catalog - amazon s3 · 325-7al (1 1/4”, 1 1/2”): 1,250,000 btu/h; 325-9l (1 1/2”, 2”):...
TRANSCRIPT
CATALOG2nd Edition
© 2015, Maxitrol Company. All Rights Reserved.
DRAFT 09.18.2013
2
Service and installation must be performed by a trained/experienced service technician.
All products used with combustible gas must be installed and used strictly in accordance with the instructions of the Original Equipment Manufacturer (OEM) and with all applicable government codes and regulations, e.g. plumbing, mechanical, and electrical codes and practices. Maxitrol products should be installed and operated in accordance with Maxitrol Safety Warning Instructions.
Maxitrol Company is NOT responsible for any errors or omissions in reliance by anyone of any information set forth in this catalog without additional reference to local requirements and applicable ordinances or codes.
Other worldwide approvals and certifications available upon inquiry.
C US
®
UA.TR.012-13
© 2015, Maxitrol Company. All Rights Reserved.
DRAFT 09.18.2013
46
Pipe Sizes ..................................3/8” to 2” threaded connections with NPT or ISO7-1 threads.
Housing Material ......................325-3L, 325-5L, 325-7AL, 325-9L: aluminum.
Mounting ..................................Suitable for multi-positional mounting. If ball check vent limiting device is installed, mount in an upright position only.
NOTE: All Maxitrol gas pressure regulators should be installed and operated in accordance with Maxitrol Safety Warning Instructions (see GPR_CSA_2PSI_MI_EN.FR).
Certifications ..............................325-3L, 325-5L, 325-7AL, 325-9L: ANSI Z21.80/CSA 6.22 Line Pressure Regulators.
Gas Types ..................................Suitable for natural, manufactured, mixed gases, liquefied petroleum gases, and LP gas-air mixtures.
Maximum Inlet Pressure ...........2 psi (13.8 kPa)
Minimum Inlet Pressure ............1 psi (6.9 kPa)
Emergency Exposure Limits .......65 psi (450 kPa) (inlet side only)
Maximum Individual Load ........Largest single appliance served by the regulator: 325-3L: 140,000 Btu/h; 325-5L: 425,000 Btu/h; 325-7AL: 1,250,000 Btu/h; 325-9L: 2,250,000 Btu/h
Capacity ....................................Total load of multiple appliance combined325-3L (3/8”, 1/2”): 250,000 Btu/h; 325-5L (1/2”): 500,000 Btu/h; 325-5L (3/4”, 1”): 600,000 Btu/h;325-7AL (1 1/4”, 1 1/2”): 1,250,000 Btu/h; 325-9L (1 1/2”, 2”): 2,250,000 Btu/h
NOTE: Capacities are used to determine the maximum multiple appliance load. The largest single appliance served by the regulator should not exceed the maximum individual load specified above.
Ambient Temperature Ranges .... -40 to 205°F (-40 to 96°C)
Minimum Regulation .................Suitable for pilot flow applications. (Circle P) (0.15 CFH NG).
Imblue Technology™ .................325-3L, 325-5L, 325-7AL, 325-9L models may be ordered with Imblue Technology™. Imblue Technology™ increases corrosion resistance and provides extra protection against the elements for regulators used in outdoor applications. Add suffix letter “B” to model number when ordering.
Maxitrol’s 325-L Series line pressure regulators are for 2 psi
piping systems. 325 Series regulators are for use on residential,
commercial, and industrial applications.
The 325 Series features a high leverage linkage assembly to
deliver positive dead-end lockup. The regulators are capable
of precise regulating control from full flow down to pilot flow.
325-3L
Specifications
325-L SERIESLever Acting Design for 2 psi Piping Systems
© 2015, Maxitrol Company. All Rights Reserved. © 2015 Maxitrol Company. All Rights Reserved.
