLOSED OPEN EARTHED
Option 4MU4: Repeat test at80 % of the rated short-duration power-frequencywithstand voltage possiblewith mounted voltage trans-
former.
Feeder voltage transformers4MT7 and 4MU3 Pluggable at the feeder with
plug-in system according toEN 50181
Connection of 4MT7 directly atthe panel connection housing
Connection of 4MU3 viaflexible cable with plug sizeS2 at the panel connectionhousing, and metal-enclosed
voltage transformer.
Voltage transformers
1Busbar voltage transformer 4MT32Feeder voltage transformer 4MT7
(connection at panel connection
housing)
3Busbar voltage transformer 4MU4 with three-position disconnector
4Feeder voltage transformer 4MU3 (not in the
panel, connection via flexible cable with plugsize S2 at the panel connection housing, andmetal-enclosed voltage transformer)
Electrical data (maximum values)
Designation 4MT3 4MU4 4MT7 4MU3
Rated voltage kV 24.0 40.5 40.5 40.5
Rated short-durationpower-frequencywithstand voltage kV
65 95 95 95
Rated lightning impulsewithstand voltage kV
125 200 200 200
Rated voltage factor Un /8h = 1.9 Un /8h = 1.9 Un /8h = 1.9 Un /8h = 1.9
Un /continuous= 1.2
Un /continuous= 1.2
Un /continuous= 1.2
Un /continuous= 1.2
Standard IEC IEC IEC IEC
GOST GOST GOST GOST
GB GB GB GB
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
48/63
48 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2012
Panel connection
Components
Features
Bushings for plugs withinside-cone plug-in systemaccording to EN 50181
Inside-cone plug-in system
for plug sizes 2, 3 and 4 Single and multiple connec-
tions possible per phase
Connection of several cableswith different plug sizespossible per phase
Connection of solid-insulatedor gas-insulated bar possible
Connection of 4MT7 voltagetransformer plugged in at thepanel connection housingversion 3
Connection of 4MU3 voltagetransformer via flexible cableand plug size 2 at the panelconnection housing
For rated normal currents upto 2500 A.
Surge arresters
Pluggable via inside-coneplug-in system size 2 or 3
Surge arresters recommendedif, at the same time,
the cable system is directly
connected to the overheadline,
the protection zone of thesurge arrester at the endtower of the overhead linedoes not cover the switch-gear.
Version 1
S2
1
Version 2
S3
1
Version 3
S2 S3 4MT7 Solid-insulated
barconnection
1 1
2
3
2
3
1 2
1 1
2 1 1 1
2 1
1 1 1
1 1
1 1
2 1
Legend
1 Panel connection housing2 Subframeh Connection height of panel connection versions
Panel connection of 8DA10, 8DB10 and 8DA11/12 for cable plugs and bar systems
Switch-geartype
Ratednormalcurrent
[A]
Standardsubframe
Highsubframe
Connection height of panel connection versions (mm)
8DA10
8DA118DA12
up to 2300X 320 240 275
X 540 460 495
2500X -70 -150 -115
X 150 70 105
8DB10 up to 2500X 120 40 75
X 540 460 495
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
49/63
49Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2012
Panel connection
Components
Panel connection of 8DA10, 8DB10 and 8DA11/12 for cable plugs and bar systems
Version 7
Gas-insulatedbar connection
1
Version 4
S2 S3Solid-insulatedbar connection
4
5
6
4
1 3
1 4
2 2
2 3 3 1
3 2
4 1
2 1
1 1
2 1
1 1 1
Version 5
S2 S3 S4
1
1 1
2 1
1 1
1 1 1
2
2 1
Connection height of panel connection versions (mm)
222 -15 294 327
442 205 514 547
-168 -405 96 -6352 -185 124 157
22 -215 94 127
442 205 514 547
Version 6
Solid-insulatedbar connection
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
50/63
50 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Panel connection (commercially available cable plugs and bar connections)
Components
Busbar and panel connection (commercially available cable plugs)
Cable type Cable sealing end Remark
Make Type Size Diameter acrosscable insulationmm
Conductorcross-sectionmm2
Thermoplastic-insulated cables 12 kV according to IEC 60502-2Single-core cable orthree-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
nkt cables CPI 2 2 12.7 - 33.6 25 - 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special toolsCPI 3 3 21.2 - 45.6 185 - 630
