TT-FFS Fast Fuel Detection Probe Description Use these instructions when a TraceTek ® TT-FFS probe has been exposed to dirt, mud, sand and after leak detection events with heavier fuels such as jet fuel, diesel, of fuel oil. For technical support, call Tyco Thermal Controls at (800) 545-6258. Care and Cleaning Instructions 2 • After soaking in water, let dry in air for 15 to 20 minutes. • Do not use compressed or heated air. 1 • Do not remove the protective mesh screen. • Place sensor in several inches of water and let soak for 15 minutes. Make sure connector stays high and dry. • DO NOT SHAKE OR STIR! 3 • Visually inspect the sensor blade but do not touch it! A sensor blade in good condition will have a uniform gray or black coating like the photo on the left. A sensor with a scratched or damaged film like that in the right picture will need to be replaced. (Note: Protective screen has been removed for clarity in these photos) 15 minutes H 2 O 20 minutes Sensor blade

Upload: others

Post on 22-Dec-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

TT-FFS Fast Fuel Detection Probe

DescriptionUse these instructions when a TraceTek® TT-FFS probe has been exposed to dirt, mud, sand and after leak detection events with heavier fuels such as jet fuel, diesel, of fuel oil.For technical support, call Tyco Thermal Controls at (800) 545-6258.

Care and Cleaning Instructions

2

• Aftersoakinginwater,letdryinairfor15to20minutes.• Donotusecompressedorheatedair.

1

• Donotremovetheprotectivemeshscreen.• Placesensorinseveralinchesofwaterandletsoakfor15minutes.Makesureconnectorstayshighanddry.

• DONOTSHAKEORSTIR!

3

• Visuallyinspectthesensorbladebutdonottouchit!Asensorbladeingoodconditionwillhaveauniformgrayorblackcoatinglikethephotoontheleft.Asensorwithascratchedordamagedfilmlikethatintherightpicturewillneedtobereplaced.(Note:Protectivescreenhas been removed for clarity in these photos)

15 minutes

H2O

20 minutes

Sensor blade

2

©2009TycoThermalContro

lsLLC

P

000001021H

5830701/09

Worldwide HeadquartersTyco Thermal Controls307ConstitutionDriveMenloPark,CA94025-1164USATel:(800)545-6258Tel:(650)216-1526Fax:(800)527-5703Fax:(650)[email protected]

CanadaTyco Thermal Controls250 West St.Trenton,OntarioCanadaK8V5S2Tel (800) 545-6258Fax (800)527-5703

Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.

Tyco and TraceTek are trademarks of Tyco Thermal Controls LLC or its affiliates.

4

• UsetheFFSProbeTestertotestthesensor. GOODSENSOR:noLEDswhentheFFSisfirstconnected,flashingLEDswhentestbuttonispushed.

BADSENSOR:LEDsflashimmediatelyonceFFSisconnected.

• Placesufficientisopropylalcoholinasmallcontainerandsoakthefulllengthofthesensorfor10minutes.

• Donotshakeorstir.Thesensorfilmisextremelyfragilewhensoakinginisopropylalcohol.Theideaistodiluteanyheavyoilwithoutdamagingthethinsensorfilm.

• Aftersoakinginisopropylalcohol,letdryintheairfor1hour.• Repeattheprocessif

necessary.• Ifthesensorfailstoresetafter3isopropylalcoholsoakingand1hourofairdryingtime,itshouldbediscarded and replaced.

Cleaning with isopropyl alcohol

Ifthesensorbladelooksgood,butstilltestsbad,itmaybecontaminatedwithaheavyfueloroilymaterial.Isopropylalcoholcanbeusedtodilutethecontaminationandspeedreset.Isopropylalcoholwillnotrepairasensorthathassustainedphysicaldamage.

FFS–Probe Tester