DRAFT 09.18.2013
47
Model Pipe SizeOutlet Pressure
Set Point
Operating Inlet Pressure
1/2 psi(3.4 kPa)
3/4 psi(5.2 kPa)
1 psi (6.9 kPa)
1 1/2 psi (10.3 kPa)
2 psi (13.8 kPa)
325-3L 3/8” x 3/8”1/2” x 1/2”
7.0” w.c. (1.7 kPa)
145(4.1)
200(5.7)
250(7.1)
250(7.1)
250(7.1)
10.0” w.c. (2.5 kPa)
110(3.1)
180(5.1)
230(6.5)
250(7.1)
250(7.1)
325-5L 1/2” x 1/2”
7.0” w.c. (1.7 kPa)
360(10.2)
485(13.7)
500(14.2)
500(14.2)
500(14.2)
10.0” w.c. (2.5 kPa)
275(7.8)
475(13.5)
500(14.2)
500(14.2)
500(14.2)
325-5L3/4” x 3/4”
1” x 1”
7.0” w.c. (1.7 kPa)
370(10.5)
520(14.7)
600(17.0)
600(17.0)
600(17.0)
10.0” w.c. (2.5 kPa)
275(7.8)
450(12.7)
570(16.1)
600(17.0)
600(17.0)
325-7AL1 1/4” x 1 1/4”1 1/2” x 1 1/2”
7.0” w.c. (1.7 kPa)
750(21.2)
1000(28.3)
1250(35.4)
1250(35.4)
1250(35.4)
10.0” w.c. (2.5 kPa)
525(14.9)
900(25.5)
1125(31.9)
1250 (35.4)
1250(35.4)
325-9L1 1/2” x 1 1/2”
2” x 2”
7.0” w.c. (1.7 kPa)
1390(39.4)
2080(58.9)
2250(63.7)
2250(63.7)
2250(63.7)
10.0” w.c. (2.5 kPa)
1050(29.7)
1660(47.0)
2090(59.2)
2250(63.7)
2250(63.7)
NOTE: See pages 58-59 for Regulator Sizing Requirements and Examples.
Outlet Pressure Range (all models)
Certified Spring ............................. 7” to 11” w.c. (1.7 to 2.7 kPa)
NOTE: See to pages 56-57 for complete Spring Selection Chart.
Model Number 7.0” w.c. (1.7 kPa) 1/2 psi (3.4 kPa) 3/4 psi (5 kPa)
325-3L 145 (4.0) 204 (5.8) 250 (7.0)
325-5L 400 (11.3) 550 (15.6) 670 (19.0)
325-7AL 815 (23.1) 1149 (32.5) 1405 (39.8)
325-9L 1360 (38.5) 2113 (59.8) 2557 (72.4)
Capacities expressed in CFH (m3/h) @ 0.64 sp gr gas
Capacities
Pressure Drop: expressed in CFH (m3/h) @ 0.64 sp gr gas
Spring Selection
LINE REGULATORS
C US
®
© 2015, Maxitrol Company. All Rights Reserved.
DRAFT 09.18.2013
48
325-5L325-3L
Model Pipe SizeVent
ConnectionSwing Radius
Dimensions
A B C
325-3L 3/8”, 1/2” 1/8” NPT3”
(76 mm)3.5”
(89 mm)4.2”
(108 mm)3.9”
(98 mm)
325-5L 1/2”, 3/4”, 1” 3/8” NPT4.9”
(124 mm)5.3”
(133 mm)5.9”
(149 mm)5.4”
(138 mm)
325-7AL 1 1/4”, 1 1/2” 1/2” NPT6.1”
(156 mm)7.3”
(184 mm)8”
(203 mm)7”
(178 mm)
325-9L 1 1/2”, 2” 1/2” NPT7.8”
(198 mm)9.4”
(239 mm)10.8”
(274 mm)9.1”
(231 mm)
NOTE: Dimensions are maximums and to be used only as an aid in designing clearance for the valve. Actual production dimensions may vary somewhat from those shown.
A
A
Dimensions
325-L SERIESLever Acting Design for 2 psi Piping Systems
© 2015, Maxitrol Company. All Rights Reserved. © 2015 Maxitrol Company. All Rights Reserved.
DRAFT 09.18.2013
49
325-7AL 325-9L
1 Seal Cap
2 Stack
3 Top Housing
4 Rubber Valve
5 Valve Seat
6 Seal Cap Gasket
7 Adjusting Screw
8 Spring
9 Vent Connection
10 Diaphragm
11 Diaphragm Plates
12 Bottom Housing
1
2
3
4
5
9
10
11
6
7
8
12
NOTE: Diagrams are graphical representations only and may differ from actual product.
A A
Lever Acting Design
LINE REGULATORS
Maxitrol Company23555 Telegraph Rd., PO Box 2230Southfield, MI 48037-2230
GPR_MS_EN_10.2015
www.maxitrol.com© 2015 Maxitrol Company
All Rights Reserved