Pfisterer CONNEX 2 13.5 - 44.0 25 - 400 Insulation material silicone rubber,with metal housingCONNEX 3 15.5 - 55.0 35 - 800
CONNEX 4 33.0 - 78.0 95 - 1600
Sdkabel SEIK 14 2 13.0 - 40.6 25 - 300 Insulation material silicone rubber,with metal housingSEIK 15 3 19.3 - 50.6 120 - 630
Tyco Electronics RPIT-321x 2 19.5 - 36.0 95 - 300 Insulation material silicone rubber,with metal housingRPIT-331x 3 26.0 - 50.0 240 - 630
Thermoplastic-insulated cables 24 kV according to IEC 60502-2
Single-core cable orthree-core cable,PE and XLPE-insulated,N2YSY (Cu) and
N2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
nkt cables CPI 2 2 17.0 - 40.0 25 - 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special toolsCPI 3 3 21.2 - 45.6 95 - 630
Pfisterer CONNEX 2 13.5 - 44.0 25 - 400 Insulation material silicone rubber,
with metal housingCONNEX 3 15.5 - 55.0 35 - 800CONNEX 4 33.0 - 78.5 95 - 1600
Sdkabel SEIK 24 2 13.0 - 40.6 25 - 300 Insulation material silicone rubber,with metal housingSEIK 25 3 19.3 - 50.6 50 - 630
Tyco Electronics RPIT-521x 2 19.5 - 36.0 50 - 300 Insulation material silicone rubber,with metal housingRPIT-531x 3 26.0 - 50.0 150 - 630
Thermoplastic-insulated cables 40.5 kVaccording to IEC 60502-2
Single-core cable orthree-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)
nkt cables CPI 2 2 17.0 - 40.0 25 - 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special toolsCPI 3 3 21.2 - 51.0 50 - 630
Pfisterer CONNEX 2 13.5 - 44.0 25 - 400 Insulation material silicone rubber,with metal housingCONNEX 3 15.5 - 55.0 35 - 800
CONNEX 4 33.0 - 78.5 95 - 1600
Sdkabel SEIK 34 2 13.0 - 40.6 35 - 300 Insulation material silicone rubber,with metal housingSEIK 35 3 19.3 - 50.6 50 - 630
Tyco Electronics RPIT-621x 2 19.5 - 36.0 50 - 185 Insulation material silicone rubber,with metal housingRPIT-631x 3 26.0 - 50.0 95 - 630
Busbar and panel connection (commercially available bar systems)
Bar type Bar connection Remark
Make Type Conductor material Max. rated current
Solid-insulated bar MGCMoser Glaser
Duresca DE Copper, aluminum 2500 A Outer sheath made of polyamide (polyamide tube)
Duresca DG Copper, aluminum 2500 A Outer sheath made of CrNi steel or aluminum(metal sheath)
Preissinger ISOBUS MR Copper, aluminum 2500 A Outer sheath made of heat shrinkable tube; insulatedwith cast-resin impregnated paper bandage
Ritz SIS Copper, aluminum 2500 A Outer sheath made of Raychem heatshrinkable tube
Gas-insulated bar MGC Moser Glaser Gaslink Copper 2500 A Aluminum housing
Preissinger ISOBUS MG Copper 2500 A Aluminum housingBusbar and panel connection (commercially available dummy plugs)
Accessories Dummy plug Remark
Make Type Size Rated voltage
Inside-cone plug-insystem accordingto EN 50181
nkt cables FPI 2 2 40.5 kV Insulation material silicone rubber,with metal housing
FPI 3 3 40.5 kV
PfistererBlindstecker
2 40.5 kV Insulation material silicone rubber,with metal housing
3 40.5 kV
4 40.5 kV
Sdkabel ISIK 14/24/34 2 12 / 24 / 40.5 kV Insulation material silicone rubber,with metal housing
ISIK 15/25/35 3 12 / 24 / 40.5 kV
Tyco Electronics RPIC-2 2 40.5 kV Insulation material silicone rubber,with metal housing
RPIC-3 3 40.5 kV
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
51/63
51Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Indicating and measuring equipment
Components
Symbols shown
VOIS+, VOIS R+ CAPDIS-S1+ CAPDIS-S2+
A0 CAPDIS-S2+: Operating voltage
not present
A1 Operating voltage present
A2 Operating voltage not present
For CAPDIS-S2+: Auxiliary power
not present
A3 Failure in phase L1, operating volt-
age at L2 and L3 (for CAPDIS-Sx+
also earth-fault indication)
A4 Voltage (not operating voltage)
present
A5 Indication Test passed
(lights up briefly)
A6 Indication Test not passed
(lights up briefly)
A7 Overvoltage present
(lights up permanently)
A8 Indication ERROR, e.g.: in case
of missing auxiliary voltage
R-HA40
-103
eps
Plug-in
voltage
indicator
per phase at
the panel front
R-HA40-104 eps
Integrated voltage indicator
VOIS+, VOIS R+
Integrated voltage detecting
system CAPDIS-S1+, -S2+
Indicators and detecting
systems
LRM system
plugged in
CAPDIS / VOIS
installed
Voltage indication
via capacitive voltage divider (principle)
C1 Capacitance integrated into bushing
C2 Capacitance of the connection leads
and the voltage indicator to earth
ULE= UN / 3 during rated operation in the
three-phase system
U2 =UA= Voltage at the capacitive interface of
the switchgear or at the voltage indicator
R-HA35-154 eps R- HA 35 -155 eps
A0
A1
A2
A3
A4
A5
A6
A7
A8
Voltage detecting systems accordingto IEC 61243-5, IEC 62271-206 (WEGA ZERO) To verify safe isolation from supply LRM detecting systems with plug-in indicator with integrated indicator, type VOIS+,
VOIS R+, WEGA ZERO
with integrated indicator, with integratedrepeat test of the interface, with inte-grated function test, type CAPDIS-S1+,WEGA 1.2, WEGA 1.2 Vario, with inte-grated signaling relay, type CAPDIS-S2+,WEGA 2.2.
Plug-in voltage indicator
Verification of safe isolation from supplyphase by phase
Indicator suitable for continuousoperation
Measuring system and voltage indicatorcan be tested
Voltage indicator flashes if high voltage ispresent.
VOIS+, VOIS R+
Integrated display, without auxiliarypower
With indication A1 to A3 (see legend) Maintenance-free, repeat test required With integrated 3-phase LRM test socket
for phase comparison With integrated signaling relay
(only VOIS R+) Degree of protection IP54.
Common features CAPDIS-Sx+
Maintenance-free Integrated display, without auxiliary
power Integrated repeat test of the interfaces
(self-monitoring) With integrated function test (without
auxiliary power) by pressing theDisplay-Test pushbutton
Adjustable for different operatingvoltages (adjustable capacitance C2)
With integrated 3-phase LRM test socketfor phase comparison
With connectable signal-lead test With overvoltage monitoring and
signaling (1.2 times operating voltage) Degree of protection IP54.
CAPDIS-S1+
Without auxiliary power With indication A1 to A7 (see legend) Without ready-for-service monitoring Without signaling relays (without auxiliary
contacts).
CAPDIS-S2+
With indication A0 to A8 (see legend) Only by pressing the Test pushbutton:
ERROR indication (A8), e.g. in case ofmissing auxiliary voltage
With ready-for-service monitoring(auxiliary power required)
With integrated signaling relay for signals(auxiliary power required).
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
52/63
52 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
ComponentsIndicating and measuring equipment
A0 For WEGA 2.2:Operating voltage not present,auxiliary power present, LCDilluminated
A1 Operating voltage presentFor WEGA 2.2: Auxiliary powerpresent, LCD illuminated
A2 Operating voltage not presentFor WEGA 2.2: Auxiliary power notpresent, LCD not illuminated
A3 Failure in phase L1,operating voltage at L2 and L3For WEGA 2.2: Auxiliary powerpresent, LCD illuminated
A4 Voltage present,current monitoring of couplingsection below limit valueFor WEGA 2.2: Auxiliary powerpresent, LCD illuminated
A5 Indication Display-Test passedFor WEGA 2.2: Auxiliary powerpresent, LCD illuminated
A6 For WEGA 2.2: LCD for missingauxiliary voltage is not illuminated
Symbols shown
LC display gray: not il luminatedLC display white: illuminated
Integrated voltage indicator
WEGA ZERO
R-HA35-151.ep
s
Integrated voltage detecting system
WEGA 1.2, WEGA 1.2 Vario
R-HA35-152.aeps
Integrated voltage detecting system
WEGA 2.2
R-HA35-153
b.eps
LRM systemplugged in
WEGAinstalled
Voltage indication
via capacitive voltage divider (principle)
C1 Capacitance integrated into bushing C2 Capacitance of the connection leads
and the voltage indicator to earthULE= UN/ 3 during rated operation in the
three-phase systemU2 = UA= Voltage at the capacitive interface of
the switchgear or at the voltage indicator
WEGA ZERO WEGA 1.2 WEGA 2.2
WEGA 1.2 Vario
WEGA ZERO
Voltage detecting systemaccording to IEC 62271-206
With indication A1 to A4(see legend)
Maintenance-free
With integrated 3-phase testsocket for phase comparison
Degree of protection IP54.
WEGA 1.2, WEGA 1.2 Vario
Voltage detecting systemaccording to IEC 61243-5
With indication A1 to A5(see legend)
Maintenance-free
Integrated repeat test of theinterface (self-monitoring)
With integrated function test(without auxiliary power) bypressing the Display Testpushbutton
With integrated 3-phaseLRM test socket for phasecomparison
Without integrated signalingrelay
Without auxiliary power
Degree of protection IP54
Adjustable for differentoperating voltages(adjustable capacitance C2)(only for WEGA 1.2 Vario).
WEGA 2.2
Voltage detecting systemaccording to IEC 61243-5
With indication A0 to A6(see legend)
Maintenance-free
Integrated repeat test of theinterface (self-monitoring)
With integrated function test
(without auxiliary power) bypressing the Display Testpushbutton
With integrated 3-phaseLRM test socket for phasecomparison
With integrated signalingrelay (auxiliary powerrequired)
Degree of protection IP54.
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
53/63
53Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Indicating and measuring equipment
Components
R-HA40-059
eps
R-HA35-127.eps
R-HA40-089.tif
Phase comparison test units according to IEC 61243-5
Verification of correctterminal-phase connections
Verification of correct terminal-phase connections possible bymeans of a phase comparisontest unit (can be ordered
separately) Safe-to-touch handling of the
phase comparison test unitby inserting it into the capaci-tive taps (socket pairs) of theswitchgear.
Phase comparison test unit
make Kries, type CAP-Phase
as combined test unit (HR and LRM) for: Voltage detection Repeat test Phase comparison Phase sequence test
Self-testThe unit does not require a battery
Phase comparison test unit
make Horstmann, type ORION 3.1as combined test unit (HR and LRM) for: Phase comparison Interface testing at the switchgear Voltage detection Integrated self-test Indication via LED and acoustic alarm Phase sequence indicator
R-HA35-127.eps
Phase comparison test unit
make Pfisterer, type EPV
as combined test unit (HR and LRM) for:
Voltage detection Phase comparison Interface test Integrated self-test Indication via LED
Phase comparison test unit
make Hachmann, type VisualPhase LCD
as combined test unit (HR and LRM) for: Voltage detection with measured-value
indication
Interface test Low voltage detection Documentable repeat test Phase comparison with LED signal and
measured-value indication Phase angle from 180 to +180 Phase sequence evaluation Frequency quality Complete self-test
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
54/63
54 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Indicating and measuring equipment
Components
Ready-for-service indication
Components Gas pressure manometers
with two or three signalingcontacts for gas pressure too
low / very low and gaspressure too high indication
Simple, visual check of theready-for-service indicator byred/green indication areas
Indication of gas pressure alsoguaranteed without auxiliaryvoltage supply
SF6gas filling equipment withnon-return valve and boltedprotective cap arranged atthe switchgear front besidegas pressure manometer
Option: Gas pressure mano-meters with temperature andpressure compensation.
Low-voltage compartment
For accommodation of protec-tion, control, measuring andmetering equipment
Partitioned safe-to-touchfrom the high-voltage part ofthe panel
Low-voltage compartment
can be removed, bus wiresand control cables areplugged in
Option: Higher low-voltagecompartment (1200 mminstead of 850 mm) possible.
Gas pressure manometer (1)for circuit-breaker housing(arranged at the panel front)
Gas monitoring for
double-busbar switchgear
8DB10
Gas pressure manometers (3) forcircuit-breaker and disconnectorhousings (arranged at the panel front)
Gas pressure manometers (2) forbusbar housings (arranged at thelateral switchgear termination)
Gas pressure manometers (4) forbusbar housings (arranged at thelateral switchgear termination)
R-HA35-145.eps
R-H
A35-147.eps
R-HA35-146.eps
R-HA35-148.eps
1
3
2
4
Gas monitoring ofsingle-busbar switchgear8DA10
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
55/63
55Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
Protection, control, measuring and monitoring equipment
Components
Overview of the device types of the SIPROTEC device series: SIPROTEC 5, SIPROTEC Compact and SIPROTEC 4
SIPROTEC 5
Overcurrent protection with PMU, control and power quality 7SJ82, 7SJ85
Distance protection with PMU and control 7SA84, 7SA86, 7SA87
Line differential protection with PMU and control 7SD84, 7SD86, 7SD87
Combined line differential and distance protectionwith PMU and control
7SL86, 7SL87
Circuit-breaker management device with PMU and control 7VK87
Overcurrent protection for lines 7SJ86
Transformer protection with PMU, control, monitoring7UT857UT867UT87
Motor protection with PMU 7SK82, 7SK85
Central busbar protection 7SS85
Bay controllers for control/interlocking tasks with PMU andmonitoring, optionally with protection funktions
6MD85, 6MD86
Digital fault recorder 7KE85
SIPROTEC Compact
Overcurrent protection 7SJ80, 7SJ81
Motor protection 7SK80, 7SK81
Voltage and frequency protection 7RW80
Line differential protection 7SD80
Distribution system controller 7SC80
SIPROTEC 4
Overcurrent protectionEASY 7SJ45/7SJ467SJ600, 7SJ601, 7SJ602
7SJ61, 62, 63, 64
Distance protection7SA522
7SA6
Line differential protection7SD600, 7SD610
7SD52, 53
Transformer differential protection 7UT612, 613, 63
Busbar protection7SS60, 7SS522
7SS52
Generator and motor protection7UM61, 7UM62, 7VE6
7UM518
Accessories for generator and motor protection 7UW50; 7XR, 3PP, 7KG61, 7XT, 4NC
Rapid changeover device 7VU683
Bay controllers
6MD61, 6MD63
6MD662, 663, 664
6MB525
U/f relay 7RW600
Transient earth-fault relay 7SN600
Breaker failure protection 7SV600
Automatic reclosing, synchrocheck 7VK61
High-impedance protection 7VH60
Protecting, controlling and monitoring are the basic require-ments placed on a complete bay controller across all tech-nology generations. The properties the user expects frommodern bay controllers are: multifunctionality, reliability,safety and communication capability.The increasing integration of many functions in one multi-
functional device leads to an optimally supported engineer-
ing process, IT security, service and testability, or simpleand safe operability of the devices and tools.On the following pages you will find functional descrip-tions for some selected devices. The low-voltage compart-ment can accommodate all customary protection, control,measuring and monitoring equipment available on the
market:
-
7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA
56/63
56 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014
ComponentsANSI design
Basic panel design
Legend for 8DA10
1Low-voltage compartment2Electronic control board,
e.g. multifunction
protection3Operating mechanism
and interlock for three-position disconnector,as well as mechanicalposition indicatorsfor three-positiondisconnector and circuit-breaker
4Manometer for gasmonitoring of feeder gascompartments
5Circuit-breaker operatingmechanism
6Voltage detecting system
7Operating mechanism andinterlock for the three-position disconnector,as well as mechanicalposition indicator forthe three-positiondisconnector at the feeder
Panel design Factory-assembled, type-tested
according to IEC 62271 Single-pole metal-enclosed, metal-clad Hermetically bolted switchgear
housings made of corrosion-resistantaluminum alloy
Switchpanel poles arranged onebehind the other
Maintenance-free in an indoorenvironment (IEC 62271-1)
Cable connection with inside-coneplug-in system according to EN 50181
Wall-standing or free-standingarrangement
Subframe, front cover, rear cover andend walls powder-coated in colorlight basic (SN 700)
Low-voltage compartmentremovable, plug-in bus wires
Degree of protection IP 65 for all high-voltage parts of
the primary circuit IP 3XD for the switchgear enclosure Option: IP 31D for the switchgear
enclosure Option: IP 41 for the low-voltage
compartment Vacuum circuit-breaker Three-position disconnector for
disconnecting and earthing by meansof the circuit-breaker
Make-proof earthing by means ofthe vacuum circuit-breaker
Option: Three-position disconnector
for disconnecting and earthing at thefeeder
For further dimensions and productrange, see pages 14 to 35.
Insulating system Switchgear housing filled with SF6gas Features of SF6gas: Non-toxic Odorless and colorless Non-inflammable Chemically neutral Heavier than air Electronegative (high-quality insulator) Pressure of the SF
6
gas in the switch-gear housing dependent on the electri-cal ratings (relative pressure at 20 C):Rated filling level: 70 kPa to 120 kPaGas leakage rate: < 0.1 % per year.
Camera system
Camera system for visual monitoringof the switch positions of the discon-nectors and earthing switches (seealso page 58).
UL certification For 8DA and 8DB ANSI design options
there is a UL or cUL certificat